Professional Documents
Culture Documents
Transistorized Inverter: Instruction Manual (Detailed)
Transistorized Inverter: Instruction Manual (Detailed)
Transistorized Inverter: Instruction Manual (Detailed)
F R - S 5 0 0
IN S T R U C T IO N M A N U A L (D e ta ile d )
W IR IN G C hapter 1
F U N C T IO N S C hapter 2
P R O T E C T IV E
F U N C T IO N S C hapter 3
H E A D O F F IC E :M IT S U B IS H I D E N K I B L D G M A R U N O U C H I T O K Y O 1 0 0 -8 3 1 0
S P E C IF IC A T IO N S C hapter 4
P r in te d in J a p a n
A-1
CAUTION
The electronic overcurrent protection does not guarantee protection of the motor
from overheating.
Do not use a magnetic contactor on the inverter input for frequent
starting/stopping of the inverter.
Use a noise filter to reduce the effect of electromagnetic interference. Otherwise
nearby electronic equipment may be affected.
Take measures to suppress harmonics. Otherwise power harmonics from the
inverter may heat/damage the power capacitor and generator.
When a 400V class motor is inverter-driven, it should be insulation-enhanced or
surge voltages suppressed. Surge voltages attributable to the wiring constants
may occur at the motor terminals, deteriorating the insulation of the motor.
When parameter clear or all clear is performed, each parameter returns to the
factory setting. Re-set the required parameters before starting operation.
The inverter can be easily set for high-speed operation. Before changing its
setting, fully examine the performances of the motor and machine.
In addition to the inverter's holding function, install a holding device to ensure
safety.
Before running an inverter which had been stored for a long period, always
perform inspection and test operation.
A-3
A-4
Contents
1.1.1 Terminal connection diagram .................................................................... 2
1.1.2 Layout and wiring of main circuit terminals............................................... 3
1.2 North America Version .............................................................................4
1.2.1 Terminal connection diagram .................................................................... 4
1.2.2 Layout and wiring of main circuit terminals............................................... 5
1.3 European Version.....................................................................................7
1.3.1 Terminal connection diagram .................................................................... 7
1.3.2 Layout and wiring of main circuit terminals............................................... 8
1.4 Description of I/O Terminal Specifications ...............................................9
1.4.1 Main circuit .................................................................................................. 9
1.4.2 Control circuit .............................................................................................. 9
1.5 How to Use the Main Circuit Terminals..................................................11
1.5.1 Cables, wiring lengths, crimping terminals, etc. ..................................... 11
1.5.2 Wiring instructions .................................................................................... 12
1.5.3 Peripheral devices .................................................................................... 13
1.5.4 Leakage current and installation of earth leakage circuit breaker...... 15
1.5.5 Power-off and magnetic contactor (MC) ................................................. 17
1.5.6 Regarding the installation of the power factor improving reactor ....... 18
1.5.7 Regarding noise and the installation of a noise filter.............................. 18
1.5.8 Grounding precautions............................................................................. 19
1.5.9 Regarding power harmonics..................................................................... 20
1.5.10 Japanese power harmonic suppression guideline............................... 20
1.6 How to Use the Control Circuit Terminals ..............................................24
1.6.1 Terminal block layout................................................................................ 24
1.6.2 Wiring instructions .................................................................................... 24
1.6.3 Changing the control logic........................................................................ 25
1.7 Input Terminals.......................................................................................28
1.7.1 Run (start) and stop (STF, STR, STOP)................................................. 28
1.7.2 Connection of frequency setting potentiometer and output frequency
meter (10, 2, 5, 4, AU).............................................................................. 31
1.7.3 External frequency selection (REX, RH, RM, RL).................................. 32
1.7.4 Indicator connection and adjustment ...................................................... 34
1.7.5 Control circuit common terminals (SD, 5, SE)........................................ 37
1.7.6 Signal inputs by contactless switches ..................................................... 37
1.8 How to Use the Input Signals
(Assigned Terminals RL, RM, RH, STR)................................................38
1.8.1 Multi-speed setting (RL, RM, RH, REX signals): Setting "0, 1, 2, 8"
Remote setting (RL, RM, RH signals): Setting "0, 1, 2"......................... 38
1.8.2 Second function selection (RT signal): Setting "3"................................. 38
I
Contents
2.8.1 Remote setting function selection .................................................. 86
2.9 Terminal Function Selection Parameters ...............................................88
2.9.1 Input terminal function selection .......................... 88
2.9.2 Output terminal function selection ......................................... 90
2.10 Operation Selection Function Parameters ...........................................91
2.10.1 Retry function ..................................................... 91
2.10.2 PWM carrier frequency ........................................................ 92
2.10.3 Applied motor ................................................................................. 93
2.10.4 Voltage input selection .................................................................. 93
2.10.5 Input filter time constant ................................................................ 94
2.10.6 Reset selection/PU stop selection ................................................ 94
2.10.7 Cooling fan operation selection .................................................... 96
2.10.8 Parameter write inhibit selection .................................................. 97
2.10.9 Reverse rotation prevention selection .......................................... 98
2.10.10 Operation mode selection ........................................................... 98
2.10.11 PID control to .................................................................... 101
2.11 Auxiliary Function Parameters ...........................................................109
2.11.1 Slip compensation ..................................................... 109
2.11.2 Automatic torque boost selection ............................................... 109
2.11.3 Motor primary resistance ............................................................ 111
2.12 Calibration Parameters ......................................................................111
2.12.1 Meter (frequency meter) calibration (Japanese version) ......... 111
2.12.2 Meter (frequency meter) calibration (NA and EC version) ...... 113
2.13 Clear Parameters ...............................................................................115
2.13.1 Parameter clear ........................................................................... 115
2.13.2 Alarm history clear ....................................................................... 115
2.14 Communication Parameters
(Only for the type having the RS-485 communication function)...........116
2.14.1 Communication settings to , ...................................... 118
2.14.2 Operation and speed command write ............................... 130
2.14.3 Link start mode selection ............................................................ 131
2
2.14.4 E PROM write selection .............................................................. 132
2.15 Parameter Unit (FR-PU04) Setting ....................................................133
2.15.1 Parameter unit display language switching ............................... 133
2.15.2 Buzzer sound control .................................................................. 133
2.15.3 PU contrast adjustment ............................................................... 134
2.15.4 PU main display screen data selection ...................................... 134
2.15.5 PU disconnection detection/PU setting lock .............................. 135
III
IV
<Abbreviations>
PU Chapter11
Control panel and parameter unit (FR-PU04)
Inverter
Mitsubishi transistorized inverter FR-S500 series
FR-S500 Chapter 2
Mitsubishi transistorized inverter FR-S500 series
Pr.
Parameter number
Chapter 3
Chapter 4
N P1 P
P1
R S T U V W
R S T U V W
IM
IM
Power supply Motor
Power supply Motor
FR-S520S-0.1K, 0.2K, 0.4K, 0.75K (-R) FR-S520S-1.5K (-R)
Jumper
Jumper
N P
N P1 P
P1
R S U V W
R S U V W
IM
IM 1
Power supply Motor
Power supply Motor
FR-S510W-0.1K, 0.2K, 0.4K (-R) FR-S510W-0.75K (-R)
N P N P
R S U V W
R S U V W
IM
IM
Power supply Motor
Power supply Motor
CAUTION
• The power supply cables must be connected to R, S, T. If they are connected to U, V, W,
the inverter will be damaged. (Phase sequence need not be matched.)
For use with a single-phase power supply, the power supply cables must be connected to
R and S.
• Connect the motor to U, V, W.
Turning on the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
N P1 P
P1
R S T U V W
R S T U V W
IM
IM
Power Motor
Power Motor supply
supply
N P N P
R S U V W
R S U V W
IM
Power Motor IM
supply Power Motor
supply
CAUTION
• The power supply cables must be connected to R, S, T. If they are connected to
U, V, W, the inverter will be damaged. (Phase sequence need not be matched.)
• Connect the motor to U, V, W.
Turning on the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
m9 Setting Description
0 Single-phase power input
---
Three-phase power input
(Factory setting)
CAUTION
Always return the C8 parameter to 0 (factory setting) after you have finished the
setting of m9.
REMARKS
*1 Only the type with RS-485 communication function.
*2 You can switch between the sink and source logic positions. Refer to page 25.
*3 When the setting potentiometer is used frequently, use a 2W 1kΩ potentiometer.
*4 The terminal functions change with input terminal function selection (Pr. 60 to
Pr. 63). (Refer to page 38, 88) (RES, RL, RM, RH, RT, AU, STOP, MRS, OH,
REX, JOG, X14, X16, (STR) signal selection)
*5 The terminal functions change with output terminal function selection (Pr. 64,
Pr. 65). (Refer to page 90) (RUN, SU, OL, FU, RY, Y12, Y13, FDN, FUP, RL,
LF, ABC signal selection)
Jumper
- +
P1
L1 L2 L3 U V W
IM
Power Motor
supply
FR-S520S-0.2K, 0.4K, 0.75K-EC (R) FR-S520S-1.5K-EC (R)
Jumper
Jumper
- +
- P1 +
P1
L1 N U V W
L1 N U V W
IM
IM
Power Motor
Power Motor supply
supply
CAUTION
• Connect the motor to U, V, W.
Turning on the forward rotation switch (signal) at this time rotates the motor
counterclockwise when viewed from the load shaft.
• For power input wiring, connect L1 to R/L1 of the terminal block and N to S/L2 of
the terminal block.
• Do not connect the power supply to U, V and W.
Frequency
FM
11
2) Application of power to the output terminals (U, V, W) of the inverter will damage
the inverter. Never perform such wiring.
3) After wiring, wire off-cuts must not be left in the inverter.
Wire off-cuts can cause an alarm, failure or malfunction. Always keep the inverter
clean.
When drilling a control box etc., take care not to let wire off-cuts enter the inverter.
5) For long distance wiring, the fast-response current limit function may be reduced or
the devices connected to the secondary side may malfunction or become faulty
under the influence of a charging current due to the stray capacity of wiring.
Therefore, note the maximum overall wiring length.
8) Before starting rewiring or other work after performing operation once, check the
voltage with a meter etc. more than 10 minutes after power-off. For some time after
power-off, there is a dangerous voltage in the capacitor.
12
13
14
Counter measures
Use the electronic overcurrent protection of the inverter.
Decrease the carrier frequency. Note that motor noise increases. Selection of
Soft-PWM (Pr. 70) makes it unoffending.
To ensure that the motor is protected against line-to-line leakage currents, it is 1
recommended to use a temperature sensor to directly detect motor temperature.
Installation and selection of no-fuse breaker
On the power receiving side, install a no-fuse breaker (NFB) to protect the primary
wiring of the inverter. Which NFB to choose depends on the power supply side
power factor (which changes with the power supply voltage, output frequency and
load) of the inverter. Especially as the completely electromagnetic type NFB
changes in operational characteristic with harmonic currents, you need to choose
the one of a little larger capacity. (Check the data of the corresponding breaker.)
For the earth leakage circuit breaker, use our product designed for harmonic and
surge suppression (Progressive Super Series). (Refer to page 13 for the
recommended models.)
CAUTION
Choose the NFB type according to the power supply capacity.
15
16
ON Inverter
MC
RA
OFF RA
RA
STF (STR)
SD
Inverter Start/Stop Circuit Example
(1) Inverter's primary side magnetic contactor (MC)
On the inverter's primary side, it is recommended to provide an MC for the following
purposes (Refer to page 13 for selection.):
1) To release the inverter from the power supply when the inverter's protective
function is activated or when the drive is not functioning (e.g. emergency stop
operation).
2) To prevent an accident caused by an automatic restart made at power restoration 1
after an inverter stop due to a power failure.
3) To rest the inverter for a long time.
The control power supply for inverter is always running and consumes a little
power. When stopping the inverter for a long time, switching inverter power off
saves power slightly.
4) To separate the inverter from the power supply to ensure safety of
maintenance/inspection work.
As the inverter's primary MC is used for the above purposes, it is equivalent to the
standard duty and select the one of class JEM1038-AC3 for the inverter input side
current.
17
capacity (kVA)
supply installation range
T Z T W 500
P<+>P1
0 10
FR-BEL(*) Wiring length (m)
REMARKS
* When connecting the FR-BEL, remove the jumper across terminals P<+>-P1.
The wiring length between FR-BEL and inverter should be 5m (16.40feet)
maximum and as short as possible.
Use the cables which are equal in size to those of the main circuit. (Refer to page
11)
Use the dedicated ground terminal to ground the inverter. (Do not use the screw in
the casing, chassis, etc.)
Use a tinned* crimping terminal to connect the earth cable. When tightening the
screw, be careful not to break the threads.
*Plating should not include zinc.
Use the thickest possible ground cable. Use the cable whose size is equal to or
greater than that indicated in the following table, and minimize the cable length. 1
The grounding point should be as near as possible to the inverter.
(Unit: mm2)
Ground Cable Size
Motor Capacity
200V, 100V class 400V class
2.2kW (3HP) or less 2 (2.5) 2 (2.5)
3.7kW (5HP) 3.5 (4) 2 (4)
For use as a product compliant with the Low Voltage Directive, use PVC cable
whose size is indicated within parentheses.
