Professional Documents
Culture Documents
Lighting Layout Power Layout: General Notes
Lighting Layout Power Layout: General Notes
Lighting Layout Power Layout: General Notes
CKT. LOAD NO. SIZE of A. GENERAL LIGHTING AND CONVENIENCE RECEPTACLE LOAD 1. SERVICE POWER SUPPLY SHALL BE 230 VOLTS, 1-PHASE, 60 HZ SYSTEM.
QTY. POLE VOLTS AMPS. V-A BREAKER CONDUIT SIZE
NO. DESCRIPTION WIRE (mm2) 2. WIRING METHOD SHALL BE DONE IN PVC FOR POWER, LIGHTING AND AUXILIARY SYSTEM.
48 SQ METER X 24 VA/SQ METER =1152 VA
3. MINIMUM SIZE OF BRANCH CIRCUIT WIRE SHALL BE 2.0 SQ. MM THW WIRES SHALL BE INSULATED FOR 600 VOLTS AND SHALL BE COLOR
1 8 LIGHTING OUTLET 2 230 3.48 800 20A 2.0 mm2 TW 15 mm Ø PVC B. SMALL APPLIANCE LOAD CODED.
2 8 CONVENIENCE OUTLET 2 230 6.26 1440 20A 3.5 mm2 TW 20 mm Ø PVC 4 CIRCUITS X 1500 VA = 6000 VA 4. ALL FLUORESCENT LAMPS SHALL HAVE SPRING LOADED HOLDERS.
3 SUBTOTAL =7152 VA 5. WHENEVER NECESSARY PULL BOX OF THE PROPER SIZE AND DIMENSIONS SHALL BE PROVIDED ALTHOUGH NOT INDICATED IN THE
SPARE PLANS.
4 SPARE 6. ALL PANEL BOARDS SHALL BE PROVIDED WITH GROUNDING TERMINAL STRIP GROUNDING SYSTEM SHALL BE CONNECTED TO A
C. APPLICATION OF DEMAND FACTOR GROUNDING ROD AND/OR TO THE NEAREST COLD WATER PIPE.
FIRST 3000 VA @ 100% DF = 3000 VA 7. ALL PANEL BOARDS SHALL BE PROVIDED WITH IDENTIFICATIONS AND LOAD DIRECTORY.
REMAINDER @ 35% DF = 1453.2 VA 8. MOUNTING HEIGHT NOT SHOWN ON PLANS SHALL BE AS FOLLOWS:
A. SWITCHES ................................... 1400MM ABOVE FLR. FIN. @ CENTER
B. CONVENIENCE OUTLET ................ 300MM ABOVE FLR. FIN. @ CENTER
TOTAL NET COMPUTED LOAD = 4453.2 VA
C. TELEPHONE OUTLET ................ 300MM ABOVE FLR. FIN. @ CENTER
LEGEND : E. SERVICE ENTRANCE D. PANELBOARD ................................ 1400MM ABOVE FLR. FIN. @ CENTER UNLESS OTHERWISE
INDICATED BY THE FIELD CONDITION
PANEL BOARD CONVENIENCE OUTLET WIRE TOTAL FULL LOAD CURRENT
9. ALL MATERIALS TO BE USED SHALL BE NEW AND APPROVED TYPE FOR THE LOCATION AND PURPOSE FOR WHICH THEY ARE TO BE
PB
=4453.2 / 230 INSTALLED.
CHANDELIER
SERVICE ENTRANCE = 19.36 A
OUTLET( TWO GANG ) 10. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY QUALIFIED LICENSE ELECTRICAL
USE 1 - 30A 2 POLE MAIN CIRCUIT BREAKER BOLT ON TYPE ENGINEER.
PINLIGHT
S 1 GANG FLUSH TYPE SWITCH
USE 2 - 14mm 2 THW WIRE IN 25mm O RSC
CIRCUIT HOMERUN Sab 2 GANG FLUSH TYPE SWITCH ALL MOUNTING HEIGHTS ARE SUBJECT TO THE APPROVAL OF THE ARCHITECT/OWNER.
Drip Loop
150
Spool Insulator
on rack
Service
Rigid Steel Conduit Entrance
( should be exposed and not Cap
welded on steel pipes )
Pipe Strap
S c
4.30 M.
a 2
Sabc b PB
ELECTRICAL RISER DIAGRAM
PB Meter Base
Sab 1 S
a 4 - 12 MM. Ø RSB
with 10MM Ø Ties
b sp.@ 0.20M O.C
2000
1500
SERVICE ENTRANCE 2 - 8.0mm2 THW CU. WIRE
20AT 20AT
1 L.O. CO. 2 N.G.L N.G.L
SPARE SPARE
25mmØ P.E Pipe
3 4 ( S - 40 )
400
200
100
5 RISER DIAGRAM
NOT TO SCALE
E-1 DRAWN 100mm THK. Gravel Base
400
PREPARED BY: DESIGNED BY: PROPOSED APPROVED BY: CONTENTS SHEET NO. :