Professional Documents
Culture Documents
Compressor Trouble Shooting
Compressor Trouble Shooting
•
•
COMPRESSORS &
PROGRAM CONTENT
3. Before starting our preliminary inspection, let's
1. MAKING PRELIMINARY INSPECTION - talk about the most important part of your
USE YOUR NATURAL SENSES
job..... Safety.
2. UNDERSTANDING "NORMAL"
OPERATION Working on air conditioning, refrigeration or
heating systems means working on components
3. ANALYZING SYSTEM OPERATION that are pressurized, rotating, and either thellnally
or electrically hol So, be careful.
1
shooting live components. Utilize all safety The purpose of the Operating Log is of course to
procedures shown in the printed instructions. maintain a running record of operation, main-
Don't take chances. tenance, and service of the system. Items like the
addition of refrigerant or oil, replacement of parts,
and a check of operating data will assist the
technician in analyzing a system problem.
2
7. Now, take a look around for the obvious. Is 9. Are there numerous system accessories such as
there an evaporator or condenser above the oil separators, liquid line solenoids, driers, sight-
compressor which might dump liquid refrigerant glasses or accumulators? All of these serve a
into the compressor? purpose, and if there is a decided need for acces-
sories, they should be installed. Keep in mind,
however, that they increase system pressure drop
and can affect system operation by reducing
refrigerant flow, oil return, and capacity. So, if not
installed and operating conectly, they can cause
system problems and even a compressor failure.
3
The compressor discharges into a muffler, at I,
which breaks up the gas pulses to protect the
piping and reduce operating sound.
4
signs of freezing up, caused perhaps by insufficient UNDERSTANDING
air flow to the evaporator or is it being used for "NORMAL" OPERATION
low temperature work where some icing is
nOllual?
SYSTEM OPERATION
-
to need a multimeter and an ammeter to measure
the voltage at the compressor and to measure the
current which the compressor is drawing. All will
be used to provide a more complete system
analysis.
6
21. Now let's take a look at how this system 23. Watch the gauges and the oil sightglass.
operates and compare its readings to those of a Heavy foaming at the sightglass should not
normal air conditioning system. While this continue more than 5 to 10 minutes after start-up.
system has an air-cooled condenser. we should If it does. there may be excessive oil or refrigerant
mention here that we will occasionally discuss in the system. Continue to check for abnoIIllai
water-cooled systems. since many of the same sounds. vibration. and even odors that may
troubleshooting techniques apply to both. indicate a problem. Listen and be sure the
unloaders "snap" in when they activate. .
OVERHEATING
COULD BE
CAUSED BY
VOLTAGE OR
CURRENT IMBALANCE
7
L1- L2 220V- 215 V = 5V 2.27 % Imbalance
L2- L3 221 V - 220V = 1V is excessive
L3 - L1 224V - 220V = 4V and must be
% Imbalance = 5 / 220 x 100 reduced to
% Imbalance = 2.27 % 2% or below.
25. Measure the voltage on the load side of the 3 26. The maximum acceptable imbalance is 2%, so
phases at the disconnect or contactor with the the voltage supplied to this compressor must be
compressor operating. Let's say you've got these balanced in the distribution system of the building
readings: or the power company's incoming power.
L1 - L2 215V
L2· L3 221V
L3 - L1 224V
660V
L 1 - L2 218V
660V divided by 3 = 220V; the average voltage.
L2 - L3 219V
Now check the differential between the average
and the actual readings. L3 - L1 221V
Then use this formula: 658/ 3 = 219.3V average voltage
8
Any cwtent imbalance over 10% must be
corrected. The imbalance is figured in the same
Find difference manner as the voltage imbalance. which is the
between each leg differential between the actual reading and the
average amperage.
and average vo~age
9
, '. '- ... , ..... -.
