Professional Documents
Culture Documents
01 Natural Venting Smoke Management NFPA 204
01 Natural Venting Smoke Management NFPA 204
01 Natural Venting Smoke Management NFPA 204
Serial
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Handbook of Smoke Control Engineering - 2012
Application
Minimum fire for fuel-restricted atrium
Offices Offices
Offices Offices
urning car) 10 12
sign purposes, the fire area of a SHEVS should not be confused with the area of operation of the sprinkler design, wh
m is fully involved in fire, some of the heat produced can be generated in flames outside the room’s opening. It is rar
ature of gases leaving the opening to exceed 1 000 °C.
10
16
47
10
Heat release rate per unit area (q f) Heat release
kW·m–2 kW
625 6,250 3.8 7,162
625 3,125 2.9 4,029
1,200 -
100
Shops Offices Hotel Guest Room Hotel Public Areas Assembly Occupancy with fixed FIRE SIZE
seating
OCCUPANCY Heat Output (MW)
Shops 5
Offices 1
15.6
2.9
11.5
11.5
Design calculation sheet
Project no: Date: ### Computed by:
Subject: Checked by:
Criteria 1-ASHRAE A-53 : Fire and Smoke Control ( 2015 ) Fire dimensions :
Zs : Smoke Layer Height above the base of fire = 2.0 m Mean flame height
Zs L
d =2 m For L < Zs →
For L ≥ Zs →
H =4 m Zs = 2 m
Mass Flow Rate in the plume : m op = 10 kg/s
If Zs is smaller than 4Ws, the smoke production rates shall be increased by the factor [4Ws/Zs] 2/3
Page 26 of 28
Design calculation sheet
Project no: Date: ### Computed by:
Subject: Checked by:
TO = 40.0 o
C 313 oK
Cp = 1.0 kJ/kg oC
𝜌 = 𝑃_𝑎𝑡𝑚/(𝑅 𝑥
K= 0.5 𝑇_𝑠 )
At equilibrium the mass flow through the vents is equal to the smoke production rate : m op = mov
T= 313 + 0.5 x 1,470
13.5 x 1 Inlet type Flap type or door open at least 55 degrees Cd,I = 0.55
R = gas constant 287 J/kg.K.
T= 95 o
C 368 K
o rplume
= 1.0 kg / m3 Vent type Drop-out vent leaving clear opening Cd,v = 0.55
rair = 1.2 kg / m3
D T = T - To = 55 o
K Less than 110 °C , natural ventilation not recommended
Assuming ration Ai / Av = 1.0
Note : Where temperature differences of less than 110°C (230°F)are expected, vent flows
might be reduced significantly; therefore, consideration should be given to using powered Total vent area Av = 12.5 m2
M a ss fl o w fr a c ti o n o f m a x im u m
exhaust.
Total inlet area Ai = 12.5 m2 0.9 m/s , velocity
r=2.8 H = 11.2 m
0.6 4 H = 16 m
0.4
0.2
0.0
0 200 400 600 800 1000
Temperature above ambient K
Page 27 of 28
Effect of temperature on Mass Flow through a vent
M as
1.0
0.8
0.6
Design
0.4 calculation sheet
Project no: Date: ### Computed by:
0.2
Subject: Checked by:
Page 28 of 28