SAUDIARAMCO.

NOTES:

1.ALL ELECTRICAL INSTALLATION SHALL BE DONE IN


ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE
(NFPA 70) AND ALL THE APPLICABLE SAUDI
ARAMCO ENGINEERING STANDARDS.

2.PANELBOARD SHALL BE MANUFACTURED AS PER SAUDI


ARAMCO MATERIAL SPEFICATION NO. 16-SAMSS-518.

OF
3.ALL CIRCUIT BREAKERS SHALL BE THERMAL MAGNETIC

CONSENT
TRIP RATED FOR 50 DEG. CELCIUS AMBIENT
TEMPERATURE.

FROM EXISTING 13.8KV-208/120V, 1000KVA 4.FULLY BUSSED CUBICLE, VENDOR SHALL PROVIDE THE
LOOP TRANSFORMER REQUIRED MINIMUM OF 10% SPARE CIRCUIT BREAKERS
L62-T301 AND MINIMUM 10% OF SPARE POLE SPACES.
(REFER TO DWG. NO.

TTEN
PA-05O273) 5.THE ENCLOSURE FOR THE PANELBOARD SHALL HAVE
THE TOP AND BOTTOM WIRE-BENDING SPACE SIZED

WRI
IN ACCORDANCE WITH NEC ARTICLE 384.35 AND

PC-0161
TABLE 373-6 (A AND B).

THE
THOUT
551-DSW(D)-009
400A, 240V, 3PH
NEMA 4X

WI NG
DRAWI
PC-0162

S
THI
551-XFR(T)-002
75kVA, 208/120-400/230V,

FROM
3{, 4W, 60HZ, dYN11
NEMA-4

NED
OBTAI
LEGEND

PC-0163

BE
PC-XXXX POWER CABLE
GATEHOUSE POWER PANEL NUMBER
551-PP-006, NEMA-4

PART,SHALL
75kVA, 220-400/230V,
3{, 4W, 60HZ, dYN1

150AF
3P
150AT
MOLDED CASE
3P

N
CIRCUIT BREAKER

I
150A, 400/230V, 3{, 4W+G, 60HZ, 10KAIC

FULL,OR
MINIATURE
1P CIRCUIT BREAKER

100AF 100AF 100AF 100AF 100AF PANELBOARD


20A 20A 20A 20A

N
3P 3P 3P 3P 3P 1P 1P 1P 1P

I
100AT 100AT 30AT 100AT 30AT (RATING AS SHOWN)

ON
REPRODUCTI
EQUIPMENT
GROUND
PC-0166

PC-0165

PC-0168
PC PHOTOCELL
PC-0164

SAUDIARAMCO.NO
SPARE LIGHTING CONTROL
LCP
551-DSW(D)-010 551-DSW(D)-012 PANEL
30A, 400V, 3PH 30A, 400V, 3PH
NEMA 4X NEMA 4X FCU FAN COIL UNIT
PC-0167

PC-0169

551-LCP-003
ACCU AIR COOLER CONDENSING UNIT
PC LCP

REFER TO PANEL SCHEDULE


551-PP-007 551-PP-008

OF
DWG. NO.
(GATEHOUSE), NEMA-4 CRASH BARRIER REFERENCE DRAWINGS
PA-05O276.001
REFER TO DWG. NO. AIR COOLED CONDENSING REFER TO DWG. NO. AIR COOLED CONDENSING
DWG. CONTROL FOR J.O. 10-00965-0001 PD-00ADCL

PROPERTY
PA-05O276.001 UNIT-GATE HOUSE PA-05O276.001 UNIT-GATE HOUSE
FCU/ACCU-01 FCU/ACCU-02 PANELBOARD SCHEDULE PA-05O276

7KW (DUTY) 7KW (STANDBY) ELECTRICAL ONE LINE DIAGRAM PA-05O273


ELECTRICAL ONE LINE DIAGRAM (REFENCE) HA-103318.051
ELECTRICAL ONE LINE DIAGRAM (REFENCE) HA-106978.046

CABLE AND CONDUIT SCHEDULE PD-05O278

SOLE
THE
ARE N
HEREINED
SCALE:

CONTAI
REVISION VALIDATION

THIS REVISION NO. C IS COVERED, FOR ALL APPROVAL AND CERTIFICATION


REQUIREMENTS, PER SAEP-334, UNDER DRAWING COMPLETION CERTIFICATE NO:

ON
10-00965-0001-001

NFORMATI
DESIGN CERTIFICATION REVIEW FOR KEY DRAWINGS OTHER
(DESIGN AGENCY) REQUIRED (SAUDI ARAMCO)

ENGG./DATE CERTIFIED BY/DATE CONST. AGENCY/DATE OPERATIONS/DATE BY/DATE

REV.NO. DATE REVISION DESCRIPTION

I
C 12/05/19 ISSUED FOR 100% PROJ. PROPOSAL

THE
JOB ORDER/EWO NO.
THIS REVISION IS NOT TO BE USED FOR
10-00965-0001 CONSTRUCTION UNTIL CERTIFIED AND DATED

SAUDI ARABIAN OIL COMPANY

AND
DRAWING TYPE

ELECTRICAL ONE LINE DIAGRAM GAT

NG
DH RABIYAH (GATE #14) - GATEHOUSE

DRAWI
AR RABIYAH PHASE V

DHAHRAN SAUDI ARABIA

S
PLANT NO. INDEX DRAWING NUMBER SHT. NO. REV. NO.

THI
551 O PA-05O274 001 C
Saudi Aramco 2615 ENG. (05/05)

RESTRICTED VECTOR CADD-05