Conductor Tension Terminal Load of Point A, Please Rework The Design Conductor Tension Terminal Load of Point B, Please Rework The Design
Conductor Tension Terminal Load of Point A, Please Rework The Design Conductor Tension Terminal Load of Point B, Please Rework The Design
INPUT DATA
No. of Conductor/Span 4
OUTPUT DATA
OBSERVATION
CONDUCTOR TENSION > TERMINAL LOAD OF POINT A, CONDUCTOR TENSION > TERMINAL LOAD OF POINT B,
PLEASE REWORK THE DESIGN PLEASE REWORK THE DESIGN
CONCLUSION
INPUT DATA
No. of Conductor/Span 2
Weight of Conductor/Length, w 1.145 kg/m
Span Length, S 7.06 m
Conductor Sagging at Mid Span, D 0.401 m
Vertical Distance Between Support, h 0.938 m
Terminal Load of Point A (Left Support) 1 kg
Terminal Load of Point B (Right Support) 1 kg
OUTPUT DATA
Dist. - The Left Support Point To The Low Point In The Catenary, XL 5.59 m
Dist. - The Right Support Point To The Low Point In The Catenary, XR 1.47 m
Horizontal Components of Tension, H 35.58 kg
Actual Conductor Length, L 7.18 m
Sag in Right Sub-Span Section, DR 0.07 m
Sag in Left Sub-Span Section, DL 1.01 m
Tension in Right Sub-Span Section, TR 35.74 kg
Tension in Left Sub-Span Section, TL 37.89 kg
OBSERVATION
CONDUCTOR TENSION > TERMINAL LOAD OF POINT A, CONDUCTOR TENSION > TERMINAL LOAD OF POINT B,
PLEASE REWORK THE DESIGN PLEASE REWORK THE DESIGN
CONCLUSION
INPUT DATA
No. of Conductor/Span 4
OUTPUT DATA
OBSERVATION
CONDUCTOR TENSION > TERMINAL LOAD OF POINT A, CONDUCTOR TENSION > TERMINAL LOAD OF POINT B,
PLEASE REWORK THE DESIGN PLEASE REWORK THE DESIGN
CONCLUSION
INPUT DATA
No. of Conductor/Span 2
Weight of Conductor/Length, w 1.145 kg/m
Span Length, S 2.276 m
Horizontal Components of Tension, H 9.89 kg
Vertical Distance Between Support, h 0.473 m
Terminal Load of Point A (Left Support) 12 kg
Terminal Load of Point B (Right Support) 12 kg
OUTPUT DATA
Dist. - The Left Support Point To The Low Point In The Catenary, XL 2.04 m
Dist. - The Right Support Point To The Low Point In The Catenary, XR 0.24 m
Conductor Sagging at Mid Span, D 0.15 m
Actual Conductor Length, L 2.35 m
Sag in Right Sub-Span Section, DR 0.01 m
Sag in Left Sub-Span Section, DL 0.48 m
Tension in Right Sub-Span Section, TR 9.91 kg
Tension in Left Sub-Span Section, TL 10.99 kg
OBSERVATION
CONDUCTOR TENSION < TERMINAL LOAD OF POINT A CONDUCTOR TENSION < TERMINAL LOAD OF POINT B
CONCLUSION
DESIGN SUFFICIENT