MAILHOT
F 07/11/2011 FIN See revision page
MODIFICATIONS /
REV. DATE AUTHOR CHECKED BY STATUS APPROVED BY
OBSERVATIONS
26/10/2012
PPTO-F 26/10/2012
CNM CCA_76J006
Name of the issuing company COMPANY CODE DOCUMENT NUMBER
The reproduction, transmission or use of this document or its contents is not permitted without express written authority. Offenders will be liable for
damages. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.
Goods labeled with "AL not equal to N" are subject to European or German export authorization when being exported out of the EU. Goods labeled
with "ECCN not equal to N" are subject to US reexport authorization. Even without a label, or with label "AL:N" or "ECCN:N", authorization may be
required due to the final whereabouts and purpose for which the goods are to be used.
The original version of this document is stored in electronic form in the ANP system. The current status of this document can be viewed only in the
EDM system.
2007.01 NP 226
A REFERENCE REV. FILE PAGE
Abstract
This document specifies In-shop Test Procedure.
Distribution : This document and its associated distribution list document are saved under Windchill
A REFERENCE REV. FILE PAGE
TABLE OF CONTENTS
1 PREFACE............................................................................................................................................................... 8
1.1 APPLICABLE DOCUMENTS ............................................................................................................................ 8
1.2 REFERENCE DOCUMENTS.............................................................................................................................. 8
1.3 GLOSSARY..................................................................................................................................................... 10
1.4 DEFINITIONS ................................................................................................................................................. 11
LIST OF TABLES
LIST OF FIGURES
1 PREFACE
N° Reference TITLE
[R1] Design requirements for the Electrical and I&C Design and Layout
NGLTH/2004/en/0028
of Black Boxes
[R3] System Quality Plan for I&C of SC3 black-box systems based on
NLE-F DC 80
SIMATIC S7
[R4] NLN-F DC66 SFCTF – List of I&C functions
[R5] NLE-F DC 120 System description of I&C
[R6] NLN-F DC 31 Specification of Software Safety Functions
[R7] NLN-F DC 22 Design Rules for Implementation on Simatic S7-F
[R8] CCA_50M001 Manufacturer Management Plan
N° Reference TITLE
1.3 GLOSSARY
BDD Basic Design Description
BLHS Biological Lid Handling Station
BLHSCP Biological Lid Handling Station Control Panel
CC Control Command
CP Control Panel
CR Control Room
DD Design Description
DDD Detailed Design Description
EPR European Pressurized water Reactor
FA Functional Analysis
FAT Factory Acceptance Test
FB Fuel Building
HMI Human Machine Interface (SCADA and PSCP)
HMS1 Horizontal Motion Stop level 1
HMS2 Horizontal Motion Stop level 2
HOS Handling Opening Station
I&C Instrumentation and Controls
ISTP In-Shop Test Procedure
ISTR In-Shop Test Report
ITP In-Shop Test Procedure
ITR In-Shop Test Report
LH Loading Hall
MCD Main Control Desk
NCR Non Conformance Report
NPP Nuclear Power Plant
OPLC Operating PLC
OL3 Olkiluoto 3 (EPR in Finland)
OS Operating System
PCU2000ETH Applicom I/O card (PROFIBUS and Ethernet S7) I/O card
PID Piping & Instrumentation Diagram
PLC Programmable Logic Controller
PM Project Manager
PS Project specifications
PSCP Penetration Station Control Panel
SC Safety Class (SC3 / SC4)
SCADA Supervisory Control And Data Acquisition
SCD Source Code Documentation
A REFERENCE REV. FILE PAGE
1.4 DEFINITIONS
The SFCTF (Spent Fuel Cask Transfer Facility) allows to transport a cask from the lifting station to the LH of
the FB, its loading with FA through the loading pit and performing its final conditioning. The SFCTF I&C is in
charge of controlling the installation for a proper functioning and to supply to the operators all needed controls
and information necessary for its management.
The SFCTF Software is in charge of control, command, supervise and keep in a constant safe situation the
SFCTF in a nuclear plant. This includes the control of a SFCTM from a Control Room with the help of SCADA
system.
SFCTF Software is made up of:
• SPLC software: the safety software is the program executed by the SPLC. This software manages all the
computerized safety I&C functions classified SC3.
• OPLC software: the operating software is the program executed by the OPLC. This software manages all
the computerized operational I&C functions classified SC4. Its role is to perform general management of
the installation and display on SFCTF HMI.
• HMI Software: the HMI software is needed to operate the SFCTF machine and includes the following
items:
o SCADA system, network and configuration,
o Functions managed by Operational SCADA,
o Functions managed by Display SCADA,
o Functions managed by PSCP HMI.
SFCTF Hardware is made up of MCD cabinet (GH140), OPLC cabinet (GH120), SPLC cabinet (GH130) and
electrical cabinets including I/O operating or safety deported devices and wired I&C functions GH310 and
GH410 (Refer to Figure 4 for localization and function).
This document aims to describe In-Shop Test Procedure and includes the following items:
• Description of OPLC, SPLC and HMI context and configuration,
• Network configuration,
• Description of the validation platform configuration,
• Description of each procedure including initial test conditions, potential faults and dysfunctions and
expected result.
Before performing these tests, it is assumed that software validation tests and control tests have fulfilled [R17]
and [R19] procedures.
A REFERENCE REV. FILE PAGE
.
Figure 1 – SFCTF software breakdown
A REFERENCE REV. FILE PAGE
3 INSTALLATION CONTEXT
SQP
Review R6
Validation
Functional Document In-Shop Tests
Analysis
Review R5
ISTR
Integration Test Document
Basic
Integration
Design
Test
Review R1 Review R4
OPLC BDD
ITR
SPLC BDD Unit Test Document Unit Test
Detailed
HMI BDD Design
ITP
OPLC DDD Review R2 Review R3
UTR
SPLC DDD
HMI DDD
Coding
UTP
ISTP
SCD
OPLC SPLC
Standard Database Standard Database
OPLC
Share SPLC
SPLC Write Data Database
Database
OPLC SPLC
Program Safety
Program
In Shop tests are intended to validate functional installation in accordance to functional requirements [R11].
Before performing In-shop tests, it is assumed that:
- Software validation tests have fulfilled [R17] procedure
- Control procedure tests has fulfilled [R19] procedure
DP master OPLC in
DPSPLC in
master
GH120 GH130
Profibus DP cabinet cabinet
DP master
ProfiSafe
Other
cabinets
GH410
Operative
part
Operator interaction
Electrical
Electrical UpperElectrical
cover
Electrical Electrical
cabinet
cabinet Operative
cabinet
cabinet
model
model partcabinet
model
model
model model
Electrical
Control
Electrical
panel
cabinet Operative
cabinet
model
model part of the
model simulator ControlBuild
project
I/O configuration
Profibus driver
Electrical
cabinet Interactions with
GH410 simulated
operative part
PROFISAFE
Repeater
CPU 317 F-2 PN/DP (SPLC)
UPPER COVER
Lower plate in place on the Lower plate Lower plate in place on the
penetration detector 1/2 penetration detector 2/2
- Initial status:
No alarm
Maintenance mode (30FCJ10GH140-S14) selected on
MCD control panel
Control panel selector set on “MCD” position
(30FCJGH140-S15)
Travelling platform screen displayed on operating SCADA
Travelling motor (AE201) selected on operating SCADA
- Action:
a. Select SFCTM travelling speed selector (30FCJ10GH140-
S21) on “LS” (Low speed) position
Set SFCTM at one station, for example at BLHS :
30FCJ13CG140-S01 and 30FCJ13CG141-S01 detectors =
true
Check SFCTM forward low speed movement by pushing
on “SFCTM run forward” push button (30FJC10GH140-
S18) on MCD Control panel (remain pushing a few
seconds).
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – BIOLOGICAL LID HANDLING DEVICE
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140S14)
Control panel selector set on “BLHS” position
(30FCJ10GH140S16)
Biological Lid handling device screen displayed on
operating SCADA
SFCTM at BLHS detectors (30FCJ13CG138-S01 and
30FCJ13CG139-S01 = true)
Biological Lid handling motor (AE401) selected on
operating SCADA
- Action:
Check gripper up movement by pushing on “Gripper up”
push button (30FCJ11GH310-S09) on BLHS control panel
(GH310 cabinet). Remain pushing during few seconds.
Check gripper movement stopped by releasing “Gripper
up” push button.
Check gripper down movement by pushing on “Gripper
down” push button (30FCJ11GH310-S10) on BLHS control
panel (GH310 cabinet). Remain pushing during few
seconds.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – BIOLOGICAL LID HANDLING DEVICE
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Check gripper movement stopped by releasing “Gripper
down” push button.
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S16 key switch)
Docking device screen displayed on operating SCADA
SFCTM not at penetration station (PS) (30FCJ13CG144-
S01 and 30FCJ13CG145-S01 = false) (else interlock of the
screw motors by SRCF#15)
- Action:
Select successively screw 1,2,3 and 4.motors (AE261,
AE271, AE281, AE291)on operating SCADA and select
corresponding position of screw key (30FCJ10GH140-S11)
(position 1&3 for screw 1 & 3 and position 2&4 for screw 2
& 4)
Check correct movement of each screw motor by pushing
on “docking penetration” push button (30FCJ10GH140-
S08) on MCD control panel. Remain pushing during a few
seconds.
Check movement of each screw motor stopped by
releasing “docking penetration” push button.
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S16 key switch)
Docking device screen displayed on operating SCADA
SFCTM not at penetration station (PS) (30FCJ13CG144-
S01 and 30FCJ13CG145-S01 = false) (else interlock of the
screw motors by SRCF#15)
- Action:
Select successively screw 1,2,3 and 4.motors (AE261,
AE271, AE281, AE291) on operating SCADA and select
corresponding position of screw key (30FCJ10GH140-S11)
(position 1&3 for screws 1 & 3 and position 2&4 for screws
2 & 4)
A REFERENCE REV. FILE PAGE
- Initial status:
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S16 key switch)
Docking device screen displayed on operating SCADA
- Action:
(a) Select AA071 valve in operating SCADA docking device
screen
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – ANTI SEISMIC LOCKING DEVICE
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action:
a. Select Anti seismic “0” motor (AE231) on operating SCADA
Check correct movement for locking anti seismic device 0
by pushing on “anti seismic lock” push button
(30FCJ10GH140-S08) on MCD control panel. Remain
pushing during a few seconds.
Check movement for locking anti seismic device 0 stopped
by releasing push button
Check correct movement for unlocking anti seismic device
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – ANTI SEISMIC LOCKING DEVICE
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
0 by pushing on “anti seismic unlock” push button
(30FCJ10GH140-S09) on MCD control panel. Remain
pushing during a few seconds.
Check movement for unlocking anti seismic device 0
stopped by releasing push button
- Action:
a. Select biological key (30FCJ10GH140-S12) on “0” and select
Biological protection “0” motor (AE241) on operating SCADA
Check opening biological protection 0 by pushing on
“Open” push button (30FCJ13GF222-S03) on SFCTM
pendant control 2 (30FCJ13GF222). Remain pushing
during a few seconds.
Check biological protection 0 movement stopped by
releasing push button.
Check closing biological protection 0 by pushing on “Close”
A REFERENCE REV. FILE PAGE
- Action:
Unlock upper cover anti seismic device with PSCP HMI
Check upper cover opening movement by starting Upper
cover opening with PSCP HMI
Check upper cover opening movement stopped by
stopping movement with PSCP HMI
Check upper cover closing movement by closing Upper
cover with PSCP HMI
A REFERENCE REV. FILE PAGE
- Action:
Select successively all valves hereafter in the
corresponding maintenance view in display SCADA
Check correct opening of each valve by pushing on “open
valve” push button (30FCJ10GH140-S08). Remain push
button until corresponding valve is not opened.
Check correct closing of each valve by pushing on “Close
valve” push button (30FCJ10GH140-S09). Remain push
button until corresponding valve is not closed.
Valves to be checked :
- Action:
Check travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) immediately
disconnected from the power supply by pushing on
“SFCTM run forward” push button (30FCJ10GH140S18) on
MCD Control panel and pushing on “Emergency Stop”
(30FCJ10GH140-S17) on MCD Control panel (“SFCTM run
forward” push button is remained)
A REFERENCE REV. FILE PAGE
- Action:
Check Service elevator motor (30FCJ13AE251-M01)
immediately disconnected from the power supply by
pushing on “Up” push button (30FCJ13GF222-S04) on
Pendant control 2 (30FCJ13GF222) and on Emergency
stop button (30FCJ13GF222-S05). “Up” push button is
remained.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – BIOLOGICAL LID HANDLING DEVICE
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action:
Check Lid handling motor (30FCJ11AE401-M01)
immediately disconnected from the power supply (motor
OFF) by pushing on “Gripper up” push button
(30FCJ11GH310-S09) on BLHS control panel (GH310
cabinet) and pushing GH310 cabinet Emergency stop
(30FCJ11GH310-S05). “Gripper up” push button is
remained.
A REFERENCE REV. FILE PAGE
- Action:
Select successively screw 1,2,3 and 4 motors (AE261,
AE271, AE281, AE291) on operating SCADA and select
corresponding position of screw key (30FCJ10GH140-S11)
(position 1&3 for screw 1 & 3 and position 2&4 for screw 2
& 4)
Check corresponding screw motor immediately
disconnected from the power supply (motor OFF) by
pushing on “docking penetration” push button
(30FCL10GH140-S08) on MCD control panel and pushing
on MCD control panel Emergency Stop (30FCJ10GH140-
S17). “Docking penetration” push button is remained.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – ANTI SEISMIC LOCKING DEVICE
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action:
a. Select Anti seismic device “0” motor (AE231) on operating
SCADA
Check anti seismic 0 motor immediately disconnected from
the power supply (motor OFF) by pushing on “anti seismic
lock” push button (30FCJ10GH140-S08) on MCD control
panel and pushing on Emergency Stop button on MCD
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – ANTI SEISMIC LOCKING DEVICE
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
control panel (30FCJ10GH140-S05). “Anti seismic lock”
push button is remained.
b. Select Anti seismic device “200” motor (AE235) on operating
SCADA
Check anti seismic 200 motor immediately disconnected
from the power supply (motor OFF) by pushing on “anti
seismic unlock” push button (30FCJ10GH140-S09) on
MCD control panel and pushing on Emergency Stop button
on MCD control panel (30FCJ10GH140-S05). “Anti
seismic unlock” push button is remained.
A REFERENCE REV. FILE PAGE
- Action:
a. Select Biological protection “0” motor (AE241) on operating
SCADA and set biological “0” on MCD control panel
(30FCJ10GH140-S12 key switch)
Check biological protection 0 motor immediately
disconnected from the power supply (motor OFF) by
pushing on “Open” push button (30FCJ13GF222-S03) on
SFCTM pendant control 2 (30FCJ13GF222) and pushing
on SFCTM pendant control 2 Emergency Stop button
A REFERENCE REV. FILE PAGE
- Action:
Unlock upper cover anti seismic device with PSCP HMI
Check Hoist motor, operational brake and auxiliary brake
immediately disconnected from the power supply (motor
and brakes OFF) by starting opening Upper cover with
PSCP HMI and pushing on “PSCP Emergency Stop” push
button (30FCJ12GH410-S06)
A REFERENCE REV. FILE PAGE
As described in the Safety Basic Design Description [R15], the Functional entity (FE) listed below are concerned.
SPLC FUNCTIONAL ENTITIES
SRCF# name Functional entity & related
specification functions Safety function Designation of SRCF
SRCF#1 FE01 S_FCT_1 Monitoring cask water level
SRCF#4 FE02 S_FCT_4 Monitoring cask fins temperature
SRCF#5 FE03 S_FCT_5 Monitoring cask water temperature
Interlock of the upper cover by the SFMB and Swivel Gate between UFSR and SFCTF zone is
SRCF#7 FE04 S_FCT_7
CLOSED
SRCF#8 FE05 S_FCT_8 Interlock of the SFMB by the upper cover
Advise the operator that the leak tightness tests of valve tools shall be validated before rinsing
SRCF#11 FE07 S_FCT_11
the valves tools
Interlock the penetration in rest position with the anti seismic locking devices when the SFCTM
SRCF#12 FE08 S_FCT_12
is at the penetration station
SRCF#13 FE09 S_FCT_13 Monitoring of cask water level for lowering the lid
Monitoring of water level for movement of the SFCTM at the penetration station towards the lid
SRCF#14 FE10 S_FCT_14
handling station
SRCF#15 FE11 S_FCT_15 Monitoring of cask water level for undocking the penetration
Interlock of penetration filling with correct docking and monitor the force on the seals of the
SRCF#16 FE12 S_FCT_16
penetration
Interlock the motion of the upper cover of the penetration with the penetration docked and cask
SRCF#17 FE13 S_FCT_17
water level
SRCF#18 FE14 S_FCT_18 Monitoring the leak tightness of the upper cover
SRCF#19 FE15 S_FCT_19 Checking the position of the biological protections and of the service elevator before the travel
of the SFCTM from the handling opening station to the lid handling station
Checking the position of the service elevator, of the penetration and of the docking screws
SRCF#20 FE16 S_FCT_20
before the travel of the SFCTM from the penetration station to the lid handling station
Checking the position of the service elevator, of the lower plate, of the docking screws, of the
SRCF#21 FE17 S_FCT_21 biological protections and of the penetration before the travel of the SFCTM from the lid
handling station to the penetration station
A REFERENCE REV. FILE PAGE
SRCF#22 FE18 S_FCT_22 Prevent the SFCTM to go directly from the handling opening station to the penetration station
when high speed is selected.