Ground the motor on the inverter side using one cable of the 4-core cable.
19
Table 1 Maximum Values of Outgoing Harmonic Currents per 1kW Contract Power
Over
Received Power Voltage 5th 7th 11th 13th 17th 19th 23rd
23rd
6.6kV 3.5 2.5 1.6 1.3 1.0 0.9 0.76 0.70
22 kV 1.8 1.3 0.82 0.69 0.53 0.47 0.39 0.36
33 kV 1.2 0.86 0.55 0.46 0.35 0.32 0.26 0.24
New installation/addition/
renewal of equipment
Calculation of equivalent
capacity sum
Over reference
capacity
Calculation of outgoing 1
harmonic current
21
22
23
PC SE RUN 10 2 5 4
SD SD STF STR RL RM RH
FM Japanese version
A B C <AM> NA, EC version
Terminal screw size: M2
Terminal screw
size: M3
REMARKS
For the cable size, wiring length, etc., refer to the instruction manual (basic).
24
CAUTION
• Make sure that the front cover is installed securely.
• The front cover is fitted with the capacity plate and the inverter unit with the rating
plate. Since these plates have the same serial numbers, always replace the
removed cover onto the original inverter.
• The sink-source logic change-over connector must be fitted in only one of those
positions. If it is fitted in both positions at the same time, the inverter may be
damaged.
25
SD SE 9
24VDC
9
PC
10 24VDC
SD
26
Current RUN 1
STF R
R
STR R SE
R 24VDC 9
10 SD
27
28
Output frequency
Pr. 60 to Pr. 62 (input terminal
function selection).
2) If the start signal terminal STF (STR)-
SD are shorted once, then opened, the
start signal is kept on and starts the
inverter. To change the rotation Time
ON
direction, short the start signal STR
(STF)-SD once, then open it. Start
(Note) Assign the stop signal to any of ON
Pr. 60 to Pr. 62 (input terminal Stop
function selection).
3-wire type connection example
3) The inverter is decelerated to a stop by
opening the signal STOP-SD once. For
the frequency setting signal and the
operation of DC dynamic brake at a
stop time, refer to paragraphs 2) to 4) in
(1) Two-wire type connection. The right
diagram shows 3-wire type connection.
4) When the signal JOG-SD is shorted, the STOP signal is invalid and the JOG signal
has precedence.
5) If the output stop signal MRS-SD is shorted, the self-holding function is not
deactivated.
DC Injection Brake and Coasting to Stop functionality
Operation External Operation or Combined PU Operation or Combined
Mode Operation Operation 1
Pr. 79 = "0", "2", "3" Pr. 79 = "0", "1", "4"
Terminals STF
(STR)-SD Set frequency Set frequency
Stop key
DC Injection disconnected changed to 0Hz changed to 0Hz
Brake (*1)
DC injection DC injection
brake operated at brake operated at
not more than DC injection not more than DC injection
DC injection
"DC injection brake operated at "DC injection brake operated at
brake enabled brake operation 0.5Hz or less. brake operation 0.5Hz or less.
frequency" set in frequency" set in
Pr. 10 Pr. 10
Coasted to a stop Coasted to a stop
at not more than at not more than
DC injection "DC injection Coasted to a stop "DC injection Coasted to a stop
brake disabled brake operation at 0.5Hz or less. brake operation at 0.5Hz or less.
frequency" set in frequency" set in
Pr. 10 Pr. 10
STOP
*1: Also stopped by the RESET key. Refer to page 94.
29
Output frequency
Starting frequency DC injection brake not operated
Pr.13 operation
(*1) frequency Pr. 10 (*4)
3Hz 0.5Hz 3Hz
0.5Hz 0.5Hz
Coasted to Time
0.5s 0.5s
Start signal DC injection DC injection a stop
brake operation brake operation
terminal time Pr. 11 ON time Pr. 11
Across STF-SD ON (*3) (*3)
ON
Across STR-SD
(*2)
REMARKS
*1 The "starting frequency" in Pr. 13 (factory-set to 0.5Hz) may be set between 0
and 60Hz.
*2. If the next start signal is given during DC injection brake operation, the DC
injection brake is disabled and restart is made.
*3. The "DC injection brake operation time" in Pr. 11 (factory-set to 0.5s) may be
set between 0 and 10s.
*4. The frequency at which the motor is coasted to a stop is not more than the "DC
injection brake operation frequency" set in Pr. 10 (factory setting = 3Hz; may be
set between 0 and 120Hz) or not more than 0.5Hz.
*5. The "starting frequency" in Pr. 13, "DC injection brake operation time" in Pr. 11
and "DC injection brake operation frequency" in Pr. 10 are the factory-set
values.
30
Starting frequency
(0 to 60Hz) Pr.2
0.5 Pr.13
0 5V Pr.73
Frequency setting signal
(10V)
(20mA)
Relationships between Frequency Setting Inputs and Output Frequencies
REMARKS
For the way to calibrate the output frequency meter, refer to the instruction manual
(basic). 1
(1) Voltage input (10, 2, 5)
Enter the frequency setting input signal of 0 to 5VDC (or 0 to 10VDC) across the
frequency setting input terminals 2-5. The maximum output frequency is reached
when 5V (10V) is input across terminals 2-5.
The power supply used may either be the inverter's built-in power supply or an
external power supply. For the built-in power supply, terminals 10-5 provide 5VDC
output.
For operation at 0 to 5VDC, set "0" in For operation at 0 to 10VDC, set "1" in
Pr. 73 to the 0 to 5VDC input. Use Pr. 73 to the 0 to 10VDC input.
terminal 10 for the built-in power
supply.
+5V 10
2 2
0 to 5VDC 0 to 10VDC
5 5
31
Speed 1
Output frequency (Hz)
Time Time
ON ON ON ON ON ON ON ON
RH RH
ON ON ON ON ON ON ON ON
RM RM
ON ON ON ON ON ON ON
RL RL
ON ON ON ON ON ON ON ON
REX REX
32
CAUTION
• Refer to page 111 for the procedure of indicator adjustment.
34
Adjustment
Analog meter
To adjust the reading of an analog indicator (ammeter), turn the calibration resistor
to change the current.
1
When using the operation panel or parameter unit for adjustment, change the pulse
width of the output waveform (calibration parameter "C1") (adjust the current through
the adjustment of the output voltage) to adjust the reading. (For details, refer to page
111.)
REMARKS
It is not recommended to use a voltage type indicator because it is easily affected
by a voltage drop, induction noise, etc. and may not provide correct reading if the
wiring distance is long.
35
Adjustment
Set the reference output value of the inverter which outputs the full-scale voltage
5VDC.
Set it in Pr. 55 for frequency monitoring reference, or in Pr. 56 for current monitoring
reference.
Use the terminal AM output calibration parameter C1 to adjust the output voltage.
[Example] 1. To set the output across AM-5 to 5VDC at the inverter output frequency
of 90Hz, set 90Hz in Pr. 55. (Factory setting: 50Hz)
2. To set the output across AM-5 to 5VDC at the inverter output current of
20A, set 20A in Pr. 56. (Factory setting: rated inverter current)
CAUTION
• Refer to page 113 for the procedure of indicator adjustment.
36
REMARKS
Terminal FM is provided for the FR-S520-0.1K to 3.7K (-R) (-C), FR-S520S-0.1K to
1.5K (-R) and FR-S510W-0.1K to 0.75 (-R), and terminal AM is provided for the
FR-S520-0.1K to 3.7K-NA, FR-S520S-0.2K to 1.5K-EC (R) and FR-S510W-0.1K to
0.75K-NA.
1
Inverter
SD
REMARKS
1. When using an external transistor connected with the external power supply, use
terminal PC to prevent a malfunction from occurring due to a leakage current.
(Refer to page 25.)
2. Note that an SSR (solid-state relay) has a relatively large leakage current at OFF
time and it may be accidentally input to the inverter.
37
Output frequency
mechanical brake (e.g. to stop
electromagnetic brake)
Terminals MRS-SD must be shorted
when the mechanical brake is
operated and be opened before motor 0.5Hz
Pr. 13
restart. "starting
(2) To provide interlock to disable frequency"
operation by the inverter Across
ON
After MRS-SD have been shorted, the MRS -SD
inverter cannot be operated if the start Across ON
STF-SD
signal is given to the inverter. (STR)
(3) To coast the motor to stop
The motor is decelerated according to the preset deceleration time and is
stopped by operating the DC injection brake at 3Hz or less. By using terminal
MRS, the motor is coasted to a stop.
39
Output frequency
started/stopped by shorting the
jog mode select terminal JOG- Forward 3Hz
DC injection brake
0.5Hz
SD and shorting/opening the rotation
start signal terminal STF or Time
Reverse
STR-SD. The jog frequency and rotation
jog acceleration/deceleration
time are set in Pr. 15 (factory ON
setting 5Hz, variable between 0 Across JOG-SD
and 120Hz) and Pr. 16 (factory Forward rotation ON
Across STF-SD
setting 0.5s, variable between 0 Reverse rotation ON
and 999s), respectively, Across STR-SD
and their settings can be changed from the operation panel or parameter unit (type with
RS-485 communication function).
The JOG signal has precedence over the multi-speed signal. (External)
1.8.8 Reset signal: Setting "10"
Used to reset the alarm stop state established when the inverter's protective function is
activated. The reset signal immediately sets the control circuit to the initial (cold) status,
e.g. initializes the electronic overcurrent protection circuit. It shuts off the inverter output
at the same time. During reset, the inverter output is kept shut off. To give this reset
input, short terminals RES-SD for more than 0.1 second. When the shorting time is long,
the operation panel or parameter unit displays the initial screen, which is not a fault.
Operation is enabled after terminals RES-SD are opened.
The reset terminal is used to reset the inverter alarm stop state. If the reset terminal is
shorted, then opened while the inverter is running, the motor may be restarted during
coasting (refer to the timing chart below) and the output may be shut off due to
overcurrent or overvoltage.
Setting either of "1" and "15" in reset selection Pr. 75 allows the accidental input of the
reset signal during operation to be unaccepted.
(For details, refer to page 94.)
When motor is restarted
during coasting, inverter
activates current limit to Coasting to stop
start acceleration. (Indicates motor speed)
Output frequency
Ordinary
acceleration
Coasting
(Hz)
Coasting time
ON ON
Across RES-SD
ON
Across
STF (STR)-SD T
T: Should be longer than the time of
coasting to stop.
CAUTION
Frequent resetting will make electronic overcurrent protection invalid.
40
♦Related parameters♦
♦
Pr. 79 "operation mode selection" (Refer to page 98)
View A 1
CAUTION
1. Do not plug the connector to a computer LAN board, fax modem socket,
telephone modular connector etc. as they are different in electrical specifications,
the inverter may be damaged.
2. Pins 2 and 8 (P5S) are provided for the parameter unit power supply. Do not use
them for any other purpose or when making parallel connection by RS-485
communication.
41
42
RDB
RDA
RDB
RDA
RSB
SDB
SDA
SDB
SDA
SDB
SDA
(*1) (*2)
CSA
CSB
SG SG SG SG
FG Station 1 Station 2 Station n
Inverter Inverter Inverter
REMARKS
*1. Make connection in accordance with the instruction manual of the computer to be
used with. Fully check the terminal numbers of the computer since they change with
the model.
*2. The inverters may be affected by reflection depending on the transmission speed or
transmission distance. If this reflection hinders communication, provide a termination
resistor. When the RS-485 connector is used for connection, a termination resistor
cannot be fitted, so use a distributor. Connect the termination resistor to only the
inverter remotest from the computer. (Termination resistor: 100Ω)
43
44
45
DC injection
11 brake 0 to 10s 0.1s 0.5s 64
operation time
DC injection
12 brake voltage 0 to 15% 0.1% 6% 64
Starting
13 frequency 0 to 60Hz 0.1Hz 0.5Hz 65
0: For constant-torque
loads,
Load pattern 1: For variable-torque
14 1 0 66
selection loads,
2: For vertical lift loads,
3: For vertical lift loads
46
Pammeter List
Jog
acceleration/
16 0 to 999s 0.1s 0.5s 67
deceleration
time
RUN key
rotation 0: Forward rotation,
17 1 0 67
direction 1: Reverse rotation
selection
0 to 500V, 888, - - -
Base frequency ---
19 (0 to 800V, 888, - - - 1V 59
voltage <888>
for the 400V class.)
