ETHANOL (6.0D X 8.825 H), Rev. 0
ETHANOL (6.0D X 8.825 H), Rev. 0
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR
CONSULTANTS
ETHANOL TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
REV 0
P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
PAGE 1 OF 26
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
TABLE OF CONTENT
1 Table of Content 2
2 Reference documents 3
3 Design data 4
4 Shell Thickness calculation 5-6
5 Bottom Plate & Annular Plate calculation 7
6 Roof Thickness calculation 8
7 Compression area calculation 9
8 Internal Pressure design 10
9 Intermediate Wind Girder calculation 11
10 Weight calculation for uncorded condition 12
11 Weight calculation for corroded condition 13
12 Wind Analysis ,14-15
13 Seismic Analysis 16-19
14 Free-board calculation 20
15 Dynamic Liquid Hoop Forces 21
16 Tank Anchorage 22-23
17 Design of Anchor Chair 24-25
18 Foundation Loadings 26
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 2 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
REFERENCE DOCUMENTS
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 3 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Design Data
Design Code = API - 650, 12th Edn, March 2013, Addendum 2, January 2016.
Shell Desigh = Annexe A,Sec A.4 of API 650
Applicable Appendix = A,B,E & F
Design internal Pressure FOL Pi = 5.727 kPa 584.00 mmWC
Vacuum Pressure (External) Pe = 0.637 kPa 65.00 mmWC
Design Temperature T = 65 °C
Operating Temperature T = 5 °C
Service = Ethanol
Product Specific Gravity G = 0.7900 min. 0.7900 max.
Design Specific Gravity G = 1.0000 Density 1000.0 kg/m³
Hydro test Specific Gravity = 1.00
Insulation Thickness = 0 mm
Flash point > 120 °C
Tank Filling / Emptying Rate = 70/70 kl/hr (Assumed)
Corrosion Allowance
Shell Plate CA = 1.50 mm
Annular Ring/Bottom/Bottom Sump CA = 1.50 mm
Roof CA = 1.00 mm
Roof Structural CA = 0.00 mm
Anchor Bolts CA = 1.50 mm (On diameter)
Seismic Design Code = IS 1893 Part 1 (2016) & 4 (2015) and API 650, Annex E
Seismic Zone = III
Seismic Zone factor IS-1893 (part 4), Annex A Z = 0.16
Seismic category IS 1893 (part 4), Sec 8.1 & Table 6 = 2
Site Class = D
Importance factor IS-1893 (part 4), Table- 3 I = 1.50
Dimensions
Tank Inside Diameter (Uncorded) Di = 6.00 m Radius = 3000 mm
Shell Height Ht = 8.825 m
Design Liquid Height HdL = 8.825 m
Type of Roof = Supported cone roof
Slope of cone Roof (As per BPCL standard) = 1 : 10 5.7106 °
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 4 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Shell Thickness Calculation
As per Annex F.2.1, Design pressure is greater than 1 kPa, hence Hd shall be incresed by P/(9.8G).
Design Liquid Level Hd = HdL + P / (9.8 G)
= 9.409 m
Allowable Stress for Hydrostatic Condition St = Min (3/4 Ys, 3/7 Ts) (Sec 5.6.2.2)
= 175.71 MPa (Table 5-2a)
Allowable stresses as per A.4.1 = 145.00 Mpa= N/mm2
Design Shell Thickness 4.9 x D x (H-0.3) x G As per API 650, (Sec A.4.1)
td = + CA
E x Sd
Hydrostatic Test Shell Thickness 4.9 x D x (H-0.3) x 1.0 (Sec 5.6.3.3) of API 650
tt =
St
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 5 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Shell Thickness by 1 Foot point Method
Course No. M.O.C. Course Design Hydro test Reqd thk Provided Remark Weight of Shell
Width > of Thk **
Height Reqd Thick. Height Reqd Thick. (td, tt, tmin)
Hd td Ht tt tr tp Uncorded Corroded
m m mm m mm mm mm kg kg
1 Bottom IS 2062 E 250 Gr BR 2.000 9.41 3.673 8.825 1.426 5.000 8.00 tp>tr, OK 2370.66 1926.16
2 IS 2062 E 250 Gr BR 2.000 7.41 3.196 6.825 1.092 5.000 8.00 tp>tr, OK 2370.66 1926.16
3 IS 2062 E 250 Gr BR 2.000 5.41 2.719 4.825 0.757 5.000 8.00 tp>tr, OK 2370.66 1926.16
4 IS 2062 E 250 Gr BR 2.000 3.41 2.242 2.825 0.422 5.000 8.00 tp>tr, OK 2370.66 1926.16
5 IS 2062 E 250 Gr BR 0.825 1.41 1.765 0.825 0.088 5.000 8.00 tp>tr, OK 977.90 794.54
Total Hs 8.825 OK Total weight 10461.00 8499.00