SRCF#23 FE19 S_FCT_23 Prevent the SFCTM to get out a station area when low speed is selected
PSRCF#4 FE20 S_FCT_P4 Interlock biological protections opening with manual command plugged
PSRCF#5 FE21 S_FCT_P5 Prevent the SFCTM to go directly from the penetration station to the handling opening station
PSRCF#6 FE22 S_FCT_P6 Interlock service elevator with manual command plugged
Table 3 – List of SPLC functional entities (FE)
Note: After each fault set, alarm or warning has to be acknowledged, ie fault set deactivated (return to normal mode by releasing fault set) and “Alarm
acquit” push button on MCD control panel (30FCJ10GH140-S04) pushed.
A REFERENCE REV. FILE PAGE
- Action:
Check :
− SC3 valves closed: AA013, AA020, AA401, AA402,
AA406, AA413, AA510, AA025, AA403
− Blinking MCD control panel Safety Alarm ON
(30FCJ10GH140-H14)
− “Abnormal cask water level L1” alarm (n°19 ) displayed
on HMI
− “Close SC3 manual valves” message displayed on
HMI (Window pop-up)
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
− PS Control Panel Buzzer (30FCJ12GH410-P01) ON
A REFERENCE REV. FILE PAGE
Note:
AA013 SC3 valve is always closed and opening movement is not
available, except for SRCF#16 initial status (SRCF#16 interlock).
According to this interlock, AA013 valve can not be opened:
action of these SRCF on valve AA013 can not be checked.
A REFERENCE REV. FILE PAGE
- Action:
Check:
− “Overheating of the fins” alarm (n°20 ) displayed on
HMI
− Blinking MCD control panel Safety Alarm ON
(30FCJ10GH140-H14)
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
- Initial status:
No alarm
- Action:
Check “Fins temperature sensor default” alarm (n°6 )
displayed on HMI, MCD Control Panel Buzzer
(30FCJ10GH140-P01) ON and PS Control Panel Buzzer
(30FCJ12GH410-P01) ON by setting CT196 and CT199
such as: CT196 – CT199 > T1_fins temperature sensor
discrepancy threshold.
- Action:
Check :
− “Overheating of the water” alarm (n°21 ) displayed on
HMI
− Blinking MCD control panel Safety Alarm ON
(30FCJ10GH140-H14)
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
- Initial status:
No alarm
- Action:
Check “Water temperature sensor default” alarm (n°8)
displayed on HMI, MCD Control Panel Buzzer
(30FCJ10GH140-P01) ON and PS Control Panel Buzzer
(30FCJ12GH410-P01) ON by setting CT195 and CT198
such as CT195 – CT198 > T1_ water temperature sensor
discrepancy threshold.
CT195 and CT198 will be set by connecting two 4-20mA
generators (1 per sensor) in 30FCJ13GH210-X201
between 13&14 and 16&17 terminals. (CT195 and CT198
sensors have been removed).
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “PS” position
(30FCJ10GH140-S16 key switch)
Upper cover screen displayed on operating SCADA
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Upper cover closed (30FCJ12CG037-S01 detector = true)
Upper cover anti seismic device unlocked
Anti-seismic device 0 & 200 locked:
− Anti seismic 0 locked 1/2 detector
(30FCJ13CG151-S01) = true
− Anti seismic 200 locked 1/2 detector
(30FCJ13CG154-S01) = true
Cask is docked :
− Penetration docked 1/2 detector (30FCJ12CG042-
S01) = true
Screw load limiter OK :
A REFERENCE REV. FILE PAGE
- Action 1:
a. SFMB not in SFCTF zone AND UFSR/SFCTF swivel gate
closed:
Check Upper cover movement available by:
− Setting SFMB not in the SFCTF zone and Swivel gate
between UFSR and SFCTF zones closed 1/2 = true :
set an open circuit between 01&02 terminals in
30FCJ12GH410-X232 terminal strip.
− Setting SFMB not in the SFCTF zone and Swivel gate
between UFSR and SFCTF zones closed 2/2 = true :
set an open circuit between 03&04 terminals in
30FCJ12GH410-X232 terminal strip.
− Starting opening upper cover with PSCP HMI
A REFERENCE REV. FILE PAGE
- Action 1:
a. Upper cover is opened
Check SFMB motor not inhibited (check close circuit
between 5&6 terminals and 7&8 in 30FCJ12GH410-X232
terminal strip) by setting upper cover open detector 1/2 &
2/2 = true (in the simulated operative part)
b. Upper cover not opened
Check :
− SFMB motor inhibited through an external interlock:
check open circuit between 5&6 terminals and 7&8
terminals in 30FCJ12GH410-X232 terminal strip
− “Upper cover is not open” warning (n°23 ) displayed on
HMI
By setting upper cover open detector 1/2 = false and upper
cover open detector 2/2 = false (in the simulated operative
part)
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Upper cover opened (upper cover open detector 1/2 & 2/2
= true in the simulated operative part)
- Action:
Check :
− interlock to SFMB switched OFF : check open circuit
between 5&6 terminals and 7&8 in 30FCJ12GH410-
X232 terminal strip
− “SFMB motor relays default” warning (n°10 ) displayed
on HMI
By setting a close circuit between 21&24 terminals of
30FCJ12GH410-K23 contactor in GH410 cabinet.
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
SFCTM not at Handling Opening Station ( 30FCJ13CG142-
S01 and 30FCJ13CG143-S01 = false)
Tightness tests of valve tools not validated
(30FCJ10GH140-S20)
- Action 1:
(a) Check:
− Blinking MCD control panel Safety Alarm ON
(30FCJ10GH140-H14)
− “Leak tightness test of valve tools shall be validated
before rinsing the valves tools” warning (n°24)
displayed on HMI
A REFERENCE REV. FILE PAGE
(b) Check :
− Blinking MCD control panel Safety Alarm OFF
(30FCJ10GH140-H14)
− “Leak tightness test of valve tools shall be validated
before rinsing the valves tools” warning (n°24)
deactivated on HMI
By pushing on “Leak tightness test on cask plug” push
button on MCD control panel (30FCJ10GH140-S20) (Push
button not remained)
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
Penetration in rest position :
− Penetration in rest position detector 1
(30FCJ12CG045-S01) = true
− Penetration in rest position detector 2
(30FCJ12CG046-S01) = true
− Penetration in rest position detector 3
(30FCJ12CG047-S01) = true
Anti seismic device screen displayed on operating SCADA
A REFERENCE REV. FILE PAGE
- Action 1:
(b) Initial status and select anti seismic 200 motor (AE235) on
operating SCADA
Check Anti seismic motors 0 (30FCJ13AE231-M01) OFF ,
“Switch OFF anti seismic motor” warning (n°25) and
“Penetration in rest position detector discrepancy alarm”
displayed on HMI by:
− Starting locking anti seismic device: push on “anti
seismic lock” push button on MCD control panel
(30FCJ10GH140-S08). Push button is remained (few
seconds)
− Setting penetration in rest position detector 1
(30FCJ12CG045-S01) = false : set a close circuit
A REFERENCE REV. FILE PAGE
- Action 2:
Repeat action 1 but set penetration in rest position detector
2 (30FCJ12CG046-S01) = false : set a close circuit
between terminals 27&28 of 30FCJ10GH130-X235
Check same expected results.
- Action 3:
Repeat action 1 but set penetration in rest position detector
3 (30FCJ12CG047-S01) = false : set a close circuit
between terminals 29&30 of 30FCJ10GH130-X235
Check same expected results.
(b) Initial status and select anti seismic 200 motor (AE235) on
operating SCADA
Check Anti seismic motors 0 (30FCJ13AE231-M01) OFF ,
“Switch OFF anti seismic motor” warning (n°25) and
“SFCTM at the Penetration station detector discrepancy
alarm” displayed on HMI by:
− Starting locking anti seismic device: push on “anti
seismic lock” push button on MCD control panel
(30FCJ10GH140-S08). Push button is remained (few
seconds)
− Activating only SFTCM at penetration station detector
1/2 (30FCJ13CG144-S01)
Check Anti seismic motors 0 (30FCJ13AE231-M01) OFF ,
“Switch OFF anti seismic motor” warning (n°25) and
“SFCTM at the Penetration station detector discrepancy
alarm” displayed on HMI by:
− Starting locking anti seismic device: push on “anti
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
A REFERENCE REV. FILE PAGE
- Action:
Check anti seismic motor OFF (no movement), “anti
seismic 0 motor and anti seismic 200 motor contactors
default” alarm (n°11) displayed on HMI , MCD Control Panel
Buzzer (30FCJ10GH140-P01) ON and PS Control Panel
Buzzer (30FCJ12GH410-P01) ON by :
− Starting locking anti seismic device (Push on “anti
seismic lock” push button on MCD control panel
(30FCJ10GH140-S08). Push button is remained
− Setting a close circuit between 11&12 terminals of
30FCJ13GH210-K18 contactor in GH210 cabinet
− Selecting anti seismic 0 motor (AE231) in operating
SCADA
- Initial status:
No alarm
SFCTM is at biological lid handling station (BLHS)
detectors (30FCJ13CG140-S01 and 30FCJ13CG141-S01
= true) on accurate position (30FCJ13CG001-B01 and
30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “BLHS” position
(30FCJ10GH140-S16 key switch)
Lid handling motor (AE401) selected on operating SCADA
- Action 1:
Check :
− Lid handling device motor (30FCJ11AE401-M01) OFF
− “Abnormal cask water level L2” warning (n°26)
displayed on HMI
By :
− Starting moving lid handling device: push on “Gripper
up“ push button (30FCJ11GH310-S09) on BLHS
control panel. Push button is remained (few seconds)
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM is at biological lid handling station (BLHS)
detectors (30FCJ13CG140-S01 and 30FCJ13CG141-S01
= true) on accurate position (30FCJ13CG001-B01 and
30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “BLHS” position
(30FCJ10GH140-S16 key switch)
Lid handling motor (AE401) selected on operating SCADA
- Action:
Check:
− Lid handling device motor (30FCJ11AE401-M01) OFF
− “Lid handling device contactors default” alarm (n°13)
displayed on HMI
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
− PS Control Panel Buzzer (30FCJ12GH410-P01) ON
By :
− Starting moving lid handling device: push on “Gripper
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
High speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
Travelling platform screen displayed on operating SCADA
Travelling motor (AE201) selected on operating SCADA
- Action 1:
Check :
− Travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) of the SFCTM
OFF.
− “Incorrect cask water level for SFCTM movement”
alarm (n°27) displayed on HMI
A REFERENCE REV. FILE PAGE
By :
− Starting moving SFCTM to lid handling station: push
“SFCTM run reverse” push button (30FCJ10GH140-
S18). Push button is remained.
− Setting an abnormal water level in the cask (L3_Cask
water level threshold - 10%) (CL197 sensor)
CL197 level is set by connecting a 4-20mA generator
in 30FCJ13GH210-X201 terminal strip between 07&08
terminal. (CL197 sensor has been removed).
Set the corresponding value according to L3_Cask
water level threshold and sensor scale, i.e. set 15.2
mA.
Initial status
Check :
− Travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) of the SFCTM
OFF.
− “SFCTM at penetration station detector discrepancy
alarm” displayed on HMI
By:
− Starting moving SFCTM to lid handling station: push
“SFCTM run reverse” push button (30FCJ10GH140-
S18). Push button is remained.
− Activating only SFTCM at PS detector 2/2
(30FCJ13CG145-S01)
Initial status
Check :
− Travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) of the SFCTM
OFF.
− “Pushbutton SFCTM run reverse contact discrepancy
alarm” displayed on HMI
By:
− Starting moving SFCTM to lid handling station: push
“SFCTM run reverse” push button (30FCJ10GH140-
S18). Push button is remained.
− Setting a close circuit between terminals 11&12 of
30FCJ10GH130-X231 terminal strip.
Initial status
Check :
− Travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) of the SFCTM
OFF.
− “HS selector contact discrepancy alarm” displayed on
HMI
By:
− Starting moving SFCTM to lid handling station: push
“SFCTM run reverse” push button (30FCJ10GH140-
S18). Push button is remained.
A REFERENCE REV. FILE PAGE
By :
− Starting moving SFCTM to lid handling station: push
“SFCTM run reverse” push button (30FCJ10GH140-
S18). Push button is remained.
− Disconnecting water level sensor (CL197 sensor) :
remove wire from terminal 08 of 30FCJ13GH210-X201
terminal strip
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Cask is docked :
− Penetration docked 1/2 detector (30FCJ12CG042-
S01) = true
− Penetration docked 2/2 detector (30FCJ12CG043-
S01) = true
Docking device screen selected on operating SCADA
- Action 1:
Check :
− Undocking devices (motor screws 30FCJ13AE261-
M01, 30FCJ13AE271-M01, 30FCJ13AE281-M01,
30FCJ13AE291-M01 ) OFF (screws motors not
available in operating SCADA)
− “Abnormal cask water level L4” warning (n°28)
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Docking device screen selected on operating SCADA
- Action:
Check :
− “Motor screw 1&3 contactor default” alarm (n°14 )
displayed on HMI
− Screw 1 motor (30FCJ13AE261-M01) OFF
− MCD Control Panel Buzzer (30FCJ10GH140-P01)
ON
− PS Control Panel Buzzer (30FCJ12GH410-P01) ON
By :
− Selecting screw 1 motor (AE261) on operating
SCADA
A REFERENCE REV. FILE PAGE
By :
− Selecting screw motor (AE281) on operating
SCADA
− Pushing on “docking penetration” push button on
MCD control panel (30FCJ10GH140-S08). Push
button is remained.
− Setting a close circuit between 11&12 terminals of
30FCJ13GH210-K22 contactor relay in GH210
cabinet
Check :
− “Motor screw 2&4 contactor default” alarm (n°14 )
displayed on HMI
− Screw 2 motor (30FCJ13AE271-M01)OFF
A REFERENCE REV. FILE PAGE
By :
− Selecting screw 2 motor (AE271) on operating
SCADA
− Pushing on “docking penetration” push button on
MCD control panel (30FCJ10GH140-S08). Push
button is remained.
− Setting a close circuit between 11&12 terminals of
30FCJ13GH210-K24 contactor relay in GH210
cabinet
Check :
− “Motor screw 1&3 contactor default” alarm (n°14 )
displayed on HMI
− Screw 4 motor (30FCJ13AE291-M01)OFF
By :
− Selecting screw 4 motor (AE291) on operating
SCADA
− Pushing on “docking penetration” push button on
MCD control panel (30FCJ10GH140-S08). Push
button is remained (few seconds).
− Setting a close circuit between 11&12 terminals of
30FCJ13GH210-K24 contactor relay in GH210
cabinet
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “PS” position
(30FCJ10GH140-S15 key switch)
Anti-seismic device 0 & 200 locked:
− Anti seismic 0 locked 1/2 detector
(30FCJ13CG151-S01) AND Anti seismic 0 locked
2/2 detector (30FCJ13CG152-S01) activated
− Anti seismic 200 locked 1/2 detector
(30FCJ13CG154-S01) AND Anti seismic 200
locked 2/2 detector (30FCJ13CG155-S01)
activated
Cask is docked :
− Penetration docked 1/2 detector (30FCJ12CG042-
S01) AND Penetration docked 2/2 detector
A REFERENCE REV. FILE PAGE
- Action 1:
(a) Check “Penetration filling not possible” alarm
deactivated (no action)
(b) Check “Penetration filling not possible” warning (n°29)
activated and AA013 valve closed, by setting a fault on
SFCTM anti-seismic device 0 :
Deactivate anti seismic 0 locked 1/2 detector
(30FCJ13CG151-S01) AND anti seismic 0 locked 2/2
A REFERENCE REV. FILE PAGE
- Note : after each fault tested, ensure initial status is OK (ie set
corresponding detector activated and push on “Correct pressure of
the penetration” push button (30FCJ10GH140-S22) and open
AA013 valve (select AA013 valve on display SCADA and push on
“Open” push button (30FCJ10GH140-S08))”.
