DC Isolating Transmitter Kusam Meco
DC Isolating Transmitter Kusam Meco
Ü FEATURES
n Aux. Power AC 85 ~ 265V or DC 85 ~ 300V
INPUT
n High Accuracy 0.1% RO at 23oC ± 5oC I/P DC
4-20M TWD- 2
IN
- 1
+ 1 PUT TWS
2 1
7 + UT1
O
n 8
A
+4
OUT1
+1 P
TV- 2
TWF- 2 min
4
Ü MODEL:TWD EX T
4 12
SINGLE OUTPUT V
Ü SPECIFICATION
Accuracy : 0.1 % RO at 23o C ± 5oC
Input Impedance : Voltage Input ³ 1M W, Current Input £ 50W
Insulation Resistance : ³100MW / DC 500V
Output Load : DC Current Mode : >750W in Output 20mA, DC Voltage Mode : 10mA
Maximum
Dielectric Strength : AC 1500V / Min, between Input / Output / Power.
Input Protection : ³ 2V DC £ 300V rms Continuous ; £ 2V DC £150V rms Continuous;
£ 20mA DC £150mA Continuous
Linearity & Repeatability : £ 0.1% Typical.
Common Mode Rejection : ³120db DC to 60Hz
Stability : £ 0.2% / Year.
Response Time : £ 400 mS
Ripple : £ 0.1% rms RO
Temperature Coefficient : £100ppm / oC From 0~60oC ; 50ppm / 25oC ± 5oC
Operation Condition : -5oC ~+55oC, 20~95% RH Non-Condensed.
Storage Condition : -10oC~+70oC, 20~95% RH Non-Condensed.
Power Fluctuation Rate : Power can support AC/DC 85~265V or DC 24V ± 10%
Aux. Power Effect : £ 0.03% / V
Housing Material : Non-Combustible PC Products, Compliance With UL 94 CLASS V-O
Mounting : DIN Rail or Wall Mounting
Dimension : 27 (W) X 119( H) X 70 (L) mm (Base)
10 +
POWER
11 -
1
DC to DC signal convertor isolator isolated output dc-dc transmitter Kusam Meco Kusum Meco Transmitter Kusam-Meco Kusum-Meco Transmitter
DC ISOLATING TRANSMITTER
Ü EXTERNAL DIMENSIONS : mm (inch)
6
3 2 1
+ 1 7 +
DIN RAIL 5
35mm wide 6 4
INPUT OUT1
2-4.2*5 6 72 - 2 8 -
MTG HOLE
59
70 4 3 +
OUT2
6 -
35.4 11-M3
SCREW
9 8 7 10 +
8 POWER
11 10
11 -
89 22
27
119 29.5
Ü TERMINAL CONNECTIONS
Connect the unit as in the diagram on the right side or refer to the connection diagram label on the side of the unit.
Ü CHECKING
l Terminal wiring : Check that all cables are correctly connected according to the connection diagram.
l Power input voltage : Check voltage of the terminal 10 ' 11
l Input : Check that the input signal is within 0-100%.
l Output : Check that the load resistance meets the described specifications.
Ü ADJUSTMENT PROCEDURE
l This unit is calibrated at the factory to meet the ordered specifications, therefore you usually do
not need any calibration.
l For matching the signal to a receiving instrument or in case of regular calibration, adjust the output
as explained in the following.
v HOW TO CALIBRATE THE OUTPUT SIGNAL :
1) ZERO : Apply 0% input and adjust output to 0%.
2) SPAN : Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above procedure 1) ~ 3).
Ü MAINTENANCE
l Regular calibration procedure is explained below :
Warm up the unit for at least 10 minutes. Apply 0%, 25%, 50%, 75% and 100% input signal. Check the output
signal for the respective input signal remains within accuracy described in the data sheet. When the output is out
of tolerance, recalibrate the unit according to the "ADJUSTMENT PROCEDURE" explained earlier.
PS. It need cut a road on black dots when electric current input 0 ~ 1mA SWITCH mA
2