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 6 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Bottom Plate Thickness Calculation
Sec 5.4
Minimum bottom plate thickness (excluding CA) tbmin = 6.00 mm + CA (Sec 5.4.1)
Corrosion allowance CA = 1.50 mm
Required bottom plate thickness tbmin + CA = 7.50 mm
Provided Bottom Plate Thickness tb = 8.00 mm OK
Minimum Projection outside shell shall be ≥ 50 mm B = 75.00 mm (Sec 5.4.2)
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 7 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Fixed Roof Plate Thickness Calculation
Sec 5.10
Corroded Weight of Roof Plate W r1' = 1245 kg 5% extra for Lap joint
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 8 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL) CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Compression area calculation
Fig. F-2, Detail b
Total Participating area available resisting the compressive force Aav = Area of Roof + Area of Shell + Area of Angle
= (Wh x th + Wc x tc + Ac)
= 1926.59 mm²
Required Cross sectional area of roof to shell junction (Sec 5.10.2.6 a) Ar = DLs / 2 π Fy tanθ
847.88 mm²
Since, participating area is greater than required area, The provided size of curb Angle is adequate. Compression Ring is not required.
The joint is non-frangible
Provide Emergency vent with flame arrestor with silica gel as per API-2000.
Does Tank have Internal Pressure Yes
Hence, Annex F is applicable
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 9 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL) CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Internal Pressure design
Annex F
Corroded Weight of roof plate & attached Structural = W r1' + W r2' + W r3' + Wr5'
= 19341 N
Internal pressure exceeds weight of roof plate, follow Sec F.1.2
Corroded Weight of Shell, Roof & attached structural = W s' + W r'
= 131520 N
Internal pressure exceeds combined weight of shell, roof and any strucural member attached to roof and any framimg supported by shell,
Design requirements in F.2 through F.8 shall met
F.3
Details of the roof to shell junction shall be in accordance with Fig.F.2.
Detail b roof to shell junction considered in accordance with Fig.F.2.
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 10 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Intermediate Wind Girders Calculation
Sec 5.9.7
Tank Nominal diameter D = 6.008 m
Thinnest Shell course thickness corroded t = 6.50 mm
Design Wind Speed (3 Sec gust) From wind calculation V = 277.77 Km/hr
Corroded Shell
Course Width, Wtr,
Course number thickness,
W (mm) (m)
tactual (mm)
1 Bottom 2.000 6.500 2.000
2 2.000 6.500 2.000
3 2.000 6.500 2.000
4 2.000 6.500 2.000
5 0.825 6.500 0.825
Sum of the transposed width of the courses Ht = Height of Transformed Shell Ht (Sec 5.9.7.2 b)
= 8.825 m
Since height of transformed shell Ht < the maximum height H1, an Intermediate Wind Girder is not required. (Sec 5.9.7.3)
PAGE 11 OF 26
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Weight Calculation for Uncorroded Condition
Shell Weight
Uncorded weight of tank shell W s1 = 10461 kg 102587 N
Weight of shell nozzles W s2 = 400 kg 3923 N (approximate)
Weight of Curb Angle W s3 = 111.0 kg 1089 N
Weight of Top wind girder W s4 = 0.0 kg 0 N
Weight of Intermediate wind girder W s5 = 0 kg 0 N No Int.wind girder
Weight of external stiffeners W s6 = 0 kg 0 N No external stiffeners
Weight of Staircase, intermediate platform ,handrails W s7 = 1809 kg 17741 N
Weight of Still wells attached to shell W s8 = 200 kg 1961 N
Weight of Fire water system supports W s9 = 0 kg 0 N (approximate)
Weight of Foam system support W s10 = 0 kg 0 N (approximate)
Weight of Floating Suction W s11 = 0 kg 0 N
Bottom Plate
Thickness of Bottom Plate = 8.0 mm
OD of Bottom Plate = 6166 mm
Weight of Bottom Plate W b1 = 2063 kg 20229 N (7% Extra for Lap Weld)
Annular Plate
Thickness of Annular Plate = 0.0 mm
Width of Annular Plate = 0.0 mm actual width shall be as per plate sizes.
