ATLANTA ELECTRICALS PVT. LTD.

W.O.No.AET1291
Transformer Sr. No.1291/90
Rating40000 kVA, 132/33 kV Transformer.
CustomerU.P. Power transmission corporation Ltd.
Sr. Page
No. Wo.
1 Transformer Test Report,
2 Transformer Physical & Dimension Report.
List of Test Certificates (Boughtout Items)

Sr. Page
Item Description Make Item Sr. No. / T.C. No.
No. No.

1 OTI (Model: 1005AH) Precimeasure Controls Pvt. Ltd. P1804222.1 1


2 WTI (Model: 1005AH) Precimeasure Controls Pvt. Ltd. P1802030.ll 2
3 WTI (Model: 1005AH) Precimeasure Controls Pvt. Ltd. P1802030.12 3
4 PRV (Model: T6-1) Atvus Industries. 1846 EV 4
^5 MOG (Model: S06-ATMS 15D) Atvus Industries. SSV02495 5
6 MOG (Model: S06 15D) Atvus Industries. SV02254 6
7 OLTC (Model: SN/500L2/350/300/16 O) CTR Manufacturing Industries Ltd. 1840262 7-8
8 OLTC-PRV(Model :T3-1) Atvus Industries. 1496 DCV 9
9 OLTC-OSR Atvus Industries. DV01226 10
10 Buchloz Relay (Model: 60R - 3} Atvus Industries. MPV03117 11
S1451006360 {1U Phase)
11 HV Bushing (145 kV / 800 Amp) Crompton Greaves Ltd. S1451006362 (IV Phase)
S1451006372 (1W Phase)
12 LV Bushing (36 kV/1000 Amp) A.S.Insulators. ASI/00107/18-19 15
13 HVCT (Ratio: 175/1.5) Amod Stampings Pvt.Ltd. 18/257 16-17
14 LVCT (Ratio: 740/1.5) Amod Stampings Pvt.Ltd. 18/256 18-19
15 Transformer Oil Apar Industries Ltd. S1T0240818 20
16 Radiator Transpares Ltd. 325/18-19 21
17 MS Tank Vinayak Engineering Co. VEC/AE PL/04 22
18 Air Cell NU -Cork products ltd. NCPL/FAS/2018-19/6588 23
19 Rubberised Cork Sheet Grindbeck 195/2018-2019 24
20 Valves (25,50 & 80 mm) Vishnu Industries. Tc No. 13,10 & 5. 25-27
21 Radiator Valve (80 NB) Gajanan Electromech. GE/AEPL/56/18-19 28
22 Breather. Rinu Transco. RT/AEPL/18-ig/SGB TC-146 29
23 Connector. VIJAY Industries. BMC01291 HV & LV 30-31

/vSS^\

7S */
F;QC;40, Rev: 10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.
1503-4, GIDC ESTATE, VITHAL UDYOGNAGR, AN AND, GUJARAT - 388 121
—i
vJ
TRANSFORMER TEST REPORT Page : 1 OF 30
Customer : ' .P.POWER TRANSMISSION CORPORATION LIMITED, LV'CKNOW W.O. No.: AET 1291 Sr. No.: 1291/90

U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW


U P Power Transmission Corporation Ltd., 13th floor, , Shakti Bhawan Ext., 14 - Ashok Marg, Lucknow - 226001.
LOI No.: 336-ESDC(Xl/m/ESD - 488 /ATLANTA/40 MVA DTD - 23/05/2018
4n TVTVA. 132 / 33 KV
8 Phase 2 Winding Rated Frequency :- 50.0 Hz.
VNvnO
H.V. Side Star Connection L.V. Side :- Star Connection.
H.V. Side 174.96 Amp (40 MVA) L.V. Side:- 699.84 Amp (40 MVA)
AET 1291 —
1291/90 —
R ON AN/ ONAF
: } Oil 45 0C Winding50 0C
+ 15 % to - 5 % In Step Of 1.25 % On HV For LV Variation - OLTC.
06.09.2018 —
10.09.2018 & 11.09.2018 —
NO Damage Observed.. ——
Ref. Standard IS 2026 -1977, (EC -60076, IS 6792, CBIP-317, ANSI CS7.12.00 & Customer Specification.