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Anti-seismic device 0 & 200 locked:
− Anti seismic 0 locked 1/2 detector
(30FCJ13CG151-S01) AND Anti seismic 0 locked
2/2 detector (30FCJ13CG152-S01) activated
− Anti seismic 200 locked 1/2 detector
(30FCJ13CG154-S01) AND Anti seismic 200
locked 2/2 detector (30FCJ13CG155-S01)
activated
Cask is docked :
− Penetration docked 1/2 detector (30FCJ12CG042-
S01) AND Penetration docked 2/2 detector
(30FCJ12CG043-S01) activated
A REFERENCE REV. FILE PAGE
- Action:
(a) Check “Movement of the upper cover is not allowed”
warning (n°30) deactivated on HMI (no action)
(b) Check
− “Movement of the upper cover is not allowed”
warning (n°30) activated on HMI
− Upper cover hoist motor OFF
− Upper cover hoist operational brake OFF
− Upper cover hoist auxiliary brake OFF
By setting successively a fault on devices hereafter and
A REFERENCE REV. FILE PAGE
Note :
- Initial status:
No alarm
- Action 1:
Check expected result of the logic table hereafter by setting
each inputs condition
A REFERENCE REV. FILE PAGE
p_ tion
cy
pp Lam tra
an
_1
_2
o 2
ar is e
n
tra ar v_ _Q_
ns k _
Q
ep
al or d f th
_Q
ss
ss
tio
g
en
se ea _Q
in
m cr
ea htne
ne
a
p
rm
_A itor
n "L ak
iz
ea
e
ht
or
la
tio m le
th
on
ig
ig
_l
"
th
pA
iv
of
kT
kT
ov
_p _M
ct
o
am
By eak
ea
ne I_a C
A
s
pe M Upp
ss
as
_L
_l
_l
as
"L
l
a
_U
ov
ov
_p
_p
_
m
C
C
C
By
R
M
ar
pp
pp
By
C
H
al
M
U
I_
M
H
1 1 0 0 0 0 1 0 0 0
0 1 0 0 0 0 0 0 0 0
1 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
1 1 1 0 0 0 1 0 0 1
0 1 1 0 1 1 0 1 0 1
1 0 1 0 1 1 0 1 0 1
0 0 1 0 1 1 0 1 0 1
1 1 0 1 0 0 1 0 0 1
0 1 0 1 1 1 0 0 1 1
1 0 0 1 1 1 0 0 1 1
0 0 0 1 1 1 0 0 1 1
1 1 1 1 0 0 1 0 0 0
0 1 1 1 1 1 0 1 1 0
1 0 1 1 1 1 0 1 1 0
0 0 1 1 1 1 0 1 1 0
- Initial status:
No alarm
SFCTM at Handling Opening Station ( 30FCJ13CG142-
S01 and 30FCJ13CG143-S01 activated)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
High speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
Travelling platform screen displayed on operating SCADA
Travelling motor (AE201) selected on operating SCADA
Biological protections opened:
− Biological protection 0 open 1/2 detector
(30FCJ13CG054-S01) AND Biological protection
0 open 2/2 detector (30FCJ13CG055-S01)
activated
− Biological protection 200 open 1/2 detector
(30FCJ13CG062-S01) AND Biological protection
200 open 2/2 detector (30FCJ13CG063-S01) = l
A REFERENCE REV. FILE PAGE
- Action 1:
(a)Check travelling forward movement available by pushing
on “SFCTM run forward” push button (30FCJ10GH140-
S18)
(b) Check :
− Travelling forward movement not available
(30FCJ13GH210-K14 and 30FCJ13GH210-K15
contactors deactivated) ,
− “SFTCM transfer is inhibited” alarm (n°32)
displayed on HMI,
by:
− Setting an incorrect position of the biological
protections:
Set Biological protection 0 open 1/2 detector
(30FCJ13CG054-S01) = false AND Biological
protection 0 open 2/2 detector (30FCJ13CG055-
S01) = false
Set Biological protection 200 open 1/2 detector
(30FCJ13CG062-S01) = false AND Biological
protection 200 open 2/2 detector
A REFERENCE REV. FILE PAGE
(c) Check :
− Travelling forward movement not available
(30FCJ13GH210-K14 and 30FCJ13GH210-K15
contactors deactivated) ,
− “SFTCM transfer is inhibited” alarm (n°32)
displayed on HMI,
by:
− Setting an incorrect position of the service
elevator:
Set Service elevator in low position 1/2 detector
(30FCJ13CG068-S01) = false AND Service
elevator in low position 2/2 detector
(30FCJ13CG069-S01) = false
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
High speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
Travelling screen displayed on operating SCADA
Travelling motor (AE201) selected on operating SCADA
Service elevator in low position:
− Service elevator in low position 1/2 detector
(30FCJ13CG068-S01) AND Service elevator in
low position 2/2 detector (30FCJ13CG069-S01)
activated
Penetration in rest position :
− Penetration in rest position detector 1
(30FCJ12CG045-S01) AND Penetration in rest
A REFERENCE REV. FILE PAGE
- Action:
(a) Check SFCTM travelling reverse movement by pushing
on “SFCTM run reverse” push button (30FCJ10GH140-
S19)
(b) Check :
− Travelling reverse movement not available
(30FCJ13GH210-K14 and 30FCJ13GH210-K15
contactors deactivated) ,
− “SFTCM transfer is inhibited” alarm (n°33 )
displayed on HMI,
A REFERENCE REV. FILE PAGE
(f) Check :
− Travelling reverse movement not available
(30FCJ13GH210-K14 and 30FCJ13GH210-K15
contactors deactivated) ,
− “SFTCM transfer is inhibited” alarm (n°33)
displayed on HMI,
by:
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM is at biological lid handling station (BLHS)
detectors (30FCJ13CG140-S01 and 30FCJ13CG141-S01
= true)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Travelling screen displayed on operating SCADA
Travelling motor selected on operating SCADA
Lower plate not installed :
− Lower plate in place 1/2 detector
(30FCJ12CG048-S01) deactivated
− Lower plate in place 2/2 detector
(30FCJ12CG049-S01) deactivated
Screws 1,2,3&4 at rest position
A REFERENCE REV. FILE PAGE
- Action 1:
(a) Check SFCTM travelling forward movement by pushing
on “SFCTM run forward” push button (30FCJ10GH140-
S18)
(b) Check :
− Travelling reverse movement not available
(30FCJ13GH210-K14 and 30FCJ13GH210-K15
contactors deactivated) ,
− “Movement of the SFCTM is not possible” alarm
(n°34)
by:
− Setting an incorrect position of the lower plate:
Set lower plate in place 1/2 detector
(30FCJ12CG048-S01) AND lower plate in place
1/2 detector (30FCJ12CG048-S01) activated
A REFERENCE REV. FILE PAGE
(g) Check :
− Travelling reverse movement not available
(30FCJ13GH210-K14 and 30FCJ13GH210-K15
contactors deactivated) ,
− “Movement of the SFCTM is not possible” alarm
(n°34)
by:
− Setting an incorrect position of the biological
protections
Set Biological protection 0 closed 1/2 detector
(30FCJ13CG056-S01) andt Biological protection
0 closed 2/2 detector (30FCJ13CG057-S01)
deactivated
(e) Check :
− Travelling reverse movement not available
(30FCJ13GH210-K14 and 30FCJ13GH210-K15
contactors deactivated) ,
− “Movement of the SFCTM is not possible” alarm
(n°34)
by:
− Setting an incorrect position of the penetration:
Set :
Penetration in rest position detector 1
(30FCJ12CG045-S01) deactivated
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at Handling Opening Station ( 30FCJ13CG142-
S01 and 30FCJ13CG143-S01 activated)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
High speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
Travelling screen displayed on operating SCADA
Travelling motor (AE201) selected on operating SCADA
- Action 1:
Check :
− SFCTM travelling forward stopped (Travelling motor
(30FCJ13AE201-M01) and operational brake of the
SFCTM (30FCJAE201-Y01) OFF
− “Safe stop of SFCTM at BLHS coming from HOS”
alarm displayed on HMI (Alarm n°35)
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM is successively at each station (corresponding
detectors activated)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Travelling screen displayed on operating SCADA
Travelling motor (AE201) selected on operating SCADA
Low speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
- Action 1:
(a) SFCTM under no station (all station detectors deactivated)
Check:
− Travelling motor (30FCJ13AE201-M01) and
operational brake of the SFCTM (30FCJ13AE201-
Y01) ON (travelling movement available)
By :
− Pushing on “SFCTM run reverse" push button
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at Handling Opening Station (30FCJ13CG142-S01
and 30FCJ13CG143-S01 = true)
Manual command is plugged (pendant control 2
30FCJ13GF222) on 30FCJ13GF218 junction box
SFCTM pendant control 2 activated
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Biological protection screen displayed on operating SCADA
“Biological key” (30FCJ10GH140-S12) selected on “All” on
the MCD control panel
- Action 1:
Check :
− Biological protections motors (30FCJ13AE241-M01 &
30FCJ13AE245-M01) OFF
− “Biological protections movement are inhibited”
warning displayed on HMI (warning n°37)
By:
− Starting opening biological protections : push on
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at Handling Opening Station (30FCJ13CG142-S01
and 30FCJ13CG143-S01 = true)
Manual command plugged (pendant control 2
30FCJ13GF222) on 30FCJ13GF218 junction box
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Biological protection screen displayed on operating SCADA
“Biological key” (30FCJ10GH140-S12) selected on “All” on
the MCD control panel
- Action:
Check :
− Biological protections motors (30FCJ13AE241-M01 &
30FCJ13AE245-M01)OFF
− “Biological protections contactors default” alarm
displayed on HMI (Alarm n°17)
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
− PS Control Panel Buzzer (30FCJ12GH410-P01) ON
By:
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 activated)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Travelling screen displayed on operating SCADA
Travelling motor selected (AE201) selected on operating
SCADA
High speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
- Action 1:
Check:
− Travelling motor (30FCJ13AE201-M01) and
operational brake of the SFCTM (30FCJ13AE201-
Y01) OFF
− “Safe stop of SFCTM at BLHS coming from PS”
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Service elevator screen displayed on operating SCADA
Service elevator motor (AE251) selected on operating
SCADA
Manual command is plugged (pendant control 2
30FCJ13GF222) on 30FCJ13GF219 junction box
- Action 1:
Check:
− Service elevator motor (30FCJ13AE251-M01)OFF
− “Service elevator movement are inhibited” warning
displayed on HMI (warning n°39)
By:
− Pushing on “Up” push button (30FCJ13GF222-
S04) on pendant control 2 (30FCJ13GF222),
push button remained.
− Unplugging pendant control 2(30FCJ13GF222)
from 30FCJ13GF219 junction box
A REFERENCE REV. FILE PAGE
- Action:
(a) Fault on AA013 valve relay (30FCJ10GH130-K06):
Check :
− “Valves relays default” alarm (n°1) displayed on H MI.
− AA013 valve closed
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
− PS Control Panel Buzzer (30FCJ12GH410-P01) ON
By:
− Opening AA013 valve: select AA013 valve in display
SCADA and push on 30FCJ10GH140-S08 push
button (push button remained until corresponding
valve is opened)
− Setting a close circuit between terminals 61&62 of
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “PS” position
(30FCJ10GH140-S16 key switch)
Upper cover screen displayed on operating SCADA
Upper cover motor selected on PSCP HMI
- Action:
Check
− Hoist motor, hoist operating brake and hoist auxiliary
brake OFF
− “Upper cover hoist motor, Upper cover hoist
operational brake & Upper cover hoist auxiliary brake
contactors default” alarm (n°9) displayed on HMI.
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
− PS Control Panel Buzzer (30FCJ12GH410-P01) ON
By:
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
Travelling screen displayed on operating SCADA
Travelling motor (AE201) selected on operating SCADA
- Action:
Check:
SFCTM motor (30FCJ13AE201-M01) and operational
brake (30FCJ13AE201-Y01) OFF
“SFCTM Motor & SFCTM Operational brake contactors
default” alarm (n°4) displayed on HMI
MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
PS Control Panel Buzzer (30FCJ12GH410-P01) ON
By:
− Setting a close circuit between terminals 41&42 of
30FCJ13GH210-K14 relay in GH210 cabinet
− Pushing on “run forward” push button
(30FCJ10GH140-S18) on MCD control panel (push
button remained a few seconds)
A REFERENCE REV. FILE PAGE
- Action:
Check “Lamp alarm circuit fault alarm (n°5) displa yed, MCD
Control Panel Buzzer (30FCJ10GH140-P01) ON and PS
Control Panel Buzzer (30FCJ12GH410-P01) ON by
removing wire from terminal 42 of 30FCJ10GH140-X231
terminal strip.
A REFERENCE REV. FILE PAGE
- Action:
(a) Loading Hall Emergency stop 1 (30FCJ13CH012-S01) check
Check :
− Travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) OFF
− Automatic SC3 valves closed (AA020, AA401, AA402,
AA406, AA413, AA510, AA025, AA403)
− Blinking MCD alarm lamp ON (30FCJ10GH140-H14)
A REFERENCE REV. FILE PAGE
Check :
− Travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) OFF
− Automatic SC3 valves closed (AA020, AA401, AA402,
AA406, AA413, AA510, AA025, AA403)
− Blinking MCD alarm lamp ON (30FCJ10GH140-H14)
− “SPLC Emergency stop 2 (safety relay 2)” alarm (n°8 3)
displayed on HMI.
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
A REFERENCE REV. FILE PAGE
Check :
− Travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) OFF
− Automatic SC3 valves closed (AA020, AA401, AA402,
AA406, AA413, AA510, AA025, AA403)
− Blinking MCD alarm lamp ON (30FCJ10GH140-H14)
− “SPLC Emergency stop 2 (safety relay 2)” alarm (n°8 3)
displayed on HMI.
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
− PS Control Panel Buzzer (30FCJ12GH410-P01) ON
By :
− Opening SC3 automatic valves: AA020, AA401,
A REFERENCE REV. FILE PAGE
Check :
− Travelling motor (30FCJ13AE201-M01) and
operational brake (30FCJ13AE201-Y01) OFF
− Automatic SC3 valves closed (AA020, AA401, AA402,
AA406, AA413, AA510, AA025, AA403)
− Blinking MCD alarm lamp ON (30FCJ10GH140-H14)
− “SPLC Emergency stop 2 (safety relay 2)” alarm (n°83)
displayed on HMI.
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
− PS Control Panel Buzzer (30FCJ12GH410-P01) ON
By :
− Opening SC3 automatic valves: AA020, AA401,
AA402, AA406, AA413, AA510, AA025, AA403
− Pushing on “Run forward” push button
(30FCJ10GH140-S18) on MCD control panel, push
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
SFCTM at Handling Opening Station (30FCJ13CG142-S01
and 30FCJ13CG143-S01 = true)
Control panel selector set on “HS” position
(30FCJ10GH140-S21 key switch)
- Action:
- Initial status:
SFCTF not powered (only the internal battery in GH210 is
used).
- Action:
Check Flashing light - buzzer 1 (CT196-H01) and flashing
light – buzzer 2 (CT 199-H01) ON (CT196 and CT199
temperature > 70°C) by removing CT196 and CT199
sensors and putting successively CT196 and CT199
sensors in hot water. Initial temperature will be up to 70°C
and temperature decreases.
Water temperature is controlled by an external temperature
sensor.
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “PS” position
(30FCJ10GH140-S15 key switch)
Anti-seismic device 0 & 200 locked:
− Anti seismic 0 locked 1/2 detector
(30FCJ13CG151-S01) = true
− Anti seismic 200 locked 1/2 detector
(30FCJ13CG154-S01) = true
Cask is docked :
− Penetration docked 1/2 detector (30FCJ12CG042-
S01) = true
Screw load limiter OK :
− Screw 1 load limiter 1/2 detector (30FCJ12CG120-
S01) = true
− Screw 2 load limiter 1/2 detector (30FCJ12CG122-
A REFERENCE REV. FILE PAGE
- Action:
Check:
− Upper cover hoist motor OFF
− Operational and auxiliary brakes OFF
− Counterweight unlocking solenoid valve (AA130)
OFF.
− Blinking MCD alarm lamp ON (30FCJ10GH140-
H14)
− PS Emergency stop 1 (safety relay 1) alarm (n°87)
displayed on HMI
− MCD Control Panel Buzzer (30FCJ10GH140-P01)
ON
− PS Control Panel Buzzer (30FCJ12GH410-P01)
ON
By:
A REFERENCE REV. FILE PAGE
- Action:
(a) Set an Under voltage in Power monitoring
(30FCJ10GW110-P01) : set parameter in 400VAC
voltage monitoring (30FCJ10GW110-P01) such as under
voltage parameter > voltage at GW110 cabinet entrance
(b) Set an Over voltage in power unit monitoring
(30FCJ10GW110-P01) : set parameter in 400VAC
voltage monitoring (30FCJ10GW110-P01) such as over
voltage parameter < voltage at GW110 cabinet entrance
Check (for (a) then (b)):
All SFCTM actuators disconnected:
Check open circuit between 1&2; 3&4 and 5&6 terminal of
30FCJ13GH210-K10 and 30FCJ13GH210-K11
contactors
All module C solenoid valve closed:
Check 0 VAC between S1&S2 terminals of
30FCJ13GH210-T01 transformer
All module B and Loading Hall solenoid valves closed:
A REFERENCE REV. FILE PAGE
- Initial status:
Correct voltage
GH310 cabinet powered ON
- Action:
(a) Measure voltage at GH310 cabinet entrance and check
230V between 1L1, 3L2 and 5L3 terminals of K13
compact starter (30FCJ11GH310-K13).
(b) Set an Under voltage in 400VAC voltage monitoring
(30FCJ11GH310-K01): set parameter such as under
voltage parameter > voltage at GH310 cabinet
entrance
(c) Set an Over voltage in 400VAC voltage monitoring
(30FCJ11GH310-K01): set parameter such as over
voltage parameter < voltage at GH310 cabinet
entrance
Check (for (b) & (c)):
− K13 compact starter (30FCJ11GH310-K13)
powered OFF: Check 0V between 1L1, 3L2 and
5L3 terminals of K13.
− “400VAC BLHS cabinet fault” warning (n°600)
A REFERENCE REV. FILE PAGE
- Initial status:
Correct voltage
GH410 cabinet powered ON
- Action:
(a) Measure voltage at GH410 cabinet entrance and check
230V between L1, L2 and L3 terminals of speed variable
unit (30FCJ12GH410-N01).