NORMAL CONDITIONS
(AIR
,
CONDITIONING
I,.~M:(~~:-:""""'.. ':'_'" ~
DUTY)
,..:x?<.*--,'
~,
~
'--
. ,
31. The point here is that in order to detelJuine 32. With these measurements, we'll continue
whether the system has a problem, you must first checking the system by calculating the superheat.
know what the operating conditions are when the Superheat is necessary to ensure that the
system and compressor are operating nOlJllally. refrigerant being returned to the compressor is in
These pressures and temperatures do vary with the form of vapor and not liquid. Liquid
equipment application and refrigerant. It's refrigerant cannot be compressed, so the superheat
therefore important to check the manufacturer's provides a safety factor that prevents pumping of
service literature for "normal" system readings liquid and its potential for breaking up valves,
before troubleshooting a system. pistons, and rods in the compressor. A W&.1J1l
vapor also provides capacity improvement over a
The number of actual readings taken during a cold vapor.
system troubleshooting procedure is dependent of
course on how quickly you fInd the problem. To calculate superheat, use a Temperature-Pressure
Also, if the load is high and the system has not Chart to convert suction pressure to saturated
been running, it may take several hours for actual evaporator suction temperature. Obtain superheat
system pressures and temperatures to stabilize. by subtracting this fIgure from the actual
temperature of the suction line at the suction
For the purposes of this section of the program, service valve.
we'll assume this R-22 system has stabilized and
we've taken some essential measurements.
10
suction temperature is about 40°F. If the actual To protect against flash gas in the liquid line, the
suction line temperature measures about 52°F, charge must be sufficient and the liquid line must
there is about 12 degIees of superheat being added be cool enough to maintain 10 to 20°F of
to the refrigerant at the leaving end of the subcooling.
• evaporator and in the suction line.
Here's how liquid subcooling is obtained. The
high pressure, high temperature hot gas leaving the
discharge line rejects superheat in the first portion
of the condenser. As the refrigerant continues
Typical Ale duty superheat through the condenser, it condenses first to a
mixture of gas and liquid, then to a liquid. The
0 liquid will fmally subcool as heat continues to be
is 10 -12 F rejected to the air or water flowing through or over
the condenser.
Normal EXV superheat
0
is 3 -10 F
RED F1GUAES • YACY'JM a' *CM' FIGURE. . . . . . . . . .
"F R-12 R-13 R-22 1I-4lOO R-5O
34. A typical air conditioning duty superheat with
a TXV would be 10 to 12°F above the saturated
evaporator temperature.
11
IF HOT GAS TEMPERATURE
EXCEEDS 275°F, CHECK:
0
2 Subcooling Loss = • High Superheat
• Lubrication
• Electrical Problem
1 % Capacity Loss
• High Compression Ratio
• Refrigerant Flow Restriction
37. So if you don't have enough subcooling, you 39. If the hot gas line temperature approaches
will be shon of capacity by about 1% for every 2 275°F, the system must be shut down and the
degrees of subcooling. cause of the high gas temperarure analyzed. The
actual temperarure of the hot gas at compressor
discharge valves is 25 to 50°F higher than the line
temperarure and the refrigerant and oil can begin
to carbonire at these elevated temperarures. High
superheat, a lubrication problem, an electrical
problem, high compression ratio, or a refrigerant
flow restriction can cause overheating of the
compressor.
12
The bottom of the head is usually at a temperature
of 80 to 120°F. The crankcase will be slightly
wallu as the oil temperature goes from 90 to DISCHARGE 260 PSI+14.7 PSI 274.7
135°F depending on loading of the system. The
motor barrel runs cooler because of the refrigerant SUCTION 68 PSI+14.7 PSI
-
- -
82.7
being drawn through it and so it will range from
60 to 105°F, depending on location. If the load is
high, it may take time to reach the lower
3.32
=--- COMPRESSION
RATIO
temperature.
1
When these operating temperatures are too cool or
too hot it means something is wrong with the
compressor or system. Check the typical operating
temperatures in the back of the workbook to 42. The last item to check is the compression
detennine the possible cause of these temperature ratio. Calculate this ratio by dividing total
• •
vanatlons. absolute discharge pressure by the total absolute
suction pressure. The resulting figure or ratio is
an indication of the work being perfOIllled by the
system.