OD of Annular Plate = 0.0 mm
Weight of Annular Plate W b2 = 0.0 kg 0 N
Note:- 1 Weights are rounded off on higher side for conservative design.
Respective fabrication drawings should be refered for exact wt.
2 Minor diff. in exact wt. & its tentative wt.will not creat any diff.
in calculated value.
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 12 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Weight Calculation for Corroded Condition
Shell Weight
Corroded weight of tank shell W s1' = 8499 kg 83347 N
Corr. Weight of shell nozzles W s2' = 340 kg 3334 N See Foot Note1
Corroded weight of Curb Angle W s3' = 111 kg 1089 N
Weight of top wind girder W s4' = 0.00 kg 0 N
Weight of Intermediate wind girder W s5' = 0 kg 0 N No Int.wind girder
Weight of external stiffeners W s6' = 0.00 kg 0 N No external stiffeners
Weight of Staircase, intermediate platform ,handrails W s7' = 1809 kg 17741 N
Weight of Still wells attached to shell W s8' = 170 kg 1667 N See Foot Note1
Weight of Fire water system support W s9' = 0 kg 0 N
Weight of Foam system support W s10' = 0 kg 0 N
Weight of Floating Suction W s11' = 0.00 kg 0 N
Bottom Plate
Corroded Thickness of Bottom Plate = 6.5 mm
OD of Bottom Plate = 6166 mm
Corroded Weight of Bottom Plate W b1' = 1676 kg 16436 N (7 % Extra for Lap Weld)
Annular Plate
Corroded Thickness of Annular Plate = 0.00 mm
Width of Annular Plate = 0.00 mm
OD of Annular Plate = 0.00 mm
Corroded Weight of Annular Plate W b2' = 0.00 kg 0.00 N
Total Corroded weight of Tank shell + attach. W s' = Sum ( W s1' : W s11' )
= 10929 kg 107178 N
Total Corroded weight of Roof + Roof structure W r' = Sum ( W r1' : W r5')
= 2482 kg 24342 N
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 13 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Stability of Tanks against Wind Load IS 875 (Part 3) 2015 / API 650
Design Wind pressure for vertical surfaces Cl. 5.2.1.k = 1838 N/m² 0.86 (V/190)² kPa
Design Wind Pressure on Conical Surfaces Cl. 5.2.1.k Pwr = 3078 N/m² 1.44 (V/190)² kPa
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 14 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Check for Overturning Stability of Tank Due to Wind Cl.5.11.2
Nominal weight of Shell and attached structure corroded W DL = 89437 N
Nominal weight supported by roof & attachments corroded DLR = 19341 N
Specific gravity for consideration of liquid weight (lesser of actual specific gravity or 0.7) GL = 0.70 m
Height for consideration of liquid weight (one-half of design liquid height) HL = 4.41 m
Minimum specified Yield Stress of the bottom plate under the shell Fby = 250.00 Mpa
Unanchored tanks with supported cone roofs must satisfy the following criteria as per (Cl.5.11.2.2)
1) Mws + Fp (Mpi) < (MDL / 1.5) + MDLR
MDL /1.5 + MDLR = 352931
0.6 Mw + Mpi = 1203983
Mws + Fp Mpi Fp = 0.4 (per Cl.5.2.2) = 1128423
(MDL + MF) /2 + MDLR = 361074
Mw + Fp Mpi Fp = 0.4 (per Cl.5.2.2) = 1391582
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 15 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Seismic Design of Tank
IS 1893 Part 1 (2016) & 4 (2015) and API 650, Annex E
Zone Factor/Peak ground acceleration Z = 0.160
Soil type = Medium Soil
Importance factor I = 1.500
Seismic user group SUG = II (E.3.1)
Anchorage System = Mechanically Anchored
Average respose acceleration coefficient IS 1893-4, Fig-1 Sa/g = 2.269 for 5%damping, for Ti
Impulsive design response spectrum acceleration coefficient, Ai
IS 1893-4, Cl.7.3.2 Ai = (Z I / 2 Rwi) x (Sa/g)
Force reduction Factor for the impulsive mode Mechanically Anchored IS:1893 ,PART 2,Table 3 R = 3.000
Ai = 0.091
≥ 0.007, OK
Natural period of the convective (sloshing) mode of behaviour of the liquid Eqn E.4.5.2-a Tc = 1.8 Ks D0.5
Sloshing Period Coefficient Eqn E.4.5.2-c Ks = 0.578/(tanh (3.68H/D))0.5
Ks = 0.578
Tc = 2.550 sec
