Evacuation Process
* What is evacuation?
— Pulling a vacuum on a system
Why?
— To remove air and moisture
How long do you evacuate?
~ To 500 microns and/or
— Max. pipe run up to 1 hour
— Mid. Pipe run up to 30 mins.
— Back to&ack installation (10 Ft.) up to 20 mins.
* * soluth
onSingle Evacuation
1. Start Pump and open valves Gaug
on Gauge Manifold
2.Continue Vacuum =>
to 500 microns
3.Shut off pump valve
4. Turn off pump
5. Wait 5 min. to see
if proper vacuum
remains
6. System ready for
charging
srMultiple Evacuation
For systems with lots of moisture:
1. Pull a vacuum to 1000 microns
— Break vacuum with nitrogen
2. Pull a second vacuum to 1000 microns
— Break vacuum with nitrogen
3. Pull a third vacuum to 1000 microns
— If system holds vacuum start charging
[a
solut
52CCAC STANDARD !
EVACUATION AND DEHYDRATION PROCESS
» Use a vacuum pump of at least 1.4IL/s (3 CFM) displacement
capable of pulling below 0.18 in. Hg. absolute pressure to evacuate
and dehydrate the whole system. An electronic vacuum indicator
shall be used to measure or indicate vacuum to about 500 microns.
Be sure to follow vacuum pump operating instructions including
oil changing. This is called the DEEP VACUUM METHOD.
» Another method used is the TRIPLE EVACUATION or DILUTION
METHOD by diluting non-condensable gasses and moisture with
refrigerant or nitrogen. However, allow system to be pressurized
for 30 minutes to 1 hour for the vapor to mix and absorb the
moisture in between the three repeats of the procedure. DO NOT
use the air conditioning or refrigerator compressor as a substitute
to a vacuum pump.
s
$ ™ solulMultiple Evacuations
1. Start pump and
open valves on gauge. @ J (4)
2. Evacuate to 1000 microns. |}
Air and moisture are
pulled from system
i.
‘
oaMultiple Evacuations : Step 1
1. Close valve to pump,
open valve to nitrogen.
2. Break vacuum with
nitrogen to about 2 psig.
osMultiple Evacuations: Step 2
1. Close valves to nitrogen tank.
2. Run compressor 5 seconds.
3. Open valve to pump.
4. Pull 2"4 vacuum to 1000 microns.
=Multiple Evacuations: Step 3
Break vacuum again
with nitrogenMultiple Evacuations: Last Step
Pull 3rd vacuum to
1000 microns.
System is now ready
for charging.
_—Charging the System
» Assumptions for the following slide:
- System refrigerant capacity over 5 pounds
- System is clean and in a vacuum
- Compressor is off
° Step #1:
- Begin charging of liquid through high side
- Shut off discharge valve when pressures
equalize
ver
soluttCharging a large system in a vacuum
Note: System is OFF.
1. Open tank valve.
2. Purge charging hose.
3. Charge liquid through
high side.
4. When pressures
equalize, close off high
side manifold valve.
5. High side charge
is complete.
6. System now ready to start
compressor and finish
charging through low
aeCharging through Low Side
Assumptions for the following slide:
» System over 5 pound capacity
v Step 1 completed, pressures equalized
» OR, system under 5 pound capacity
v Compressor off, system in vacuum
Procedure:
1. Close high side valve on gauge manifold
2. Start compressor
3. Charge refrigerant through low side
All blended refrigerants must be charged by liquid
4. Charge to proper condensing temperatureCharging system through the low side.
Close off high side
1. Start compressor.
2. Open low side valve
and charge by liquid. ===> [}
3. Monitor compressor
amps while charging
liquid.
4. Monitor head pressure
until correct condenser
split is reached.
System now charged to
“present conditions” on a
EV system.
el 7.
manual for proper charging of
critically charged systems and
units with flooded condensers
a»Removing Gauges
* While the unit is running, return as much
refrigerant to the system as possible:
- Bleed the high pressure in the hoses
- To the low pressure side of the unit
EE
solutRemove Gauges Properly
1. Shut off tank valve. while aca oles
2. Back seat discharge service
valve. ‘ D
3. Open high & low side manifold
valves.
4. Purge high side vapor
in the gauge hoses into
the suction service valve.
5. Back seat suction
service valve.
Now, you are ready to
remove your gauges.
ea