13
R- 22 Air R 12 Med R 502 Low
Condo Temp, Ref, Temp, Ref,
Ambient Air T 9O "F go F 90F
43. Now we've covered "Making a Preliminary 44. Remember, these readings do vary based on
Inspection" and "Understanding Normal equipment application and operating conrutions.
Operation." As you've seen, the system has great For instance, an R-12 system on meruum temp-
influence on how efficiently and how reliably the erature refrigeration duty, or an R-502 system on
compressor operates. We've also discussed the low temperature refrigeration duty will have
readings and observations that might be made on different readings. Always refer to the man-
a normal R-22 ali conrutioning system. ufacturer's service literature to find typical
rearungs for your unit or system. A typical
temperature/pressure comparison chart for different
refrigerants is provided in Appenrux B.
14
QUIZ #1
INITIAL INSPECTION AND "NORMAL" OPERATION
•
1. A long or uninsuIated suction line can cause:
a. excessive superheat. c. high subcooling.
b. low superheat. d. low subcooling.
5. (True or False?) A discharge line muffler breaks up gas pulses to protect the piping and reduces
• •
operating nOise.
6. A device in the liquid line that prevents liquid from migrating to the compressor at shutdown is a:
a. TXV. c. liquid line solenoid valve.
b. discharge line muffler. d. all of the above.
8. (True or False?) Rust streaks on the compressor are an indication of not enough superheat.
9. (True or False?) Whenever possible, test equipment and gauges should be connected to a system
when the system is turned ON.
10. (True or False?) When powering up a system, the thelJllostat should first be in the OFF position
before closing the disconnect.
11. Knocking, rattling, or heavy buzzing in the compressor at start-up is an indication of:
a. undercharge. c. overcharge.
b. liquid refrigerant in the compressor. d. high superheat.
12. On a 3-phase system, the voltage imbalance should not be above or below the average voltage by
more than %.
15
13. To properly diagnose a system problem you must fIrst:
a. measure the system operating conditions. c. know the system normal operating
b. check the system with your sense of smell conditions.
hearing. sight and touch. d. check the voltage imbalance.
15. (True or False?) Superheat ensures that only liquid returns to the compressor.
16. The metering device must be fed a constant supply of liquid refrigerant to prevent:
a. flooding the compressor with liquid. c. low superheat
b. flash gas. d. all of the above.
17. (True or False?) Subcooling of 2 or 3°F ensures suffIcient liquid to prevent "Flash Gas" at the
metering device.
19. Every 2°F of subcooling equals how much change in system capacity:
a. 0.5% c. 2.0%
b. 1.0% d. 5.0%
16
L
t _ _ _ _ _ __ _ _ _ _ _ _ _ _ __ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ ______. . . . . . . . . . . . . . .
•
Low capacity
Low or high pressures
Low or high temperatures
Low or high superheat
Low or high subcooling
Low or high compressor current draw 47. If the system doesn't start or run, first check
Low or high compression ratio the temperarure control to be sure it is set
properly, and that the setting is below the space
temperarure. Check the power circuit to be sure
there is line power. Check the control circuit
voltage to be sure it is correct. Also check the
safety switches.
17
and nonnal operating temperatures have been
exceeded. power should be shut off and the
compressor allowed to cool.
When the compressor is overheated. the cause
must be determined. High superheat, electrical
problems. lubrication problems. or condenser
problems are possible causes.
18
•
As discussed earlier in the program, perhaps the
air flow is restricted by dirty filters, a dirty coil or
closed dampers. Maybe corroded fin collars and
tubes are also reducing capacity. Or maybe the
problem is in the air-moving equipment such as
motors, belts and blowers or fans. An evaporator
fan running backwards, or a loose set screw on a
sheave or pulley can also affect capacity.