ROUTINE TEST
ROUTINE TEST Page No.
Measurement of voltage Ratio & Polarity Test at all Taps. — 2
3
3
4
5
Chock of Core & frame Isolation for Liquid Immersed Transformer .. ... 5
5
Induced Over Voltage Withstand Test (ACSD1 With Partial Diascharge Measurement. 6
7-8
9
9
Load Loss, Impedance Voltage & CT Ratio Measurement (At Tap No.: 5,1 & 17). ,— -■ ■■ 10
11
12
13
13
14 - 20
21 - 30

■ '
■-
Total Pages:! 30

A
Tested By: PPr®ve^ By: Witnessed By :

R^^^Pra^patl Anuj Pratap Singh


Sr. Testing Engr. Manager Testing Executive Engineer ET & C0
AEPL, V.U. Nagar. V. ^ J^AEPLVV-U. Nagar. UPPTCL, Or. Noida
Note- 1) liiis ceruficwe shall not be reproduced in paji nnderanvcifcumifusces 2! PuW.rai.on of ihisreport re<iuire» pr.or permission in wni.ng from AEPl.
3) Reported tesuits relate to the item tested ■») Only the test asked by the cusiomer have been earned out.
F:QC;40, Rev; 10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.
C\
TRANSFORMER TEST REPORT Page ; 2 OF 30
Customer : U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW [W.O. No.: AET 1291 Sr. No.: 1291/90
ROUTINE TEST RESULTS
1. MEASUREMENT OF VOLTAGE RATIO & POLARITY TEST ALL TAPS :
Phase " U •' Phase " V " Phase W " Phase
Measured Calculated Measured Calculated Measured Calculated Max Min.
Tap No.
Ratio % Error Ratio % Error Ratio % Error Limit Limit.

1. 4.211 4.194 -0.39 4.194 -0.39 4.194 -0.39 4.232 4.189

2. 4.156 4.148 -.0.19 4.148 -0.19 4.147 -0.21 4.177 4.135

3. 4.103 4.102 -0.01 4.102 -0.01 4.103 0.01 4.123 4.082

4. 4.051 4.057 0.16 4.056 0.13 4.056 0.13 4.071 4.030

S. (N.T.) 4.000 4.010 0.25 4.010 0.25 4.010 0.25 4.020 3.980

6. 3.95; 3.964 0.34 3.963 0.31 3.964 0.34 3.970 3.93!

7. 3.902 3.918 0.40 3.917 0.37 3.918 0.40 "3.922 3.883

8. 0
3.855 3.872 0,43 3.872 6.43 3.872 0.43 3.875 3.836

9. 3.810 3.826 0,43 3.825 0.40 3.826 0.43 3.829 3.790

10, 3.765 3.780 0.40 3.780 0.40 3..780 0.40 3.784 3.746

11. 3.721 3.734 0.35 3.734 0.35 3,734 0.35 3.740 3.702

12. 3.678 3.688 0.27 3.688 0.27 3.689 0.29 3.697 3.660

13. 3.636 3.647 0.29 3.648 0.32 3.648 0.32 3.655 3.618

14. 3.596 3.608 0.35 3.608 0.35 3.608 0.35 3.613 3.578

15. 3.556 3.568 0.35 3.567 0.32 3.568 0.35 3.573 3.538

16. 3.516 3.528 0.33 3.527 0.30 3.528 0.33 3.534 3.499

17. 3.478 3.488 0.28 3.488 0.28 3.488 0.28 3.496 3.451
1

Note :• 1- As Per IS 2026, The Permissible % Ratio Error is +/• 0.5 %.


Note: N.T. : Normal Tap Position.

Harsh Hirpara,, \rr- \ Anuj Pratap Singh


Sr. Testing Bngr. " ! '■ Executive Engineer ET & CD
AEPL, V.U. Nakar.x : r UPPTCL, Gr. Noida
\/v
X<?
vi-J, -
F:QC:40. Rev;10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

9 TRANSFORMER TEST REPORT 3 OF 30


Customer: U-P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW )W.6. Wo.i AET 1291 1291/90
2. MAGyETIC BAT. AWCS TEST and MAGMET12ING CURRENT MEASUREMENT: (At Tap No. ; 3)
A. Magnetic balance test;
From HV Side
XU - IN IV - IN 1W - IN
436 361 80
218 436 218
58 387 440

From LV Side
2U-2N 2V - 2N 2W - 2N
436 341 96
218 433 214
67 370 434
B. Magnetizing Current test:
Apply 3 Phase AC on LV Terminal & HV Kept Open
Voltage Applied 3 Measured Current |m. A)
2U2V 436 2U 24.80
433 2V 12.95
2W2U 434 2W 22.00
Apply 3 Phase AC on HV Terminal & LV Kept Open
Voltage Applied Measured Current (m. A)
1U1V 436 1U 2.56
1V1W 435 IV 1.34
IW1U 440 JW 2.30
3. VECTOR GROUP TEST : (At Tap No. : 5)
1U - 2U Shorted. 1U - 2U Shorted. 1U,2U
Measurement
1UIV = 436 1V2V = 324 2N
1V1W = 435 1V2W = 390 2W ..2 V
1W1U = 435 1W2W = 327
1W2V = / ^^'1- N
394
1U2N = 63 I.W IV
1N2N = 190 YNynO
1U1N = 253 Hence Vector Group Is YNynO.
Sr. No. Variflcation Condition Measured Value
1V2W = 1W2V 390 394
2. 1V2V = 1W2W 324 327
3. 1U2N + lN2N'p--luil4: 63.0 190 253.0

