HP/LP Bypass Automation: Function Description

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

CCI AG Switzerland

Im Link 11 Function description


P.O. Box 65
CH-8404 Winterthur
TELEFON ++41-(0)52-264 95 00
TELEFAX ++41-(0)52-264 95 01

HP/LP Bypass Automation


HP HP HP HP BPE1 BPE2
1. Introduction PS PS PS PT TT TT

30 years experience with Sulzer Bypass


Systems, including controls and safety (Option)
functions, show that the bypass-controller is Signal Conditioning
neither a integrated part of the boiler Operator
Safety
controls nor the turbine controls. The Sulzer Setpoint Generation
function Control
bypass system is rather an independent Interface

system which serves the operational Test Valve Positioners


requirements of the complete plant (i.e.
boiler and turbine). The number of active
signals between the bypass controller and
other systems is small. Much more important
is a bypass controller which fulfils exactly BP1 BP2 BPE1BPE2 BD1 BD2

the requirements of the bypass operation and Figure 1 HP-Bypass controller (2 lines)
allows the easy implementation of safety including safety function
functions or other quick opening or quick
closing functions. The life conserving
operation of the heavily stressed valves and With a few standardized interface signals the
pipework, especially by accurate steam Sulzer bypass controller can be tied easily
desuperheating in all operating modes and into an overall plant automation. The duty of
transients, poses a special challenge for the the HP bypass controller can be summarized
Sulzer bypass controller. for the different operating conditions as
follows:
2. HP bypass controller • Boiler start up

The Sulzer HP bypass controller is an The controller has to control and increase
integrated system with the functions signal the boiler steam pressure according to the
conditioning, control and valve positioning steam production of the boiler. The bypass
(Figure 1). The type of operator interface has to divert the steam flow to the reheater,
can be tailored to the needs of the individual thus ensuring a proper steam flow through
plant. The below described functions for superheater and reheater. The bypass
start up as well as for shut down are fully controller has to control the temperature of
automated. the steam to the reheater whenever steam is
flowing through the bypass.
• Turbine start up
The HP bypass controller has to control the
steam pressure until the boiler master
controller can take over the pressure control.

640/30.04.04/Ri D1_HDNDe 1/4


• Load operation 2.1 Pressure control
The bypass is closed but the controller is Figure 3 shows in more detail the structure
ready to prevent excessive live steam of the pressure controller and the pressure
pressure or excessive pressure gradients. setpoint generator. The different functions
• Turbine load rejection/trip
and operating modes of the pressure
controller are represented again in the start
The controller opens the bypass valves, if up diagram of Figure 4.
necessary with the help of the quick opening
devices, in order to prevent excessive live At the begin of a cold start the minimum
steam pressure and controls the pressure opening (Ymin) is active. It ensures
until the turbine picks up load again. immediately after ignition an open path and
• Safety Function therefore a steam flow through the
superheater and reheater.
Regulations of various countries allow the
use of the HP Bypass valves as safety valves When there is enough steam production to
for the HP part of the boiler without any reach a predetermined minimum pressure
additional conventional safety valves on the (pmin) the controller begins to control the
HP side. for this the HP Bypass has to be live steam pressure by opening the bypass
equipped with a hardwarewise fully valves.
independent safety system. Functionally this
system is fully integrated into the bypass When the valve positions reach a
controller to ensure smooth transients predetermined value Ym (determined by the
between safety and control function. desired steam flow during boiler start up) the
setpoint generator begins to increase the
Main Steam Line
pressure setpoint in accordance with the
HP Turbine
PT PS PS PS steam production of the boiler, but with a
1/3 limited maximum gradient.
Safety
System
YT

OP! BPE1 BD1 Setpoint PT

BP1
Generator Pressure
OP! YT BPE2 BD2 Controller
Pressure BP2
Controller Rate Limiter
C Ym
TT Temperature RTL M
Controller A SCO M
X A
X
TT
Reheater
S
Cold Reheat Line C YT
PS
PT Pressure Transmitter C C Ymin
TT Temperature Transmitter
YT Position Transmitter Pmin p
PS Pressure Switch
start up follow

