Fig. 1.

Schematic diagram of CSIRO microgrid system

TABLE I. PV OUTPUT POWER AND CURRENT THD

Inverter No. 38 43 46 37 40 41 47 39 35 42 45 44 36
PV output power (W) 654 1481 46.7 655 1450 1450 93.5 1465 1465 1434 109.1 46.8 639
Rated Power (W) 1000 1500 1000 1000 1500 1500 1500 1500 1500 1500 1500 1000 1000
P/Pr (%) 65.40 98.74 4.68 65.5 99.67 99.67 6.23 97.7 97.7 95.6 7.27 4.68 63.9
Current THD(%) 2.59 2.74 20.77 1.85 2.11 4.19 35.93 4.77 2.55 3.37 17.52 21.74 1.87

40 35.93
90-100 P/Pr(%) 60-70 P/Pr(%) less than 10% P/Pr
Current THD (%)

30 20.77 21.74
17.52
20
10 2.74 2.11 4.19 4.77 2.55 3.37 2.59 1.85 1.87
0
43 40 41 39 35 42 38 37 36 46 47 45 44
Inverter No.

Fig.2. Current THD of the PV inverter for different loading conditions

those data, the THD will be analyzed by using FFT function ∑ I


in Matlab. THD (1)
I
III. SIMULATION AND EXPERIMENT RESULTS Table I shows the PV output power, ratio of actual power
output and rated power (P/Pr) and THD of the current and
A. Harmonics and PV output power the PV generated power. Inverters are numbered 35 to 47,
This experiment has been carried out at the CSIRO and their nameplate capacity is either 1000W or 1500W, as
microgrid to find the relationship between harmonic provided in the third row of the table. Those data can be
distortion and PV output power levels. A total of 13 PV divided into three groups based on power level, which is
inverters which operated at different power output levels representing full load, half load and light load condition, as
have been connected to the grid in parallel by distribution shown in Fig. 2.
over the three phases. Actual waveforms were captured at It can be seen from Fig. 2 that the THD of the inverter
8000 samples per second and the THD was calculated from with low power output is up to around 20 times higher than
this equation: the THD of the inverter with high power output. The

204