Tested By':
5i y ■ S\ \
Witnessed By
o :

Harsh Hirpara' £ Anuj Pratap Singh


Sr. Testing Engr' Executive Engineer ET & CD
AEPL, V.U. Nagat; UPPTCL. Gr. Noida

O
F:QC:40, Rev; 10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

TRANSFORMER TEST REPORT Page : 4 OF 30


Customei' ; U-P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW (w.O. No.-. |AET 1291 Sr.No. : 1291/90
4. WINDING RESISTANCE TEST !-

HV Winding Resistance (Ohm)


Tap. No. 1U - IV IV - 1W 1W - 1U Average

1 1.2354 1.2346 1.2347 1.2349

2 1.2179 1.2172 1.2171 1.2174

3 1.2003 1.1993 1.1991 1.1996

4 1.1826 1.1818 1,1819 1.1821

S(N.T.) 1.1649 1.1644 1.1643 1.1645

6 1.1473 1.1466 1.1465 1.1468

7 1.1297 1.1290 1.1291 1;I293

8 1.1121 1.1114 1.1113 1.1116

9 1,0942 1.0939 1.0936 1.0939


a

10 1.0766 1.0760 1.0761 1.0762

11 1.0586 1.0584 1.0590 1.0587

12 1.0411 1.0407 1.0404 .. 1.0407 ■.

13 1.0253 1.0250 1.0247 1.0250

14 1.0099 1.0098 1.0095 1.0097

15 0.9942 o 0.9940 0.9937 0.9940

16 0.9789 0.9785 0.9784 0.9786

17 0.9627 0.9629 0.9626 0.9627

LV Winding Resistance (m. Ohm)


Tap No. ; s Temp.(Tl): ( In0C)
2U - 2V 62.50 Top : 39.90

2V - 2W 62.55 Bottom : 38.50

2W-2U 62.58 Avg. : 39.20

Average ^ 62.54 '

Tested By : Witnessed By :

Harsh Hirpara Anuj Pratap Singh'


Sr. Testing Ehgr., Executive Engineer ET 8t CD
AEPL, V.U. Nagar!1—-— UPPTCL, Gr. Noida
F;QC:40, Rev: 10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

Q TRANSFORMER TEST REPORT Page !


Customer : U.P.POWER TRAMSMISSIOK CORPORATION LIMITED, LUCKNOW |W.O. So.: |AET 1291 1291/90

5. INSULATION RESISTANCE MEASUREMENT : (S KV)

Time: 15 Sec. 60 Sec. 60O Sec. A.I. P.I. Test Temp. (Tl); 0
C
Sec. G ohms G ohms G ohms (60/15) (600/60) Voltage Top : 39.90
HV TO LV 3.42 7.21 12.90 2. IX 1,79 5 kV
Bottom : 38.50
HV TO Earth 3.62 6.20 12.70 1.71 2.05 5 kV
Avg. : 39.20
LV To Earth 3.08 6.01 11.60 1.95 1.93 5 kV

6. Check of Core & frame Isolation for Liquid Immersed Transformer

15 Sec. 60 Sec.
Configuration
G ohms G ohms
Core to Frame 1.90 3.78
Fram6 to Earth 2.20 3.49 Values are in G Ohm
Test voltage : 2.5 kV
Core to Earth 1-31 2.24

7. SEPARATE SOURCE VOLTAGE WITHSTAND TEST ; ( TaR No.: 5)

Following Voltages Applied At SO Hz For 60 Sec.


Voltage applied between short - circuited all H.V.+ N terminals.
{All L.V. + N terminals & tank earthed.) :38.0 kV & Withstood OK.
Voltage applied between short - circuited all L.V. + N terminals.
{All H.V.+ N terminajs & tank earthed.) : 70.0 KV & Withstood OK.