Figure 2 HP-Bypass System with Safety Function


(two line system)
Basic control diagram

Operating modes: pressure control (fixed pr. Ps)


start up
Figure 2 shows the main elements of a two follow (Bypass closed)
line HP bypass with the main control C fixed value S set value

functions:
Figure 3 HP-Bypass pressure controller
• pressure controller
• temperature controller
• injection water isolation valve control
• safety function

640/30.04.04/Ri D1_HDNDe 2/4


Pressure/Load/Flow
%
factor for the heavily stressed walls of the
100 valves and piping.
80 3. LP bypass controller
Ymin Pmin Start up press. follow
contr.
60
The Sulzer LP bypass controller is an
40 integrated system with the functions signal
SH
conditioning, control and valve positioning
Pressure
20 Turbine
Load
(Figure 5). The type of operator interface
Steam
Flow can be tailored to the needs of the individual
Time plant. With a few standardized interface
Valve position
signals the Sulzer bypass controller can be
% tied easily into an overall plant automation.
100

Although independent in operation from the


50
Ym HP bypass controller the LP bypass
Ymin
controller must operate in conjunction with
Time
the HP Bypass system and allow the excess
steam flow which is not admitted to the
Figure 4 Cold start up with HP-Bypass
turbine to pass to the condenser.
Once the target pressure for starting the
turbine (psynch) is reached, the setpoint PT RH RH
PT PT TT
generator switches to (fixed) pressure
control. As the turbine starts to accept steam
the bypass will start to close until the turbine
consumes all the steam produced by the (Option)
boiler and the bypass is fully closed. Signal Conditioning

As soon as the bypass is closed the pressure Setpoint Generation Operator


setpoint tracks the actual pressure plus a Control
Interface
threshold dp which keeps the bypass closed
(follow mode). The maximum gradient of the Valve Positioners
pressure setpoint is still limited. If the life
steam pressure exceeds this gradient, the
bypass will start to open and the controller
returns to pressure control mode. The
pressure is controlled by the bypass until LPI1 LPI2 LP1 LP2 LPE1 LPE2
normal operation has been restored and the
bypass is closed again. Figure 5 LP-Bypass controller (2 lines)

2.2 Temperature control


3.1 Pressure Control
Regarding temperature control it should be
mentioned here only that accurate control of The duty of the LP bypass pressure
the steam temperature under all operating controller for the different operating modes
conditions requires a controller well matched can be summarized as follows:
to the wide range of operating conditions of
a HP bypass (low load, quick opening at full
load, etc.). Accurate control of the
temperature under all this operating
conditions is an important life conserving

640/30.04.04/Ri D1_HDNDe 3/4


• Boiler start up If power operated reheater safety valves are
The controller has to control the steam provided (e.g. Sulzer MSV valves),
pressure in the reheater system. The coordinated operation of the reheater safety
injection controller has, when ever the LP valves with the LP bypass can further
bypass is open, to control the desuperheating improve plant operation for the case of
of the steam so that it can be accepted by the turbine trip or load rejection at high load.
condenser. The Sulzer LP bypass controller can provide
the necessary signals for operation of the
• Load operation reheater safety valves.
The bypass is closed but the controller 3.2 Injection water control
monitors the reheat steam pressure in order
to open and control the pressure whenever Because the steam conditions after the LP
an unacceptable pressure increase is bypass desuperheater are usually near or at
monitored. saturation condition, the temperature after
the desuperheater cannot be used as control
• Condenser protection signal. The necessary injection water flow
Whenever the condenser is not able to accept and valve position of the injection valve
the steam or the injection water system is must therefore be calculated from the steam
unavailable, the controller has to close the flow and steam conditions. The steam flow
bypass through a separate safe channel in is in turn a function of the steam conditions
order to protect the condenser. and the valve position of the bypass valve.
The LP bypass controller provides the
HP Turbine
necessary computing functions to perform
this calculations and uses the calculated
Reheater
injection water demand as setpoint for the
water flow controller.
LP-Bypass
PT TT isolating valves
1st stage pr. Cond.
PT protection
PT T RH
F LP-Bypass
control valves
Setpoint Pressure YT

generator Controller
T RH YT
P RH P RH C
FT
C
FT

PT

Condenser

Figure 6 LP-Bypass system (2 lines)


