Cable Schedule For Dangote Flour Mills Calabar

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

CABLE SCHEDULE FOR 33/11KV 7.

5MVA TRANSFORMER PROTECTION


AT DANGOTE FLOUR MILLS, CALABAR

33KV ABB INDOOR CONTROL PANEL 19 core control cable 33KV ABB OHB36 VACCUM OUTDOOR CIRCUIT BREAKER
s/n Fayroule marker Connection Function Terminal Block no cable no Fayroule marker Connection Function Terminal Block no
1 J1 DC SUPPLY POSSITIVE X4 3 1 J1 DC SUPPLY POSSITIVE 137
2 J2 DC SUPPLY NEGATIVE X4 4 2 J2 DC SUPPLY NEGATIVE 138
3 H1 AC SUPPLY PHASE X4 1 3 H1 AC SUPPLY PHASE 139
4 H2 AC SUPPLY NEUTRAL X4 1 4 H2 AC SUPPLY NEUTRAL 140
5 K3 OPEN BREAKER COMMAND X4 2 5 K53 OPEN BREAKER COMMAND 132
6 K9 CLOSE BREAKER COMMAND X4 9 6 K9 CLOSE BREAKER COMMAND 136
7 L3 BREAKER OPENED INDICATION X4 4 7 K35 BREAKER OPENED INDICATION 108
8 L5 BREAKER CLOSED INDICATION X4 2 8 K33 BREAKER CLOSED INDICATION 109
9 L7 BREAKER SPRING CHARGED INDICATION X4 3 9 K37 BREAKER SPRING CHARGED INDICATION 112
10 L11 TRIP COIL AND CIRCUIT HEALTHY X4 5 10 K53 TRIP COIL AND CIRCUIT HEALTHY 133
11 J1 MOTOR DC SUPPLY POSSITIVE X4 X 11 J1 MOTOR DC SUPPLY POSSITIVE 143
12 J2 MOTOR DC SUPPLY NEGATIVE X4 X 12 J2 MOTOR DC SUPPLY NEGATIVE 144
13 L13 TRIP COIL 2 AND CIRCUIT HEALTHY X4 X 13 K53 A TRIP COIL 2 AND CIRCUIT HEALTHY 134