Acceleration/
deceleration 60Hz
20 1 to 120Hz 0.1Hz 62
reference <50Hz>
frequency
Stall
prevention
21 0 to 31, 100 1 0 68
function
Standard operation functions
selection
Stall
22 * prevention 0 to 200% 1% 150% 69
operation level
Stall
prevention
operation level
23 0 to 200%, - - - 1% --- 69
compensation
factor at
double speed
Multi-speed
24 * setting 0 to 120Hz, - - - 0.1Hz --- 61
(speed 4)
Multi-speed
25 * setting 0 to 120Hz, - - - 0.1Hz --- 61
(speed 5)
Multi-speed
26 * setting 0 to 120Hz, - - - 0.1Hz --- 61 2
(speed 6)
Multi-speed
27 * setting 0 to 120Hz, - - - 0.1Hz --- 61
(speed 7)
Stall
prevention
operation 60Hz
28 0 to 120Hz 0.1Hz 69
reduction <50Hz>
starting
frequency
47
Acceleration/
1: S-pattern acceleration/
29 deceleration 1 0 71
deceleration A,
pattern
2: S-pattern acceleration/
deceleration B
Frequency
31 0 to 120Hz, - - - 0.1Hz --- 72
jump 1A
Frequency
32 0 to 120Hz, - - - 0.1Hz --- 72
jump 1B
Standard operation functions
Frequency
33 0 to 120Hz, - - - 0.1Hz --- 72
jump 2A
Frequency
34 0 to 120Hz, - - - 0.1Hz --- 72
jump 2B
Frequency
35 0 to 120Hz, - - - 0.1Hz --- 72
jump 3A
Frequency
36 0 to 120Hz, - - - 0.1Hz --- 72
jump 3B
37 Speed display 0, 0.1 to 999 0.1 0 73
Frequency
60Hz
38 setting voltage 1 to 120Hz 0.1Hz 74
<50Hz>
gain frequency
Frequency
60Hz
39 setting current 1 to 120Hz 0.1Hz 74
<50Hz>
gain frequency
Start-time
ground fault 0: Not detected 0
40 1 78
detection 1: Detected <1>
selection
Up-to-
Output terminal functions
time
Second
45 deceleration 0 to 999s, - - - 0.1s --- 62
time
Second torque
46 0 to 15%, - - - 0.1% --- 58
boost
Second V/F
47 (base 0 to 120Hz, - - - 0.1Hz --- 59
frequency)
48
Pammeter List
detection level
Current detection
Output current
detection
49 0 to 10s 0.1s 0s 80
signal delay
time
Zero current
50 0 to 200% 1% 5% 81
detection level
Zero current
51 0.05 to 1s 0.01s 0.5s 81
detection time
0: Output frequency,
1: Output current,
Control panel
100: Set frequency
52 * display data 1 0 82
during stop/output
selection
frequency during
operation
0: Setting dial
Display functions
Frequency
frequency setting
setting
53 * mode 1 0 83
operation
1: Setting dial
selection
potentiometer mode
FM (AM) 0: Output frequency
terminal monitor
54 * 1 0 82
function 1: Output current
selection monitor
Frequency
60Hz
55 * monitoring 0 to 120Hz 0.1Hz 84
<50Hz>
reference
Current Rated
56 * monitoring 0 to 50A 0.1A output 84
reference current
Automatic restart
Restart
57 0 to 5s, - - - 0.1s --- 84
functions
coasting time
Restart
58 0 to 60s 0.1s 1s 84
cushion time 2
0: Without remote
setting function
1: With remote setting
Additional function
function
Remote With frequency
setting setting storage
59 1 0 86
function function
selection 2: With remote setting
function
Without frequency
setting storage
function
49
50
Pammeter List
Input filter time 1 to 8:
74 1 1 94
constant Exponential average
value of 2n at the
setting of n
0: Reset normally
enabled/PU stop
key disabled
1: Enabled at alarm
occurrence only/PU
Reset stop key disabled
75 * selection/PU 14: Reset normally 1 14 94
stop selection enabled/normally
Operation selection functions
decelerated to stop
15: Enabled at alarm
occurrence
only/normally
decelerated to stop
0: Operation started at
Cooling fan
power-on
76 operation 1 1 96
1: Cooling fan ON/OFF
selection
control
0: Write is enabled only
during a stop
Parameter 1: Write disabled
77 * write disable (except some 1 0 97
selection parameters)
2: Write during
operation enabled
0: Both forward rotation
and reverse rotation
Reverse
enabled,
rotation
78 1: Reverse rotation 1 0 98
prevention
disabled,
selection
2: Forward rotation
disabled
Multi-speed 2
Multi-speed operation function
51
12)
Multi-speed
85 * setting (speed 0 to 120Hz, - - - 0.1Hz --- 61
13)
Multi-speed
86 * setting (speed 0 to 120Hz, - - - 0.1Hz --- 61
14)
Multi-speed
87 * setting (speed 0 to 120Hz, - - - 0.1Hz --- 61
15)
PID action 20: PID reverse action,
88 1 20 101
selection 21: PID forward action
PID
89 * proportional 0.1 to 999%, - - - 0.1% 100% 101
band
PID control
PID integral
90 * 0.1 to 999s, - - - 0.1s 1s 101
time
91 PID upper limit 0 to 100%, - - - 0.1% --- 101
92 PID lower limit 0 to 100%, - - - 0.1% --- 101
PID action set
93 * point for PU 0 to 100% 0.01% 0% 101
operation
PID differential
94 * 0.01 to 10s, - - - 0.01s --- 101
time
Rated motor
95 0 to 50%, - - - 0.01% --- 109
slip
Slip compensation
Slip
96 compensation 0.01 to 10s 0.01s 0.5s 109
time constant
Constant-
output region
97 slip 0, - - - 1 --- 109
compensation
selection
Automatic
Automatic torque
52
Pammeter List
calibration
900
C1 111
<NA,
AM terminal
EC>
calibration
901
Frequency setting
Calibration parameters
0: Not executed
CLr Parameter clear 1: parameter clear 1 0 115
2: all clear
0: Not cleared,
Alarm history
ECL * 1: Alarm history 1 0 115
clear
clear
Note 2: Settings may differ because of calibration parameters.
Parameters only for the type having the RS-485 communication function (When the
parameter unit (FR-PU04) is used, operation from the operation panel is not
accepted.)
Com-
Minimum
muni- Cus-
Func- Indica- Setting Factory Refer
cation Name Setting Range tomer
tion tion Incre- Setting To:
Parame- Setting
ments
ter
0 to 31:
Communication Specify the 2
n1 (331) 1 0 118
Communication Parameters
53
Number of
n5 (335) communication 0 to 10, - - - 1 1 118
retries
Communication
0s
n6 (336) check time 0 to 999s, - - - 0.1s 118
<- - ->
interval
n7 (337) Wait time setting 0 to 150ms, - - - 1 --- 118
0: Command write
from computer,
Operation
n8 (338) 1: Command write 1 0 130
command write
from external
terminal
0: Command write
from computer,
Speed command
n9 (339) 1: Command write 1 0 130
write
from external
terminal
Communication Parameters
54
Pammeter List
0: Selectable
between
output
frequency
and output
current
100: (during stop):
PU main display Set
n16
screen data frequency, 1 0 134
Communication Parameters
(992) *
selection output
current
(during
operation):
Output
frequency,
output
current
0: Without PU
disconnection
error,
PU 1: Error at PU
n17 disconnection disconnection,
1 0 135
(993) detection/PU 10: Without PU
setting lock disconnection
error (PU
operation
disable)
For details of the program, refer to page 118 onwards.
REMARKS
1. The parameter numbers within parentheses are those for use of the parameter
unit (FR-PU04).
2. Set "9999" when setting a value "- - -" using the parameter unit (FR-PU04).
3. The decimal places of a value 100 or more (3 digits or more) cannot be
displayed.
2
4. The parameters marked * can be changed in setting during operation if "0"
(factory setting) is set in Pr. 77 "parameter write disable selection". (Note that
Pr. 53, Pr. 70 and Pr. 72 may be changed only during PU operation.)
55
Parameter Numbers
Purpose of Use
Parameter numbers which must be set
Use of extended function parameters Pr. 30
Pr. 53, Pr. 79
Operation mode selection
(Communication parameters n10, n17)
Acceleration/deceleration Pr. 7, Pr. 8, Pr. 16, Pr. 20, Pr. 29, Pr. 44,
time/pattern adjustment Pr. 45
Selection of output characteristics
Pr. 3, Pr. 14, Pr. 19
optimum for load characteristics
Output frequency restriction (limit) Pr. 1, Pr. 2
Pr. 1, Pr. 38, Pr. 39,
Operation over 60Hz <50Hz>
Related to operation
56
Calibration parameter C1
Display of monitor on control panel or
Pr. 52, Communication parameter n16
parameter unit (FR-PU04)
Display of speed, etc Pr. 37, Pr. 52
Motor stall prevention Pr. 21, Pr. 22, Pr. 23, Pr. 28
57
Output voltage
inverter-to-motor distance is long or
motor torque is insufficient in the low
speed range (stall prevention is
activated).
Motor torque in the low-frequency
range can be adjusted to the load Pr.0
to increase the starting motor Setting range
Pr.46
torque.
0 Output frequency (Hz)
Factory Setting
Parameter Name Remarks
Setting Range
(Note) FR-S520 (S)-0.1K to 3.7K: 6%
FR-S540-0.4K, 0.75K: 6%
6%/5%/4%
0 Torque boost 0 to 15% FR-S510W-0.1K to 0.75K: 6%
(Note) FR-S540-1.5K, 2.2K: 5%
FR-S540-3.7K: 4%
0 to 15%, - - -: Function invalid. Setting is
46 Second torque boost --- --- enabled when Pr. 30 = "1".
<Setting>
Assuming that the base frequency voltage is 100%, set the 0Hz voltage in %.
Use the RT signal to switch between two different torque boosts. (Turn on the RT
signal to make Pr. 46 valid(*).)
REMARKS
* The RT signal acts as the second function selection signal and makes the other
second functions valid.
When using an inverter-dedicated motor (constant-torque motor), make setting as
indicated below.
• FR-S520-0.1K to 0.75K ..... 6%, FR-S520-1.5K to 3.7K ..... 4%
• FR-S540-0.4K, 0.75K ..... 6%, FR-S540-1.5K ..... 4%,
FR-S540-2.2K, 3.7K ..... 3%
• FR-S520S-0.1K to 0.75K ..... 6%, FR-S520S-1.5K ..... 4%
• FR-S510W-0.1K to 0.75K ..... 6%
If you leave the factory setting as it is and change the Pr. 71 value to the setting for
use of the constant-torque motor, the Pr. 0 setting changes to the above value.
CAUTION
• Selecting automatic torque boost control makes this parameter setting invalid.
• A too large setting may cause the motor to overheat or result in an overcurrent
trip. The guideline is about 10% at the greatest.
♦Related parameters♦
♦
RT signal (second function "Pr. 46") setting⇒ Pr. 60 to Pr. 63 "input terminal function
selection" (refer to page 88)
Constant-torque motor setting ⇒ Pr. 71 "applied motor" (refer to page 93)
Automatic torque boost control selection ⇒ Pr. 98 "automatic torque boost selection (motor
capacity)" (refer to page 109)
58
Pr.1
Set frequency
Pr.2
0 5,10V
(4mA) (20mA)
Factory Setting
Parameter Name Setting Range
<EC version>
1 Maximum frequency 60Hz <50Hz> 0 to 120Hz
2 Minimum frequency 0Hz 0 to 120Hz
<Setting>
Use Pr. 1 to set the upper limit of the output frequency. If the frequency of the
frequency command entered is higher than the setting, the output frequency is
clamped at the maximum frequency.
Use Pr. 2 to set the lower limit of the output frequency.
REMARKS
When using the potentiometer (frequency setting potentiometer) connected across
terminals 2-5 to perform operation above 60Hz <50Hz>, change the Pr. 1 and Pr. 38
(Pr. 39 when using the potentiometer across terminals 4-5) values.
CAUTION
When the Pr. 2 setting is higher than the Pr. 13 "starting frequency" value, note
that the motor will run at the set frequency by merely switching the start signal
on, without entering the command frequency.
♦Related parameters♦
♦
Starting frequency setting ⇒ Pr. 13 "starting frequency" (refer to page 65)
Maximum frequency setting using external potentiometer
⇒ Pr. 30 "extended function display selection" (refer to page 72), Pr. 38 "frequency setting 2
voltage gain frequency", Pr. 39 "frequency setting current gain frequency" (refer to page 74)
59
CAUTION
1. Set 60Hz in Pr. 3 "base frequency" when using a Mitsubishi constant-torque motor.
2. When automatic torque boost is selected, Pr. 47 is invalid. When automatic
torque boost is selected, setting "- - -" or "888" in Pr. 19 uses the rated output
voltage.
REMARKS
* The RT signal serves as the second function selection signal and makes the
other second functions valid.
♦Related parameters♦
♦
When rated motor frequency is "50Hz" ⇒ Pr. 14 "load pattern selection" (refer to page 66)
RT signal (second function "Pr. 47") setting ⇒ Pr. 60 to Pr. 63 (input terminal function
selection) (refer to page 88)
Motor setting ⇒ Pr. 71 "applied motor" (refer to page 93)
Automatic torque boost selection ⇒ Pr. 98 "automatic torque boost selection (motor capacity)"
(refer to page 109)
60
Time Time
ON ON ON ON ON ON ON ON
RH RH
ON ON ON ON ON ON ON ON
RM RM
ON ON ON ON ON ON ON
RL RL
Priority: RL>RM>RH
ON ON ON ON ON ON ON ON
REX REX
Factory
Setting
Parameter Name Setting Remarks
Range
<EC version>
Multi-speed setting 60Hz
4 0 to 120Hz
(high speed) <50Hz>
Multi-speed setting
5 30Hz 0 to 120Hz
(middle speed)
Multi-speed setting
6 10Hz 0 to 120Hz
(low speed)
Multi-speed setting 0 to 120Hz, "- - -" = no setting. Setting
24 to 27 ---
(speeds 4 to 7) --- enabled when Pr. 30 = "1".
