Professional Documents
Culture Documents
Optimization of The Accuracy of Semi-Indirect Energy Metering System
Optimization of The Accuracy of Semi-Indirect Energy Metering System
ENGINEER XLVIINo.
Vol.XLVII, , No.03,03,
pp.pp. [page
[1-11], range], 2014
2014
The Institution
© The InstitutionofofEngineers,
Engineers,SriSri Lanka
Lanka
Abstract: Difference between a measurement reading and the true value of that measurement is
known as accuracy. The measuring device or system should have the capability to measure and match
the actual value to the quantity that is being measured to an acceptable accuracy declared by
respective standards. Measurements of electrical energy in various demand categories of different
utilities have their own limits. The employed measuring system is designed according to the demand
category. Semi indirect metering system is being used to measure energy consumed between 42 kVA
to 1 MVA by the governing Sri Lankan utility, Ceylon Electricity Board (CEB). It requires a current
transformer (CT), an energy meter and lead wires only. In general, such systems are installed after
certain standard checkups carried out for individual accuracy of CTs and energy meters in a standard
testing laboratory. However, it has been observed that there is a considerable deviation of accuracy
than expected when considering the accuracy of the whole system setup. Replacing of analogue
meters by digital meters in semi indirect measuring environment to establish an automated meter
reading system by a Utility has exclusive advantages such as immunity tamper up to certain extent
and features supported by enhance data communication facilities etc. However, careful study is
required to omit the potential of getting deviated the total system error beyond the desired limits due
to the burden mismatch owing to CTs, energy meters and associated lead wires. In this research study,
it was observed that considerable percentage of semi indirect metering systems installed are operating
at under burden condition. The study focused to minimize the error deviation of semi indirect
metering system owing to the above mentioned factors with a new concept of appropriate burden
matching. The study also concentrated on to finding the factors affecting the accuracy and how to
eliminate the error through a simple error compensation method. In here all the experiments were
done in the laboratory for 100/5 semi indirect metering model and it describes the methodology for
improving the accuracy clearly by appropriate component selection using developed charts for
different contract demands operating at different power factors depending on the application.
1 ENGINEER
ENGINEER
1.2 Background 2.1 Energy Meters
Electro-mechanical meters were used for semi- The energy meters installed are of
indirect metering system during past few Programmable Polyphase Meters (PPM) of
decades in Sri Lanka. Two types of analogue accuracy class 1 with remote meter reading
meters are widely being used in this regard to facility [1]. EDMI and PREMIER are the main
measure electrical energy (kWh) and Maximum brand types available in Sri Lanka having
electricity demand (kVA). Table 1 shows the burden of 0.5 VA under extreme operating
meter specifications. conditions.
CT2
Phase displacement error of a CT is the
CT3
difference in phase displacement between the
P.P.M primary and secondary current vectors [6].
Figure 2 and 3 shows the variation of ratio error
(%) and displacement error (min) against the
nominal current for a CT-ARW Class-1. It also
shows that the ratio error increases negatively
and displacement error increases positively
M.C.C.B
Lead wires
while varying the nominal current from 2.5% In
Load Side to 120% In respectively. Total error comes out to
be the contribution of both ratio error and
Figure 1-Schematic diagram of the phase displacement error.
Semi-indirect metering system
ENGINEER
ENGINEER 2
120 100 60 40 20 5 2.5 be almost around 1m and average power
0
-0.045 -0.075
factors were more than 0.89. Operating current
I n% (%In) was observed to be very much lower with
-0.16
-0.2 -0.22
respect to the rated current of CTs. Although
Ratio Error (%)
-0.325
-0.4 the overall error of semi-indirect metering
-0.6
system at the surveyed location were
-0.66 approximately around 3%, the individual error
-0.8 of the energy meters were within the class of
-1
-0.955 0.5, thereby the additional error was introduced
into the system by CTs and lead wires.