Regional Period of transition for longer mode Cl.E.4.6.1 TL = 4.000 sec Tc ≤ TL
Average respose acceleration coefficient IS 1893-4, Fig-1 Sa/g = 0.533 for min of (TL,Tc)
Multiplying factor for other damping IS 1893-2, cl. 4.5.2 Kd = 1.75 from 5% to 0.5%
IS 1893-4, Cl.7.3.2 Ac = (Z I / 2 R) x (Kd Sa/g)
Force reduction Factor for the convective mode IS:1893 ,PART 2 R = 3.000
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 16 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Design Loads
Total weight of tank shell and appurtenances Ws = 133666 N (with +5% Margin)
Total weight of fixed tank roof & roof supp. Structures Wr = 29514 N (with +5% Margin)
Weight of the Tank bottom Wf = 21240 N (with +5% Margin)
Weight of tank contents based on specific weight of product (upto Design liquid level with design G) Wp = 2446965 N
Hence, Wi = 2083804 N
Effective Convective (sloshing) portion of the liquid weight, W c = 0.23 D/H tanh(3.67 H/D) Wp (E.6.1.1-3)
= 383136 N
When D/H ≥ 1.333 Equation 5 Xi = 0.375 H (E.6.1.2-1) Xis = 0.375 [1 + 1.333{(0.866 (D/H) / tanh (0.866 D/H)) - 1}] H
When D/H < 1.333 Equation 6 Xi = [0.5 - 0.094 D/H] H (E.6.1.2-2) Xis = [0.5 + 0.06 D/H] H (E.6.1.2.2-2)
D/H = 0.68 < 1.333
Hence Xi = 3.848 m Xis = 4.773 m
Height from the bottom of the tank shell to the center of action of lateral seismic force related to the convective liquid force
for ringwall moment for slab moment
(cosh ((3.67H/D) -1 (E.6.1.2.1-3) cosh (3.67H/D) -1.937 (E.6.1.2.2-3)
Xc = 1- H Xcs = 1- H
3.67H/D sinh (3.67H/D) 3.67H/D sinh (3.67H/D)
= 7.203 m = 7.217 m
Height from the bottom of the tank shell to the roof & roof Xr = Shell Height + 1/3 cone roof Height
appurtenances center of gravity = 8.925 m
Height from the bottom of the tank shell to the shell's Xs = Shell Height / 2
center of gravity = 4.413 m
0.5
Ringwall Overturning Moment (E.6.1.5-1) Mrw = {[Ai (W i Xi + W s Xs + Wr Xr)]² + [Ac (W c Xc)]²}
= 811647 N.m
Slab Overturning Moment (Eqn.L-3) Ms = {[Ai (W i Xis + W s Xs + W r Xr + W ns Xs..
.. + Wnr Xr)]² + [Ac (Wc Xcs)]²}0.5
= 985475 N.m
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 17 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Resistance To Design Loads
Self Anchored
Force resisting uplift in annular region (E.6.2.1.1-1a) wa = 99 ta ( Fy H Ge)0.5 ≤ 201.1 H D Ge
Calculated design uplift load due to product pressure per unit wint = [Pi (π Di² /4)] / π D
circumferential length 8590.68 N/m
Therefore, J = 1.521
(Table E.6)
0.785 < J ≤ 1.54, Tank is uplifting, but shell is stable for the design load providing the shell compression requirements are satisfied.
Anchor Bolts are provided due to wind.
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 18 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
The allowable Shell compression 'Fc' > Maximum Shell Compression 'σc', Hence Safe
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 19 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Freeboard
Height of the sloshing wave above the product design height δs = 0.42 D Af (E.7.2-1)
For SUG I and II,
When, Tc ≤ 4 Equation 11 Af = K SD1 I (1 / Tc ) (E.7.2-2)
When, Tc > 4 Equation 12 Af = K SD1 I (4 / Tc² ) (E.7.2-3)
For SUG III,
When, Tc ≤ TL Equation 13 Af = K SD1 I (1 / Tc ) (E.7.2-4)
Tc > TL Equation 14 Af = K SD1 I (TL / Tc² ) (E.7.2-5)
Convective design response spectrum acceleration coefficient, Ac K SD1 I (TL / Tc² ) Ac = 0.037 (E.4.6.1-5)
Design, 5% damped, spectral response accel. parameter at short periods (Back calculated from Ac) SD1 = Ac / K I (TL / Tc² )
= 0.027
For SUG =II & SDS ≤ 0.33g, a Freeboard of 0.7δs is recommended for economic considerations (Table E.7)
Therefore, Freeboard δ = 0.7δs
= 0.042 m
Sliding Resistance, Vs
Vs = μ (W s+ W r+ W f+ W p) (1 - 0.4Av) (E.7.6-1)
μ = 0.4
Therefore, Vs = 1027082 N
Allowable Shear Stress > actual Shear Stress in the weld Sw, Hence Safe.