Multi-speed setting 0 to 120Hz, "- - -" = no setting. Setting
80 to 87 ---
(speeds 8 to 15) --- enabled when Pr. 30 = "1".
<Setting> 2
Set the running frequencies in the corresponding parameters.
Each speed (frequency) can be set as desired between 0 and 120Hz during inverter
operation.
When the parameter of any multi-speed setting is read, turn the setting dial to
change the setting.
In this case, press the SET key ( WRITE key) to store the frequency. (This is also
enabled in the external mode.)
The setting is reflected by pressing the SET key ( WRITE key).
Assign the terminals used for signals RH, RM, RL and REX using Pr. 60 to Pr. 63.(*)
61
REMARKS
* When terminal assignment is changed using Pr. 60 to Pr. 63, the other functions
may be affected. Check the functions of the corresponding terminals before
making setting.
The frequency-set external terminals have the following priority:
Jog > multi-speed operation > AU (terminal 4) > terminal 2
♦Related parameters♦
♦
Maximum, minimum frequency setting ⇒ Pr. 1 "maximum frequency", Pr. 2 "minimum
frequency" (refer to page 59)
Assignment of signals RH, RM, RL, REX to terminals ⇒ Pr. 60 to Pr. 63 (input terminal
function selection) (refer to page 88)
External operation mode setting ⇒ Pr. 79 "operation mode selection" (refer to page 98)
Computer link mode ⇒ Pr. 79 "operation mode selection" (refer to page 98), communication
parameter n10 "link start mode selection" (refer to page 131)
Speed command write ⇒ Communication parameter n9 "speed command write"
(refer to page 130)
62
60 120
Acceleration/
deceleration time (s)
5 5 12
15 15 35
2. If the Pr. 20 setting is changed, the settings of calibration functions Pr. 38 and
Pr. 39 (frequency setting signal gains) remain unchanged.
To adjust the gains, adjust calibration functions Pr. 38 and Pr. 39.
3. When the setting of Pr. 7, Pr. 8, Pr. 44 or Pr. 45 is "0", the acceleration/
deceleration time is 0.04 seconds.
4. If the acceleration/deceleration time is set to the shortest value, the actual motor
acceleration/deceleration time cannot be made shorter than the shortest
acceleration/deceleration time which is determined by the mechanical system's J
(inertia moment) and motor torque. 2
* When the RT signal is on, the other second functions (Pr. 44, Pr. 45, Pr. 46,
Pr. 47) are also selected.
♦Related parameters♦
♦
Base frequency setting ⇒ Pr. 3 "base frequency" (refer to page 59)
Acceleration/deceleration pattern, S-pattern acceleration/deceleration A
⇒ Pr. 29 "acceleration/deceleration pattern" (refer to page 71)
Calibration function ⇒ Pr. 38 "frequency setting voltage gain frequency", Pr. 39 "frequency
setting current gain frequency" (refer to page 74)
RT signal setting ⇒ Pr. 60 to Pr. 63 (input terminal function selection) (refer to page 88)
Jog acceleration/deceleration time ⇒ Pr. 16 "jog acceleration/deceleration time"
(refer to page 67)
63
♦Related parameters♦
♦
When constant-torque motor is used ⇒ Pr. 71 "applied motor" (refer to page 93)
By setting the DC
injection brake voltage
(torque), operation time
and operation starting
Pr.10
frequency, the stopping "Operation
accuracy of positioning frequency"
operation, etc. or the Time
Pr.12
timing of operating the DC injection "Operation
DC injection brake to brake voltage voltage"
stop the motor can be Time
adjusted according to the
Pr.11 "Operation time"
load.
64
CAUTION
Install a mechanical brake. No holding torque is provided.
60
be set in the range 0 to 60Hz.
Pr.13
0 Time
Frequency setting signal (V)
Foward rotation ON
Factory Setting
Parameter Name Remarks
Setting Range
13 Starting frequency 0.5Hz 0 to 60Hz Setting is enabled when Pr. 30 = "1".
CAUTION
The inverter will not start if the frequency setting signal is less than the value set in
Pr. 13 "starting frequency". 2
For example, when 5Hz is set in Pr. 13, the motor will not start running until the
frequency setting signal reaches 5Hz.
CAUTION
Note that when Pr. 13 is set to any value lower than Pr. 2 "minimum frequency",
simply turning on the start signal will run the motor at the preset frequency if the
command frequency is not input.
♦Related parameters♦
♦
Minimum frequency setting ⇒ Pr. 2 "minimum frequency" (refer to page 59)
65
voltage
voltage
voltage
Output
Output
Output
Output
rotation rotation
Factory Setting
Parameter Name Remarks
Setting Range
0: For constant-torque loads Setting is
Load pattern 0, 1, 2, 1: For variable-torque loads enabled
14 0
selection 3 2: For vertical lift loads when Pr. 30
3: For vertical lift loads = "1".
CAUTION
1. When automatic torque boost control is selected, this parameter setting is
ignored.
2. Pr. 46 "second torque boost" is made valid when the RT signal turns on.
The RT signal acts as the second function selection signal and makes the other
second functions valid.
♦Related parameters♦
♦
Automatic torque boost ⇒ Pr. 98 "automatic torque boost selection (motor capacity)" (refer to
page 109)
Boost setting ⇒ Pr. 0 "torque boost", Pr. 46 "second torque boost" (refer to page 58)
Assignment of RT signal to terminal when second torque boost is used
⇒ Pr. 60 to Pr. 63 (input terminal function selection) (refer to page 88)
66
Acceleration
Deceleration
Deceleration
Activated Operation Activated Operation
Constant
Constant
: Not not : Not not
speed
speed
activated continued activated continued
(*) (*)
0 16
1 17
2 18
3 19
4 20
5 21
6 22
7 23
8 24
9 25
10 26
11 27
12 28
13 29
14 30
15 31
Regenerative Driving
100
68
CAUTION
Always perform test operation.
Stall prevention operation performed during acceleration may increase the
acceleration time.
Stall prevention operation performed during constant speed may cause sudden
speed changes.
Stall prevention operation performed during deceleration may increase the
deceleration time, increasing the deceleration distance.
Factory
2
Setting
Parameter Name Setting Remarks
Range
<EC version>
Stall prevention operation
22 150% 0 to 200%
level
Setting is
Stall prevention operation
0 to - - -: Pr. 22 enabled
23 level compensation factor ---
200%, - - - equally when
at double speed
Pr. 30 = "1".
Stall prevention operation 60Hz 0 to
28
reduction starting frequency <50Hz> 120Hz
69
Pr.22 (Pr.22=150%,
Stall prevention
Stall prevention
Reduction ratio
Pr.23=100%, Pr.28=60Hz)
150
112.5
90
75
Pr.23
<Setting>
Generally, set 150% (factory setting) in Pr. 22 "stall prevention operation level".
Setting "0" in Pr. 22 disables stall prevention operation.
To reduce the stall prevention operation level in the high frequency range, set the
reduction starting frequency in Pr. 28 "stall prevention operation reduction starting
frequency" and the reduction ratio compensation factor in Pr. 23.
Calculation expression for stall prevention operation level
Pr. 22 - A Pr. 23 - 100
Stall prevention operation level (%) = A + B × [ ]×[ ]
Pr. 22-B 100
Pr. 28 (Hz) × Pr. 22 (%) Pr. 28 (Hz) × Pr. 22 (%)
where, A = ,B=
output frequency (Hz) 120Hz
By setting "- - -" (factory setting) in Pr. 23, the stall prevention operation level is
constant at the Pr. 22 setting up to 120Hz.
REMARKS
When the fast-response current limit is set in Pr. 21 "stall prevention function
selection" (factory setting), do not set any value above 170% in Pr. 22. The torque
will not be developed by doing so.
If the Pr. 22 value is set to higher than 170%, make setting in Pr. 21 to disable the
fast-response current limit.
In vertical lift applications, make setting so the fast-response current limit is not
cativated. Torque may not be produced, causing a gravity drop.
CAUTION
Do not set a small value as the stall prevention operation current.
Otherwise, torque generated will reduce.
Test operation must be performed.
Stall prevention operation during acceleration may increase the acceleration time.
Stall prevention operation during constant speed may change the speed suddenly.
Stall prevention operation during deceleration may increase the deceleration
time, increasing the deceleration distance.
70
frequency (Hz)
frequency (Hz)
f1
Output
Output
Output
fb
f2
<Setting>
Pr. 29
Function Description
Setting
Linear
Acceleration is made to the set frequency linearly.
0 acceleration/
(Factory setting)
deceleration
For machine tool spindle applications, etc.
Used when acceleration/deceleration must be made in a short
time to a high-speed region of not lower than the base frequency.
S-shaped
Acceleration/deceleration is made in a pattern where fb (base
1 acceleration/
frequency) acts as the inflection point of an S shape, and you can
deceleration A (*)
set the acceleration/deceleration time which matches the motor
torque reduction in the constant-output operation region of not
lower than the base frequency.
For conveyor and other load collapse prevention applications, etc.
S-shaped Since acceleration/deceleration is always made in an S shape
2 acceleration/ from f2 (current frequency) to f1 (target frequency), this function
deceleration B eases shock produced at acceleration/deceleration and is
effective for load collapse prevention, etc.
CAUTION 2
* As the acceleration/deceleration time, set the time taken to reach the Pr. 3 "base
frequency" value, not the Pr. 20 "acceleration/deceleration reference frequency"
value. For details, refer to page 59.
♦Related parameters♦
♦
Base frequency (acceleration/deceleration time setting) setting ⇒ Pr. 3 "base frequency"
(refer to page 59)
For setting of "1" (S-shaped acceleration/deceleration A)
⇒ Pr. 44 "second acceleration/deceleration time", Pr. 45 "second deceleration time" (refer to
page 62)
71
Factory Setting
Parameter Name Remarks
Setting Range
Extended function 0: Without display,
30 0 0, 1
display selection 1: With display
Factory
Parameter Name Setting Range Remarks
Setting
31 Frequency jump 1A --- 0 to 120Hz, - - -
32 Frequency jump 1B --- 0 to 120Hz, - - -
- - -: Function invalid
33 Frequency jump 2A --- 0 to 120Hz, - - -
Setting is enabled when
34 Frequency jump 2B --- 0 to 120Hz, - - -
Pr. 30 = "1"
35 Frequency jump 3A --- 0 to 120Hz, - - -
36 Frequency jump 3B --- 0 to 120Hz, - - -
<Setting>
To fix the frequency at 30Hz between Pr. 33 and Pr. 34 Pr.34:35Hz
Pr.33:30Hz
(30Hz and 35Hz), set 30Hz in Pr. 33 and 35Hz in Pr. 34.
To jump to 35Hz between 30 and 35Hz, set 35Hz in Pr.33:35Hz
Pr.34:30Hz
Pr. 33 and 30Hz in Pr. 34.
CAUTION
During acceleration/deceleration, the running frequency within the set area is valid.
REMARKS
Write inhibit error " " occurs if the frequency jump setting ranges overlap.
72
Factory Setting
Parameter Name Remarks
Setting Range
0: Output Setting is enabled
37 Speed display 0 0, 0.1 to 999
frequency when Pr. 30 = "1".
<Setting>
To display the machine speed, set in Pr. 37 the machine speed for 60Hz operation.
CAUTION
• The motor speed is converted from the output frequency and does not match the
actual speed.
• When you want to change the monitor (PU main display) of the operation panel,
refer to Pr. 52 "operation panel display data selection" and communication
parameter n16 "PU main display screen data selection".
• Since the operation panel indication is 3 digits, make a setting so that the monitor
value does not exceed "999". If the Pr. 1 value is higher than 60Hz and
Pr. 1 value × Pr. 37 value > 60Hz × 999
(write error) occurs when Pr. 1 or Pr. 37 is written.
REMARKS
When you set the speed in Pr. 37, the speed is monitored in the monitor frequency
setting mode.
At this time, setting can be made in the minimum setting increments of 0.01r/min.
Due to the restrictions on the resolution of the set frequency, the indication in the
second decimal place may differ from the setting.
CAUTION
Make sure that the running speed setting is correct.
Otherwise, the motor might run at extremely high speed, damaging the machine. 2
♦Related parameters♦
♦
To choose running speed monitor display ⇒ Pr. 52 "operation panel display data selection"
(refer to page 82)
FR-PU04 display switching ⇒ Communication parameter n16 "PU main display screen data
selection" (refer to page 134)
73
frequency (Hz)
( Pr.38 ) ( Pr.39 )
(Across (Across
Output
Output
terminals terminals
2-5) 4-5)
0Hz( C2 ) 0V 0Hz( C5 ) 4mA
5V or 10V 20mA
(0% C3 ) (100% C4 ) Pr.73 (20% C6 ) (100% C7 )
Frequency setting voltage signal Frequency setting current signal
Factory Setting Setting
Parameter Name Remarks
<EC version> Range
Frequency setting voltage gain 60Hz
38 1 to 120Hz
frequency <50Hz>
Frequency setting current gain 60Hz
39 1 to 120Hz
frequency <50Hz>
Frequency setting voltage bias
C2 (902) 0Hz 0 to 60Hz
frequency Setting is enabled
C3 (902) Frequency setting voltage bias 0% * 0 to 300% when Pr. 30 = "1".