Figure 2 – Ratio Error variation
20
18.66 2.5 Ferraris Vs solid state meters
Modernization replaced the classical induction
Displacement Error(min)
15
12.95
meters by solid-state meters. Besides ensuring
10
precise metering, latter enables remote meter
6.25
5
3.77
reading and various metering systems such as
1.92 In% Automatic Metering Management (AMM). In
0
120-1.51 100
-0.71
60 40 20 5 2.5 addition to the expanded functions, they differ
-5 from the Ferraris in terms of electrical
Figure 3 – Displacement Error variation properties, and particularly their self-
consumption (meter burden). Since in the
2.3 Lead Wires course of years electrical properties such as
Even though the lead wire length selection transformation ratio, instrument security factor
process is not well defined in the respective etc. of measuring VTs and CTs remain more or
specifications used by the utilities, for example less unchanged for the majority of end users,
CEB 57:1997 states that the cross sectional area their measuring properties are mostly effected
of the connecting cables should not be less than by under-burdening of the secondary circuit
2 mm2 [3]. Under the circumstances, an caused by replacement of the Ferraris meters by
established method has not been practised so the electronic ones. Normally the power
far and moreover, there is not much of an consumption of electronic meters is from five to
attention is given technically when selecting the ten times smaller compared to the Ferraris
lead wire lengths in burden matching meters [7],[8]. Specification of VA burdens of
perspective. Most of the installations are CTs often come across with specified values of
observed to be carried out using 2.5 mm2 or 1 2.5, 5, 10, 15 VA. These burden values arrived at
mm2 double insulated multi strand wire the specifications are decided or documented
lengths. Also, it is worthwhile to note at this by end users, project engineers, process
point that the Lead wires not only affect the CT consultants and engineering consultants by
burden but also exposed for tampering. making hypothetical burden calculations &
Therefore the lead wire selection for semi inflating the values. These methods invariably
indirect metering system is an important lead to select inappropriate burden values of
exercise to be observed very carefully. CTs thus leading to inaccurate reading. Old
bulk supply metering system (>42kVA)
2.4 Semi-indirect metering system data consisted of two separate meters for active and
A comprehensive survey was carried out at apparent energy measurement where the
randomly selected factories in Kurunegala area burden of metering path is much higher with
to analyse the present situation of semi indirect respect to that of static meters. Thus, when
metering system. Data collection was done by replacing two analogue meters with a single
visiting each location. Appendix-A, Table-A1 digital meter, the operating burden of
shows the technical details gathered. Onsite secondary circuits of measuring CTs get further
testing was carried out by using high precision lowered.
portable test equipment (Zera MT 310, class-1)
to measure the energy meter accuracy, overall
error and instant parameters. Average power 3.0 Literature Survey
factor and average load were obtained by the
load survey of PPM. Here it was observed that Neither any technical literature found nor any
the burden of all CTs is 15VA and burden of research work has been carried out so far as to
meters is 0.5 VA. Wire lengths are observed to analyse the performance of the present
33 ENGINEER
ENGINEER
situation. Only routine tests had been carried Zx = Za+Zb can be varied when vary the lead
out to verify the energy meter accuracy only. wire length/cross section. When the wire
However, it was observed while surfing the length Zb increases, Ib get decreases. With this
internet that Slovenia and India has faced low burden condition, positive deviation of
similar under burden miss-matching metering accuracy can be observed. According to the
condition due to replacement of Ferraris meters above analysis over burden condition may lead
by solid state meters as in Sri Lanka [4]. to make negative error of accuracy. In this
project, lead wire length was varied and
selected the best cross sectional area to give the
4. Theoretical Analysis sufficient burden for secondary.
ENGINEER
ENGINEER 4
error is increased when the primary power semi indirect metering model prepared for this
factor decreases. experiment.
Ep
Np Ie
Np Ip1 Np I p
NpI e
θ2 NpI p1
θ NpIp
β2 1 β
1
Ie
Iw
Im
NsIs δ1
δ = (θ-β)
N s Is δ 2
18
5.3 Appropriate burden matching
According to the surveyed data (2.4), it can be
16
observed that the opposite burdens of the CTs
14 are very much lower than the rated burden.
12 0.0 Deg
With this lower burden condition, positive
deviation of accuracy is observed. The
C T E r r o r (%)
0.5 Deg
10 1.0 Deg
theoretical analysis shows that the over burden
8 condition may lead to make negative error for
6
metering accuracy. Also, in this research study,
it is proposed to vary the lead wire length and
4
the cross sectional area to give the sufficient
2 burden for the CT secondary. The experiments
0
were carried out for different wire lengths,
1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 loads and power factor conditions to get an
Power Factor
insight feeling to see the metering accuracy
Figure 7 - Power measurement error vs. power
variation. Length of the lead wires were
factor and phase angle error.