52. If the evaporator entering air (return air) 54. In liquid-chilled systems, anything which
temperatures are high enough to call for operation, lowers liquid flow through the cooler can prevent
then something is preventing the evaporator from the system from picking up the load.
picking up the load. This may be caused by an air
The flow of the liquid through the cooler must be
flow problem preventing heat transfer from the air
great enough to load the refrigerant with heat.
to the refrigerant
19
Restricted flow caused by scaling or other factors A restriction in the suction line screen, a partially
could cause refrigerant temperatures low enough to closed service valve or a restricted back pressure
freeze the water or other liquid in the cooler. This regulator, accumulator or suction line would
poses a serious threat to the system and to the probably also restrict refrigerant flow and result in
compressor in addition to capacity problems. low capacity and related symptoms such as high
superheat
20
With any of these symptoms we could have the For instance, insufficient air flow or water flow
potential for compressor damage. The fault causing through or over the condenser will reduce heat
these conditions must be COllected. removal from the refrigerant and the condenser
will act like it is too small to do the job. 1b.is will
cause inefficient condensing, elevated pressures
and power draw, and reduced system capacity.
SYSTEM OPERATING AT
•
REDUCED CAPACITY
REDUCTION OF
• Check Load HEAT TRANSFER
• Check Evaporator Flow
• Check Refrigerant Flow _ Dirty or Blocked Coils
• Check Refrigerant Charge _ Damaged Fins or Fin
Collars
_ Abnormal Motor Rotation
59. To sum up the points made: if the system
appears to be performing at a reduced capacity, the
evaporator load, evaporator air or liquid flow,
refrigerant flow path, and refrigerant charge must 61. In air-cooled systems, coils that are dirty, too
be checked. close to a wall, or too close to each other, will
cause a reduction in heat transfer. Coils may
become blocked by vegetation. As with the
evaporator, damaged or bent fins and eroded fin
CONDENSER PROBLEMS collars are also a possible cause of trouble. A
motor running slowly or backward will produce
- Load Too High? high saturated discharge and low subcooling.
_ Water or Air Flow
Problem?
WATER COOLED SYSTEMS
- Restricted Refrigerant
• Insufficient Flow
Flow?
• Defective Pump
• Dirt
• Scaled Piping
60. On the high side of the system, the purpose of • Defective Pressure
the condenser is to receive high pressure, high Controls
temperature gas from the compressor and to de- • Blocked Cooling
superheat it, condensing the gas to liquid and Tower
subcooling the liquid. The heat from the
evaporator load, the superheat, and the heat of
compression must be transferred to the condenser 62. In water-cooled systems, insufficient flow of
cooling medium. If this heat transfer process is water, air in the water supply, defective pumps,
not completed, system operation or capacity will restricted water line strainers, scaled water piping,
be affected. defective head pressure controls, or dirty or
blocked cooling towers, will also cause high
21
saturated discharge temperature and low sub- collars. Or there may be a problem with the
cooling. Sometimes a combination of several condenser or flow of refrigerant.
factors may be involved.
To quickly check the effectiveness of the
condenser, measure the temperature of the air or
water as it enters the condenser and as it leaves
EXCESSIVE LOAD the condenser. An appreciable rise in temperature
of the air or water must be measured in order to
achieve cooling of the refrigerant and its change of
state from hot gas to WaIlII liquid. Check product
literature for recommended air or water flow and
temperature rise. If air and water flow are okay
and the temperature rise is lower than it should be,
the condenser may be undersized or contain non-
condensibles.
22
t
Any condition which dettacts from the heat
transfer between the air or water and the
refrigerant in the condenser will have symptoms
similar to those mentioned above.
. .""
••••
TVX PASSING LIQUID AND VAPOR
66. If there is air, nitrogen or any other ~ .L ~ .o . re. 'OJ TO
COO '8" • •• EVAPORATOR
noncondensible gas in the system, it will occupy
space in the top of the condenser and reduce the Q)~O. oa ~"o "
space needed by the refrigerant. This, in effect, • • • •
creates a condenser that is too small to do the job.