Basic control diagram

During load operation the first stage pressure


of the turbine serves as load signal for the
setpoint generator which generates a load
dependent (sliding) pressure setpoint.

With large bypass valves, their flow capacity


at high reheater pressure can exceed the
absorption capacity of the condenser. For
such cases the steam flow to the condenser
must be limited by the bypass controller.

640/30.04.04/Ri D1_HDNDe 4/4


Functional description

Function description HP Bypass control

1. Overview (Diagram D)

The HP-Bypass Controller consists of the following parts


Pressure setpoint generation (Diagrams DA/RA)
Pressure controller (Diagram DB/TB)
Temperature controller (Diagram DC)
Spraywater isolation control (diagram DF)

2. Pressure setpoint generation

2.1 Startup

2.1.1 Mode Selection (Diagram RA)


The “startup mode” is set by the operator or by the signal “Boiler fire on” from the
DCS. When the “startup mode” is selected, the setpoint generator can be in three
different operating conditions:
• min pressure
• pressure ramp
• restart
The “min pressure” is active whenever the main steam pressure is below “Pmin”.
The “pressure ramp” is active when the main steam pressure is above “Pmin” and
below “Psync”.
The “restart” is active when the pressure is above “Pmin” and the BP valve is closed.
The signal “start sequence” is generated when the operating “min pressure” or
“pressure ramp” is on.
The “startup mode” is deselected as soon as the pressure reaches “Psync” and the BP
valve is open. The “startup mode” is also deselected when the signal “HP Turbine
loaded” is active or when the pressure controller is switched to manual.

The “fixed pressure mode” is active when the “startup mode”, the “follow mode “ and
the “shut down mode” is not active.

The “follow mode” is active when the BP valve is closed and the DEH signal “HP
Turbine loaded” is on or the DCS signal “Boiler fire on” is off . or when the. Further
the “Follow mode” is on when BP controller is in manual.

0640/06.12.04 Bi HP_Bypass.doc 1/5


Rev. 0
Functional description

2.1.2 Setpoint Generator (Diagram DA)

At startup, with no pressure in the boiler the setpoint generator is in the “min pressure”
condition. The pressure setpoint “Ps actual” is then set at pressure value “Pmin”. And
the pressure controller open the BP valve to a minimum position value “Ymin” (see: 3.
Pressure Controller).
As soon as the main steam pressure is above “Pmin” the “pressure ramp” condition is
activated. The pressure setpoint “Ps demand” is increased, whenever the BP valve
position “Yset” exceed the position value “Ym”. The increase of the pressure setpoint
is limited by the gradient limiter and only positive pressure gradient are allowed
during “pressure ramp” operation, decrease of the pressure setpoint “Ps actual” is not
permitted in this operation mode.
As soon as the main steam pressure reaches “Psync” the “startup mode” is deselected
and the “fixed pressure mode” is activated. The pressure setpoint “Ps demand” is set at
the current last pressure setpoint “Ps actual”. In “fixed pressure mode” the “Pressure
setpoint” can be adjusted by the operator.
When the “HP turbine loaded” the BP valve will close automatically due to pressure
drop. As soon the BP valve is closed the setpoint generator will switch over to “follow
mode” (see: 2.2 Load Operation). In this mode pressure setpoint “Ps actual” will
follow main steam pressure.