33KV ABB INDOOR CONTROL PANEL 10 core control cable 7.5MVA 33/11KV POWER TRANSFORMER
s/n Fayroule marker Connection Function Terminal Block no cable no Fayroule marker Connection Function Terminal Block no
1 K1 WINDING TEMPERATURE ALARM X2 14 1 L1 WINDING TEMPERATURE ALARM 1
2 K35 WINDING TEMPERATURE ALARM X2 18 2 L2 WINDING TEMPERATURE ALARM 2
3 K1 WINDING TEMPERATURE TRIP X2 14 1 K1 WINDING TEMPERATURE TRIP 3
4 K37 WINDING TEMPERATURE TRIP X2 19 3 K2 WINDING TEMPERATURE TRIP 4
5 K1 OIL TEMPERATURE ALARM X2 14 1 L3 OIL TEMPERATURE ALARM 7
6 K31 OIL TEMPERATURE ALARM X2 15 4 L4 OIL TEMPERATURE ALARM 8
7 K1 OIL TEMPERATURE TRIP X2 14 1 K3 OIL TEMPERATURE TRIP 9
8 K33 OIL TEMPERATURE TRIP X2 16 5 K4 OIL TEMPERATURE TRIP 10
9 K1 MAIN TANK BUCHOLZ ALARM X2 14 1 L5 MAIN TANK BUCHOLZ ALARM 17
10 K39 MAIN TANK BUCHOLZ ALARM X2 21 6 L6 MAIN TANK BUCHOLZ ALARM 18
11 K1 MAIN TANK BUCHOLZ TRIP X2 14 1 K5 MAIN TANK BUCHOLZ TRIP 15
12 K41 MAIN TANK BUCHOLZ TRIP X2 22 7 K6 MAIN TANK BUCHOLZ TRIP 16
13 K1 TAP CHANGER BUCHOLZ ALARM X2 14 1 L7 TAP CHANGER BUCHOLZ ALARM 19
14 K39 TAP CHANGER BUCHOLZ ALARM X2 21 8 L8 TAP CHANGER BUCHOLZ ALARM 20
15 K1 TAP CHANGER BUCHOLZ TRIP X2 14 1 K7 TAP CHANGER BUCHOLZ TRIP 21
16 K41 TAP CHANGER BUCHOLZ TRIP X2 22 9 K8 TAP CHANGER BUCHOLZ TRIP 22
17 K1 PRESSURE RELIEF VALVE X2 14 1 K9 PRESSURE RELIEF VALVE 23
18 K41 PRESSURE RELIEF VALVE X2 14 10 K10 PRESSURE RELIEF VALVE 24
33KV ABB INDOOR CONTROL PANEL 12 core control cable 33KV OUTDOOR CURRENT TRANSFORMER
s/n Fayroule marker Connection Function Terminal Block no cable no Fayroule marker Connection Function Terminal Block no
1 D11 RED PHASE CT FOR METERING X1 1 1 R 1S1 RED PHASE CT FOR METERING 1
2 D31 YELLOW PHASE CT FOR METERING X1 3 2 Y 1S1 YELLOW PHASE CT FOR METERING 2
3 D51 BLUE PHASE CT FOR METERING X1 5 3 B 1S1 BLUE PHASE CT FOR METERING 3
4 D71 STAR POINT CT FOR METERING X1 7,8 4 R 1S2, Y 1S2, B 1S2 STAR POINT CT FOR METERING 4
5 A11 RED PHASE CT FOR PROTECTION X1 13 5 R 2S1 RED PHASE CT FOR PROTECTION 5
6 A31 YELLOW PHASE CT FOR PROTECTION X1 15 6 Y 2S1 YELLOW PHASE CT FOR PROTECTION 6
7 A51 BLUE PHASE CT FOR PROTECTION X1 17 7 B 2S1 BLUE PHASE CT FOR PROTECTION 7
8 A71 STAR POINT CT FOR PROTECTION X1 19,20 8 R 2S2, Y 2S2, B 2S2 STAR POINT CT FOR PROTECTION 8

33KV ABB INDOOR CONTROL PANEL 4 core control cable 33KV OUTDOOR VOLTAGE TRANSFORMER TRANSFORMER
s/n Fayroule marker Connection Function Terminal Block no cable no Fayroule marker Connection Function Terminal Block no
1 E111 RED PHASE VT FOR METERING X1 9 R R S1 RED PHASE VT FOR METERING 1
2 E131 YELLOW PHASE VT FOR METERING X1 10 Y Y S1 YELLOW PHASE VT FOR METERING 2
3 E151 BLUE PHASE VT FOR METERING X1 11 B B S1 BLUE PHASE VT FOR METERING 3
4 E171 STAR POINT VT FOR METERING X1 12 X R S2, Y S2, B S2 STAR POINT VT FOR METERING 4

33KV ABB INDOOR CONTROL PANEL 4 core control cable 11KV INDOOR PROTECTION PANEL
s/n Fayroule marker Connection Function Terminal Block no cable no Fayroule marker Connection Function Terminal Block no
1 A111 RED PHASE CT FOR DIFFERENTIAL X1 1 R A11 RED PHASE CT FOR DIFFERENTIAL 1
2 A131 YELLOW PHASE CT FOR DIFFERENTIAL X1 3 Y A31 YELLOW PHASE CT FOR DIFFERENTIAL 2
3 A151 BLUE PHASE CT FOR DIFFERENTIAL X1 5 B A51 BLUE PHASE CT FOR DIFFERENTIAL 3
4 A171 STAR POINT CT FOR DIFFERENTIAL X1 7,8 X A71 STAR POINT CT FOR DIFFERENTIAL 4