(b) Set an under voltage in 400VAC voltage monitoring
(30FCJ12GH410-K01): set parameter such as under
voltage parameter > voltage at GH410 cabinet entrance
(c) : Set an under voltage in 400VAC voltage monitoring
(30FCJ12GH410-K01) : set parameter such as under
voltage parameter < voltage at GH410 cabinet entrance
Check (for (b) & (c)):
Speed variable unit powered OFF: Check 0V between L1,
L2 and L3 terminals of 30FCJ12GH410-N01
“400VAC BLHS cabinet fault” warning (n°800) display ed on
HMI
MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
A REFERENCE REV. FILE PAGE
- Initial status:
Correct voltage
GH210 cabinet powered ON
- Action:
(a) Measure voltage at GH410 cabinet entrance and check
30FCJ13GH210-K13 contactor closed and power cut
voltage monitoring lamp (30FCJ13GH210-H01) OFF
(b) Set an under voltage : set parameter in 400VAC voltage
monitoring (30FCJ13GH210-K45) such as under voltage
parameter > voltage at GH410 cabinet entrance
(c) Set an Over voltage : set parameter in 400VAC voltage
monitoring (30FCJ13GH210-K45) such as over voltage
parameter < voltage at GH410 cabinet entrance
- Action:
(1) Emergency stop button (30FCJ13GH210-S16) on GH210 control
panel
(a) SC3 automatic valves check (excepted AA013 valve) check
Check :
− SC3 Automatic valves closed (AA020, AA401, AA402,
AA406, AA413, AA510, AA025 and AA403)
− Blinking MCD alarm lamp ON (30FCJ10GH140-H14)
− “SFCTM Emergency stop (safety relay 1)” alarm (n°84 )
displayed on HMI.
− “Emergency stop” lamp (30FCJ13GH210-H20) ON
A REFERENCE REV. FILE PAGE
By:
− Selecting Anti seismic screen on operating SCADA
− Selecting anti seismic motor 0 on HMI
− Pushing on “Anti seismic lock” push button
(30FCJ10GH140-S08), push button remained
− Pushing on Emergency stop push button
(30FCJ13GH210-S16)
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “BLHS” position
(30FCJ10GH140-S16 key switch)
Lid handling device screen displayed on operating SCADA
- Action:
- Action
Check : Service elevator motor (30FCJ13AE251-M01) OFF
by:
− Connecting pendant control 2 (30FCJ13GF222) to
30FCJ13GF219 junction box
− Activating SFCTM pendant control 2 (30FCJ13GF222)
− Pushing on “elevator down” push button
(30FCJ13GF222-S03), push button remained
− Disconnecting pendant control 2 (30FCJ13GF222)
from 30FCJ13GF219 junction box
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Seismic detection (SFCTM accelerometer)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Emergency stop for seismic detection (SFCTM accelerometer)
1
- Initial status: (SRCF#16 initial status to access opening AA013
valve)
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “PS” position
(30FCJ10GH140-S15 key switch)
Anti-seismic device 0 & 200 locked:
− Anti seismic 0 locked 1/2 detector
(30FCJ13CG151-S01) = true
− Anti seismic 200 locked 1/2 detector
(30FCJ13CG154-S01) = true
Cask is docked :
− Penetration docked 1/2 detector (30FCJ12CG042-
S01) = true
Screw load limiter OK :
− Screw 1 load limiter 1/2 detector (30FCJ12CG120-
S01) = true
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Seismic detection (SFCTM accelerometer)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− Screw 2 load limiter 1/2 detector (30FCJ12CG122-
S01) = true
− Screw 3 load limiter 1/2 detector (30FCJ12CG124-
S01) = true
− Screw 4 load limiter 1/2 detector (30FCJ12CG126-
S01) = true
− Penetration leak tightness made : “Correct
pressure of the penetration” push button
(30FCJ10GH140-S22) pushed (not to be
remained)
− All motorized valves opened: AA025, AA450, AA465,
AA472, AA473, AA474, AA006, AA008, AA012, AA419,
AA020, AA030, AA031, AA032, AA033, AA034, AA035,
AA036, AA302, AA401, AA402, AA403, AA406, AA413,
AA510, AA407, AA408, AA409, AA414, AA071, AA076,
AA081, AA086, AA130, AA212A, AA212B
- Action:
Simulate a seismic detection (SFCTM accelerometer
(30FCJ13CS210-S01): Disconnect wire from terminal
45 from 30FCJ13GH210-X132 terminal strip.
Check :
− “Close all manual valves” information displayed on HMI
− “SFCTM warning seismic detection” warning (n°4 09)
displayed on HMI
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Seismic detection (SFCTM accelerometer)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− All motorized valves closed (AA025, AA450, AA465,
AA472, AA473, AA474, AA006, AA008, AA012, AA419,
AA020, AA030, AA031, AA032, AA033, AA034, AA035,
AA036, AA302, AA401, AA402, AA403, AA406, AA413,
AA510, AA407, AA408, AA409, AA414, AA071, AA076,
AA081, AA086, AA130, AA212A, AA212B)
− All SFCTM actuators OFF :
Start SFCTM travelling motor (AE201) and check
travelling motor OFF
Start Anti-seismic 0&200 motors (AE231 and
AE235) and check anti-seismic motors OFF
Start Service elevator motor (AE251) and check
service elevator motor OFF
Start biological protection 0&200 motors (AE241
and AE245) and check biological protections
0&200 motors OFF
Start docking motors (AE261, AE271, AE281,
AE291)and check docking motors OFF
− Hoist motor OFF, operational and auxiliary brakes
closed :
Open operational brake and check operational
brake closed
Open auxiliary brake and check auxiliary brake
closed
Start opening hoist upper cover and check upper
cover motor OFF
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Seismic detection (SFCTM accelerometer)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− Lid handling motor OFF : Start lid handling motor
(AE401) and check lid handling motor OFF
− MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Seismic detection (Upper cover accelerometer)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Emergency stop for seismic detection (Upper cover accelerometer)
1
- Initial status: (SRCF#16 initial status to access opening AA013
valve)
No alarm
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01 = true) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “PS” position
(30FCJ10GH140-S15 key switch)
Anti-seismic device 0 & 200 locked:
− Anti seismic 0 locked 1/2 detector
(30FCJ13CG151-S01) = true
− Anti seismic 200 locked 1/2 detector
(30FCJ13CG154-S01) = true
Cask is docked :
− Penetration docked 1/2 detector (30FCJ12CG042-
S01) = true
Screw load limiter OK :
− Screw 1 load limiter 1/2 detector (30FCJ12CG120-
S01) = true
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Seismic detection (Upper cover accelerometer)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− Screw 2 load limiter 1/2 detector (30FCJ12CG122-
S01) = true
− Screw 3 load limiter 1/2 detector (30FCJ12CG124-
S01) = true
− Screw 4 load limiter 1/2 detector (30FCJ12CG126-
S01) = true
− Penetration leak tightness made : “Correct
pressure of the penetration” push button
(30FCJ10GH140-S22) pushed (not to be
remained)
All motorized valves opened: AA025, AA450, AA465,
AA472, AA473, AA474, AA006, AA008, AA012, AA419,
AA020, AA030, AA031, AA032, AA033, AA034, AA035,
AA036, AA302, AA401, AA402, AA403, AA406, AA413,
AA510, AA407, AA408, AA409, AA414, AA071, AA076,
AA081, AA086, AA130, AA212A, AA212B
- Action:
Simulate a seismic detection (Upper cover accelerometer
(30FCJ13CS410-S01): Disconnect wire from terminal
01 from 30FCJ12GH410-X134 terminal strip.
Check :
− “Upper cover warning seismic detection” warning
(n°806) displayed on HMI
− All motorized valves closed (AA025, AA450, AA465,
AA472, AA473, AA474, AA006, AA008, AA012, AA419,
AA020, AA030, AA031, AA032, AA033, AA034, AA035,
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Seismic detection (Upper cover accelerometer)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
AA036, AA302, AA401, AA402, AA403, AA406, AA413,
AA510, AA407, AA408, AA409, AA414, AA071, AA076,
AA081, AA086, AA130, AA212A, AA212B)
− All SFCTM actuators OFF :
Start SFCTM travelling motor (AE201) and check
travelling motor OFF
Start Anti-seismic 0&200 motors (AE231 and
AE235) and check anti-seismic motors OFF
Start Service elevator motor (AE251) and check
service elevator motor OFF
Start biological protection 0&200 motors (AE241
and AE245) and check biological protections
0&200 motors OFF
Start docking motors (AE261, AE271, AE281,
AE291)and check docking motors OFF
− Hoist motor OFF, operational and auxiliary brakes
closed :
Open operational brake and check operational
brake closed
Open auxiliary brake and check auxiliary brake
closed
Start opening hoist upper cover and check upper
cover motor OFF
− Lid handling motor OFF : Start lid handling motor
(AE401) and check lid handling motor OFF
MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC30 Depassivate hardware input / output modules
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
FC30 Depassivate hardware input / output modules
1
- Initial status:
No alarm
- Action
− Disconnect power supply from safety module and
check corresponding alarm displayed on HMI
− Reconnect power supply for safety module and check
corresponding module automatically depassivated
(check no fault on corresponding module).
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC30 Depassivate hardware input / output modules
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
5 from power supply.
− Alarm displayed to check :
Digital output card on ET200M “SPLC_GH130” slot 7 in fault
Digital output card on ET200M “SPLC_GH130” slot 8 in fault
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC30 Depassivate hardware input / output modules
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Digital output card on ET200M “SPLC_GH410” slot 5 in fault
- Action
As described in the Operating Basic Design Description [R14] and Functional analysis [R11], the Functional
entity (FE) listed below are concerned.
OPLC FUNCTIONAL ENTITIES
ORCF Name Functional entity & Designation of ORCF
(Specification) related functions
ORCF#1 FE01 General Management
ORCF_1_1 General Management
ORCF#2 FE02 Management of alarms & stops
ORCF_2_1 Alarms and Stops
ORCF#3 FE03 Management of SFCTM
ORCF_3_1 Management of SFCTM Travelling in LH
ORCF_3_2 Management of Anti seismic devices 0 & 200
ORCF_3_3 Management of Biological protections 0 & 200
ORCF_3_4 Management of service elevator
ORCF_3_5 Management of docking devices (screw 1 to 4)
ORCF#4 FE04 Management of BLHS
ORCF_4_1 Management of the Lid handling device
ORCF_4_2 Management of the gripper
ORCF#5 FE05 Management of Penetration Station
ORCF_5_1 Management of the upper cover hoist
ORCF_5_2 Management of the anti seismic locking device for
upper cover
ORCF#6 FE06 Management of Fluid Circuits
ORCF_6_1 Management of automatic valve AA006
ORCF_6_2 Management of automatic valve AA008
ORCF_6_3 Management of automatic valve AA012
ORCF_6_4 Management of automatic valve AA013
ORCF_6_5 Management of automatic valve AA020
ORCF_6_6 Management of automatic valve AA025
ORCF_6_7 Management of automatic valve AA030
ORCF_6_8 Management of automatic valve AA031
ORCF_6_9 Management of automatic valve AA032
ORCF_6_10 Management of automatic valve AA033
ORCF_6_11 Management of automatic valve AA034
ORCF_6_12 Management of automatic valve AA035
ORCF_6_13 Management of automatic valve AA036
ORCF_6_14 Management of automatic valve AA302
ORCF_6_15 Management of automatic valve AA401
ORCF_6_16 Management of automatic valve AA402
ORCF_6_17 Management of automatic valve AA403
ORCF_6_18 Management of automatic valve AA406
ORCF_6_19 Management of automatic valve AA407
ORCF_6_20 Management of automatic valve AA408
ORCF_6_21 Management of automatic valve AA409
ORCF_6_22 Management of automatic valve AA413
ORCF_6_23 Management of automatic valve AA414
ORCF_6_24 Management of automatic valve AA419
ORCF_6_25 Management of automatic valve AA450
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
Check Communication fault between OPLC and operating
SCADA :
“Ethernet communication OPLC - operating SCADA
Fault” warning (n°216) displayed on operating SCAD A
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_1: Profibus slave status checking
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
- Action:
Check “Profibus communication ET200M GH120 slave
fault” warning (n°224) displayed on operating SCADA by
causing a configuration fault on the Profibus : suppress an
ET200 component (for example disconnect ET200M
profibus connector X52 (30FCJ9351C cable) in GH120
cabinet)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_2: Operating mode management
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_2: Operating mode management
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− Maintenance mode : checked in” Basic motion
checks : service elevator” and PSRCF#1
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_2: Operating mode management
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
checks: upper cover hoist” and SRCF10.
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_3: Displaying (HMI, light)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
- Action:
(a) Test of Maintenance mode lamp on GH210, GH310 and
GH410 control panel
Check :
− “SFTCM Maintenance mode “ lamp
(30FCJ13GH210-H30) OFF
− “Maintenance mode” lamp (30FCJ11GH310-H08)
OFF
− “Maintenance mode” lamp (30FCJ12GH410-H08)
OFF
By selecting normal mode on MCD control panel
(30FCJ10GH140-S14 key switch) and on operating SCADA
Check :
− “SFTCM Maintenance mode “ lamp
(30FCJ13GH210-H30) ON
− “Maintenance mode” lamp (30FCJ11GH310-H08)
ON
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_3: Displaying (HMI, light)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− “Maintenance mode” lamp (30FCJ12GH410-H08)
ON
By selecting maintenance mode on MCD control panel
(30FCJ10GH140-S14 key switch) and on operating SCADA
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_3: Displaying (HMI, light)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Check lamp hereafter ON :
30FCJ11GH310-H07
30FCJ11GH310-H08
By pushing on 30FCJ11GH310-S06 “test lamp” push
button.
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch) to access Operating
SCADA Parameters screen
- Action:
Check
− Correct active cask displayed on Operative SCADA
common bar area
− Consistency sequences displayed (sequence screen)
on operating SCADA with cask selected
− Consistency cask parameters on calibration screen
on operating SCADA
Nota : If the “buzzer shut down “ push button has been pushed and a
alarm is still active, this alarm must be OFF before the check of
the buzzers.
A REFERENCE REV. FILE PAGE
6 - Initial status:
No alarm
SFCTF powered
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
Check correct interlock management by setting
corresponding input states (see table here after.
Note :
Inputs :
- LH door closed => set a close circuit between 05&06
terminals in 30FCJ10GH120-X40 terminal strip
- LH door not closed => Set an open circuit between
05&06 terminals in 30FCJ10GH120-X40 terminal strip
- LH door opened : Set a close circuit between 03&04
terminals in 30FCJ10GH120-X40 terminal strip
- LH door not opened: Set a open circuit between 03&04
terminals in 30FCJ10GH120-X40 terminal strip
Outputs :
- SFCTF power status external interlock = 1 : check
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_8: Management of analog sensors
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_10: HMI to PLC management
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_11: PLC to HMI management
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_13: Management of sequential process for Castor cask
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
“Cask type” selector (30FCJ10GH140-S13 key switch) on
Castor
- Action:
Select Castor sequence 0 in operating SCADA (list of
sequences and steps)
Run all Castor sequences including “Incident sequences”
- Check :
Correct sequences progress ([R24])
Correct expected operator message (action for operation
and validation)
Correct screen displayed on display SCADA according to
sequence selected ([R16])
Correct information displayed to the operator in sequence
view for pressure tests (tests conform or not conform)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_14: Management of sequential process for TN13 cask
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
“Cask type” selector (30FCJ10GH140-S13 key switch) on
TN13
- Action:
Select TN13 sequence 0 in operating SCADA (list of
sequences and steps)
Run all TN13 sequences including “Incident sequences”
- Expected result :
TN13 sequences displayed on operating SCADA
Correct sequences progress ([R24])
Correct expected operator message (action for operation
and validation)
Correct screen displayed on display SCADA according to
sequence selected ([R16])
Correct information displayed to the operator in sequence
view for pressure tests (tests conform or not conform)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_1_1_15: Management of safety conditions
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_2_1_0 to FC_ORCF_2_1_11: Management of alarms and stop
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
Check “incoherence fault” displayed on operating SCADA
for AA006 valve by setting AA006 contactor = true (set
Valve AA006 closed limit switch (30FCJ16 CG006B -S01)
and Valve AA006 open limit switch (30FCJ16 CG006A -S01
= true)
Check alarm always active by stopping AA006 valve
incoherence (set Valve AA006 open limit switch (30FCJ16
CG006A -S01 = false)
Check “incoherence fault” inactive by pushing on “alarm
acquit” push button (30FCJ10GH140-S04)
Check only “SPLC Emergency stop (safety relay 1)” alarm
(n°82) displayed on HMI by :
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – FC_ORCF_2_1_0 to FC_ORCF_2_1_11: Management of alarms and stop
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Setting an incoherence fault on AA006 valve (set Valve
AA006 open limit switch (30FCJ16 CG006A -S01 =
true)
Pushing on Emergency push button (30FCJ10GH140-
S17) on MCD control panel
A REFERENCE REV. FILE PAGE
SFC FC_ORCF_3_5_0
Output database updating FC_ORCF_3_5_1
Counters management FC_ORCF_3_5_2
Temporisations management FC_ORCF_3_5_3
Screws synchronism FC_ORCF_3_5_4
Table 9 – List of FE03 functions
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – SFCTM Positioning from station to station
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
High speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
Travelling screen displayed on operating SCADA SFC
travelling selected on SCADA
SFCTM is successively under each station (forward and
reverse travel)
- Action:
Check :
- Correct transfer of the SFCTM from HOS to BLHS n
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – SFCTM Positioning from station to station
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Flashing lights with buzzer ON (SFCTM in movement)
(30FCJ13EJ212-H01and 30FCJ13EJ213-H01)
- SFCTM stopped on corresponding cam selector
- Correct activation / deactivation of the operational brakes
(brake release detectors (30FCJ13CG073-S01,
30FCJ13CG074-S01, 30FCJ13CG075-S01,
30FCJ13CG076)-S01
- Consistency of HMI information (on operating SCADA
travelling screen): SFCTM at cam selector position
By selecting “Travel HOS to BLHS” on operating SCADA and
pushing on “SFCTM run forward” push button (30FCJ10GH140-
S18) (push button not to be remained)
Check :
- Correct transfer of the SFCTM from BLHS to PS
- Flashing lights with buzzer ON (SFCTM in movement)
(30FCJ13EJ212-H01and 30FCJ13EJ213-H01)
- SFCTM stopped on corresponding cam selector
- Correct activation / deactivation of the operational brakes
(brake release detectors (30FCJ13CG073-S01,
30FCJ13CG074-S01, 30FCJ13CG075-S01,
30FCJ13CG076)-S01
- Consistency of HMI information (on operating SCADA
travelling screen): SFCTM at cam selector position
By selecting “Travel BLHS to PS” on operating SCADA and
pushing on “SFCTM run forward” push button (30FCJ10GH140-
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – SFCTM Positioning from station to station
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
S18) (push button not to be remained)
Note : “SFCTM run forward” push button has to be maintained
until “safe stop of SFCTM from PS to BLHS detectors
(30FCJ13CG148-S01 and 30FCJ13CG149-S01) have been
deactivated.