In case of pressurized boiler at startup the “restart” condition is selected while the BP
valve is closed. In the “restart” condition the pressure setpoint “Ps actual” is following
the main steam pressure but only negative pressure gradients are allowed. As soon as
the boiler pressure starts to increase the bypass valve will start to open. When the BP
valve open the setpoint generator will go to “pressure ramp” condition if the pressure
is still below “Psync” or to “fixed pressure mode” if the pressure at startup is already
above “Psync”.

P re s s u r e / L o a d / F lo w

100 % S ta rt S e q u e n c e .
Turbine on
M in P re s s u re F ix e d
80 % P re s s Ram p P r e s s u re . F o llo w

60 %

40 % P sync S H -P r e s s u r e P S H
T u r b in e L o a d
20 %
S t e a m F lo w
P m in

F ire o n T im e
T u rb in e lo a d e d
B P v a lv e
100 %

Y BP
50 %
Ym

Y m in

T im e

0640/06.12.04 Bi HP_Bypass.doc 2/5


Rev. 0
Functional description

2.2 Load Operation (Diagram /DA/RA)

During load operation, i.e. when the HP turbine is taking over all the produced steam,
the bypass valves are closed. The “follow mode” is activated.
In the “follow mode” the pressure setpoint “Ps actual” is following the actual main
steam pressure. The maximum pressure gradient is limited, depending on the actual
main steam pressure. A differential pressure “dP” is added to the pressure setpoint “Ps
actual” to keep the BP valve closed (see: 3. Pressure Controller).
If the main steam pressure is increasing above the Bypass controller setpoint “Ps
actual + dP” the BP valve starts to open. The setpoint generator is switched over to
“fixed Pressure mode”.

D e s ig n P re s s u re (P m a x + d P m a x )
P re s s .

M a x . P re s s u re (P m a x )

B yp a s s fa s t o p e n in g
(P s a c tu a l + d P m a x )

B yp a s s C o n tro lle r S e tp o in t
(P s a c tu a l + d P )

P re s s u re s e tp o in t
(P s a c tu a l)

M o d ifie d S lid in g P re s s u re

Load

2.3 Shut down

2.3.1 Mode selection (Diagram RA)


When a plant shutdown is planned the “Shut down mode” can be selected by the
operator. The “Shut down mode” can only be selected when the DEH signal “HP
Turbine loaded” is active and the BP controller is on auto. As soon as the DEH signal
“HP Turbine loaded” is deactivated the “Shut down mode” is deselected and the
setpoint generator change to “fixed pressure mode”.
When the boiler shuts down, the DCS signal “Boiler fire on” is deactivated, the BP
valve will close and the setpoint generator is switched to “follow mode”

0640/06.12.04 Bi HP_Bypass.doc 3/5


Rev. 0
Functional description

2.3.2 Setpoint Generator (Diagram DA)

At “Shut down mode” the pressure setpoint “Ps actual” is following the main steam
pressure but only negative gradients are allowed. As soon as the boiler pressure starts
to increase the BP valve start to open.
After the “Shut down mode” is deselected the setpoint generator is on “fixed pressure
mode”. At “fixed pressure mode” the setpoint generator controls the actual pressure.
As soon the boiler shuts down the BP valve is closing and the pressure generator is
switched to “follow mode”. In “follow mode” the pressure setpoint will again follow
the actual main steam pressure.

P re s s u re / L o a d / F lo w

100 %
F o llo w Shut
F ix e d
m ode down
p re s s u re F o llo w m o d e
80 % m ode

P r e s s .-S e tp o in t
60 %
M a in S te a m P r e s s u r e
40 %

S te a m F lo w
20 % T u r b in e L o a d

T u rb in e o ff F ire o ff T im e

B P v a lv e

100 %

Y BP
50 %

3. Pressure Controller (Diagram DB)


The pressure controller is receiving the actual main steam pressure signal and the
pressure setpoint “Ps actual” from the setpoint generator. It is generating the BP valve
position demand signal.