C4 (903) Frequency setting voltage gain 96% * 0 to 300%
Frequency setting current bias
C5 (904) 0Hz 0 to 60Hz
frequency
C6 (904) Frequency setting current bias 20% * 0 to 300%
C7 (905) Frequency setting current gain 100% * 0 to 300%
* Settings may differ because of calibration parameters.
The parameter numbers within parentheses are those for use of the parameter unit (FR-PU04).
When the parameter unit (FR-PU04) is used, operation from the operation panel is not accepted.
POINT
Bias setting for 0-5VDC (0-10VDC) input Use calibration parameters C2, C3 for setting.
Gain setting for 0-5VDC (0-10VDC) input Use Pr. 38, calibration parameter C4 for
setting.
Bias setting for 4-20mADC input Use calibration parameters C5, C6 for
setting.
Gain setting for 4-20mADC input Use Pr. 39, calibration parameter C7 for
setting.
(For 4 to 20mADC input, set "4" in any of Pr. 60 to Pr. 63 (input terminal function
selection) and assign AU (current input selection) to any of terminals RH, RM, RL
and STR, and turn on the AU signal.)
74
REMARKS
For the way to change the output frequency setting of the frequency setting
potentiometer, refer to the instruction manual (basic).
77
REMARK
When a ground fault is detected with "1" set in Pr. 40, an approximate 20ms delay
occurs at every start.
♦Related parameters♦
♦
Assignment of SU signal to terminal ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 90)
78
frequency (Hz)
The output frequency detection
Forward Pr.42
signal (FU) is output when the rotation
output frequency reaches or Time
Output
exceeds the setting. This function Reverse
rotation Pr.43
can be used for electromagnetic
Output
brake operation, open signal, etc. signal ON ON
You can also set the detection of FU OFF OFF OFF
the frequency used exclusively for
reverse rotation.
This function is effective for switching the timing of electromagnetic brake
operation between forward rotation (rise) and reverse rotation (fall) during vertical
lift operation, etc.
Factory Setting
Parameter Name Remarks
Setting Range
Output frequency
42 6Hz 0 to 120Hz Setting is
detection
enabled
Output frequency
0 to 120Hz, - - -: Same as when Pr. 30
43 detection for reverse ---
--- Pr. 42 setting = "1".
rotation
<Setting>
Refer to the above chart and set the corresponding parameters.
When Pr. 43 "output frequency detection for reverse rotation" ≠ "- - -", the Pr.42
setting applies to forward rotation and the Pr.43 setting applies to reverse rotation.
Use Pr. 64 or Pr. 65 (output terminal function selection) to assign the terminal used
for FU signal output.
CAUTION
Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other functions.
Make setting after confirming the function of each terminal.
♦Related parameters♦
♦
Assignment of FU signal to terminal ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C 2
terminal function selection" (refer to page 90)
79
Output current
the output current detection signal Pr.48
(Y12) is output from the inverter's
open collector output terminal. Pr.49
Time
Factory Setting
Parameter Name Remarks
Setting Range
Output current detection
48 150% 0 to 200%
level Setting is enabled when
Output current detection Pr. 30 = "1"
49 0s 0 to 10s
signal delay time
<Setting>
Parameter
Description
Number
Set the output current detection level.
48
100% is the rated inverter current.
Set the output current detection time. Set the time from when the output
49 current has risen above the Pr. 48 setting until the output current detection
signal (Y12) is output.
CAUTION
• Once turned on because the current has risen above the preset detection level,
the output current detection signal is held on for at least 100ms (approximately).
• Using Pr. 64 or Pr. 65 to change terminal assignment may affect the other
functions. Make setting after confirming the function of each terminal.
♦Related parameters♦
♦
Assignment of Y12 signal to terminal ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page 90)
80
POINT
If the output is lower than the Pr.50 setting for longer than the time set in Pr. 51
during inverter operation, the zero current detection (Y13) signal is output from the
inverter's open collector output terminal.
<Setting>
Parameter Description
Set the zero current detection level.
50 Set the level of zero current detection in terms of the percentage of the rated
inverter current from the output current value of 0 [A].
Set the zero current detection time.
51 Set a period of time from when the output current falls to or below the Pr. 50
setting to when the zero current detection signal (Y13) is output.
CAUTION
• If the current falls below the preset detection level but the timing condition is not
satisfied, the zero current detection signal is held on for about 100ms.
• When the terminal functions are changed using Pr. 64, Pr. 65, the other functions 2
may be affected. Confirm the functions of the corresponding terminals before
making settings.
• When one inverter is used to run (connect) multiple motors sequentially, the zero
current detection signal (Y13) may be output. Set 13% or more for the 0.1K, and
8% or more for the 0.2K. (If the sum of motor capacities is less than the zero
current detection level current or if the motor capacity per motor is less than the
zero current detection level current)
♦Related parameters♦
♦
Assignment of Y13 signal to terminal ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B, C
terminal function selection" (refer to page90)
81
You can also use the SET key to change the display. (Refer to the instruction
manual (basic) for the operation procedure.)
The pulse train output terminal FM (analog voltage output terminal AM) is
available for signal output. (Make selection using the Pr. 54 "FM (AM) terminal
function selection" value.)
<Setting>
Parameter Setting
Pr. 52 Pr. 54 Full-Scale Value of FM
Signal Type Unit
Operation panel FM (AM) (AM) Level Meter
LED terminal
Output Pr. 55 "frequency monitoring
Hz 0/100 0
frequency reference"
Pr. 56 "current monitoring
Output current A 1 1
reference"
When "100" is set in Pr. 52, the monitor value changes depending on whether the
inverter is during stop or running.
Pr. 52
0 100
During running/stop During stop During running
Output frequency Output frequency Set frequency Output frequency
REMARKS
• During an error, its definition appears.
• During reset, the values displayed are the same as during a stop.
• For selection of the parameter unit (FR-PU04) monitor display, refer to the
communication parameter n16 "PU main display screen data selection". (Page 134)
CAUTION
The unit displayed on the operation panel is only A and other units are not displayed.
♦Related parameters♦
♦
Speed display ⇒ Pr. 37 "speed display" (refer to page 73)
Adjustment of FM (AM) level meter full-scale value ⇒ Calibration parameter C1 "FM (AM)
terminal calibration" (refer to page 111)
Monitoring reference ⇒ Pr. 55 "frequency monitoring reference", Pr. 56 "current monitoring
reference" (refer to page 84)
82
Factory Setting
Parameter Name Remarks
Setting Range
0: Setting dial
frequency setting
Setting is
Frequency setting mode
53 0 0, 1 enabled when
operation selection 1: Setting dial
Pr. 30 = "1"
potentiometer
mode
POINT
Set "1" (extended function parameter valid) in Pr. 30 "extended function display
selection".
Set "1" (setting dial potentiometer mode) in Pr. 53 "frequency setting operation
selection".
Operation example Changing the frequency from 0Hz to 60Hz during operation
Operation Display
RUN
1. Mode/monitor check PU
REMARKS
• If flickering "60.0" turns to "0.0", the Pr. 53 "frequency setting operation selection"
setting may not be "1".
• Independently of whether the inverter is running or at a stop, the frequency can
be set by merely turning the dial.
• When the frequency is changed, it will be stored as the set frequency often 10 seconds.
Refer to (page 82).
83
Output or display
Output or display
referenced when the
output frequency or
output current is selected
for the FM (AM) terminal.
• The Japanese Output Output
Pr.55 Pr.56
version has the FM frequency frequency
terminal feature, and
the NA and EC
versions have the AM
terminal feature.
Factory
Setting
Parameter Name Setting Remarks
Range
<EC version>
Frequency monitoring 60Hz
55 0 to 120Hz
reference <50Hz> Setting is enabled
Current monitoring Rated output when Pr. 30 = "1"
56 0 to 50A
reference current
<Setting>
Refer to the above diagrams and set the frequency monitoring reference value in
Pr. 55 and the current monitoring reference value in Pr. 56.
Pr. 55 is set when Pr. 54 "FM (AM) terminal function selection" = "0" and Pr. 56 is set
when Pr. 54 = "1".
Set the Pr. 55 and Pr. 56 values so that the output pulse train output of terminal FM is
1440 pulses/s (the output voltage of terminal AM is 5V).
CAUTION
• The maximum pulse train output of terminal FM is 2400pulses/s. If Pr. 55 is not
adjusted, the output of terminal FM will be filled to capacity. Therefore, adjust Pr. 55.
• The maximum output voltage of terminal AM is 5VDC.
Factory Setting
Parameter Name Remarks
Setting Range
Restart 0 to 5s,
57 ---
coasting time ---
Setting is enabled when Pr. 30 = "1"
Restart cushion
58 1s 0 to 60s
time
84
CAUTION 2
When automatic restart after instantaneous power failure has been selected,
the motor and machine will start suddenly (after the restart coasting time has
elapsed) after occurrence of an instantaneous power failure. Stay away from
the motor and machine.
When you have selected automatic restart after instantaneous power failure,
apply in easily visible places the CAUTION seals supplied to the instruction
manual (basic).
The motor is coasted to a stop as soon as you turn off the start signal or press
STOP
the RESET key during the restart cushion time after instantaneous power failure.
85
ON ON
Acceleration(RH) ON
ON
Deceleration(RM)
Clear(RL) ON
Forward rotation ON ON ON ON
(STF)
Power supply ON ON
REMARKS
• When the remote function is used, the output frequency of the inverter can be
compensated for as follows:
External operation mode Frequency set by RH/RM operation plus external
analog frequency command
PU operation mode Frequency set by RH/RM operation plus setting dial
or PU digital preset frequency
<Operation panel operation procedure>
Monitor, frequency Turn setting dial to Press SET key to
setting mode MODE make correction. complete setting.*
* When you have set "1" in Pr. 53 "frequency setting operation selection", you
need not press the SET key.
86
Use Pr. 59 to select whether the remote setting function is used or not and whether
the frequency setting storage function* in the remote setting mode is used or not.
When "remote setting function - yes" is selected, the functions of terminals RH, RM
and RL are changed to acceleration (RH), deceleration (RM) and clear (RL).
Use Pr. 60 to Pr. 62 (input terminal function selection) to set the signals RH, RM, RL.
* Frequency setting storage function
The remote setting frequency (frequency set by RH/RM operation) is stored in
memory.
When power is switched off once and then on again, the inverter resumes
running at this setting of output frequency. (Pr. 59="1")
REMARKS
A restart (STF signal ON) after ON-OFF of the clear signal (RL) should be made
after more than 1 minute has elapsed. The output frequency provided when a
restart is made within 1 minute is the output frequency given after the clear signal
(RL) is turned off (multi-speed frequency).
frequency(Hz)
(*2)
(*1)
2
Output
Acceleration (RH) ON ON
Clear (RL) ON ON
Forward rotation ON ON
ON ON
(STF)
ON ON
Power supply
1 minute or less More than 1 minute
(*1) External operation frequency or PU operation frequency except multi-speed
(*2) Multi-speed frequency
87
CAUTION
When selecting this function, re-set the maximum frequency according to the
machine.
♦Related parameters♦
♦
Maximum frequency setting ⇒ Pr. 1 "maximum frequency" (refer to page 59)
Output frequency acceleration/deceleration time ⇒ Pr. 7 "acceleration time",
Pr. 8 "deceleration time" (refer to page 62)
Time setting for acceleration/deceleration ⇒ Pr. 44 "second acceleration/deceleration time",
Pr. 45 "second deceleration time"
(refer to page 62)
88
REMARKS
• One function can be assigned to two or more terminals. In this case, the function
is activated when one of the multiple terminals used for assignment turns on.
• The speed command priorities are higher in order of jog, multi-speed setting (RH,
RM, RL, REX) and AU.
• Use common terminals to assign multi-speeds (7 speeds) and remote setting.
They cannot be set individually.
(Common terminals are used since these functions are designed for speed
setting and need not be set at the same time.)
89
RUN terminal
64 function 0
selection
0, 1, 3, 4,
11 to 16, Setting is enabled when Pr. 30 = "1"
98, 99
A, B, C
terminal
65 99
function
selection
<Setting>
Signal Parameters
Setting Function Operation
Name Referred to
Output during operation when the
0 RUN Inverter running inverter output frequency rises to or Pr. 2, Pr.13
above the starting frequency.
Output when the output frequency is
1 SU Up to frequency Pr. 41
reached.
Output while stall prevention function Pr. 21, Pr. 22,
3 OL Overload alarm
is activated. Pr. 23, Pr. 28
Output frequency Output when the output frequency
4 FU Pr. 42, Pr. 43
detection rises to or above the setting.
Output when the inverter is ready to
Inverter operation
11 RY be started by switching the start —
ready
signal on.
Output current Output when the output current rises
12 Y12 Pr. 48, Pr. 49
detection to or above the setting.
Zero current Output when the output current
13 Y13 Pr. 50, Pr. 51
detection reaches 0.
14 FDN PID lower limit
15 FUP PID upper limit Outputs the detection signal under
Pr. 88 to Pr. 94
PID forward-reverse PID control.
