Digsi 5 Quick Notes Digsi-5-Qn0020: Device Modes & Test Suite
Digsi 5 Quick Notes Digsi-5-Qn0020: Device Modes & Test Suite
Digsi 5 Quick Notes Digsi-5-Qn0020: Device Modes & Test Suite
SIPROTEC 5 relays operate in one of four defined modes. Process Mode is the normal operating mode, with
Commissioning Mode and Simulation Mode enabling special testing features.
HV Power File: DIGSI-5-QN0020v1 Device Modes and Test Suite.docx Page 1 of 5 Originator: Warwick Beech
Version 1. Nov 2018
Changing the Mode will cause the relay to restart, so USB/network communications will need to be re-
established. (With firmware V6.0 onwards, a change from Process to Commissioning Mode does not require
a restart).
HV Power File: DIGSI-5-QN0020v1 Device Modes and Test Suite.docx Page 2 of 5 Originator: Warwick Beech
Version 1. Nov 2018
Scenario Commissioning
1 – Normal Protection function Not active
2 – External trip function Not active
3 – User created signal Forcing of binary input, results in that signal being processed
4 – CFC function Forcing of binary input, results in that signal being processed
5 – SCADA output Not active
6 – SCADA control Not active
HV Power File: DIGSI-5-QN0020v1 Device Modes and Test Suite.docx Page 3 of 5 Originator: Warwick Beech
Version 1. Nov 2018
Scenario Commissioning
1 – Normal Protection function Active
2 – External trip function Active
3 – User created signal Active
4 – CFC function Active
5 – SCADA output Active
6 – SCADA control Active
The following conditions were used during the CONTROL FUNCTIONS test:
1. Operate switching directly
2. Ignore interlocking conditions
The following conditions were used during the CIRCUIT BREAKER test:
1. Operate switching directly
2. Ignore interlocking conditions
Scenario Process
1 – Normal Protection function Active [1]
2 – External trip function Active [1]
3 – User created signal Active
4 – CFC function Active
5 – SCADA output Active
6 – SCADA control Active
[1] If protection function operates, then breaker cannot be opened/closed via control test till that fault is reset
HV Power File: DIGSI-5-QN0020v1 Device Modes and Test Suite.docx Page 4 of 5 Originator: Warwick Beech
Version 1. Nov 2018
HV Power File: DIGSI-5-QN0020v1 Device Modes and Test Suite.docx Page 5 of 5 Originator: Warwick Beech
Version 1. Nov 2018