PROJECT PROJECT : 40 MGD WTP AT MAHESHTALA

THE SUPERINTENDING ENGINEER, MECHANICAL CIRCLE-I, E&M


END USER SECTOR, K.M.D.A.

DOC TITLE TRANSFORMER SIZING CALCULATION

DOC NUMBER TR. CAL / PCEP / TEPL / LT PDB /


2021-22 / 145

PCE PROJECTS PVT. LTD.


MANUFACTURER : Address : 51, Chanditala Main Road,
Kolktata - 53

MAIN CONTRACTOR M/s. TRADERS & ENGINEERS PVT. LTD.


SHEET 3 OF 3
Transformer Detail:

Transformer Size 1250.00 KVA


Transformer Secondary Voltage:(v2) 433 Volt
% Impedance: (z) 5%
Allowable Voltage Drop in System: 10%

Load Details :

Total KW 639.58 KW
Total Full Load Current 1318.24 Amp
Motor Volt: (L-L) 415 Volt
Efficiency 0.96
Power Factor: 0.8
Locaked Rotor Current: (Max) 600%

Total Full Load Current when all other loads are running except 90KW 1169.8 Amp

Motor InRush KVA At Starting when 1 no. 90KW Motor is started + Running KVA 1107.53 KVA

Calculations:
Full Load Current of Transformer : (IL) 1667 Amp
Short Circuit Current at Transformer Secondary: (Isc) 33335 Amp
Max KVA of Transformer at Isc 25000.00 KVA
Motor InRush KVA on Starting 1 no. 90KW Motor when all other loads are running 1107.53 KVA
Voltage Drop at Transformer Secondary Due to Motor inRush 4.4%
Transformer Secondary Voltage 414 Volt

Result:
(1) Motor Full Load Current <= 65% Transformer Full Load Current No
(2) Voltage Drop at Transformer Secondary Due to Motor inRush Within limit
(3) Transformer Size: 1250 KVA