Check :
- Correct transfer of the SFCTM from PS to BLHS
- Flashing lights with buzzer ON (SFCTM in movement)
(30FCJ13EJ212-H01and 30FCJ13EJ213-H01)
- SFCTM stopped on corresponding cam selector
- Correct activation / deactivation of the operational brakes
(brake release detectors (30FCJ13CG073-S01,
30FCJ13CG074-S01, 30FCJ13CG075-S01,
30FCJ13CG076)-S01
- Consistency of HMI information (on operating SCADA
travelling screen): SFCTM at cam selector position
By selecting “Travel PS to BLHS” on operating SCADA and
pushing on “SFCTM run reverse” push button (30FCJ10GH140-
S19)
Note : “SFCTM run reverse” push button has to be maintained
until “safe stop of SFCTM from HOS to BLHS detectors
(30FCJ13CG146-S01 and 30FCJ13CG147-S01) have been
deactivated.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – SFCTM Positioning from station to station
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Check :
- Correct transfer of the SFCTM from BLHS to HOS
- Flashing lights with buzzer ON (SFCTM in movement)
(30FCJ13EJ212-H01and 30FCJ13EJ213-H01)
- SFCTM stopped on corresponding cam selector
- Correct activation / deactivation of the operational brakes
(brake release detectors (30FCJ13CG073-S01,
30FCJ13CG074-S01, 30FCJ13CG075-S01,
30FCJ13CG076)-S01
- Consistency of HMI information (on operating SCADA
travelling screen): SFCTM at cam selector position
By selecting “Travel BLHS to HOS” on operating SCADA and
pushing on “SFCTM run reverse” push button (30FCJ10GH140-
S19) (push button not to be remained)
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
High speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
Travelling screen displayed on operating SCADA SFC
travelling selected on SCADA
SFCTM at Handling Opening Station (for example) on cam
selector (30FCJ13CG142-S01 and 30FCJ13CG143-S01)
- Action:
Check correct accurate positioning (on operating SCADA
travelling platform screen) by :
Selecting “accurate positioning” on travelling platform
screen.
Moving SFCTM to accurate position with forward / reverse
movements according to SFCTM positioning screen
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
High speed selected on MCD control panel
(30FCJ10GH140-S21 key switch)
Travelling screen displayed on operating SCADA (for HMI
only)
SFC travelling selected on SCADA
- Action:
(a) Over travel (end of LH side)
− Set SFCTM at BLHS (coming from PS) :
30FCJ13CG140-S01 and 30FCJ13CG141-S01 = true
− Select travel from BLHS to PS on operating SCADA
− Push on “run forward” push button (30FCJ10GH140-
S18) on MCD control panel
A REFERENCE REV. FILE PAGE
- Check :
Dedicated warning (n°408) on operating SCADA : “SFC TM
in over travel position (Loading Hall door side)”
Travelling motor (30FCJ13AE201-M01) and operational
brake (30FCJ13AE201-Y01) OFF and operational brake
(AA802 valve) closed.
Dedicated alarm (n°407) on operating SCADA : “SFCTM in
over travel position (End of Loading Hall side)”
Travelling motor (30FCJ13AE201-M01) OFF and
operational brake (30FCJ13AE201-Y01) (AA802 valve)
closed.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Anti seismic devices 0 & 200 management
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action:
(a) Lock the Anti seismic locking devices 0 & 200
Push on “anti seismic lock” push button
(30FCJ10GH140-S08) on MCD control panel
(b) Unlock the Anti seismic locking devices 0 & 200
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Anti seismic devices 0 & 200 management
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Push on “anti seismic unlock” push button
(30FCJ10GH140-S09) on MCD control panel
- Check :
Correct locking/unlocking (Anti seismic device screen
display on operating SCADA) : check correct status of
anti seismic lock / unlock detectors :
− Anti seismic 0 unlocked 30FCJ13CG150-S01
− Anti seismic 200 unlocked 30FCJ13CG153-S01
− Anti seismic 0 locked 1/2 30FCJ13CG151-S01
− Anti seismic 0 locked 2/2 30FCJ13CG152-S01
− Anti seismic 200 locked 1/2 30FCJ13CG154-S01
− Anti seismic 200 locked 2/2 30FCJ13CG155-S01
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Biological Lid protections management 0 & 200
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
SFCTM is at biological lid handling station (BLHS)
detectors (30FCJ13CG140-S01 and 30FCJ13CG141-S01)
on accurate position (30FCJ13CG001-B01 and
30FCJ13CG002-B01)
Biological protection screen displayed on operating SCADA
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
SFC biological protection selected on operating SCADA
SFCTM pendant control 2 (30FCJ13GF222) connected to
30FCJ13GF218 junction box
SFCTM pendant control 2 (30FCJ13GF222) activated
MCD selector set on “SFCTM” (30FCJ10GH140-S15 key
switch)
Biological protection selected on ALL (30FCJ10GH140-S12
key switch)
Biological protections closed :
− Biological protection 0 closed 1/2 detector
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Biological Lid protections management 0 & 200
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
(30FCJ13CG056-S01) = true
− Biological protection 0 closed 2/2 detector
(30FCJ13CG057-S01) = true
− Biological protection 200 closed 1/2 detector
(30FCJ13CG156-S01) = true
− Biological protection 200 closed 2/2 detector
(30FCJ13CG157-S01) = true
- Action:
(a) Open Biological Lid protections 0 & 200 with SFCTM
pendant control 2 (30FCJ13GF222).
Push on “Open” push button
(b) Closed Biological protections 0 & 200 with SFCTM
pendant control 2 (30FCJ13GF222)
Push on “Close” push button
- Check :
Correct opening/closing (HMI information on Biological
protection screen on Operating SCADA): biological
protections movement stopped when corresponding
detectors are true
Check correct status of biological protections open / close
detectors:
− Biological protection 0 closed 1/2 detector
(30FCJ13CG056-S01)
− Biological protection 0 closed 2/2 detector
(30FCJ13CG057-S01)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Biological Lid protections management 0 & 200
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− Biological protection 200 closed 1/2 detector
(30FCJ13CG156-S01)
− Biological protection 200 closed 2/2 detector
(30FCJ13CG157-S01)
− Biological protection 0 open 1/2 detector
(30FCJ13CG054-S01)
− Biological protection 0 open 2/2 detector
(30FCJ13CG055-S01)
− Biological protection 200 open 1/2 detector
(30FCJ13CG062-S01)
− Biological protection 200 open 2/2 detector
(30FCJ13CG063-S01)
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
SFTCM elevator screen selected on display SCADA
MCD selector set on “SFCTM” (30FCJ10GH140-S15 key
switch)
SFC Elevator screen displayed on operating SCADA
SFCTM is at biological lid handling station (BLHS)
detectors (30FCJ13CG140-S01 and 30FCJ13CG141-S01)
on accurate position (30FCJ13CG001-B01 and
30FCJ13CG002-B01)
Service elevator in low position :
− Service elevator in low position detector 1/2
(30FCJ13CG068-S01) = true
− Service elevator in low position detector 2/2
(30FCJ13CG069-S01) = true
SFCTM pendant control 2 (30FCJ13GF222) connected to
30FCJ13GF219 junction box
A REFERENCE REV. FILE PAGE
- Action:
(a) Move Service Elevator up and stop movement: Push on
“Up” push button (30FCJ13GF222-S04) and release
command. Be careful: Service elevator is normally stopped
by operator as soon as the service elevator is in contact
with the lower plate. For in-shop test, lower plate is not
present. Don’t move to high service elevator.
(b) Move Service Elevator down in lower position : Push on
“down” push button (30FCJ13GF222-S03)
- Check :
(a) Correct moving and stop when “Up” push button is
released.
(b) Correct moving and stop on low position detectors
(Check consistency HMI information on Operating SCADA
Elevator screen). Check correct status of service elevator
in low position detectors :
− Service elevator in low position detector 1/2
(30FCJ13CG068-S01) = true
− Service elevator in low position detector 2/2
(30FCJ13CG069-S01) = true
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Service elevator in maintenance mode
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
SFTCM elevator screen selected on display SCADA
MCD selector set on “SFCTM” (30FCJ10GH140-S15 key
switch)
Service elevator motor (AE251) selected
SFCTM is at biological lid handling station (BLHS)
detectors (30FCJ13CG140-S01 and 30FCJ13CG141-S01)
on accurate position (30FCJ13CG001-B01 and
30FCJ13CG002-B01)
Service elevator in low position :
− Service elevator in low position detector 1/2
(30FCJ13CG068-S01) = true
− Service elevator in low position detector 2/2
(30FCJ13CG069-S01) = true
SFCTM pendant control 2 (30FCJ13GF222) connected to
30FCJ13GF219 junction box
SFCTM pendant control 2 (30FCJ13GF222) activated
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Service elevator in maintenance mode
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action:
Move Service Elevator down in over lower position: Push
on “down” push button (30FCJ13GF222-S03) and check
movement of the service elevator lower than the lower
position in normal mode available.
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
Screws selector set on “ALL” (30FCJ10GH140-S11)
Docking device screen displayed on operating SCADA
All screws in rest position :
- Screw 1 at rest position 1/2 (30FCJ13CG079-S01) =
true
- Screw 2 at rest position 1/2 (30FCJ13CG083-S01) =
true
- Screw 3 at rest position 1/2 (30FCJ13CG087-S01) =
true
- Screw 4 at rest position 1/2 (30FCJ13CG091-S01) =
true
A REFERENCE REV. FILE PAGE
- Action:
(a) Start docking device sequence: push on “docking
penetration” push button (30FCJ10GH140-S08). Push
button not remained
(b) Start undocking device sequence: push on “undocking
penetration” push button (30FCJ10GH140-S09). Push
button not remained.
- Check :
(a) Correct angular positioning :
- Screw 1 angular positioning detector
(30FCJ13CG078-S01) = true
- Screw 2 angular positioning detector
(30FCJ13CG082-S01) = true
- Screw 3 angular positioning detector
(30FCJ13CG086-S01) = true
- Screw 4 angular positioning detector
(30FCJ13CG090-S01) = true
All screws lifted up in upper position :
- Screw 1 in upper position 30FCJ13CG081-S01 =
true
A REFERENCE REV. FILE PAGE
- Check :
Four screw motors OFF (screw 1 revolution – screw 2,3&4
A REFERENCE REV. FILE PAGE
- Check :
Four screw motors OFF (screw 2 revolution – screw 2,3&4
revolution > synchronism threshold) and sequence
stopped.
Dedicated warning in Operating SCADA common area :
“Turn number of screw 2 incoherent in function the other
screw” (warning n°471)
- Check :
Four screw motors OFF (screw 3 revolution – screw 2,3&4
revolution > synchronism threshold) and sequence
stopped.
Dedicated warning in Operating SCADA common area :
“Turn number of screw 3 incoherent in function the other
screw” (warning n°472)
- Check :
Four screw motors OFF (screw 4 revolution – screw 2,3&4
revolution > synchronism threshold) and sequence
stopped.
Dedicated warning in Operating SCADA common area :
“Turn number of screw 4 incoherent in function the other
screw” (warning n°473)
A REFERENCE REV. FILE PAGE
SFC FC_ORCF_4_1_0
Output database updating FC_ORCF_4_1_1
Counters management FC_ORCF_4_1_2
Temporisations management FC_ORCF_4_1_3
Load management FC_ORCF_4_1_4
Over travel FC_ORCF_4_1_5
ORCF_4_2 Management of the gripper
SFC FC_ORCF_4_2_0
Output database updating FC_ORCF_4_2_1
Counters management FC_ORCF_4_2_2
Temporisations management FC_ORCF_4_2_3
Table 10 – List of FE04 functions
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the Lid handling device
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
Lid handling device screen displayed on operating SCADA
SFC Lid handling device selected on operating SCADA
SFCTM is at biological lid handling station (BLHS)
detectors (30FCJ13CG140-S01 and 30FCJ13CG141-S01)
on accurate position (30FCJ13CG001-B01 and
30FCJ13CG002-B01)
- Action:
(a) Select TN13 or Castor cask (30FCJ10GH140-S13 key
switch)
Lift the Lid Handling device in high position (push on
“gripper up” push button (30FCJ10GH140-SS09) on
MCD control panel)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the Lid handling device
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
(b) Select TN13 cask (Lid handling device in high position)
Push on “Gripper down” push button (30FCJ10GH140-
S08) on MCD control panel
- Check :
Correct gripper moving (HMI information Lid handling
device screen)
Correct stop on dedicated cask detectors
− Gripper in upper position detector 1
(30FCJ13CG023-S01)
− Gripper in upper position detector 2
(30FCJ13CG024-S01)
− Biological lid on castor cask detector
(30FCJ11CG027-S01)
− Biological lid on TN13 cask detector
(30FCJ11CG021-S01)
Dedicated MCD panel lam: Gripper down
(30FCJ10GH140-H06) and Gripper up (30FCJ10GH140-
H07) lamp ON when initial conditions are OK.
