Professional Documents
Culture Documents
Temp - Incoming Power Calculations Rev
Temp - Incoming Power Calculations Rev
FM Top Motor
220 250 280
Motor Data
Motor Power (kw) 5500.00
Armature Voltage 1200.00
Armature current (I dc) 5100.00 11220 12750 14280
Resultant current @100%continuous,280% for
3 secs every 3600secs 5103.82 Case 1
Resultant current @100%continuous,250% for
60 secs every 180secs 6246.20 Case 2
Resultant current @100%continuous,220% for
90 secs every 120secs 7029.86 Case 3
Supply Data
Incoming Voltage 11000.00
Secondary Voltage (Vac) 1300.00
Frequency (Hz) 50.00
KVA =Sqrt(3)*Vac*0.816*Idc 13563.02 9370.53 (Base Kva)
Check
Available DC voltage at full load 1386.45 >=1200
Prep : DKV/ATPA-ME
Proj :Welspun Stand Drive Lang :E
Appr : DKV/ATPA-ME
Resp. dept. : ATPA-ME Rev. ind.: -
Doc.kind :Design Calc
Date: 2005/07/04 Sheet: 1
Title :Main Stand Trafo
No. of sh.: 4
Motor Data
Transformer Data
Overloads
1 Motor Data
1.1 Motor Power 5500 Kw
Resultant Current Combining case1 280% for 3 secs and 100% Assuming First Pass
5459.62 with INGOT
continous for 114 Secs in a cycle of 120 secs
Resultant Current Combining case2 250% for 60 secs and 100% 9710.11
continous for 60 Secs in a cycle of 120 secs
Resultant Current Combining case3 220% for 90 secs and 100% 10045.83
continous for 30 Secs in a cycle of 120 secs Amps
Resultant Current Combining case2 250% for 80 secs, 220% for Refering Sample loading
60 Secs and 100% continous for 40 Secs in a cycle of 180 secs 10687.04
sheet
Drive Data
Rating Amps
Type
Incoming Voltage 1190 Volts
Field Type