The pressure controller has one M/A station to control the BP valve.
At signals “BP open “ the BP valve will open to 100%. During this signal controller is
set manual and follow the valve position. After the signal the controller set automatic
At signal “BP close trip” the BP valve will be closed by the close command signal to
to the valve. The controller is set to manual.

0640/06.12.04 Bi HP_Bypass.doc 4/5


Rev. 0
Functional description

In “follow mode” when the “dP on” is active a differential pressure is added to the
pressure setpoint “Ps actual” to keep BP valve close.

At “startup mode” when the “min pressure” condition is active the BP valve are
opened to a minimum position “Ymin”. The “Ymin on“ is deselcted when position is
above the minimum position “Ymin”.

4. Fast open / close logic (Diagram TB)


The “BP open” command for the BP valve is generated from DEH signals “Turbine
trip” or “Generator switch trip” or when the main steam pressure has reached the
quick opening pressure threshold “dp max” above the pressure setpoint “Ps actual”.
The “BP open” is blocked when pressure is below the pressure “Pfo” and the “startup
sequence” is active or when the “BP close trip “ is active.

The “BP close trip” command is generated when the BP outlet temperature exeed the
pressure “Tmax”.

5. Temperature control (Diagram DC)


The temperature controller is receiving the actual signal “HP-BP outlet temperature”
from the transmitter and the “Temp setpoint“ set by the operator. The controller is
generating the spraywater valve position demand signal.
The feed forward signal is generated from “Main steam pressure” and BP valve
position and is added to the valve position demand signal. With the adjustable value
“wpl” the feed forward signal can be adapted.

The temperature controller has one M/A station to control the sprayvalve BPE valve.
The temperature controller is set automatic mode as soon the BP valve is open.
When the BP valve closes the spraywater valve closes also, and the temperature
controller is set to manual.

6. Spraywater isolation valve control (Diagram DF)

The spraywater isolation valve is open as soon the BP valve is open. When the BP
valve is closed the spraywater isolation valve is closed again.

0640/06.12.04 Bi HP_Bypass.doc 5/5


Rev. 0
Functional description

Parameter list HP Bypass control

Function DWG Unity Denom. Default Definition/Description


Minimum pressure /DA [Mpa] Pmin 1 Min. range of pressure set point

Maximum pressure /DA [Mpa] Pmax 20 Max. range of pressure set point

Syncronisation /RA [Mpa] Psync 8 Minimum pressure, at which


pressure turbine can be started and
syncronised

Fast opening release /TB [Mpa] Pfo 15 General release for fast opening
pressure

Pressure gradient /DA [Mpa] P1 5 Fixed point 1 for Gradient


/DA [Mpa] P2 6 Fixed point 2 for Gradient
/DA [Mpa/min] GRD1 0.4 Gradient 1 f(P1)
/DA [Mpa/min] GRD2 1.2 Gradient 2 f(P2)
/DA [Mpa/min] GRD3 0.2 Gradient 3
Gradient in „min pressure“
/DA [Mpa/min] GRD4 0.2 Gradient 4
Gradient in „pressure ramp“
/DA [Mpa/min] GRD5 0.4 Gradient 4
Gradient in„restart“
/DA [Mpa/min] GRD6 0.6 Gradient 4
Gradient in ”shut down”

Fast opening /TB [Mpa] dp max 0.5 Control deviation fast opening
P steam high

Follow up /DB [Mpa] dP 0.5 Additional dP to the setpoint to


produces a neg. control deviation
to keep the valve closed

Minimum opening /DB [%] Ymin 10 Is set at „start up“


Medium opening /DA [%] Ym 30 Equilibrium in „pressure ramp“
at constant steam procuction

Feedforward /DC [-] wpl 0.5 Feed forward signal

0640/06.12.04 Bi HP_Para.doc 1/1


Rev. 0
Functional description

Function description LP Bypass control

1. Overview (Diagram D)

The LP-Bypass Controller consists of the following parts


Pressure setpoint generation (Diagrams DG)
Pressure controller (Diagram DH)
Condenser protection (Diagram DM)
Temperature controller (Diagram DK1/DK2)
Spraywater isolation control (Diagram DL)