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the Lid handling device
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
Lid handling device screen display selected on operating
SCADA
SFC Lid handling device selected on operating SCADA
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Gripper in upper position :
− Gripper in upper position detector 1
(30FCJ13CG023-S01) = true
− Gripper in upper position detector 2
(30FCJ13CG024-S01) = true
- Action:
Lift down the biological lid handling device : Push on
“Gripper down” push button (30FCJ10GH140-S08 on MCD
control panel
- Check :
Gripper in position on SFCTM detectors (30FCJ11CG022)
Consistency of HMI information (Lid handling device screen
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the Lid handling device
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
display on operating SCADA): Biological lid on SFCTM plug
support detector (30FCJ11CG022) = true
- Action:
(a) Select TN13 cask type (30FCJ10GH140-S13 key
switch)
Set an abnormal overload (TN13 over load threshold +
A REFERENCE REV. FILE PAGE
- Check :
(a) & (b) Lid Handling motor OFF (30FCJ11AE401-M01)
(electrical Lid Handling motor brake automatically OFF)
Dedicated warning displayed on Operating SCADA:
− Load measurement TN13 Cask over load
(warning n°614)
− Load measurement CASTOR Cask over load
(warning n°615)
− Load measurement TN13 Cask under load
(warning n°616)
− Load measurement CASTOR Cask under load
(warning n°617)
A REFERENCE REV. FILE PAGE
I (mA)
TN13 Castor
Over load +10% 18.4 16.2
Under load -10% 4.9
A REFERENCE REV. FILE PAGE
- Action:
Lift down the biological lid handling device : push on
“gripper down” push button on MCD control panel
Set an over travel detection : set Lid handling over travel
A REFERENCE REV. FILE PAGE
- Check :
Lid Handling motor (30FCJ11AE401-M01) OFF
Dedicated warning in Operating SCADA common area :
“Lid handling over travel” (warning n°606)
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “MCD” position
(30FCJ10GH140-S15 key switch)
Lid handling device screen selected on operating SCADA
SFC gripper selected on operating SCADA
SFCTM is at biological lid handling station (BLHS)
detectors (30FCJ13CG140-S01 and 30FCJ13CG141-S01)
on accurate position (30FCJ13CG001-B01 and
30FCJ13CG002-B01)
Gripper unlocked : Gripper unlocked detector
30FCJ11CG011-S01 = true
- Action:
(a) Lock the gripper : push on “gripper lock” push button
(30FCJ10GH140-S08) on MCD control panel
(b) Unlock the gripper : push on “gripper unlock” push
A REFERENCE REV. FILE PAGE
- Check :
Correct gripper locking / unlocking (Consistency of HMI
information on Lid handling device screen on operating
SCADA) :
− Check correct status of lock / unlock detectors
(30FCJ11CG010-S01 and 30FCJ11CG011-S01)
− Check correct status (open / close) of the “gripper
locking solenoid valve” (AA212B) and of the
“gripper unlocking solenoid valve (AA212A)
Dedicated MCD panel lamp : Gripper lock lamp
(30FCJ10GH140-H08) and Gripper unlock lamp
(30FCJ10GH140-H09) ON when initial conditions are OK
SFC FC_ORCF_5_2_0
Output database updating FC_ORCF_5_2_1
Counters management FC_ORCF_5_2_2
Temporisations management FC_ORCF_5_2_3
Table 11 – List of FE05 functions
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the upper cover hoist
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “PS” position
(30FCJ10GH140-PS)
Upper cover screen displayed on operating SCADA
SFC Hoist upper cover selected on operating SCADA
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Upper cover closed : Upper cover closed detector = true (in
the simulated operative part)
Upper cover unlocked : Upper cover unlocked detector
(30FCJ12CG130-S01) = true
Anti-seismic device 0 & 200 locked:
− Anti seismic 0 locked 1/2 detector
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the upper cover hoist
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
(30FCJ13CG151-S01) = true
− Anti seismic 200 locked 1/2 detector
(30FCJ13CG154-S01) = true
Cask is docked :
− Penetration docked 1/2 detector (30FCJ12CG042-
S01) = true
Screw load limiter OK :
− Screw 1 load limiter 1/2 detector (30FCJ12CG120-
S01) = true
− Screw 2 load limiter 1/2 detector (30FCJ12CG122-
S01) = true
− Screw 3 load limiter 1/2 detector (30FCJ12CG124-
S01) = true
− Screw 4 load limiter 1/2 detector (30FCJ12CG126-
S01) = true
- Action:
(a) Open the upper cover : push on “Open upper cover”
push button (30FCJ12GH410-S10)
(b) Close the upper cover : push on “close upper cover”
push button (30FCJ12GH410-S11)
- Expected result :
(a) Correct moving for opening (HMI information in the
simulated operating part) :
1 – Operating and auxiliary brakes opened : operating
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the upper cover hoist
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
brake open detector and auxiliary brake open
detector switched ON
2 - Consistency hoist motor speed according to the
status of the detector in the Positions selector
device:
a - Start at low speed
b - Low speed for closing detector 1 and low
speed for closing detector 2 switched on
c - High speed
d - Low speed for opening detector switched ON
e - Low speed
f - Upper cover open detector 1/2 & 2/2 switched
ON
g - Hoist motor OFF,
Operational and auxiliary brakes OFF
(Operating brake close detector and auxiliary
brake close detector switched ON
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the upper cover hoist
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
a - Start at low speed
b - Low speed for opening detector switched ON
c - High speed
d - Low speed for closing detector 1 and low
speed for closing detector 2 switched on
e - Low speed
f - Upper cover close detector switched ON
g - Hoist motor OFF,
Operational and auxiliary brakes OFF
(Operating brake close detector and auxiliary
brake close detector switched ON)
- Action:
Open the upper cover : push on “Open upper cover” push
button (30FCJ12GH410-S10)
Set an abnormal speed of the hoist motor (incremental
encoder threshold +10% in the simulated operating part)
- Check :
Hoist motor stopped
Both electrical brakes applied
Dedicated warning in Operating SCADA: “Over speed hoist
upper cover motor” (warning n°818)
A REFERENCE REV. FILE PAGE
- Action:
Open the upper cover with simulated PS control panel
Set an abnormal load detection (Set Load limiter detector =
true in the simulated operative part)
- Expected result :
Hoist motor stopped
Both electrical brakes applied
Dedicated warning in Operating SCADA: “Over load
detected on traction rope, upper cover device” (warning
n°812)
A REFERENCE REV. FILE PAGE
- Action:
(a) Open the upper cover with simulated PS control panel
Set over travel detection (Set upper cover open over
travel detector = true in the simulated operative part)
(b) Close the upper cover with simulated PS control panel
Set over travel detection (Set upper cover closed over
travel detector = true in the simulated operative part)
- Expected result :
Hoist motor stopped
Both electrical brakes applied
Dedicated warning in Operating SCADA common area:
(a) Upper cover in over travel open position (warning
A REFERENCE REV. FILE PAGE
6.1.3.5.2 Management of the anti seismic locking devices for upper cover
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the anti seismic locking devices for upper cover
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Control panel selector set on “PS” position
(30FCJ10GH140-PS)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of the anti seismic locking devices for upper cover
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Upper cover screen display selected on operating SCADA
SFC Hoist upper cover selected on operating SCADA
SFCTM at penetration station (PS) (30FCJ13CG144-S01
and 30FCJ13CG145-S01) on accurate position
(30FCJ13CG001-B01 and 30FCJ13CG002-B01)
Upper cover closed : Upper cover closed detector = true (in
the simulated operative part)
Upper cover unlocked : Upper cover unlocked detector =
true (in the simulated operative part)
- Action:
(a) Lock upper cover anti seismic locking devices : push
on “counterweight lock” push button (30FCJ11GH410-S12)
(b) Unlock upper cover anti seismic locking devices: push
on “counterweight unlock” push button (30FCJ12GH410-
S13)
- Expected result :
Correct locking/unlocking (SCADA and operative part
model view and information) :
Check correct status of upper cover locked / unlocked
detector and automatic valve AA130
A REFERENCE REV. FILE PAGE
Note:
− For analog sensors, only the value displayed on HMI (according to the input generated by a 4-20mA generator) is checked. Alarm and
threshold are checked in SVTP.
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
(a) Select successively each automatic valve on operating
SCADA
Select successively open and close valve on MCD
control panel (30FCJ10GH140-S08 and
30FCJ10GH140-S09 push button)
(b) TTLE checks
TTLE fault will be generated by disconnecting open
limit switch of each valve => disconnect open limit
switch from the concerned terminal (table hereafter)
Select successively each automatic valve on operating
SCADA and push on “Open valve” push button
(30FCJ10GH140-S08)
A REFERENCE REV. FILE PAGE
Close circuit to
Automatic Cabine
set terminals to
valve t
connect
AA025 X134-11&12
GH120
AA450 X134-15&16
AA465 X134-19&20
A REFERENCE REV. FILE PAGE
- Check :
(a) Correct open / close valve – No alarm
(b) Dedicated alarm on operating SCADA: Time Too Long
for Execution
(c) Dedicated alarm on operating SCADA: Incoherence
fault
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
(a) TTLE check :
For each manual valve hereafter: open the
corresponding valve but open switch must not be
activated
(b) Incoherence check
All manual valves closed. Set a close circuit between
the corresponding open limit switch terminals (table
hereafter).
A REFERENCE REV. FILE PAGE
- Check :
(a) Dedicated alarm on operating SCADA: Time Too Long
for Execution
(b) Dedicated alarm on operating SCADA: Incoherence
fault
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
Connect a 4-20mA generator between X102-01&02
terminals in GH120 cabinet. (CF190 sensor has been
removed)
Set successively flow values from 4 to 20mA. Read
corresponding analog value in display SCADA
- Check :
3
For I=4mA => check 0 m /h
3
For I=12mA => check 10 m /h
3
For I=20mA => check 20 m /h
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Corresponding sequence in progress (see hereafter)
- Action:
The check of this sensor is made during sequence
process: this sensor is used during sequence 12, 18 and
19 and this function is only activated during these
sequences.
When CF191 sensor is used, principle is to set
successively this sensor true and false (correct flow and
incorrect flow) and check when flow is NOK correct warning
displayed on operating SCADA.
A REFERENCE REV. FILE PAGE
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Corresponding sequence in progress (see hereafter)
- Action:
The check of this sensor is made during sequence
process: this sensor is used during sequence 19 and this
function is only activated during this sequence.
When CL194 sensor is used, principle is to set successively
this sensor true and false (correct level and incorrect level)
and to check when water level is NOK correct warning
displayed on operating SCADA.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of CL195 & CL196
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
The checking of the CL195 and CL196 is made during the checking of
the SRCF#18.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Level sensor sensors management (CL197, CL198, CL199)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Maintenance mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
Connect a 4-20mA generator between the corresponding
terminals :
X201-07&08 terminals in GH210 cabinet for CL197
X201-10&11 terminals in GH210 cabinet for CL199
X102-11&12 terminals in GH210 cabinet for CL198
Set successively pressure values from 4 to 20mA. Read
corresponding analog value in display SCADA
- Check:
CL199 sensor :
For I=4mA => check 0 mm
For I=12mA => check 12500 mm
For I=20mA => check 25000mm
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Level sensor sensors management (CL197, CL198, CL199)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
CL198 sensor :
For I=4mA => check 4479 mm
For I=12 mA => check 4979 mm
For I=20mA => check 5479 mm
CL197 sensor :
For I=4mA => check 4479 mm
For I=12 mA => check 4979 mm
For I=20mA => check 5479 mm
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Pressure sensors management (CP180, CP181, CP182, CP183, CP198, CP199)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
Connect a 4-20mA generator between the corresponding
terminals :
X102-01&02 terminals in GH210 cabinet for CP180
X102-03&04 terminals in GH210 cabinet for CP181
X102-05&06 terminals in GH210 cabinet for CP182
X102-07&08 terminals in GH210 cabinet for CP183
X102-09&10 terminals in GH210 cabinet for CP198
X101-01&02 terminals in GH120 cabinet for CP199
Set successively pressure values from 4 to 20mA. Read
corresponding analog value in display SCADA
- Check
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Pressure sensors management (CP180, CP181, CP182, CP183, CP198, CP199)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
For I=12 mA => 500 mbar
For I=20mA => 1000 mbar
CP199 sensor
For I=4mA => 0 mbar
For I=12 mA => 5 bars
For I=20mA => 10 bars
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
Corresponding sequence in progress (see hereafter)
- Action:
The check of this sensor is made during sequence
process: this sensor is used during sequence 5, 7, 9, 12,
14, 15 & 18 and this function is only activated during this
sequence.
When CP197 sensor is used, principle is to set
successively this sensor true and false (correct pressure
and incorrect pressure) and to check when pressure is
NOK correct warning displayed on operating SCADA and
MCD Control Panel Buzzer (30FCJ10GH140-P01) ON
.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Temperature sensors management (CT194, CT195, CT196, CT197, CT198, CT199)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
No alarm
Normal mode selected on MCD control panel
(30FCJ10GH140-S14 key switch)
- Action:
Connect a 4-20mA generator between the corresponding
terminals :
X103-01&02 terminals in GH120 cabinet for CT194
X201-13&14 terminals in GH210 cabinet for CT195
X201-01&02 terminals in GH210 cabinet for CT196
X102-13&14 terminals in GH210 cabinet for CT197
X201-16&17 terminals in GH210 cabinet for CT198
X201-04&05 terminals in GH210 cabinet for CT199
Set successively pressure values from 4 to 20mA. Read
corresponding analog value in operating SCADA
(Parameters screen)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Temperature sensors management (CT194, CT195, CT196, CT197, CT198, CT199)
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Check
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of SFCTM start-up outside FB
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action 1:
Open GH210 cabinet
Set compact thermostat 30FCJ13GH210-S08 and
30FCJ13GH210-S04 to the same threshold (threshold =
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of SFCTM start-up outside FB
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
ambient temperature + 10°C)
Set 30FCJ13GH210-R01 & 30FCJ13GH210-R02 regulated
heater for cabinet temperature threshold : threshold =
ambient temperature + 10°C
Connect 400VAC external power supply in
30FCJ13GH210-305 electrical socket
- Check 1:
30FCJ13GH210-H25 lamp OFF (Cabinet temperature not
sufficient)
Check 30FCJ13GH210-R01 & 30FCJ13GH210-R02
regulated heater ON (hot air flow)
- Action 2:
Close GH210 cabinet
Wait for heating
- Check 2:
30FCJ13GH210-H25 lamp ON (Cabinet temperature
sufficient)
- Action 4:
Close GH210 cabinet
Push on external start push button (30FCJ13GH210-S05)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of SFCTM start-up outside FB
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Check 3:
SFCTM powered (30FCJ13GH210-H24 SFCTM power
started lamp ON)
A REFERENCE REV. FILE PAGE
- Initial status:
SFCTM outside FB
SFCTM connected to the 400VAC external power supply
SFCTM start-up outside FB procedure fulfilled
- Action 1:
Set compact thermostat 30FCJ13GH210-S07 threshold =
ambient temperature - 10°C
- Expected result 1:
Motors heater authorization lamp (30FCJ13GH210-H27)
ON
- Action 2:
Push Start motor heater push button (30FCJ13GH210-
S10)
A REFERENCE REV. FILE PAGE
- Expected result 2:
“Motors heaters ON” lamp ON (30FCJ13GH210-H26) :
check +230VAC between terminals 73&74 in
30FCJ13GH210-X12 terminal strip
- Action 3:
Push Stop motor heater push button (30FCJ13GH210-
S12)
- Expected result 3:
“Motors heaters ON” lamp OFF (30FCJ13GH210-H27) :
check 0VAC between terminals 73&74 in 30FCJ13GH210-
X12 terminal strip
- Action 4 :
Set compact thermostat 30FCJ13GH210-S07 threshold =
ambient temperature + 10°C
- Expected result 4:
Motors heater authorization lamp (30FCJ13GH210-H27)
OFF
- Initial status:
SFCTM outside FB
SFCTM connected to the 400VAC external power supply
SFCTM start-up outside FB procedure fulfilled
A REFERENCE REV. FILE PAGE
- Action :
Check 0VAC between 71&72 terminals in 30FCJ13GH210-
X12 terminal strip
Set plug-in relay 30FCJ13GH210-K46 threshold =
mechanical reducer (30FCJ13AE201-R01) ambient
temperature +10°C
- Expected result :
External mechanical reducer heater (30FCJ13AE201-R02)
ON => Check +230VAC between 71&72 terminals in
30FCJ13GH210-X12 terminal strip
External mechanical reducer heater (30FCJ13AE201-R02)
OFF when reducers temperature has reached
30FCJ13GH210-K46 threshold => check 0VAC between
71&72 terminals in 30FCJ13GH210-X12 terminal strip
Biological 0 & 200 motor heater
- Initial status:
A REFERENCE REV. FILE PAGE
- Action :
Repeat travelling motor heater test procedure
- Expected result :
Same result as travelling motor heater but terminals to
check are :
− For biological 0 motor heater : 75&76 terminals in
30FCJ13GH210-X12 terminal strip
− For biological 200 motor heater : 77&78 terminals
in 30FCJ13GH210-X12 terminal strip
Anti-seismic 0 & 200 motor heater
Note : Anti seismic 0 & 200 motor heaters (30FCJ13AE231-R01 &
30FCJ13AE235-R01) start and stop automatically with
travelling motor heater command.
This test will be done during travelling motor heater test.
- Initial status:
SFCTM outside FB
SFCTM connected to the 400VAC external power supply
SFCTM start-up outside FB procedure fulfilled
- Action :
A REFERENCE REV. FILE PAGE
- Expected result :
Same result as travelling motor heater but terminals to
check are :
− For anti seismic 0 motor heater : 79&80 terminals
30FCJ13GH210-X12 terminal strip
− For anti seismic 200 motor heater : 81&82 erminals
in 30FCJ13GH210-X12 terminal strip
Elevator heater
Note : Elevator motor heater (30FCJ13AE251-R01) start and stop
automatically with travelling motor heater command.
This test will be done during travelling motor heater test.
- Initial status:
SFCTM outside FB
SFCTM connected to the 400VAC external power supply
SFCTM start-up outside FB procedure fulfilled
- Action :
Repeat travelling motor heater test procedure
- Expected result :
− Same result as travelling motor heater but
terminals to check are : 83&84 terminals in
30FCJ13GH210-X12 terminal strip
A REFERENCE REV. FILE PAGE
- Action 1:
Connect SFCTM pendant control 1 (30FCJ13GF221) to
GH210 cabinet
Push on activate push button (30FCJ13GF221-S02)
Push “Buzzer” push button (30FCJ13GF221-S01) of the
SFCTM pendant control 1 (30FCJ13GF221)
Push successively on “travelling forward” (30FCJ13GF221-
S03) and “Travelling reverse” push button
(30FCJ13GF221-04) of the SFCTM pendant control 1
(push button is remain a few seconds)
- Check 1:
“Pendant control activated” lamp (30FCJ13GF221-H01)
ON
A REFERENCE REV. FILE PAGE
- Action 2:
Push on “SFCTM run forward” push button push button
30FCJ13GF221-S03 of the SFCTM pendant control 1.
Push button is remained.
Push on Emergency stop (30FCJ13GF221-S05) on the
SFCTM pendant control 1 (30FCJ13GF221)
- Check 2:
Travelling motor OFF – Travelling not available
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of biological protections 0 & 200 outside FB
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Initial status:
SFCTM outside FB
SFCTM connected to the 400VAC power supply
SFCTM start-up outside FB procedure fulfilled
Biological protections not opened (visual inspection)
- Action 1:
Connect SFCTM pendant control 2 (30FCJGF222) to
30FCJ13GF218 junction box
Push “Buzzer” push button (30FCJGF222-S01) of the
SFCTM pendant control 2
Push successively on “Biological open” push button
(30FCJ13GF222-S03) and “Biological close” push button
(30FCJ13GF222-S04) of the SFCTM pendant control 2
(30FCJ13GF222) (push button is remained a few seconds)
- Check 1:
“Pendant control activated” lamp (30FCJ13GF222-H01)
ON
“Flashing light and buzzer 1” (30FCJ13EJ212-H01) and
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Management of biological protections 0 & 200 outside FB
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
“flashing light and buzzer 2” (30FCJ13EJ213-H01) ON
(Only when operator push on “buzzer” push button)
Correct movement of the biological protections, and
movement is stopped when push button is released.