16 RL
rotation output
Output when a minor fault (fan failure
98 LF Minor fault output or communication error warning) Pr. 76, Pr. n5
occurs.
Output when the inverter's protective
99 ABC Alarm output function is activated to stop the output —
(major fault).
REMARKS
The same function may be set to more than one terminal.
90
Factory Setting
Parameter Name Remarks
Setting Range
66 Retry selection 0 0 to 3
Number of 0, 1 to
67 retries at alarm 0 10, 101
occurrence to 110
Setting is enabled when Pr. 30 = "1"
Retry waiting 0.1 to
68 1s
time 360s
Retry count
69 0 0
display erase
<Setting>
Use Pr. 66 to choose the protective functions (major failures) for retries.
Protective Functions (Major Failures) for Retries
Pr. 66 Setting
OCT OVT THM THT FIN GF OHT OLT PE PUE RET CPU OPT
0
1
2
3
* Indicates the retry items selected. (OCT denotes any of OC1 to OC3 and OVT
any of OV1 to OV3.)
91
CAUTION
When you have selected the retry function, stay away from the motor and
machine unless required. They will start suddenly (after the reset time has
elapsed) after occurrence of an alarm.
When you have selected the retry function, apply in easily visible places the
CAUTION seals supplied to the instruction manual (basic).
<Setting>
Refer to the following list and set this parameter according to the motor used.
Pr. 71 Setting Electronic Overcurrent Protection Thermal Characteristic
0 Thermal characteristics matching a standard motor
1 Thermal characteristics matching the Mitsubishi constant-torque motor
CAUTION
Set this parameter correctly according to the motor used.
Incorrect setting may cause the motor to overheat and burn.
93
REMARKS
Increase the filter time constant if steady operation cannot be performed due to
noise. A larger setting results in slower response. (The time constant can be set
between approximately 1ms to 1s with the setting of 0 to 8. A larger setting results
in a larger filter time constant.)
Factory Setting
Parameter Name Remarks
Setting Range
Reset selection/ 0, 1,
75 14 Setting is enabled when Pr. 30 = "1"
PU stop selection 14, 15
<Setting>
Pr. 75
Reset Selection PU Stop Selection
Setting
STOP
0 Reset input normally enabled. The PU stop key is invalid. Note that the RESET
Enabled only when the protective key is valid only in the PU operation mode or
1
function is activated. combined operation mode (Pr. 79 = "4").
STOP
14 Reset input normally enabled. Pressing the RESET key decelerates the
Enabled only when the protective inverter to a stop in any of the PU, external and
15
function is activated. communication operation modes.
94
Speed
a stop, switch off the STF or STR
signal.
PU PU
Time
2) Press the EXT key to EXT key
Control panel
PU STOP
key
show . ........ ( canceled) STF ON RESET
PU EXT (STR) OFF
3) Press the key to return to
EXT .
4) Switch on the STF or STR signal. Stop and restart example for external operation
REMARKS
• By entering the reset signal (RES) during operation, the inverter shuts off its
output while it is reset, the internal thermal summation value of the electronic
overcurrent protection and the number of retries are reset, and the motor coasts.
• The Pr. 75 value can be set any time. Also, if parameter (all) clear is executed,
this setting will not return to the initial value.
• When the inverter is stopped by the PU stop function, the display alternates
between and . An alarm is not output.
STOP
(2) How to make a restart when a stop is made by the RESET key
input from the PU
1) After completion of deceleration
Speed
95
REMARKS
In either of the following cases, fan operation is regarded as faulty, is shown on
the control panel, and the minor fault (LF) signal is output. Use any of Pr. 64, Pr. 65
(output terminal function selection) to allocate the terminal used to output the LF
signal.
Pr. 76 = "0"
When the fan comes to a stop with power on.
Pr. 76 = "1"
When the inverter is running and the fan stops during fan ON command or the fan
starts during fan OFF command.
CAUTION
When the terminal assignment is changed using Pr. 64, Pr. 65, the other functions
may be affected. Confirm the functions of the corresponding terminals before
making settings.
96
Factory Setting
Parameter Name Remarks
Setting Range
Parameter
77 write disable 0 0, 1, 2 Setting is enabled when Pr. 30 = "1"
selection
<Setting>
Pr. 77 Setting Function
Parameter values may only be written during a stop in the PU operation
0
mode. (*)
Write disabled.
1
Values of Pr. 22, Pr. 30, Pr. 75, Pr. 77 and Pr. 79 can be written.
Write can be performed during operation. Write can be performed
2
independently of the operation mode.
CAUTION
• * The parameters * screened in the parameter list can be set at any time. Note
that the Pr. 70 and Pr. 72 values may be changed during PU operation only.
• If Pr. 77 = 2, the values of Pr. 17, Pr. 23, Pr. 28, Pr. 60 to Pr. 63, Pr. 71, Pr. 79,
Pr. 98, Pr. 99, CLr cannot be written during operation. Stop operation when
changing their parameter settings.
• By setting "1" in Pr. 77, the following clear operations can be inhibited:
Parameter clear
All clear
2
97
POINT
Used for a machine which runs only in one direction, e.g. fan, pump.
(The setting of this function is valid for the combined, PU, external and
communication operations.)
Factory Setting
Parameter Name Remarks
Setting Range
Reverse rotation
78 prevention 0 0, 1, 2 Setting is enabled when Pr. 30 = "1"
selection
<Setting>
Pr. 78 Setting Function
0 Both forward and reverse rotations allowed
1 Reverse rotation disallowed
2 Forward rotation disallowed
98
REMARKS
Either "3" or "4" may be set to select the PU/external combined operation. These
settings differ in starting method.
In case of the type having the RS-485 communication function, refer to page 116 for
the computer link operation mode.
*1. When the FR-PU04 is connected, the LED indication (PU, EXT) is not lit.
*2. The LED indication (PU, EXT) flickers in the computer link operation mode.
*3. Lit when the operation panel is used. Extinguished when the FR-PU04 is used.
99
1) Preparation
Set "7" in Pr. 79 (operation mode selection).
Set the terminal used for MRS signal input with any of Pr. 60 to Pr. 63 (input terminal
function selection).
Refer to page 88 for Pr. 60 to Pr. 63 (input terminal function selection).
REMARKS
When terminal assignment is changed using Pr. 60 to Pr. 63, the other functions
may be affected.
Check the functions of the corresponding terminals before making settings.
2) Function
MRS Signal Function/Operation
Output stopped during external operation.
Operation mode can be switched to PU operation mode.
ON
Parameter values can be rewritten in PU operation mode.
PU operation allowed.
Forcibly switched to external operation mode.
OFF External operation allowed.
Switching to PU operation mode inhibited.
100
REMARKS
When terminal assignment is changed using Pr. 60 to Pr. 63, the other functions
may be affected.
Check the functions of the corresponding terminals before making settings.
For details refer to page 88.
2) Function
This switching is enabled during an inverter stop only and cannot be achieved
during operation.
X16 Signal Operation Mode
ON External operation mode (cannot be changed to the PU operation mode)
OFF PU operation mode (cannot be changed to the external operation mode)
to Refer to to (page 61).
POINT
Made valid by turning on the X14 signal. Use Pr. 60 to Pr. 63 (input terminal
function selection) to make assignment.
101
<Setting>
(1) Basic PID control configuration
Inverter circuit :
Motor
Pr. 93 or Treminal 2 PID operation Manipulated
+- 1 variable IM
Set point Kp 1+ Ti S +Td S
Terminal 4
Feedback signal (Process value)
Kp: Proportion constant Ti: Integral time S: Operator Td: Differential time
REMARKS I action
Time
PI action is the sum of P and I actions.
PI action
Time
102
REMARKS
I action
The PID action is the sum of P, I and D Time
actions. D action
Time
y=at 2 +bt+c
PID action
Time
4) Reverse action [Heating]
Increases the manipulated + X>0
Set point
variable (output frequency) if X<0
-
deviation X = (set point - Feedback signal
process value) is positive, (Process value)
and decreases the Set point 2
Deviation
manipulated variable if
deviation is negative. Cold up
Hot down
Process value
103
Deviation
A
(24V)
(Set point setting) 5
C Forward (reverse)
4 rotation output
signal common
(Process value) 4 to 20mA
0 24V
DC
power supply (*1)
AC1
200/220V 50/60Hz
CAUTION
*1. The power supply must be selected in accordance with the power specifications
of the detector used.
*2. The output signal terminals used depends on the Pr. 64, Pr. 65 settings.
*3. The input signal terminal used depends on the setting of Pr. 60 to Pr. 63.
• The contact input signal (AU Signal) need not be turned on.
104
105
Parameter setting Adjust the PID control parameters, Pr. 88 to Pr. 94.
Run
106
No
Adjust parameters. Optimize parameters.
2
Set the proportional band and While the process value is steady,
integral time to slightly higher values the proportional band and integral
and set the differential time to a time may be reduced and the
slightly lower value to stabilize the differential time increased
process value. throughout the operation.
END
*When calibration Use Pr. 38 and calibration parameters C2 to C4 (terminal 2)
is required and Pr. 39 and calibration parameters C5 to C7 (terminal 4) to
calibrate the detector output and set point setting input.
Make calibration in the PU mode when the inverter is at a stop.
107
0 0 0
0 5 (V) 0 4 20 (mA) 0 100 Deviation (%)
REMARKS
• If the multi-speed (RH, RM, RL) signal or jog operation (jog) signal is entered,
PID control is stopped and multi-speed or jog operation is started.
• When the terminal functions are changed using Pr. 60 to Pr. 65, the other
functions may be affected. Confirm the functions of the corresponding terminals
before making settings.
• When PID control is selected, the minimum frequency is the frequency set in the
calibration parameter C2 and the maximum frequency is the frequency set in
Pr. 38. (The Pr. 1 "maximum frequency" and Pr. 2 "minimum frequency" settings
are also valid.)
♦Related parameters♦
♦
X14 signal assignment ⇒ Pr. 60 to Pr. 63 (input terminal function selection) (refer to page 88)
FUP, FDN and RL signal assignment ⇒ Pr. 64 "RUN terminal function selection", Pr. 65 "A, B,
C terminal function selection" (refer to page 90)
Voltage input selection (0 to ±5V, 0 to ±10V) ⇒ Pr. 73 "0-5V/0-10V selection" (refer to page 93)
Operation mode selection ⇒ Pr. 79 "operation mode selection" (refer to page 98)
Making terminal calibration ⇒ Pr. 38, Pr. 39, C2 to C7 (calibration parameters) (refer to page 74)
108
<Setting>
Synchronous speed at base frequency - rated speed
Rated slip = ×100[%]
Synchronous speed at base frequency
Parameter Setting Function
0.01 to 50% Used to set the rated motor slip.
95
0, - - - Slip compensation is not made.
96 0.01 to 10s Used to set the slip compensation response time. (*)
Slip compensation is not made in the constant output
0
97 range (frequency range above the frequency set in Pr. 3).
--- Slip compensation is made in the constant output range.
* When this value is made smaller, response will be faster.
However, as load inertia is greater, a regenerative overvoltage (OVT) error is
more liable to occur.
REMARKS
When making slip compensation at 60Hz<50Hz>, set the maximum frequency to
slightly higher than 60Hz<50Hz>.
In the factory setting status, it is clamped at 60Hz<50Hz>.
109
<Setting>
Parameter Setting Description
--- Ordinary V/F control and torque boost (Pr. 0, Pr. 46) are valid.
98 0.1 to 3.7kW Automatic torque boost control valid
(*) (Set the applied motor capacity or one rank lower motor capacity.)
* The setting range changes with the inverter: 0.2kW to 3.7kW, - - - for the 400V
class.
Also when the Pr. 98 setting is other than "- - -", Pr. 3 "base frequency" and Pr. 19
"base frequency voltage" are valid.
When "- - -" or "888" is set in Pr. 19, the rated output voltage is selected.
CAUTION
* During operation using automatic torque boost, write to Pr. 3 and Pr. 19 is disabled
if "2" is set in Pr. 77.
♦Related parameters♦
♦
Torque boost ⇒ Pr. 0 "torque boost", Pr. 46 "second torque boost" (refer to page 58)
Base frequency ⇒ Pr. 3 "base frequency", Pr. 19 "base frequency voltage" (refer to page 59)
Applied motor setting ⇒ Pr. 71 "applied motor" (refer to page 93)
Motor primary resistance ⇒ Pr. 99 "motor primary resistance" (refer to page 111)
110
Factory Setting
Parameter Name Remarks
Setting Range
Motor primary 0 to 50Ω,
99 --- Setting is enabled when Pr. 30 = "1"
resistance ---
♦Related parameters♦
♦
Applied motor setting ⇒ Pr. 71 "applied motor" (refer to page 93)
Automatic torque boost selection ⇒ Pr. 98 "automatic torque boost selection (motor capacity)"
(refer to page 109)
111
RUN
6. If the inverter is at a stop, press the RUN PU
RUN key to start it. (The motor EXT
Setting is complete.
Flicker ... Parameter setting complete!!
By turning the setting dial , you can read another parameter.
Press the SET key to return to the indication (step 3).
Press the SET key twice to show the next parameter ( ).
112
POINT
By setting the Pr. 54 "FM terminal function selection" value, preset Pr. 55 "frequency
monitoring reference" or Pr. 56 "current monitoring reference" to the running
frequency or current value at which the output signal is 1440 pulses/s.