increased gradually from 1-8 meters and power
factor varied from 1.0-0.8. Results were
5. Methodology observed using high accuracy working
standard of class 0.02. A CT of 100/5 having
5.1 Proposed solution for improvement 5VA and a class 0.5 meter of having 0.5 VA
Laboratory experiments were performed to burdens were used to execute the test
analyse the existing metering system from experiment. It is noted that the burden value
which the chart based solution is proposed for variation for different wire lengths, cross
optimum accuracy. Figure 8 shows the 100/5
5 ENGINEER
ENGINEER
sectional area and secondary CT current values 6.2 Variation of accuracy against power
are linearly distributed as shown in Figure 9. factor under different load conditions
12
Maximum expected overall accuracy of this
1.0 mm2 & 6A
100/5 test model would be 1% due to 0.5
10 10.01 accuracy class of the energy meter and current
transformer. But all the results in every state of
Wire Burden (VA)
8
7.5
1.0 mm2 & 5A
7.01
the experiment were more than 2%. As per the
6 results obtained by the experiments, wire
length (burden) and power factor gives
5.05 5.26
2.5 mm2 & 6A
4.04
significant deviation for the accuracy. At unity
4
3.5
3.03 2.81
2
2.53
1.75
2.02 2.1 2.5 mm2 & 5A power factor condition, its nominal current
variation not much effect for the accuracy
1.4
1.01
0.702
0
0
0
2 4 6 8
(around 0.2%). Appendix-C, Figure C1 to C5
Wire Length (m)
illustrates above variation for power factor 1,
Figure 9-Burdens of lead wires 0.98, 0.95, 0.9 and 0.85 respectively.
lengths. 1
0.957
0.8 0.785
Accuracy variation for 1 m wire length 0.682
Error (%)
5.5 0.643
0.6 0.583
0.537
5 0.4
pf=0.5 Voltage Analogue meter
0.2 Voltage Digital meter
4.5 Voltage (V)
Overall accuracy (%)
0
4 150 200 240 260 265 270
pf=0.8
-0.2
3.5
pf=0.85
pf=0.9 Figure 11 - Accuracy variation for different
3 pf=0.95
pf=0.98
voltages at base current & pf = 0.8
2.5 pf=1
ENGINEER
ENGINEER 6
(Wire length) were effectively changed the Existing system
overall accuracy of the semi indirect metering
system. Effectiveness of voltage variation is Calculate the current
negligible for solid state meter for wide range for contract demand
of voltage variation.
Is the Contract No
Error (%) Error (%) Error (%) Replace the CT
Error (%) demand ≤ 120 %In
With a closer one
of the CT or closer
Nominal current
In %
Yes
Power factor Wire Length (m) Voltage (V)
PF=0.95
PF=1
Burden for 6 A
component selection under two main criterions. Burden for 5.5 A
12 Burden for 5 A
6
Example: 1 2
5 VA
Figure 14
7 ENGINEER
ENGINEER
7. Conclusion 3. Ceylon Electricity Board, STEEL BOXES
FOR HOUSING BULK SUPPLY METERS,
One of the major findings derived from this CEB Standard 050-1997.
research is that the secondary circuits equipped
with solid state energy meters installed under 4. CIRED, 20th International Conference on
semi indirect metering system are operating at electricity distribution, page 0105, Prague,
under burden conditions depending on the 8-11 June 2009.
connected CT with high burden. The actual
opposite burdens of the measuring CTs are less 5. EDISON ELECTRIC INSTITUTE, 2002,
than 25% of the rated burden. Therefore the Hand Book for Electricity metering Tenth
system operating at under burden condition Edition, EDITION ELECTRIC INSTITUTE,
does not yield to exact measurement of energy Washington.
thus; an improvement is required. Method of
accuracy improvement through maximization 6. International Electro Technical commission,
of CT performances and appropriate burden 2003-2, Current Transformer, International
matching is proposed here. It explains the Standard, IEC 60044–1.
methodology of selecting CTs and lead wire
lengths carefully while keeping the utility in 7. International Electro Technical commission,
the safe side. For given measuring CTs, 2003-1, Static meter for active energy,
electricity meters and known cross-section, the
International Standard, IEC 62053–22, First
desired total burden of the secondary circuit
edition.
can be achieved by an appropriate selection of
the conductor length. Moreover the other
8. International Electro Technical commission,
charts can be developed for more accuracy such
2003-1, Electromechanical meters for active
as 0.2% under extreme condition subjected to
the p.f. constraints. The attractive feature here energy, International Standards, IEC
is that the low cost of implementation and the 62053–11, First edition.
least technical expertise requirement. Also
reliability is much greater compared to 9. http://www.arwtransformers.co.uk/CTInfo,
electronic compensation and no routine Visited, 14th December 2013.
inspection and periodical calibration are
required. 10. http://www.currenttransformers.co.in,
Visited, 14th December 2013.