- Action 2:
Push Emergency stop (30FCJ13GF222-S05) on the
SFCTM pendant control 2 (30FCJ13GF222)
Push successively on “Biological open” push button
(30FCJ13GF222-S03) and “Biological close” push button
(30FCJ13GF222-S04) of the SFCTM pendant control 2
(30FCJ13GF222)
- Check 2:
Biological protection motors (30FCJ13GE241-M01 &
30FCJ13GE245-M01) OFF
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Elevator movement not available outside the LH
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Connect SFCTM pendant control 2 (30FCJ13GF222) to
30FCJ13GF219 junction box
Push successively on “Elevator up” push button
(30FCJ13GF222-S03) and “Elevator down” push button
(30FCJ13GF222-S04) of the SFCTM pendant control 2
(30FCJ13GF222)
- Check:
Service elevator motor (30FCJ13AE251-M01) OFF -
movement not available
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Cask position system check
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Adjust the adjustable table with the three levelling screws
according to corrections indicated on the terminal
Adjust the three adjustable screws.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Cask position system check
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Start positioning the cask in the SFCTM: adjust the
positioning according to the correction values displayed
and the four cask positioning video cameras
(30FCJ14AZ001-E01, 30FCJ14AZ001-E02,
30FCJ14AZ001-E03, and 30FCJ14AZ001-E04) on the
remote control terminal (GF233).
When positioning OK, put the cask on the adjustable plate.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Cask locking screws check
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action 1:
Check Dedicated warning displayed on operating SCADA :
− Upper trunnion 1 unlocked
− Upper trunnion 2 unlocked
− Upper trunnion 3 unlocked
− Upper trunnion 4 unlocked
- Action 2:
Place in contact the four “upper trunnion locking devices”
with the corresponding trunnion of the cask.
Check :
Correct locking of the cask : check correct status of the
upper trunnion detectors in operating SCADA
− Upper trunnion 1 locked detector (30FCJ13CG108-
S01) = true
− Upper trunnion 2 locked detector (30FCJ13CG109-
S01) = true
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Cask locking screws check
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− Upper trunnion 3 locked detector (30FCJ13CG110-
S01) = true
− Upper trunnion 4 locked detector (30FCJ13CG111-
S01) = true
Warning displayed on operating SCADA deactivated:
− Upper trunnion 1 unlocked
− Upper trunnion 2 unlocked
− Upper trunnion 3 unlocked
− Upper trunnion 4 unlocked
A REFERENCE REV. FILE PAGE
- Action :
Try to communicate from the intercom in the MCR
(30FCJ10GH140-N01) with :
− Intercom (30FCJ11GH310-N02) installed in the BLHS
(UFA 18 015)
− Intercom (30FCJ11GH410-N03) installed in the PS
(UFA 19 021)
− Intercom (30FCJ10-AZ233-E01)installed in the LH
(UFA 10 015)
- Check :
Communication between MCR and the stations OK.
Speaker in LH (30FCJ10AZ234-E01) allowed hearing
announcement made from the MCR to the LH.
A REFERENCE REV. FILE PAGE
6 Network printer
- Initial status:
SFCTF powered
- Action :
Push on “report / printing” screen button on operating
SCADA
Select “Print” button on “report / printing” screen
- Check :
Correct printing
A REFERENCE REV. FILE PAGE
- Action :
Open successively the 4 safety gates
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – SFCTM warehousing rack detection
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Open the warehousing rack
Check :
− Hand tools box closed 1 detector (30FCJ13CG102-
S01 = false on operating SCADA
− Check Hand tools box closed 2 detector
(30FCJ13CG103-S01 = false on operating SCADA
Close the warehousing rack
Check :
− Hand tools box closed 1 detector (30FCJ13CG102-
S01 = true on operating SCADA (travelling platform
screen)
− Hand tools box closed 2 detector (30FCJ13CG103-
S01 = true on operating SCADA (travelling platform
screen)
A REFERENCE REV. FILE PAGE
- Action :
Lock the both sliding support and check in operating
SCADA (travelling platform screen) that front sliding
support locked detector (30FCJ13CG070-S01) and rear
sliding support locked detector (30FCJ13CG077-S01) are
true.
Unlock the both sliding support and check in operating
SCADA (travelling platform screen) that front sliding
support locked detector (30FCJ13CG070-S01) and rear
sliding support locked detector (30FCJ13CG077-S01) are
false.
A REFERENCE REV. FILE PAGE
- Action :
(a) Close “Main power supply” breaker
(b) Push on “lights test” push button
(c) Push on “Run pump P1” push button
(d) Push on “Stop pump P1” push button
(e) Push on “Cleaning pump P1” push button”
(f) Push on “Stop cleaning pump P1” push button
(g) Push on “Run pump P2” push button
(h) Push on “Stop pump P2” push button
(i) Push on “Cleaning pump P2” push button
(j) Push on “Stop cleaning pump P2” push button
(k) Push on “Run pump P1” push button
Push on “Emergency Stop” push button
(l) Push on “Run pump P2” push button
Push on “Emergency Stop” push button
(j) Simulate a fault on pump 1 : set a close circuit between
A REFERENCE REV. FILE PAGE
- Check:
(a) Power On lamp ON
(b) All lamp ON
(c) Pump P1 running: check corresponding status in
display SCADA
(d) Pump P1 OFF
(e) Cleaning pump P1 running
(f) Cleaning pump P1 OFF
(g) Pump P2 running: check corresponding status in
display SCADA
(h) Pump P2 OFF
(i) Cleaning pump P2 running
(j) Cleaning pump P2 OFF
(k) Pump P1 OFF
(l) Pump P2 OFF
(j) Dedicated alarm on operating SCADA
(k) Dedicated alarm on operating SCADA
Note 1 : Pump 1 = pump AP034
Pump 2 = pump AP035
Note 2 : Status of the pumps is checked in the corresponding view on
display SCADA when maintenance mode is selected.
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Control panel lamp test
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
(a) GH140 MCD control panel : Push on “Test lamp” push
button (30FCJ10GH140-S07)
(b) GH210 control panel : Push on “Test lamp” push button
(30FCJ13GH210-S03)
(c) GH310 control panel : Push on Test lamp” push button
(30FCJ11GH310-S06)
(d) GH410 control panel : Push on “Test lamp” push button
(30FCJ12GH410-S09)
- Check:
(a) All GH140 MCD control panel lamp ON
(b) All GH210 control panel lamp ON
(c) All GH310 control panel lamp ON
(d) All GH410 control panel lamp ON
A REFERENCE REV. FILE PAGE
12 Buzzer check
- Initial status:
No initialisation
- Action :
No specific action. This function is checked during SRCF#
and ORCF checks.
- Check:
MCD control panel buzzer on (30FCJ10GH140-P01) ON
when any alarm occurred.
GH410 control panel buzzer on (30FCJ12GH410-P01) ON
when any Upper cover alarm is occurred.
A REFERENCE REV. FILE PAGE
13 Lights check
- Initial status:
SFCTM powered
- Action :
Push on “start lighting” push button (30FCJ13GH210-S11)
Push on “stop lighting” push button (30FCJ13GH210-S13)
Push on “start video camera lighting” push button
(30FCJ13GH210-S14)
Push on “Stop video camera lighting’ push button
(30FCJ13GH210-S15)
- Check:
Lighting 1 to lighting 8 (30FCJ13EJ111-H01 to
30FCJ13EJ111-H08) ON
Lighting 1 to lighting 8 (30FCJ13EJ111-H01 to
30FCJ13EJ111-H08) OFF
Video camera light (30FCJ13EJ119-H01) ON
Video camera light (30FCJ13EF119-H01) OFF
A REFERENCE REV. FILE PAGE
Operational function with load corresponds to the Upper cover with water pressure. For In-Shop tests, Upper cover is not present: operational function with
load (FC_ORCF_5_1) can’t be tested.
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Anti seismic locking device manual backup
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Activate manual drive system 0&200 with the
corresponding tool
- Check:
Manual Locking and unlocking anti seismic 0&200
workable
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Service elevator manual backup
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Release electrical brake with the manual release device
Activate manual drive system with the corresponding tool
- Check:
Manual Service elevator movement workable
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Biological Lid Handling device manual backup
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Remove manual drive bonnet of the electrical motor
Unlock manual brake
Activate manual drive system with the corresponding tool
- Check :
Manual Biological Lid Handling movement workable
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Gripper device manual backup
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Activate manual drive system (no specific tool)
- Check :
Gripper device movement workable
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Docking of the penetration device manual backup
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Unlock manual brake (release manual lever)
Activate manual drive system with the corresponding tool
- Check :
Manual docking/undocking of the penetration workable
9 PERIODIC TESTS
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Test of Upper cover brakes
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Test of Upper cover brakes
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
− Screw 1 load limiter 1/2 detector (30FCJ12CG120-
S01) = true
− Screw 2 load limiter 1/2 detector (30FCJ12CG122-
S01) = true
− Screw 3 load limiter 1/2 detector (30FCJ12CG124-
S01) = true
− Screw 4 load limiter 1/2 detector (30FCJ12CG126-
S01) = true
- Action :
Step 1 : Operating and auxiliary brakes check when the Upper
cover is closed
- On the PSCP HMI, select successively Operating and
Auxiliary brakes.
- Open then close successively operating and auxiliary brakes
- Check :
Step 1 : Correct moving of the brakes : Correct status of
hoist break detectors (Operating brake open/close detector
and Auxiliary open/close detector)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Test of Upper cover brakes
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
Step 2 : Movement of the upper cover stopped
9.2 Test of the self locking ability of the biological lid handling gear
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Test of the self locking ability of the biological lid handling gear
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
2 Test of the self locking ability of the biological lid handling gear
- Initial status:
No alarm
Gripper not in lower position with TN13 Biological Lid
(maximum load)
- Action :
Unlock manual brake (release manual lever)
- Check :
Gripper in starter position (no movement)
A REFERENCE REV. FILE PAGE
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Test of the biological lid handling brake
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
COMPONENT FACTORY TEST INSPECTION OPERATION SHEET – Test of the biological lid handling brake
OBSERVATIONS:
Conformance measuring devices,
OPERATIONS DATE NAME + VISA PERMITTED RESULTS Status discrepancy sheet…
- Action :
Lift down lid handling device (push on “gripper down” push
button (30FCJ11GH310-S10) on BLHS control panel)
Push on Emergency stop button (30FCJ11GH310-S05) on
BLHS control panel
- Check :
Motor and brake immediately OFF – Biological Lid
Handling movement Stopped.
A REFERENCE REV. FILE PAGE
ADRES
NAME FROM CLASS MESSAGE_TEXT N° DBX
S
ET200M_GH130_DI3 SPLC A Digital input card on ET200M “SPLC_GH130” slot 6 in fault 95 DB200 DBX60,7
ET200M_GH130_DO1 SPLC A Digital output card on ET200M “SPLC_GH130” slot 7 in fault 96 DB200 DBX70,0
ET200M_GH130_DO2 SPLC A Digital output card on ET200M “SPLC_GH130” slot 8 in fault 97 DB200 DBX70,1
ET200M_GH210_DI1 SPLC A Digital input card on ET200M “SPLC_GH210” slot 4 in fault 98 DB200 DBX70,2
ET200M_GH210_DI2 SPLC A Digital input card on ET200M “SPLC_GH210” slot 5 in fault 99 DB200 DBX70,3
ET200M_GH210_DI3 SPLC A Digital input card on ET200M “SPLC_GH210” slot 6 in fault 100 DB200 DBX70,4
ET200M_GH210_DO1 SPLC A Digital output card on ET200M “SPLC_GH210” slot 7 in fault 101 DB200 DBX70,5
ET200M_GH210_DO2 SPLC A Digital output card on ET200M “SPLC_GH210” slot 8 in fault 102 DB200 DBX70,6
ET200M_GH210_AI SPLC A Analog input card on ET200M “SPLC_GH210” slot 9 in fault 103 DB200 DBX70,7
ET200M_GH310_DI SPLC A Digital input card on ET200M “SPLC_GH310” slot 4 in fault 104 DB200 DBX80,0
ET200M_GH310_DO SPLC A Digital output card on ET200M “SPLC_GH310” slot 5 in fault 105 DB200 DBX80,1
ET200M_GH410_DI SPLC A Digital input card on ET200M “SPLC_GH410” slot 4 in fault 106 DB200 DBX80,2
ET200M_GH410_DO SPLC A Digital output card on ET200M “SPLC_GH410” slot 5 in fault 107 DB200 DBX80,3
SPLC_Com_error_output ethernet W Ethernet alarms communication SPLC - OPLC Fault 220 DB200 DBX270,4
OPLC_GH120_com_fault profibus W Profibus communication ET200M GH120 slave fault 224 DB200 DBX280,0
SFCTM_M_GH210_com_fault profibus W Profibus communication ET200M GH210 slave fault 225 DB200 DBX280,1
BLHS_GH310_com_fault profibus W Profibus communication ET200M GH310 slave fault 226 DB200 DBX280,2
Upper_cover_com_fault profibus W Profibus communication ET200M GH410 slave fault 227 DB200 DBX280,3
SFCTM_S_GH210_com_fault profibus W Profibus communication ET200S GH210 slave fault 228 DB200 DBX280,4
HMI_TP_com_fault profibus W Profibus communication OPLC PSCP fault 229 DB200 DBX280,5
Accurate_positionning
Low_alarm_value W Accurate positionning sensor 2 over low limit 420 DB200 DBX520,4
2
Accurate_positionning
analog_value_fault W Accurate positionning sensor 2 in fault 421 DB200 DBX520,5
2
Pressure measurement on valve tool A (CP180 sensor) over hight
hight_alarm_value CP180 W 422 DB200 DBX520,6
limit
Pressure measurement on valve tool A (CP180 sensor) over Low
Low_alarm_value CP180 W 423 DB200 DBX520,7
limit
analog_value_fault CP180 W Pressure measurement on valve tool A (CP180 sensor) in fault 424 DB200 DBX530,0
Pressure measurement on valve tool B (CP181 sensor) over hight
hight_alarm_value CP181 W 425 DB200 DBX530,1
limit
Pressure measurement on valve tool B (CP181 sensor) over Low
Low_alarm_value CP181 W 426 DB200 DBX530,2
limit
analog_value_fault CP181 W Pressure measurement on valve tool B (CP181 sensor) in fault 427 DB200 DBX530,3
Pressure measurement on valve tool C (CP182 sensor) over hight
hight_alarm_value CP182 W 428 DB200 DBX530,4
limit
Pressure measurement on valve tool C (CP182 sensor) over Low
Low_alarm_value CP182 W 429 DB200 DBX530,5
limit
analog_value_fault CP182 W Pressure measurement on valve tool C (CP182 sensor) in fault 430 DB200 DBX530,6
Pressure measurement test tool for lid (CP183 sensor) over hight
hight_alarm_value CP183 W 431 DB200 DBX530,7
limit
Pressure measurement test tool for lid (CP183 sensor) over Low
Low_alarm_value CP183 W 432 DB200 DBX540,0
limit
analog_value_fault CP183 W Pressure measurement test tool for lid (CP183 sensor) in fault 433 DB200 DBX540,1
Pressure measurement for leaktightness tests (CP198 sensor)
hight_alarm_value CP198 W 434 DB200 DBX540,2
over hight limit
Pressure measurement for leaktightness tests (CP198 sensor)
Low_alarm_value CP198 W 435 DB200 DBX540,3
over Low limit
Pressure measurement for leaktightness tests (CP198 sensor) in
analog_value_fault CP198 W 436 DB200 DBX540,4
fault
Water level measurement in cask and loading pit (CL199 sensor)
hight_alarm_value CL199 W 437 DB200 DBX540,5
over hight limit
Water level measurement in cask and loading pit (CL199 sensor)
Low_alarm_value CL199 W 438 DB200 DBX540,6
over Low limit
A REFERENCE REV. FILE PAGE
Time to long for start screw 1/2/3/4 motor for undocking, SFC