This can be checked by shutting the system off, 68. The capacity of the metering device is
allowing the condenser to settle out to ambient reduced greatly if it is fed vapor; so an adequately
temperature, and checking the pressure of the sized condenser that is operating correctly without
refrigerant at the discharge service valve. Pressure the presence of non-condensibles must supply
should be within 5 psig of the pressure called for subcooled liquid to the metering device.
at room temperature. Higher pressures indicate the
Remember that the latent heat of vaporization (the
presence of noncondensibles.
changing of a liquid to a vapor) is where the
Noncondensibles must be removed from the refrigerant really picks up the load. If it's a vapor
system by complete evacuation and recharging of as it enters the evaporator, it can't do an adequate
the system. Air must be purged from the water job.
supply of water-cooled condensers.
Some vapor is formed at the needle valve of the
TXV even when it is fed subcooled liquid, but the
TXV should not be fed vapor or a vapor-liquid
mixture, since the metering device is sized for
regulating the flow of liquid Ten to 20°F of
subcooling is recommended for good perfollllance
and higher system efficiency.
23
69. This also assures that a liquid seal is present 71. The frequency of the valve operation will
at the TXV, especially in the case of long liquid show sharp peaks and valleys rather than the
lines, where there is the danger of "flash gas." slower, flatter cycle of a nOIlllal valve. This is
Flash gas is formed from pressure drop caused by called "hunting".
the friction of the tube walls to the flow of
refrigerant. It can drop the pressure to the point
that the liquid reverts back to a vapor.
24
I
73. An excessive charge of refrigerant will raise 75. If this separation is opened, such as at a tear
the pressure in the system. This affects the ability in the valve plate gasket or if the cast iron "web"
of the TXV to control refrigerant flow, causing between the suction and discharge sections of the
low superheat and possible compressor floodback. compressor head is broken or leaking, high
The superheat will be low and the subcooling high. pressure, high temperature gas will flow into the
suction side of the compressor.
Any of these problems, if allowed to continue, will
take their toll with regard to compressor reliability.
25
REVIEW
• Work Safely
• Don't Check Moving Parts
While System is Operating
• Use Your Natural Senses
• Compare Actual Temperatures
and Pressures to Normal Operating
Data For Your System
77. This can be a very frustrating condition, since 79. In this section, we've covered the more
the customer and the technician may feel that there common causes of operating problems. Now,let's
is a problem, but it will be very difficult to review some of the major points that were covered
pinpoint the exact cause without disassembly. in this program.
As a separation opens wider or if the valve breaks,
• The most important aspect of your job is to
the problem becomes more apparent by a decrease
work safely.
in high-low side pressure differential. The smaller
differential in pressures, with the suction pressure
• DO NOT CHECK MOVING PARTS, such as
going higher and the discharge pressure lower also
pulleys, sheaves, wheels, fans, or other moving
decreases the compression ratio.
parts WHILE OPERATING. Disconnects
must be opened, locked and tagged before
checking these moving components.
26
,
- a
= ='
-
- ::.
':::::..
~-
refrigerant charge, lubrication system and
electrical power must be checked.
27
SYSTEM ANALYZER
The System Analyzer, attached to this page, provides a basic, sequential procedure for identifying a
compressor or system problem. Once you're familiar with this procedure, it will become routine on every
service call. More sophisticated analysis and testing may be required to determine what's wrong with
a system. To use the analyzer, follow this step-by-step procedure.
I. Check off reasons for the service call. Talk to the owner or tenant. Request an equipment log.
All can provide important clues.
3. Record system nameplate data. It's the easiest way to get acquainted with a system. Besides, you'll
need this infoullation to troubleshoot and identify equipment in service literature.
4. Look around. A simple inspection may quicldy reveal the problem. Use your natural senses.
5. Start the system. Make sure all components are operational. Check for obvious defects.
Before going to Step 6, review the "typical" system operating pressures and temperatures shown in
Table 3.
CAUTION: The "typical" operating pressures and temperatures shown in Table 3 are provided
solely to demonstrate this method of analyzing systems. Since actual readings will vary with the
items that affect systems operation such as system components, application, load, outdoor
temperature, etc., the Table 3 readings should not be used as the basis for troubleshooting systems.
