Limit State of Servicibility Is800

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

IS 800:2007

loss of stability of the structure or any part of c) The permanent actions (loads) and effects
it including support and foundation. contributing to resistance shall be multiplied
with a partial safety factor 0.9 and added
5.4.1 Design Strength
together with design resistance (after
The Design Strength, S~, is obtained as given below multiplying with appropriate partial safety
from ultimate strength, SUand partial safety factors for factor). Variable actions and their effects
materials, y~ given in Table 5. contributing to resistance shall be disregarded.

Sd=s,lym d) The resistance effect shall be greater than or


equal to the destabilizing effect. Combination
where partial safety factor for materials, y~ account of imposed and dead loads should be such as
for: to cause most severe effect on overall stability.
a) Possibility of unfavorable deviation of
material strength from the characteristic value, 5.5.1.2 Sway stability

b) Possibility of unfavorable variation of The whole structure, including portions between


member sizes, expansion joints, shall be adequately stiff against sway.
c) Possibility of unfavorable reduction in To ensure this, in addition to designing for applied
member strength due to fabrication and horizontal loads, a separate check should be carried
tolerances, and out for notional horizontal loads such as given in 4.3.6
to evaluate the sway under gravity loads.
d) Uncertainty in the calculation of strength of
the members. 5.5.2 Fatigue

5.5 Factors Governing the Ultimate Strength Generally fatigue need not be considered unless a
structure or element is subjected to numerous
5.5.1 Stability
significant fluctuations of stress. Stress changes due
Stability shall be ensured for the structure as a whole to fluctuations in wind loading normally need not be
and for each of its elements. This should include, considered. Fatigue design shall be in accordance with
overall frame stability against overturning and sway, Section 13. When designing for fatigue, the partial
as given in 5.5.1.1 and 5.5.1.2. safety factor for load, yf, equal to unity shall be used
for the load causing stress fluctuation and stress range.
5.5.1.1 Stability against overturning
5.5.3 Plastic Collapse
The structure as a whole or any part of it shall be
designed to prevent instability due to overturning, uplift Plastic analysis and design may be used, if the
or sliding under factored load as given below: requirement specified under the plastic method of
analysis (see 4.5) are satisfied.
a) The Actions shall be divided into components
aiding instability and components resisting 5.6 Limit State of Serviceability
instability.
Serviceability limit state is related to the criteria
b) The permanent and variable actions and their
governing normal use. Serviceability limit state is limit
effects causing instability shall be combined
state beyond which the service criteria specified below,
using appropriate load factors as per the Limit
are no longer met:
State requirements, to obtain maximum
destabilizing effect. a) Deflection limit,

Table 5 Partial Safety Factor for Materials, y~


(Clause 5.4. 1)

SI Definition Partial Safety Factor


No.

i) Resistance, governed by yielding, Ymo 1.10


ii) Resistance of member to buckling, ymo 1.10
iii) Resistance, governed by ultimate stress, y~t 1.25
iv) Resistance of connection: Shop Fabrications Field Fabrications
a) Bolts-Friction Type, y~r 1.25 1.25
b) Bolts-Bearing Type, ym~ 1.25 1.25
c) Rivets, Ym, 1.25 1.25
d) Welds, ymW 1.25 1.50

30
IS 800:2007

b) Vibration limit, or a building component should not impair the strength


c) Durability consideration, and of the structure or components or cause damage to
finishings. Deflections are to be checked for the most
d) Fire resistance.
adverse but realistic combination of service loads and
Unless specified otherwise, partial safety factor for their arrangement, by elastic analysis, using a load
loads, y~,of value equal to unity shall be used for all factor of 1.0. Table 6 gives recommended limits of
loads leading to serviceability limit states to check the deflections for certain structural members and systems.
adequacy of the structure under serviceability limit Circumstances may arise where greater or lesser values
states. would be more appropriate depending upon the nature
of material in element to be supported (vulnerable to
5.6.1 Dejection
cracking or not) and intended use of the structure, as
The deflection under serviceability loads of a building required by client.

Table 6 Deflection Limits

Type of Deflection DesignLoad Member Supporthtg Maximum


Building Deflection
(1) (2) (3) (4) (5) (6)

Elastic cladding Span/150


Live load/ Whrd load Purlinsand Girts Span/l 80
Brittle cladding
[
Elastic cladding Span/240
t,iVC load Simplespan
Brittle cladding Spatr/300
Elastic cladding Span/120
LNe load Cantilever span
Brittle cladding Span/150
Profiled Metal Sheeting Sparr/180
L!ve load/Wind load Rafter supporting
Plastered Sheeting Sparr1240
Crane load (Manual Crane Spaa/500
Gantry
operation)
Crane load (Electric Crane Spanl150
Gantry
operation up to 50 t)
Crane load (Electric Crane Span/l 000
Gantry
operationover 50 t)
Elastic cladding Height/l 50
No cranes Column
Masonry/Brittle cladding Height/240
Crane (absolute) SpanMOO

Crane + wind Gantry (lateral) Relative displacement


between rails supporting IOmm
crane
Gantry (Elastic cladding; Height/200
Column/frame pendent operated)
Crane+wind
Gantry (Brittle cladding; cab Height/400
operated)
Elements not susceptible to Sparr/300
cracking
Live load Floor and Roof
Elements susceptible to Spsm/360
cracking
Elements not susceptible to
Span/l 50
cracking
Live load Cantilever
Elements susceptible to
Span/180
cracking
Elastic cladding Height/300
Whrd Building
Brittle cladding Height/500
Wind Inter storey drift — Storey height/300

31

You might also like