Motor_start_undocking_time_expired SFC docking W 481 DB200 DBX600,1
docking device step 9
undocking_time_expired SFC docking W Time to long for undocking, SFC anti seismic device step 10 482 DB200 DBX600,2
Time to long for stop screw 1/2/3/4 motor for undocking, SFC
Motor_stop_undocking_time_expired SFC docking W 483 DB200 DBX600,3
docking device step 11
Time to long for lift down screw 1/2/3/4, SFC anti seismic device
Lift_down_time_expired SFC docking W 484 DB200 DBX600,4
step 12
TTLE_fault motor travelling W Time to long for execution travelling motor 488 DB200 DBX610,0
overheat_fault motor travelling W overheat fault for travelling motor 489 DB200 DBX610,1
thermal_circuit_braker_fault motor travelling W Thermal circuit braker released for travelling motor 490 DB200 DBX610,2
TTLE_fault motor0 anti seimic W Time to long for execution anti seismic 0 motor 491 DB200 DBX610,3
overheat_fault motor0 anti seimic W overheat fault for anti seismic 0 motor 492 DB200 DBX610,4
thermal_circuit_braker_fault motor0 anti seimic W Thermal circuit braker released for anti seismic 0 motor 493 DB200 DBX610,5
TTLE_fault motor200 anti seimic W Time to long for execution anti seismic 200 motor 494 DB200 DBX610,6
overheat_fault motor200 anti seimic W overheat fault for anti seismic 200 motor 495 DB200 DBX610,7
thermal_circuit_braker_fault motor200 anti seimic W Thermal circuit braker released for anti seismic 200 motor 496 DB200 DBX620,0
Motor 0 biological
TTLE_fault W Time to long for execution biological protection 0 motor 497 DB200 DBX620,1
protection
Motor 0 biological
overheat_fault W overheat fault for biological protection 0 motor 498 DB200 DBX620,2
protection
Motor 0 biological
thermal_circuit_braker_fault W Thermal circuit braker released for biological protection 0 motor 499 DB200 DBX620,3
protection
Motor 200 biological
TTLE_fault W Time to long for execution biological protection 200 motor 500 DB200 DBX620,4
protection
Motor 200 biological
overheat_fault W overheat fault for biological protection 200 motor 501 DB200 DBX620,5
protection
Motor 200 biological
thermal_circuit_braker_fault W Thermal circuit braker released for biological protection 200 motor 502 DB200 DBX620,6
protection
TTLE_fault motor elevator W Time to long for execution elevator motor 503 DB200 DBX620,7
overheat_fault motor elevator W overheat fault for elevator motor 504 DB200 DBX630,0
thermal_circuit_braker_fault motor elevator W Thermal circuit braker released for elevator motor 505 DB200 DBX630,1
TTLE_fault motor screw 1 W Time to long for execution screw 1 motor 506 DB200 DBX630,2
overheat_fault motor screw 1 W overheat fault for screw 1 motor 507 DB200 DBX630,3
A REFERENCE REV. FILE PAGE
thermal_circuit_braker_fault motor screw 1 W Thermal circuit braker released for screw 1 motor 508 DB200 DBX630,4
TTLE_fault motor screw 2 W Time to long for execution screw 2 motor 509 DB200 DBX630,5
overheat_fault motor screw 2 W overheat fault for screw 2 motor 510 DB200 DBX630,6
thermal_circuit_braker_fault motor screw 2 W Thermal circuit braker released for screw 2 motor 511 DB200 DBX630,7
TTLE_fault motor screw 3 W Time to long for execution screw 3 motor 512 DB200 DBX640,0
overheat_fault motor screw 3 W overheat fault for screw 3 motor 513 DB200 DBX640,1
thermal_circuit_braker_fault motor screw 3 W Thermal circuit braker released for screw 3 motor 514 DB200 DBX640,2
TTLE_fault motor screw 4 W Time to long for execution screw 4 motor 515 DB200 DBX640,3
overheat_fault motor screw 4 W overheat fault for screw 4 motor 516 DB200 DBX640,4
thermal_circuit_braker_fault motor screw 4 W Thermal circuit braker released for screw 4 motor 517 DB200 DBX640,5
TTLE_fault valve screw 1 W Time to long for execution screw 1 valve 518 DB200 DBX640,6
incoherence_fault valve screw 1 W incoherence fault for screw 1 valve 519 DB200 DBX640,7
TTLE_fault valve screw 2 W Time to long for execution screw 2 valve 520 DB200 DBX650,0
incoherence_fault valve screw 2 W incoherence fault for screw 2 valve 521 DB200 DBX650,1
TTLE_fault valve screw 3 W Time to long for execution screw 3 valve 522 DB200 DBX650,2
incoherence_fault valve screw 3 W incoherence fault for screw 3 valve 523 DB200 DBX650,3
TTLE_fault valve screw 4 W Time to long for execution screw 4 valve 524 DB200 DBX650,4
incoherence_fault valve screw 4 W incoherence fault for screw 4 valve 525 DB200 DBX650,5
hight limit
Load measurement lid handling device cell 1 (CW406 sensor) over
Low_alarm_value load_cell_1 W 609 DB200 DBX760,1
Low limit
Load measurement lid handling device cell 1 (CW406 sensor) in
analog_value_fault load_cell_1 W 610 DB200 DBX760,2
fault
Load measurement lid handling device cell 2 (CW407 sensor) over
hight_alarm_value load_cell_2 W 611 DB200 DBX760,3
hight limit
Load measurement lid handling device cell 2 (CW407 sensor) over
Low_alarm_value load_cell_2 W 612 DB200 DBX760,4
Low limit
Load measurement lid handling device cell 2 (CW407 sensor) in
analog_value_fault load_cell_2 W 613 DB200 DBX760,5
fault
overload_cask TN13 W Load measurement TN13 Cask overload 614 DB200 DBX760,6
overload_cask CASTOR W Load measurement CASTOR Cask overload 615 DB200 DBX760,7
underload_cask TN13 W Load measurement TN13 Cask overload 616 DB200 DBX770,0
underload_cask CASTOR W Load measurement CASTOR Cask overload 617 DB200 DBX770,1
SFC lid handling Time to long for start lid handling motor in down direction, SFC lid
Motor_start_down_time_expired W 624 DB200 DBX780,0
device handling device step 2
SFC lid handling Time to long for down lid handling device in position, SFC lid
lid_handling_down_time_expired W 625 DB200 DBX780,1
device handling device step 3
SFC lid handling Time to long for stop lid handling motor in down direction, SFC lid
Motor_stop_down_time_expired W 626 DB200 DBX780,2
device handling device step 4
SFC lid handling Time to long for start lid handling motor in up direction, SFC lid
Motor_start_up_time_expired W 627 DB200 DBX780,3
device handling device step 5
SFC lid handling Time to long for up lid handling device in upper position, SFC lid
Lid_handling_up_time_expired W 628 DB200 DBX780,4
device handling device step 6
SFC lid handling Time to long for stop lid handling motor in up direction, SFC lid
Motor_stop_up_time_expired W 629 DB200 DBX780,5
device handling device step 7
lock_time_expired SFC gripper W Time to long for lock lid handling device, SFC gripper step 2 630 DB200 DBX780,6
unlock_time_expired SFC gripper W Time to long for unlock lid handling device, SFC gripper step 4 631 DB200 DBX780,7
motor lid handling
TTLE_fault W Time to long for execution lid handling motor 640 DB200 DBX800,0
device
motor lid handling
overheat_fault W overheat fault for lid handling motor 641 DB200 DBX800,1
device
TTLE_fault valve gripper locking W Time to long for execution gripper valve (AA212B) 642 DB200 DBX800,2
A REFERENCE REV. FILE PAGE
incoherence_fault valve gripper locking W incoherence fault for gripper valve (AA212B) 643 DB200 DBX800,3
valve gripper
TTLE_fault W Time to long for execution gripper valve (AA212A) 644 DB200 DBX800,4
unlocking
valve gripper
incoherence_fault W incoherence fault for gripper valve (AA212A) 645 DB200 DBX800,5
unlocking
PS ALARM GROUP
Power_off_400VAC_PS GH410 W 400VAC PS cabinet fault 800 DB200 DBX1000,0
Power_off_230VAC_PS GH410 W 230VAC PScabinet fault 801 DB200 DBX1000,1
Power_off_24VAC_PS GH410 W 24VAC PS cabinet fault 802 DB200 DBX1000,2
Power_off_24VDC_PS_operating_I/O
GH410 W 24VDC PS operating I/O module fault 803 DB200 DBX1000,3
_module
Power_off_24VDC_PS_safety_I/O_
GH410 W 24VDC PS safety I/O module fault 804 DB200 DBX1000,4
module
Power_off_24VDC_PS_safety_HW GH410 W 24VDC PS safety HW fault 805 DB200 DBX1000,5
Upper_cover_accelerometer GH410 W Upper cover warning seismic detection 806 DB200 DBX1000,6
upper_cover_voltage_monitoring GH410 W upper cover voltage monitoring in fault 807 DB200 DBX1000,7
upper_cover_closed_over_travel GH410 W Upper cover in over travel close position 808 DB200 DBX1010,0
upper_cover_open_over_travel GH410 W Upper cover in over travel open position 809 DB200 DBX1010,1
overcrossed GH410 W Overcrossed traction rope, upper cover device 810 DB200 DBX1010,2
slack_rope GH410 W Slack rope detected on traction rope, upper cover device 811 DB200 DBX1010,3
load_limiter GH410 W Over load detected on traction rope, upper cover device 812 DB200 DBX1010,4
Speed measurement of hoist upper cover motor (VSD feedback)
hight_alarm_value VSD_speed W 815 DB200 DBX1020,0
over hight limit
Speed measurement of hoist upper cover motor (VSD feedback)
Low_alarm_value VSD_speed W 816 DB200 DBX1020,1
over low limit
Speed measurement of hoist upper cover motor (VSD feedback)
analog_value_fault VSD_speed W 817 DB200 DBX1020,2
in fault
overspeed_motor hoist_motor_codeur W Over speed hoist upper cover motor 818 DB200 DBX1020,3
Time to long for start hoist upper cover motor in open direction,
Motor_start_up_time_expired SFC hoist upper cover W 824 DB200 DBX1030,0
SFC upper cover device step 2
brake_open_up_time_expired SFC hoist upper cover W Time to long for open operating and auxiliary brakes in open 825 DB200 DBX1030,1
A REFERENCE REV. FILE PAGE
incoherence_fault Valve AA032 W Incoherence fault for Valve AA032 1033 DB200 DBX1290,1
TTLE_fault Valve AA033 W Time to long for execution Valve AA033 1034 DB200 DBX1290,2
incoherence_fault Valve AA033 W Incoherence fault for Valve AA033 1035 DB200 DBX1290,3
TTLE_fault Valve AA034 W Time to long for execution Valve AA034 1036 DB200 DBX1290,4
incoherence_fault Valve AA034 W Incoherence fault for Valve AA034 1037 DB200 DBX1290,5
TTLE_fault Valve AA035 W Time to long for execution Valve AA035 1038 DB200 DBX1290,6
incoherence_fault Valve AA035 W Incoherence fault for Valve AA035 1039 DB200 DBX1290,7
TTLE_fault Valve AA036 W Time to long for execution Valve AA036 1040 DB200 DBX1300,0
incoherence_fault Valve AA036 W Incoherence fault for Valve AA036 1041 DB200 DBX1300,1
TTLE_fault Valve AA302 W Time to long for execution Valve AA302 1042 DB200 DBX1300,2
incoherence_fault Valve AA302 W Incoherence fault for Valve AA302 1043 DB200 DBX1300,3
TTLE_fault Valve AA401 W Time to long for execution Valve AA401 1044 DB200 DBX1300,4
incoherence_fault Valve AA401 W Incoherence fault for Valve AA401 1045 DB200 DBX1300,5
TTLE_fault Valve AA402 W Time to long for execution Valve AA402 1046 DB200 DBX1300,6
incoherence_fault Valve AA402 W Incoherence fault for Valve AA402 1047 DB200 DBX1300,7
TTLE_fault Valve AA403 W Time to long for execution Valve AA403 1048 DB200 DBX1310,0
incoherence_fault Valve AA403 W Incoherence fault for Valve AA403 1049 DB200 DBX1310,1
TTLE_fault Valve AA406 W Time to long for execution Valve AA406 1050 DB200 DBX1310,2
incoherence_fault Valve AA406 W Incoherence fault for Valve AA406 1051 DB200 DBX1310,3
TTLE_fault Valve AA407 W Time to long for execution Valve AA407 1052 DB200 DBX1310,4
incoherence_fault Valve AA407 W Incoherence fault for Valve AA407 1053 DB200 DBX1310,5
TTLE_fault Valve AA408 W Time to long for execution Valve AA408 1054 DB200 DBX1310,6
incoherence_fault Valve AA408 W Incoherence fault for Valve AA408 1055 DB200 DBX1310,7
TTLE_fault Valve AA409 W Time to long for execution Valve AA409 1056 DB200 DBX1320,0
incoherence_fault Valve AA409 W Incoherence fault for Valve AA409 1057 DB200 DBX1320,1
TTLE_fault Valve AA413 W Time to long for execution Valve AA413 1058 DB200 DBX1320,2
incoherence_fault Valve AA413 W Incoherence fault for Valve AA413 1059 DB200 DBX1320,3
TTLE_fault Valve AA414 W Time to long for execution Valve AA414 1060 DB200 DBX1320,4
incoherence_fault Valve AA414 W Incoherence fault for Valve AA414 1061 DB200 DBX1320,5
TTLE_fault Valve AA419 W Time to long for execution Valve AA419 1062 DB200 DBX1320,6
A REFERENCE REV. FILE PAGE
incoherence_fault Valve AA419 W Incoherence fault for Valve AA419 1063 DB200 DBX1320,7
TTLE_fault Valve AA450 W Time to long for execution Valve AA450 1064 DB200 DBX1330,0
incoherence_fault Valve AA450 W Incoherence fault for Valve AA450 1065 DB200 DBX1330,1
TTLE_fault Valve AA465 W Time to long for execution Valve AA465 1066 DB200 DBX1330,2
incoherence_fault Valve AA465 W Incoherence fault for Valve AA465 1067 DB200 DBX1330,3
TTLE_fault Valve AA472 W Time to long for execution Valve AA472 1068 DB200 DBX1330,4
incoherence_fault Valve AA472 W Incoherence fault for Valve AA472 1069 DB200 DBX1330,5
TTLE_fault Valve AA473 W Time to long for execution Valve AA473 1070 DB200 DBX1330,6
incoherence_fault Valve AA473 W Incoherence fault for Valve AA473 1071 DB200 DBX1330,7
TTLE_fault Valve AA474 W Time to long for execution Valve AA474 1072 DB200 DBX1340,0
incoherence_fault Valve AA474 W Incoherence fault for Valve AA474 1073 DB200 DBX1340,1
TTLE_fault Valve AA510 W Time to long for execution Valve AA510 1074 DB200 DBX1340,2
incoherence_fault Valve AA510 W Incoherence fault for Valve AA510 1075 DB200 DBX1340,3
TTLE_fault Manual Valve AA003 W Time to long for execution Manual Valve AA003 1080 DB200 DBX1350,0
incoherence_fault Manual Valve AA003 W Incoherence fault for Manual Valve AA003 1081 DB200 DBX1350,1
TTLE_fault Manual Valve AA005 W Time to long for execution Manual Valve AA005 1082 DB200 DBX1350,2
incoherence_fault Manual Valve AA005 W Incoherence fault for Manual Valve AA005 1083 DB200 DBX1350,3
TTLE_fault Manual Valve AA040 W Time to long for execution Manual Valve AA040 1084 DB200 DBX1350,4
incoherence_fault Manual Valve AA040 W Incoherence fault for Manual Valve AA040 1085 DB200 DBX1350,5
TTLE_fault Manual Valve AA050 W Time to long for execution Manual Valve AA050 1086 DB200 DBX1350,6
incoherence_fault Manual Valve AA050 W Incoherence fault for Manual Valve AA050 1087 DB200 DBX1350,7
TTLE_fault Manual Valve AA052 W Time to long for execution Manual Valve AA052 1088 DB200 DBX1360,0
incoherence_fault Manual Valve AA052 W Incoherence fault for Manual Valve AA052 1089 DB200 DBX1360,1
TTLE_fault Manual Valve AA053 W Time to long for execution Manual Valve AA053 1090 DB200 DBX1360,2
incoherence_fault Manual Valve AA053 W Incoherence fault for Manual Valve AA053 1091 DB200 DBX1360,3
TTLE_fault Manual Valve AA059 W Time to long for execution Manual Valve AA059 1092 DB200 DBX1360,4
incoherence_fault Manual Valve AA059 W Incoherence fault for Manual Valve AA059 1093 DB200 DBX1360,5
TTLE_fault Manual Valve AA060 W Time to long for execution Manual Valve AA060 1094 DB200 DBX1360,6
incoherence_fault Manual Valve AA060 W Incoherence fault for Manual Valve AA060 1095 DB200 DBX1360,7
TTLE_fault Manual Valve AA061 W Time to long for execution Manual Valve AA061 1096 DB200 DBX1370,0
A REFERENCE REV. FILE PAGE
incoherence_fault Manual Valve AA061 W Incoherence fault for Manual Valve AA061 1097 DB200 DBX1370,1
TTLE_fault Manual Valve AA093 W Time to long for execution Manual Valve AA093 1098 DB200 DBX1370,2
incoherence_fault Manual Valve AA093 W Incoherence fault for Manual Valve AA093 1099 DB200 DBX1370,3
TTLE_fault Manual Valve AA303 W Time to long for execution Manual Valve AA303 1100 DB201 DBX1370,4
incoherence_fault Manual Valve AA303 W Incoherence fault for Manual Valve AA303 1101 DB202 DBX1370,5
TTLE_fault Manual Valve AA425 W Time to long for execution Manual Valve AA425 1102 DB203 DBX1370,6
incoherence_fault Manual Valve AA425 W Incoherence fault for Manual Valve AA425 1103 DB204 DBX1370,7
A REFERENCE REV. FILE PAGE
Parameter
Analog sensor
TN13 castor
Operating application
OPLC software
software
SCADA application
SCADA software
software
Designation Code
SPLC program
signature