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 20 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Dynamic Liquid Hoop Forces
When, D/H ≥ 1.333 Equation 15 Ni = 8.48 Ai GDH [ (Y/H) - 0.5 (Y/H)² ] tanh (0.866 D/H) (E.6.1.4-1a)
When, D/H < 1.333 & Y < 0.75D Equation 16 Ni = 5.22 Ai GD² [ (Y / 0.75D) - 0.5 (Y/ 0.75D)² ] (E.6.1.4-2a)
When, D/H < 1.333 & Y ≥ 0.75D Equation 17 Ni = 2.6 Ai GD² (E.6.1.4-3a)
Convective hoop membrane force in tank shell Nc , Nc = 1.85 Ac GD² Cosh[3.68(H-Y)/D] / Cosh(3.68H / D) (E.6.1.4-4a)
Product Hydrostatic Membrane Force Nh , Nh = 4.9 (Y-0.3) D G
Total Combined Hoop Stress, σT = Nh ± SQRT (Ni² + Nc² + (Av Nh / 2.5)² / t (E.6.1.4-6)
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 21 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL) CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Tank Anchorage
Material For Anchor Bolts IS 1367 /IS:2062 Gr.A IS 1367 /IS:2062 Gr.A
Minimum Yield Strength of Anchor Bolts Fy = 250.00 MPa or 380 Mpa, whichever is less
Therefore, Fy = 250.00 MPa (Table 5.21a-Fy)
Corroded wt of roof plate plus W 1 = Corroded Roof plate Weight + Corroded Shell Weight & its attachement
corroded wt of shell and any other corroded = W r1' + W s1' + W r2' + W s2' +W s3' W s5' + W s6' + W s7' + W s8' + W s9' + W s10' + W r4'
permanent attachments acting on shell = 124391.9 N
Corroded weight of the shell and W 2 = Corroded Shell Weight & its attachement + Wt of Compression ring
any corroded permanent attachments acting on the shell = Ws1' + Wr2' + Ws2' +Ws3' Ws5' + Ws6' + Ws7' + Ws8' + Ws9' + Ws10' + Wr4'
including the portion of the roof plates and framing acting on the shell = 112179.5 N
Nominal weight of the roof plates plus W 3 = UnCorroded Roof plate Weight + UnCorroded Shell Weight & its attachement
the nominal weight of the shell and = W r1 + W s1 + W r2 + W s2 + W s3 + W s5 + W s6 + W s7 + W s8 + W s9 + W s10 + W r4
any other permanent attachments acting on the shell = 147840.2 N
Allowable Stress
Net Uplift Formula, U Uplift load
Uplift Load case Shell Anchor
N N Mpa Mpa
Design Pressure [(Pi x D² x 785] - W 1 37892 2 /3 Fty 167 5 /12 Fy 104
Test Pressure [(Pt x D² x 785] - W 3 14443 5 /6 Fty 208 5 / 9 Fy 139
Wind Load Pwr x D² x 785 + [4 x Mws/D]-W 2 772204 5 /6 Fty 208 0.8 Fy 200
Seismic Load [4 x Ms /D] -W 2 (1 - 0.4Av) 430913 5 /6 Fty 208 0.8 Fy 200
Design Pressure + Wind [Fp (Pi + Pwr) x D² x 785]+[4Mws/D] - W 1 772579 5 /6 Fty 208 5 / 9 Fy 139
Design Pressure + Seismic [Fp (Pi x D² x 785]+[4Ms/D] - W 1(1 - 0.4Av) 483910 5 /6 Fty 208 0.8 Fy 200
Frangibility Pressure [(3 x Pf x D² x 785] - W 3
Frangibility Pressure is not applicable for non frangible joint hence not considered.