At 1440 pulses/s, the meter generally deflects to full-scale.
113
RUN
7. Press the RUN key to start the RUN PU
inverter. (The motor need not be EXT
connected.)
+
8. Turn the setting dial to
Analog indicator
adjust the indicator needle
to the desired position. -
Setting is complete.
Flicker ... Parameter setting complete!!
By turning the setting dial , you can read another parameter.
Press the SET key to return to the indication (step 4).
Press the SET key twice to show the next parameter ( ).
REMARKS
• Depending on the set value, it may take some for the needle to move.
• If "1" is set in Pr. 30 "extended function display selection", the calibration parameter
C1 "AM terminal calibration" can also be set in the external operation mode.
• When the FR-PU04 is used, make calibration with Pr. 901.
114
115
F
(Switching must
not be made)
Symbol Switching Type Switching Method
PU
A PU operation to external Using the EXT key of the operation panel or
operation PU EXT
/ key of the parameter unit (FR-PU04)
PU
B External operation to PU Using the EXT key of the operation panel or
operation PU EXT
/ key of the parameter unit (FR-PU04)
External operation to Using the H0000:
C Communication
computer link operation computer program Read (H7B)/
operation
Computer link operation to Using the Write (HFB)
D H0001: External
external operation computer program operation
Switching must not be made
E PU operation to computer (External operation may be selected at A and then
link operation switched to computer link operation at C *)
Switching must not be made
F Computer link operation to (External operation may be selected at D and then
PU operation switched to PU operation at B *)
* When "1" is set in the communication parameter n10 "link start mode selection",
the inverter is placed in the computer link operation mode at power-on or inverter
reset. (Note that it is overridden by the Pr. 79 "operation mode selection" setting.)
REMARKS
Unlike the other inverters, the FR-S500 series is not the type of inverter whose
operation panel is removed to make communication.
When the setup software is used to switch to the PU operation mode (Pr. 79 = 1, 3,
4), parameter setting cannot be made. At that time, pressing the RUN key of the
operation panel starts the inverter.
116
POINT
To make RS-485 communication between the inverter and personal computer, the
operation mode must be set to the "computer link operation mode".
Pr. 79 "operation mode selection" ≠‚ "1, 3, 4"
and communication parameter n10 "link start mode selection" = "1"
Reset the inverter after setting the communication parameters n1, n2, n3, n4, n7,
n11. The values set are registered once the inverter is reset.
117
Communication-related parameters
Factory
Setting Setting Reflection
Parameter Name Remarks
<NA, EC Range Timing
version>
Communication
n1 (331) 0 0 to 31 After reset
station number
Communication 48, 96,
n2 (332) 192 After reset
speed 192
0, 1, 10,
n3 (333) Stop bit length 1 After reset
11
Parity check
n4 (334) presence/ 2 0, 1, 2 After reset
absence Setting is enabled
Number of when Pr. 30 = "1"
0 to 10,
n5 (335) communication 1 Immediately
---
retries
Communication 0s 0, 0.1 to
n6 (336) check time <- - -> 999s, Immediately
interval (*1) (*2) ---
Wait time 0 to 150ms,
n7 (337) --- After reset
setting ---
n11 (341) CR/LF selection 1 0, 1, 2 After reset
*1. To make communication, set any value other than 0 in the communication
parameter n6 "communication check time interval".
*2. Factory setting of NA and EC versions.
The parameter numbers within parentheses are those for use of the parameter unit
(FR-PU04).
Refer to page 177 for the instruction codes.
Communication specifications
Item Computer
Conforming standard RS-485 Standard
Number of inverters
1:N (max. 32 inverters)
connected
Communication speed Selected between 19200, 9600 and 4800bps
Control protocol Asynchronous
Communication method Half-duplex
Communication
118
119
REMARKS
*1. If a data error is detected and a retry must be made, execute retry operation
with the user program. The inverter comes to an alarm stop if the number of
consecutive retries exceeds the parameter setting.
*2. On receipt of a data error occurrence, the inverter returns "reply data 3)" to the
computer again. The inverter comes to an alarm stop if the number of
consecutive data errors reaches or exceeds the parameter setting.
Inverter
time *5
*3 Inverter
time *5
Format B
Instruction
station code Sum *4
ENQ number check
1 2 3 4 5 6 7 8 9 Number of characters
2) Reply data from inverter to computer during data write
[No data error detected] [Data error detected]
*3 Inverter Inverter
*3 station Error
Format C station *4 Format D *4
ACK number NAK number code
Number Number
1 2 3 4 of 1 2 3 4 5 of
characters characters
3) Reply data from inverter to computer during data read
[No data error detected] [Data error detected] 2
REMARKS
• The inverter station numbers may be set between H00 and H1F (stations 0 and
31) in hexadecimal.
• *3 indicates the control code.
• *4 indicates the CR or LF code.
When data is transmitted from the computer to the inverter, codes CR (carriage
return) and LF (line feed) are automatically set at the end of a data group on
some computers. In this case, setting must also be made on the inverter
according to the computer.
Also, the presence and absence of the CR and LF codes can be selected using n11.
• At *5, when communication parameter n7 "waiting time setting" ≠ - - -, create the
communication request data without "waiting time" in the data format.
(The number of characters is decremented by 1.)
122
Computer
REMARKS
When communication parameter n7 "waiting time setting" ≠‚ "- - -", create the
communication request data without "waiting time" in the data format. (The number
of characters is decremented by 1.)
6) Response time
Data sending time
(refer to the following calculation expression)
123
Instruction
number
E
Station
Sum
Waiting
code
time
(Example 1) N Data check
Computer Inverter Q code
0 1 E 1 1 0 7 A D F 4 Binary code
ASCII code H05 H30 H31 H45 H31 H31 H30 H37 H41 H44 H46 H34
H H H H H H H H H
30 + 31 + 45 + 31 + 31 + 30 + 37 + 41 + 44
H
= 1F4
Sum
number
S E Sum
Station
H H H H H H
30 + 31 + 31 + 37 + 37 + 30
H
= 130
Sum
8) Error code
If any error is found in the data received by the inverter, its definition is sent back to
the computer together with the NAK code. (Refer to page 128.)
REMARKS
1. When the data from the computer has an error, the inverter will not accept that
data.
2. Any data communication, e.g. run command, monitoring, is started when the
computer gives a communication request. Without the computer's command, the
inverter does not return any data. For monitoring, therefore, design the program
to cause the computer to provide a data read request as required.
3. When accessing the parameter settings, data for link parameter expansion
setting differs between the parameters as indicated below:
Instruction
Data
Code
H00: Pr. 0 to Pr. 99 can be accessed.
Read H7F H01: Calibration parameters C1 to C7 (Pr. 900 to
Link Pr. 905) and communication parameter n13
parameter (Pr. 145) can be accessed.
expansion H03: Communication parameters n1 to n12
setting Write HFF (Pr. 331 to Pr. 342) can be accessed.
H09: Communication parameters n14 to n17
(Pr. 990 to Pr. 993) can be accessed.
124
125
126
127
129
4 — Either — Either
(AU)
Selection function
Start self-holding
5 — — External External
selection (STOP)
6 Output stop (MRS) Either Either External External Pr. 79 ≠ "7"
External thermal relay
7 External External External External
input (OH)
15-speed selection
8 Computer External Computer External Pr. 59 = "0"
(REX)
Jog operation selection
9 — — External External
(JOG)
10 Reset (RES) Either Either Either Either
PID control valid
14 Computer External Computer External
terminal (X14)
PU-external operation
16 External External External External
switch-over (X16)
Reverse rotation
--- Computer Computer External External
command (STR)
130
[Explanation of table]
External : Operation is valid only from external terminal signal.
Computer : Operation is valid only from sequence program.
Either : Operation is valid from either of external terminal and computer.
— : Operation is invalid from either of external terminal and computer.
CAUTION
When Pr. 79 "operation mode selection" is set to "7" (PU operation interlock function),
only the external terminal is made valid independently of the n8 and n9 settings
because the MRS terminal is shared.
Factory Setting 2
Parameter Name Remarks
Setting Range
Link start mode
n10 (340) 0 0, 1 Setting is enabled when Pr. 30 = "1"
selection
The parameter number in parentheses is the one for use of the parameter unit (FR-PU04).
131
CAUTION
When the parameter unit (FR-PU04) is used, operation from the operation panel is
STOP
not accepted. (The stop key ( RESET key) is valid)
Factory
Setting Setting
Parameter Name Remarks
<NA, EC Range
version>
0
n13 (145) PU display language 0 to 7 Setting is enabled when Pr. 30 = "1"
<1>
The parameter number in parentheses is the one for use of the parameter unit (FR-PU04).
<Setting>
n13 Setting Display Language
0 Japanese
1 English
2 German
3 French
4 Spanish
5 Italian
6 Swedish
7 Finish
Factory Setting
Parameter Name Remarks
Setting Range
0: Without sound
PU buzzer sound
n14 (990) 1 0, 1 1: With sound (factory setting)
control
Setting is enabled when Pr. 30 = "1"
The parameter number in parentheses is the one for use of the parameter unit (FR-PU04).
133
<Setting>
When you set 100 in n16, the monitor value changes depending on whether the
inverter is at a stop or running.
n16
0 100
During operation/stop During stop During operation
Output frequency Output frequency Set frequency Output frequency
Output current Output current
Alarm display Alarm display
REMARKS
During an error, the output frequency at error occurrence appears.
During MRS, the values displayed are the same as during a stop.
♦Related parameters♦
♦
Speed display ⇒ Pr. 37 "speed display" (refer to page 73)
134
Factory Setting
Parameter Name Remarks
Setting Range
PU disconnection Setting is enabled when
n17 (993) 0 0, 1, 10
detection/PU setting lock Pr. 30 = "1"
<Setting>
n17 Setting PU Disconnection Detection PU Setting Lock
Operation is continued as-is if the PU is
0
disconnected (without PU disconnection detection)
PU operation valid
Inverter output is shut off when the PU is
1
disconnected (with PU disconnection detection)
Operation is continued as-is if the PU is
10 PU operation invalid*
disconnected (without PU disconnection detection)
STOP
* The monitor display and RESET key are valid.
REMARKS
When RS-485 communication operation is performed through the RS-485
connector, the reset selection/PU stop selection function is valid but the PU 2
disconnection detection function is invalid.
CAUTION
Do not reset the inverter while the start signal is being input.
Doing so will cause the inverter to start immediately after a reset, leading to
hazardous conditions.
135
Chapter 1
Chapter 2
Chapter33
Chapter 4
136
137
138
139
140
141
142
143
144
A M
0
B N
1
C O
2
D o
3
E P
4
F S
5
G T
6
H U
7
I V
8
J r
9
L -
146
148
149
500VDC
megger
Earth terminal
Periodic*
Inspection
Daily
Item
condensing.
Check for Visual and No fault.
unusual auditory checks.
Overall unit
vibration and
noise.
3
Measure voltage Within Meter, digital
across inverter permissible AC multimeter
Power Check that main
terminals R-S-T (DC) voltage
supply circuit voltage is
fluctuation
voltage normal.
(Refer to page
161)
150
Periodic*
Inspection
Daily
Description Method Criterion Instrument
2 years
1 year
Item
terminal). S, T, U, V, W
General
(2) Check for and ground
loose screws terminal with
and bolts. megger.
(3) Check for (2) Retighten.
overheat on (3) Visual check.
each part.
(4) Clean.
(1) Check (1), (2) Visual (1), (2) No fault.
conductors check.
Conductors, for distortion.
cables (2) Check cable
sheaths for
breakage.
Terminal Check for
Visual check No fault
block damage.
Disconnect
cables from
inverter and
Inverter Check measure across
module resistance terminals R, S, Refer to page Analog
Converter across T↔P, N, and 153. meter
module terminals. across U, V,
W↔P, N with a
Main circuit
meter with a
100Ω range.
(1) Check for (1), (2) Visual (1), (2) No fault. Capacity
liquid check. (3) 85% or meter
leakage. (3) Measure with more of
(2) Check for capacity rated
Smoothing safety valve meter. capacity.
capacitor projection
and bulge.
(3) Measure
electrostatic
capacity.
(1) Check for (1) Auditory (1) No fault.
chatter check. (2) No fault.
during (2) Visual check.
operation.
Relay
(2) Check for
rough
surface on
contacts.
151
Periodic*
Inspection
Daily
Description Method Criterion Instrument
2 years
1 year
Item
panel.
(2) Clean. (2) Clean with
rag.
Check that Must satisfy Voltmeter,
reading is Check reading of specified and
Meter ammeter,
normal. meters on panel. management
values. etc.
(1) Check for (1) Auditory, (1), (2) No fault.
unusual sensory,
vibration visual
and noise. checks.
General (2) Check for (2) Check for
unusual unusual odor
odor. due to
Motor
overheat,
damage, etc.
(1) Check with (1) Disconnect 5MΩ or more. 500V
3
megger cables from megger
Insulation (across U, V, W
resistance terminals (including
and ground motor cables).
terminal).
Note: The value for the 400V class is indicated in the parentheses.
* For periodic inspection, contact you nearest Mitsubishi sales representative.