2. Pressure setpoint generation (Diagram DG)


In the “min pressure” operation the turbine is not on load. The pressure setpoint “Ps
RHH actual” is set to the pressure “Pmin”. The minimum pressure setpoint can also be
increased by the operator if an higher setpoint is required.
At “load pressure” operation the pressure setpoint “Ps RHH actual” is generated from
the transmitter signal “Turbine 1st stage pressure”. The pressure setpoint “Ps RHH
actual” changes in function of the turbine load of the unit.
P re s s u re / L o a d / F lo w

100 %

80 % M in P re s s u re L o a d P re s s u re

60 %

40 % H o t re h e a t p re s s

P m in T u r b in e L o a d
20 %

S te a m F lo w
F ire o n T im e
T u rb in e lo a d e d
B P v a lv e
100 %

Y LBP
50 %

T im e

0640/06.12.04 Bi LP_Bypass.doc 1/3


Rev. 0
Functional description

3. Pressure controller (Diagram DH)

The pressure controller is receiving the actual hot reheat steam pressure signal (1 out
of 2 selection of two transmitter signals) and the pressure setpoint “Ps RHH actual”
from the setpoint generator. It is generating the LBP valves position demand signal.

Each LBP valve has one M/A station.


At signal “LBP close trip” from condenser protection the LBP valves will be closed by
the close command to the valves and the controller is set to manual.
The PI controller is set to manual when both LBP valves are set to manual. The
controller then is tracking the max valve position.

The maximal LBP valve opening is limited by the steam flow to the condensator. As
soon the “LBP steam flow” the LBP valve start to close.

4. Condenser protection (Diagram /DM)

The “LBP close trip” command for the LBP valve is generated from condenser
protection switches. Each one of the following criteria are activating the “LBP close
trip” command:
- Condenser press. high (2 out of 3)
- Condenser temp. high
- Condenser level high
- LBP spraywater pressure low.

5. Temperature controller (Diagram /DK1/DK2)

The temperature controller is receiving the actual signal Fw “LBP spraywater flow”
from the transmitter. The spraywater setpoint Fws is calculated out of the steam
pressure, steam temperature and LBP valve position . The controller is generating the
spraywater valve position demand signal.

The temperature controller has one M/A station to control the sprayvalve LP-BPE
valve.
The temperature controller is set to automatic mode as soon the LBP valve is open.
When the LBP valve is closed the spraywater valve is also closed, the controller is set
to manual.

6. Spraywater isolation valve control (Diagram DL)

0640/06.12.04 Bi LP_Bypass.doc 2/3


Rev. 0
Functional description

The spraywater isolation valve is open as soon the LBP valve is open. When the LBP
valve is closed the spraywater isolation valve is closed again.

0640/06.12.04 Bi LP_Bypass.doc 3/3


Rev. 0
Functional description

Parameter list LP Bypass control

Function DWG Unity Denom. Default Definition/Description


Pressure setpoint /DG [Mpa] Pmin 0.2 Min. range of pressure set point
/DG [Mpa] Pmax 5 Max. range of pressure set point
/DG [MPa] P1 0 Fixed point 1 for Setpoint
/DG [MPa] P2 20 Fixed point 2 for Setpoint
/DG [MPa] Ps1 0 Setpoint 1 Ps = f(P1st)
/DG [MPa] Ps2 5 Setpoint 2 Ps = f(P1st)

Calculation of /DK [m3/h] kvs kv at 100% valve stroke


Spraywater /DK [KJ/Kg] Ew Enthalpy spraywater
/DK [KJ/Kg] Ek Enthalpy steam after LBP

0640/06.12.04 Bi LP_Para.doc 1/1


Rev. 0

You might also like