Check manufacturer's installation and service literature for this type of operational data.
6. Record actual temperature and pressure measurements in Table 3 on lines A through U. Compare
them to typical readings taken from manufacturer's literature. Use them to calculate superheat,
subcooling, compression ratio and capacity. Analyze this infoullation to determine the system
problem.
7. Go to the "Quick System Analysis" chart on page 4 of the System Analyzer to verify the problem.
8. Use the System Analyzer to perfOl'1ll exercises 1 through 5 on the following pages; then complete
Quiz 2 on page 36
29
•
SYSTEM ANALYZER
The System Analyzer, attached to this page, provides a basic, sequential procedure for identifying a
compressor or system problem. Once you're familiar with this procedure, it will become routine on every
service call. More sophisticated analysis and testing may be required to determine what's wrong with
a system. To use the analyzer, follow this step-by-step procedure.
1. Check off reasons for the service calL Talk to the owner or tenant Request an equipment log.
All can provide important clues.
3. Record system nameplate data. It's the easiest way to get acquainted with a system. Besides, you'll
need this information to troubleshoot and identify equipment in service literature.
4. Look around_ A simple inspection may quickly reveal the problem. Use your natural senses.
5. Start the system. Make sure all components are operational. Check for obvious defects.
Before going to Step 6, review the "typical" system operating pressures and temperatures shown in
Table 3.
CAUTION: The "typical" operating pressures and temperatures shown in Table 3 are provided
solely to demonstrate this method of analyzing systems. Since actual readings will vary with the
items that affect systems operation such as system components, application, load, outdoor
temperature, etc., the Table 3 readings should not be used as the basis for troubleshooting systems.
Check manufacturer's installation and service literature for this type of operational data.
6. Record actual temperature and pressure measurements in Table 3 on lines A through U. Compare
them to typical readings taken from manufacturer's literature. Use them to calculate superheat,
subcooling, compression ratio and capacity. Analyze this information to determine the system
problem.
7. Go to the "Quick System Analysis" chart on page 4 of the System Analyzer to verify the problem.
8. Use the System Analyzer to perform exercises 1 through 5 on the following pages; then complete
Quiz 2 on page 36
29
EXERCISE 2
SYMPTOMS:
- Compressor starts and runs for short periods then shuts down
- Discharge pressure rises to 320 psig at time of compressor shut down
- Suction pressure higher than nOllllal
- Amps increase with compressor run time to 15-20% above nameplate rating
- Superheat is low
- Subcooling is high
- System pressure at shutdown equalizes at 182 psig at 95°F ambient
31
TROUBLESHOOTING EXERCISES
(System Analyzer)
These exercises will help you apply the knowledge you've gained from this program. Use the Quick
System Analysis chart on page 4 of the System Analyzer to help you complete exercises I through 5.
EXERCISE 1
SYMPTOMS:
- Compressor starts and runs for short periods then shuts down
- Suction pressure drops to 35 psig during during short run periods
- Discharge pressure is 200 psig
- Low superheat, high subcooling
- Low amperage
- Low evaporator air
30
EXERCISE 3
SYMPTOMS:
- Evaporator air adequate
- Suction pressure: 78 psig
- Discharge pressure: 280 psig
- Superheat: 2-3°F
- Air entering evaporator: 85°F
- Air leaving evaporator: 75°F
- Subcooling: 0-2°F
- Amps: 5% above nameplate rating
- Water temperature rise across condenser: 18°F
- System pressure at shutdown equalizes at 168 psig at 90°F ambient
Hint: Use the "Quick System Analysis" chart to solve this problem.
32
-- - -.
EXERCISE 4
SYMPTOMS:
- Suction pressure: 76 psig
- Adequate evaporator air
- Discharge pressure: 275 psig
- Superheat: 3°F
- Air entering evaporator: 83 OF
- Air leaving evaporator: 73°F
- Subcooling: 4°F
- Amps: 5% above nameplate rating
System pressure equalizes at 179 psig at 90°F ambient
- Sightglass clear
Hint: Use the "Quick System Analysis" chart to solve this problem.
