SPECIFICATIONS: K-GENERATION R2-SERIES

PURY-P***T(Y)SKMU-A
208V
PURY-P72TKMU-A (-BS) PURY-P96TKMU-A (-BS) PURY-P120TKMU-A (-BS) PURY-P144TKMU-A (-BS)
/230V
Model Name
460V PURY-P72YKMU-A (-BS) PURY-P96YKMU-A (-BS) PURY-P120YKMU-A (-BS) PURY-P144YKMU-A (-BS)

Power Source 208 / 230V, 3-Phase, 60Hz / 460V, 3-Phase, 60Hz


Btu/h
72,000 96,000 120,000 144,000
Capacity
kW
Power 4.4 7.05 9.44 11.2
Cooling
Input
A
Current 13.5 / 12.2 / 6.1 21.7 / 19.6 / 9.8 29.1 / 26.3 / 13.1 34.5 / 31.2 / 15.6
Capacity Input
(Nominal) *1 Btu/h
80,000 108,000 135,000 160,000
Capacity
kW
Power 5.92 8.28 10.86 13.54
Heating Input
A
Current 18.2 / 16.5 / 8.2 25.5 / 23.0 / 11.5 33.4 / 30.7 / 15.1 41.7 / 37.7 / 18.8
Input

MCA A 23 / 21 / 11 34 / 31 / 15 45 / 42 / 21 53 / 48 / 24
Electrical Supply Recommended
A 25 / 15 35 / 20 50 / 25 60 / 25
Fuse Size
Type X Quantity Propeller Fan x 1 Propeller Fan x 2
Fan Airflow Rate CFM 6,200 11,300 11,300
External Static Pressure Selectable; 0, 0.12 or 0.24"W.G.; factory set to 0"W.G.
Type X Quantity INVERTER-driven Scroll Hermetic x 1
Compressor Operating Range 17% to 100% 16% to 100% 15% to 100%
Lubricant MEL32
Refrigerant Type R410A
External Finish Pre-coated galvanized steel sheet (Plus Powder Coating for -BS type) <Munsell 5Y 8/1 or similar>
Height In. 64-31/32
Dimensions
Width In. 48-1/16 68-29/32
HxWxD
Depth In. 29-5/32
Net Weight Pounds 503 / 534 538 / 574 715 / 743
Sound Pressure Level
dB(A) 58.0 60.0 61.0
(As Measured in an Anechoic Room)
High Pressure Protection High pressure sensor, High pressure switch
Inverter Circuit
Protection Devices Over-current protection
(Compressor / Fan)
Fan Motor Thermal switch
Liquid
(High Pressure) In. 5/8 3/4 7/8
Refrigerant Pipe (Brazed)
Dimensions Gas
(Low Pressure) In. 3/4 7/8 1-1/8
(Brazed)

Indoor Unit Total Capacity 50% to 150% of outdoor unit capacity


Connectable Model / Quantity P06 - P96 / 1 to 18 P06 - P96 / 1 to 24 P06 - P96 / 1 to 30 P06 - P96 / 1 to 36

Operating Cooling D.B. **Outdoor: 23° to 115° F


Temperature Range Heating W.B. Outdoor: -13° to 60° F

Efficiency Ratings *2

EER (Ducted/Non-Ducted) *2 13.9 / 15.5 12.2 / 13.6 11.7 / 12.2 11.7 / 12.7

IEER (Ducted/Non-Ducted) *2 21.1 / 22.1 19.7 / 20.9 18.6 / 20.8 18.0 / 20.9

COP (Ducted/Non-Ducted) *2 3.81 / 3.72 3.64 / 3.71 3.45 / 3.61 3.41 / 3.28

SCHE (Ducted/Non-Ducted) *2 23.6 / 24.48 17.4 / 23.5 16.8 / 19.7 18.2 / 20.2

Notes:
*1 Rating Conditions: Specifications are subject to change without notice.
Cooling | Indoor: 80°F (26.7°C) DB / 67°F (19°C) WB; Outdoor: 95°F (35°C) DB.
Heating | Indoor: 70°F (21.1°C) DB; Outdoor: 47°F (8.3°C) DB / 43°F (6°C) WB. LIMITED WARRANTY | Seven-year compressor and one year parts. See our
website for details on specific additional application installation coverage.
*2. Efficiency values based on AHRI 1230 test method.
** Extended ambient cooling operation range down to -10° F DB Low Ambient Kit required.
-BS indicates Seacoast Protection option.