152
P R Continuity N R Discontinuity
module
S P Discontinuity S N Continuity
D2 D5
P S Continuity N S Discontinuity
T P Discontinuity T N Continuity
D3 D6
P T Continuity N T Discontinuity
U P Discontinuity U N Continuity
TR1 TR4
P U Continuity N U Discontinuity
Inverter
module
V P Discontinuity V N Continuity
TR3 TR6
P V Continuity N V Discontinuity
W P Discontinuity W N Continuity
TR5 TR2
P W Continuity N W Discontinuity
(Assumes the use of an analog meter.)
Converter
P
module Inverter module
TR1 TR3 TR5
D1 D2 D3
R C U
S V
T W
D4 D5 D6
TR4 TR6 TR2
N
REMARKS
The FR-S520S-0.1K to 1.5K and FR-S510W-0.1K to 0.75K do not have T, D3 and D6.
153
CAUTION
For parts replacement, consult the nearest Mitsubishi FA Center.
154
CAUTION
If the air flow is set in the wrong
direction, the inverter life can be shorter.
155
(3) Relays
To prevent a contact fault, etc., relays must be changed according to the number of
accumulative switching times (switching life).
156
Input Output
voltage voltage
Input Output
current current
Single-phase 200V
power input
Single-phase 100V
power input
Inverter
Ar W11 R U Au W21
Vr Vu
3-phase
As W12 S V Av To motor
power supply
Vs Vv
At W13 T W Aw W22
Vt Vw
P N
The FR-S520S-0.1K to 1.5K :Moving-iron type
and FR-S510W-0.1K to
0.75K do not have As, At, :Electrodynamometer type
Vt, Vs, W12 and W13. V
+ - :Moving-coil type
Instrument
types :Rectifier type
157
Frequency setting
used)
signal Across 4 (+)-5 4 to 20mADC
(Internal resistance:
50kΩ or larger)
158
common.
"5" is
Frequency setting
Across 10 (+)-5 5VDC
power supply
Approximately 5VDC at
maximum frequency
(without frequency meter)
T1
SD is common.
Moving-coil type
(Meter, etc. may be
used) 8VDC
Across FM (+)-SD
Frequency meter (Internal resistance:
50kΩ or larger)
T2
signal Pulse width T1:
Adjusted with C1
Pulse cycle T2:
Set with Pr. 55 (Pr,56)
common.
Approximately 5VDC at
5 is
Across AM (+)-5 maximum frequency
(without frequency meter)
Moving-coil type
common.
Across STF, STR, (Meter, etc. may be 20 to 30VDC when open.
SD is
Start signal
RH, RM, RL, MRS, used) ON voltage: 1V or less
Select signal
RES-SD (Internal resistance: SD is common.
50kΩ or larger)
Continuity check
<Normal> <Fault>
Across A-C Moving-coil type Across
Alarm signal Discontinuity Continuity
Across B-C (such as a meter) A-C:
Across
Continuity Discontinuity
B-C:
CAUTION
1. Use FFT to measure the output voltage accurately. It can not be measured
accurately with a meter or general instrumentation.
2. When the carrier frequency exceeds 5kHz, do not use the instrument because
overcurrent losses occurring in the metallic parts inside the instrument will
increase and may lead to burnout.
In this case, use an approximate effective value type instrument.
159
Chapter 1
Chapter 2
Chapter 3
Chapter44
160
161
162
163
164
DC braking
operation voltage (0 to 15%)
Frequency Analog input 0 to 5VDC, 0 to 10VDC, 4 to 20mA
setting
Digital input Entered from control panel.
signal
Forward and reverse rotation, start signal
Start
STF, STR automatic self-holding input (3-wire input) can
signal
be selected.
Used to reset alarm output provided when
Alarm reset
protective function is activated.
Up to 15 speeds can be selected. (Each speed
can be set between 0 and 120Hz, running
Multi-speed selection
speed can be changed during operation from
Input signals
165
166
φ5 hole
- +
118 (4.65)
128 (5.04)
Rating plate
5 (0.20)
167
5 (0.20)
FR-S510W-0.75K(-NA)
φ5 hole
- +
118 (4.65)
128 (5.04)
Rating plate
5 (0.20)
Cooling fan×1
5 (0.20) 18.5 D3
6 (0.24) W1 6 (0.24) (0.73) D2 D1
W D
3-phase 200V power supply
Capacity W W1 D D1 D2 D3
1.5K, 2.2K 108 (4.25) 96 (3.78) 135.5 (5.33) 65 (2.56) 52 (2.05) 8 (0.31)
3.7K 170 (6.69) 158 (6.22) 142.5 (5.61) 72 (2.83) 52 (2.05) 5 (0.20)
3-phase 400V power supply
Capacity W W1 D D1 D2 D3
0.4K, 0.75K 108 (4.25) 96 (3.78) 129.5 (5.10) 59 (2.32) 52 (2.05) 5 (0.20)
1.5K 108 (4.25) 96 (3.78) 135.5 (5.33) 65 (2.56) 52 (2.05) 8 (0.31)
2.2K 108 (4.25) 96 (3.78) 155.5 (6.12) 65 (2.56) 72 (2.83) 8 (0.31)
3.7K 108 (4.25) 96 (3.78) 165.5 (6.52) 65 (2.56) 82 (3.23) 8 (0.31)
168
18.5 (0.73)
(0.97) 23.75 (0.93)
15 10.5 13 11.75
(0.51)
1.5 (0.06)
72 (2.83) (0.59) (0.41) 48 (1.89) (0.46)
5- 4 hole
21.5 (0.85)
20 (0.79)
17 (0.67)
1.5
(0.06)
14.5 (0.57)
13 (0.51)
81.5 (3.21)
125 (4.92)
80 (3.15)
1.25
(0.05)
5-M3 hole
Effective depth 4.5
40 (1.57) 40 (1.57)
(Unit:mm (inches))
Choose the mounting screws whose length will not exceed the effective depth of
the mounting threads.
169
170
171
172
173
174
# Measures
It is recommended to take either of the following measures:
(1) Rectifying the motor insulation
For the 400V class motor, use an insulation-rectified motor. Specifically
1) Specify the "400V class inverter-driven, insulation-rectified motor".
2) For the dedicated motor such as the constant-torque motor and low-vibration
motor, use the "inverter-driven, dedicated motor".
175
176
Multi-speed setting
5 05 85 0.01Hz 0
(middle speed)
Multi-speed setting
6 06 86 0.01Hz 0
(low speed)
7 Acceleration time 07 87 0.1s 0
8 Deceleration time 08 88 0.1s 0
Electronic thermal O/L
9 09 89 0.01A 0
relay
Extended function display
30 1E 9E 1 0
selection
79 Operation mode selection 4F None 1 0
The extended function parameters are made valid by setting "1" in Pr. 30 "extended
function display selection".
Data Code Link Parameter
Computer
Extension
Func- Parameter Link Data
Name Setting
tion Number Read Write Setting
(Data Code
Increments *
7F/FF)
DC injection brake
10 0A 8A 0.01Hz 0
operation frequency
DC injection brake
11 0B 8B 0.1s 0
operation time
DC injection brake
12 0C 8C 0.1% 0
Standard operation functions
voltage
13 Starting frequency 0D 8D 0.01Hz 0
14 Load pattern selection 0E 8E 1 0
15 Jog frequency 0F 8F 0.01Hz 0
Jog acceleration/
16 10 90 0.1s 0
deceleration time
RUN key rotation
17 11 91 1 0
direction selection
19 Base frequency voltage 13 93 0.1V 0
Acceleration/deceleration
20 14 94 0.01Hz 0
reference frequency
Stall prevention function
21 15 95 1 0
selection
Stall prevention operation
22 16 96 0.1% 0
level
177
27 1B 9B 0.01Hz 0
(speed 7)
Stall prevention operation
28 reduction starting 1C 9C 0.01Hz 0
frequency
Acceleration/deceleration
29 1D 9D 1 0
pattern
31 Frequency jump 1A 1F 9F 0.01Hz 0
32 Frequency jump 1B 20 A0 0.01Hz 0
33 Frequency jump 2A 21 A1 0.01Hz 0
34 Frequency jump 2B 22 A2 0.01Hz 0
35 Frequency jump 3A 23 A3 0.01Hz 0
36 Frequency jump 3B 24 A4 0.01Hz 0
37 Speed display 25 A5 0.001 0
Frequency setting
38 26 A6 0.01Hz 0
voltage gain frequency
Frequency setting current
39 27 A7 0.01Hz 0
gain frequency
Start-time ground fault
40 28 A8 1 0
detection selection
Up-to-frequency
41 29 A9 0.1% 0
sensitivity
functions
terminal
Output frequency
Output
42 2A AA 0.01Hz 0
detection
Output frequency
43 detection for reverse 2B AB 0.01Hz 0
rotation
Second acceleration/
44 2C AC 0.1s 0
deceleration time
functions
Second
178
level
Output current detection
49 31 B1 0.1s 0
signal delay time
Zero current detection
50 32 B2 0.1% 0
level
Zero current detection
51 33 B3 0.01s 0
time
Control panel display
52 34 B4 1 0
data selection
Display functions
Frequency setting
53 35 B5 1 0
operation selection
FM (AM) terminal
54 36 B6 1 0
function selection
Frequency monitoring
55 37 B7 0.01Hz 0
reference
Current monitoring
56 38 B8 0.01A 0
reference
Automatic
functions
selection/Frequency
59 3B BB 1 0
setting storage function
selection
RL terminal function
60 3C BC 1 0
selection
RM terminal function
61 3D BD 1 0
selection
RH terminal function
functions
selection
Terminal
62 3E BE 1 0
selection
STR terminal function
63 3F BF 1 0
selection
RUN terminal function
64 40 C0 1 0
selection
A, B, C terminal function
65 41 C1 1 0
selection
Operation selection
66 Retry selection 42 C2 1 0
Number of retries at
67 43 C3 1 0
functions
alarm occurrence
68 Retry waiting time 44 C4 0.1s 0
69 Retry count display erase 45 C5 1 0
70 Soft-PWM setting 46 C6 1 0
71 Applied motor 47 C7 1 0
179
73 0-5V/0-10V selection 49 C9 1 0
74 Input filter time constant 4A CA 1 0
Reset selection/PU stop
75 4B CB 1 0
selection
Cooling fan operation
76 4C CC 1 0
selection
Parameter write disable
77 4D None 1 0
selection
Reverse rotation
78 4E CE 1 0
prevention selection
Multi-speed setting
80 50 D0 0.01Hz 0
(speed 8)
Multi-speed setting
81 51 D1 0.01Hz 0
(speed 9)
Multi-speed operation
Multi-speed setting
82 52 D2 0.01Hz 0
(speed 10)
Multi-speed setting
83 53 D3 0.01Hz 0
(speed 11)
Multi-speed setting
84 54 D4 0.01Hz 0
(speed 12)
Multi-speed setting
85 55 D5 0.01Hz 0
(speed 13)
Multi-speed setting
86 56 D6 0.01Hz 0
(speed 14)
Multi-speed setting
87 57 D7 0.01Hz 0
(speed 15)
88 PID action selection 58 D8 1 0
89 PID proportional band 59 D9 0.1% 0
PID control
Constant-output region
97 slip compensation 61 E1 1 0
selection
Automatic torque boost
98 selection 62 E2 0.01kW 0
(Motor capacity)
99 Motor primary resistance 63 E3 0.001Ω 0
180
Frequency setting 1
C3 (902) 5E DE 0.1%
voltage bias (6C/EC=1)
Frequency setting 1
C4 (903) 5F DF 0.1%
voltage gain (6C/EC=1)
Frequency setting current 1
C5 (904) 60 E0 0.01Hz
bias frequency (6C/EC=0)
Frequency setting current 1
C6 (904) 60 E0 0.1%
bias (6C/EC=1)
Frequency setting current 1
C7 (905) 61 E1 0.1%
gain (6C/EC=1)
C8 (269) Parameter set by manufacturer. Do not set.
parameters
Communication station
n1 (331) 1F 9F 1 3
number
n2 (332) Communication speed 20 A0 1 3
n3 (333) Stop bit length 21 A1 1 3
Parity check
n4 (334) 22 A2 1 3
presence/absence
Number of
Communication parameters
n5 (335) 23 A3 1 3
communication retries
Communication check
n6 (336) 24 A4 0.1s 3
time interval
n7 (337) Wait time setting 25 A5 1 3
n8 (338) Operation command write 26 A6 1 3
n9 (339) Speed command write 27 A7 1 3
n10 (340) Link start mode selection 28 A8 1 3
n11 (341) CR/LF selection 29 A9 1 3
n12 (342) E2PROM write selection 2A AA 1 3
n13 (145) PU display language 2D AD 1 1
n14 (990) PU buzzer sound control 5A DA 1 9
n15 (991) PU contrast adjustment 5B DB 1 9
PU main display screen
n16 (992) 5C DC 1 9
data selection
PU disconnection
n17 (993) 5D DD 1 9
detection/PU setting lock
The parameter numbers within parentheses are those for use of the parameter unit
(FR-PU04).
* Though parameter setting by RS-485 communication can be made in the setting
increments indicated in the table, note that the valid setting increments are as
indicated in the parameter list (page 46).
181