33
--
EXERCISE 5
SYMPTOMS:
- Evaporator air adequate
- Suction pressure: 55 psig
- Discharge pressure: 210 psi g
- Superheat: 30°F
- Air entering evaporator: 85°F
- Air leaving evaporator: 78°F
- Subcooling: 0 to 3°F
- Amps: 20% below nameplate rating
- Cloudy or flashing in sightglass
- System pressures equalize at 156 psig at 85°F ambient
Hint: Use the "Quick System Analysis" chart to solve this problem.
34
EXERCISE SOLUTIONS
(System Analyzer)
1. Most likely cause is "s" - incorrect evaporator fan motor specxl. However "C," restricted evaporator
air filters, will give the sallie conditions.
3. Most likely cause is "c" - Condenser water shortage. Probably due to either a partially plugged water
filter/strainer or defective water control valve. Check filter/strainer fIrst to be assured there is an
adequate supply of condensing water.
4. Most likely cause is "s" - Non-condensibles in the condenser will cause these conditions.
5. Most likely cause is "s" - Undercharge. Probably due to system leak. Determine source of leak and
repair before adding charge. Check for leaks at mechanical and exposed joints flfSt
35
QUIZ #2
ANALYZING SYSTEM AND COMPRESSOR PROBLEMS
1. (True or False?) If a system won't start, check the thelJllostat, power, and control components in
that order.
2. When the cooling load is reduced below its normal operating condition; the system will operate at
_ _ _ _ _ _ _(increased/decreased) capacity, pressures, temperatures, and compressor CWlent
draw.
3. Increasing fan speed by adjusting the sheave on the drive pulley is limited by:
a. rated amps of the drive motor. c. type of fan.
b. fan speed. d. number of fan blades.
4. (True or False?) Reduced refrigerant flow through the evaporator will cause the superheat to
•
mcrease.
5. The device that desuperheats, condenses and subcools the hot gas is the:
a. evaporator. c. condenser.
b. TXV. d. compressor.
7. Condenser fan rwming backwards will cause the discharge pressure and temperature to
_ _ _ _ _ _ (increase/decrease).
8. On a water-cooled system; a defective pump, dirty cooling tower, scale in the piping or defective
head pressure control will cause (Iow/high) subcooling.
9. (True or False?) The evaporator coil is 25 to 33% larger than the condenser coil because it must
pick up heat from the area being conditioned.
10. (True or False?) Non-condensible gas ends up in the top of the condenser.
11. A system pressure reading a few minutes after shutdown exceeding 5 psig of the figure obtained
from the refrigerant Temperature-Pressure Chart is an indication of:
a. defective TXV. c. non-condensibles in the system.
b. overcharge. d undercharge.
36
,
14. (True or False?) An overcharge will increase system pressures beyond the control of the TXV and
result in low superheat, floodback:. and high subcooJing.
15. (True or False?) The high and low sides of a refrigeration system are divided in the compressor
•
heads and in the metering device.
37
I
QUIZ KEY
QUIZ#!
Page No.
I. a 8 3
2. T 8 3
3. b 8 3
4.c 9 3
5.T 10 4
6.c 12 4
7.a 13 4
8.T 15 5
9.F 20 6
10. T 22 7
II. b 22 7
12. 2% 24 7
13. c 31 10
14. b 32 10
15. F 32 10
16. b 35 II
17. F 35 II
18. d 32 & 36 10 & II
19. b 37 12
20. c 41 13
21. b 42 13
QUIZ #2
I. T 47 17
2. decreased 51 19
3. a 53 19
4. T 55 20
5. c 60 21
•
6. Increase 60 21
•
7. Increase 61 21
8. low 62 21, 22
9. F 65 22
10. T 66 23
II. c 66 23
12. decreases 69 24
13. a 71 24
14. T 73 25
15. T 74 25
38
APPENDIX A
39
APPENDIX B
Typical Temperature-PrfAAure Comparison
for Common Refrigerants
40