Acknowledgement
11. http://powermetrix.com,Visited, 14th
The authors would like to offer their December 2013.
appreciation to Eng. S.R.K. Gamage DGM,
Planning & Development Branch, Distribution 12. http://www.umsmeters.co.uk, Visited,
Division-1 and Eng. Kamal Perera CE, 14th December 2013.
Development Branch, Distribution Division-1
of CEB for their assistance by providing 13. http://www.zera.de, Visited, 10th January
facilities for this research study and many 2014.
thanks for the helpful comments suggestions
and the guidance provided by Dr. Narendra de 14. http://www.edmi-meters.com, Visited,
Silva of LECO. 12th February 2014.
References
ENGINEER
ENGINEER 8
Appendix-A
Table - A1
Customer Factory-1 Factory-2 Factory-3 Factory-4 Factory-5
Contract demand (kVA) 1000 630 400 630 630
Average load (kVA) 300 201 69 320 196
Avg. line current (A) 421 293 92 408 277
Average power factor 0.99 0.89 0.98 0.97 0.96
CT type ITL ARW ITL ITL ARW
CT Accuracy class 01 01 01 01 01
CT ratio 1600/5 1200/5 800/5 1200/5 800/5
CT Burden (VA) 15 15 15 15 15
Meter type Premier Premier Premier Premier Edmi
Accuracy class 01 01 01 01 01
Meter Burden (VA) 0.5 0.5 0.5 0.5 0.5
L1 - 1.1 L1- 1.0 L1 – 0.9 L1 – 1.0 L1 – 1.0
Length of Lead wires (m) L2– 1.0 L2 – 1.1 L2 – 1.0 L2 – 1.0 L2 – 1.0
L3 – 0.9 L3 – 1.2 L3 – 1.1 L3 – 1.0 L3 – 1.0
Area of the lead wire (mm2) 2.5 2.5 2.5 2.5 2.5
Meter error 0.34 0.31 -0.36 0.25 0.32
Overall error** 2. 94 3. 3 3.15 3.1 3.2
Average current as % In 26% 24.4% 11.5% 34% 34.6%
** including measurement error
Appendix-B
Accuracy variation for 2m wire length Accuracy variation for 4m wire length
6 pf=0.5
pf=0.5 7
5 6
Overall accuracy(%)
Overall accuracy(%)
5
4
pf=0.8 4 pf=0.8
pf=0.85
pf=0.85
3 pf=0.9 3
pf=0.9
pf=0.95
2 pf=0.95
pf=0.98
pf=0.98
2 pf=1.0 pf=1.0
1
Nominal current (%I n ) Nominal current (%I n )
1 0
10 20 30 40 50 60 70 80 90 100 120 10 20 30 40 50 60 70 80 90 100 120
Figure B1 Figure B2
Accuracy variation for 6m wire length Accuracy variation for 8m wire length
9 10
pf=0.5
8 pf=0.5
7 8
Overall accuracy(%)
6
Overall accuracy(%)
6
5
4 pf=0.8 4
pf=0.8
3 pf=0.85 pf=0.85
pf=0.9 2 pf=0.9
2
pf=0.95 pf=0.95
1 pf=0.98 pf=0.98
0
pf=1.0 pf=1.0
0 10 20 30 40 50 60 70 80 90 100 120
-1 10 20 30 40 50 60 70 80 90 100 120 -2
Nominal current (%I n ) Nominal current (%I n )
Figure B3 Figure B4
9 ENGINEER
ENGINEER
Appendix-C
1.5
Accuracy (%)
1
1
0.5
0.5
0
1 2 4 6 8
0
-0.5
1 2 4 6 8
-1 -0.5
Wire Length (m) Wire Length (m)
Figure C1 Figure C2
2 60% In
70% In 2
Accuracy (%)
Accuracy (%)
60% In
1.5
1.5
1
0.5
0
0.5
1 2 4 6 8 10
-0.5
0
1 2 4 6 8 -1
Wire Length (m) Wire Length(m)
Figure C3 Figure C4
ENGINEER
ENGINEER 10
For Power Factor 0.85
3.5
120% In
100% In
3
90% In
80% In
2.5
70% In
60% In
2
Accuracy (%)
1.5
0.5
0
1 2 4 6 8 10
-0.5
Wire Length(m)
Figure C5
11 11 ENGINEER
ENGINEER