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 22 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL) CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Design of anchor Bolts & Chairs
The Tank Anchor Shall be size to provide atleast following Minimum Anchorage Resistance. (As per Cl.E.6.2.1.2 of API 650)
Design uplift load on anchors per unit circumferential length W AB = (1.273 x Mrw / D^2) - wt(1-0.4Av) (As per E.6.2.1.2-1)
= 20804.23 N/m
The Anchor Seismic Design Load per Bolt PAB = W AB x (π x D) / N where, N is the provided number of Anchor bolts.
= 49084.18 N
Allowable Anchor
Uplift load U Induced Stress Sb Design Check
Uplift Load case Bolt Stress
N Mpa MPa
Design Pressure 37892 104.17 6.76 Adequate
Test Pressure 14443 138.89 2.58 Adequate
Wind Load 772204 200.00 137.74 Adequate
Seismic Load 430913 200.00 76.87 Adequate
Design Pressure + Wind 772579 138.89 137.81 Adequate
Design Pressure + Seismic 483910 200.00 86.32 Adequate
Frangibility Pressure -- -- -- --
Frangibility Pressure is not applicable for non frangible joint hence not considered.
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 23 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL) CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Design of Anchor Chair - As per AISI T-192 Vol II Part V B
j
Q = 75.0 mm = 2.953 inches
a = 190.0 mm = 7.480 inches
b = 189.0 mm = 7.441 inches
c = 18.0 mm = 0.709 inches a g
Hole dia.d = 42.0 mm = 1.654 inches
e = 98.0 mm = 3.858 inches
BCD = 6220.0 mm = 244.882 inches j
= 3004.0 = 118.268 f
radius,R mm inches
b
e min = 51.7 mm = 2.037 inches
f=B-d/2 = 70.0 mm = 2.756 inches
radius
f min = 24.2 mm = 0.952 inches
c
B = 91.0 mm = 3.583 inches k
g = 105.0 mm = 4.134 inches ts
A = 300.0 mm = 11.811 inches tp A
j = 12.0 mm = 0.472 inches e
k = 132.0 mm = 5.197 inches m
m = 6.5 mm = 0.256 inches Shell thk + Pad thk Q
ts = 6.5 mm = 0.256 inches pcd
tp = 8.0 mm = 0.315 inches
t = (ts + tp) = 14.5 mm = 0.571 inches
Bending plus direct stress in top plate S = ( P e/ t^2 ) x [ ( 1.32Z / {(1.43aA^2/Rt +(4 a A^2)^0.333} + (0.031 / ( R t )^0.5)]
Where,
Reduction Factor Z = 1.0 / [ [ { ( 0.177x a x m ) / ( R x t )^0.5 } x ( m^2 / t^2 ) ] + 1 ]
= 0.992
P x e / t^2 = 391.78
1.32 x Z = 1.309
1.43 x a x A^2 / (R x t) = 22.102
( 4 x a x A^2 )^0.333 = 16.056
Bending plus direct stress in top plate S = 14.920 Ksi
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 24 OF 26
No reproduction in full or in part of this document shall be made for any use other than for the purpose of the Contract without the written consent of Owner
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL) CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
VERTICAL PLATE :
Min thk = 12.00 mm
0.04 ( A - c) = 0.444 inch
= 11.280 mm
Hence, provided thickness of vertical plate is OK.
jk => P / 25
jk = 2.46
P / 25 = 1.32
PAGE 25 OF 26
CONSTRUCTION OF TANKS AT PARADEEP COASTAL
GABATIA
INSTALLATION OF BHARAT PETROLEUM CORPORATION LTD.
ENGINEERS &
DOCUMENT TITLE: MECHANICAL DESIGN CALCULATION (STATIC) FOR ETHANOL
TANKS (6.00 M DIA x 8.825 M HT)CONE ROOF (200 KL)
CONSULTANTS
REV 0 P.O.
CONTRACTOR DOC. NO: BPCL/GEC/ETHA/CAL/PARA-01 NO.4507657541/06.02.2020
Rev
Foundation Loadings
The self weight of roof and live load will be transferred to tank shell
Live Load transferred to Foundation
Live Roof Load Lr = 1.00 kPa
Area of Roof Ar = 28.84 m²
Total Live Load WL = 28.84 kN
Circumference of Tank C = 18.87 m
Live Load transferred to Foundation LL = WL / C
= 1.528 kN/m
This document and the information contained herein are the sole property of Owner and shall be treated as confidential.
PAGE 26 OF 26