TestetJ By : Witnessed By :
. Hrfpara,\- %v
Harsh Anuj Pratap Singb
Sr. Testing Engr., Executive Engineer ET & CD
AEPL, V.U. NagafS - ' UPPTCL, Gr. Noida
F;QC:40, Rev: 10. dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

Q TRANSFORMER TEST REPORT Page ;


U.P.POWER TRANSMISSION CORPORATION LIMITED, UICKNOW )W.O. No.: |AET 1291 lSr.No. : 1291/90

8. INDUCED OVER VOLTAGE WITHSTAND TEST jACSDl WITH PARTIALDISCHARGE MEASUREMENT :


A. Induced Over Voltage Withstand Test (ACSD) Ph To Ph Method
Um : 14S.0 kV
Tap No.: 1
Test Freq. ; 100.0 Hz. Time Duration
1.1 Um : 159.5 kV A. B, C, D& E 5 min.
C = 60 Sec.
2 = 1.3 Um: 188.5 kV

Partial Discharge (pC)


Time Voltage
Uphase Vphase Wphase
U1 0 Min. Ambient 20 19 20
/ U2
/ 5 Min. 1.1 Um 42 43 43
''l.l Urn 1.1 5 Min. U2 65 64 62
Ustart , <Ust3rt 60 Sec. U1 Withstood
5 Min. U2 63 62 61
5 Min. l.l Um 41 40 40

B. Induced Over Voltage Withstand Test (ACSD) Ph.To Earth Method


Um : 145.0 kV
Tap No
Test Freq. 100.0 Hz. Time Duration :
1.1 Um/v3 92.000 kV A, B, C, D& E = 5 min.
C ' 50 Sec.
U2 = 1.5 Um/V3: 125.000 kV

Partial Discharge (pC)


Time Voltage
Uphase Vphase i Wphase
U1
r y U2 U3 0 Min. Ambient 19 19 18
/l.l Urn/vs' 1.1 Urri/v'3 5 Min. 1.1 U m / V3 36 37 35
Ustart <Ustart 5 Min. U2 56 58 57
60 Sec. U1 Withstood
5 Min. U2 55 53 55
5 Min. 1.1 Um/V3 35 32 34

TestedJSy,-:' Witnessed By :

Harsh Hirpara Anuj Pratap Sing


Sr. Testing Engr. Executive Engineer ET & CD
AEPL, V.U. Wagar. UPPTCL, Gr. Noida
F:QC:40, Rev;10. dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

a TRANSFORMER TEST REPORT Page : 7 OF 30


Customer : U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKWOW |W.O. No.; AET 1291 1291/90
.1. NO LOAD LOSS AND MAGNETIZING CURRENT MEASUREMENT (at 100 % of Rated Voltage) At Tap No.: 5 ;
CTH = 5/5 = 1 PTR = 33000/V3 / 110/V3 = 300 Frequency ! (Hz) 50.000
Frequency correction applied
Note Frequncy Correction to feed rated Voltage for N.L.L. Measurement - Grid Frequncy x Rated Voltage
Rated Frequncy
50.000 x 63.508 63.508
50.000
63.508 x 1.732 x 300 = 33000 instead of 33000 Volt
Vmean = 63.508 32999.72 Volt Vrms = 63.630 33063.12 Volt
100 % Of c V (rms)
Element Amp Watt
33.00 kV (Per Ph)
(1) R Phase 63.901 0,38994 24.469
W1
(2) Y Phase 63.331 0.22520 13.073
63.508 Rated W2
Volt at 50 Hz 63.657 0.32826 19.539
(3) B Phase W3
Average : 63.630 0.31447 57.081
W1+W2+W3
Measured Losses = 57.081 x 1 x 300 17124.3 . Watt
Magnetizing Current is 0.3145 x 1=- 0.31447 Amp When Excited from LV side at 100 % rated voltage.
C 0.31447 x 100
Hence Percentage Magnetizing Current - 699.84 = 0.0449 %.
Hence HV / LV Magnetizing Current is 0.0449 % Of rated Current Of HV And LV.
Corrected No Load Loss = 17091.40 Watt
| Guaranteed No Load Loss 18.00 KW Max. T
9.2. NO LOAD LOSS AND MAGNETIZING CURRENT MEASUREMENT (at 90 % of Rated Voltage) At Tap No.: 5 :
Grid Frequncy
Note Frequncy Correction to"feed rated Voltage for N.L.L. Measurement - x Rated Voltage
Rated Frequncy
50.000 x 57.157 57.157
50.000
x 1.732 x 300 = 29700 instead of 29700 Volt
29699.65 Volt Vrms = 57.330 29789.54 Volt
Frequency : (Hz) 50.000

90 % Of Element V (rms) Amp Watt


33.00kV ; (Per Ph)
(1) R Phase 57.647 0.35137 19.984
W1
(2)Y Phase 56.964 0.20287 10.977
57.157 Rated W2
Volt at 50 Hz 57.380 0.28779 15.553
(3)B Phase W3
Average j 57.330 0.28068 46.514
W1+W2+W3
Measured Losses = 46.514 x1 x 300 13954.2 Watt
Corrected No Load Loss = 139X1.96 Watt
Hence HV / LV Magnetizing^Current is 0.0401 % Of rated Current Of HV And LV.

Tested By : Witnessed By :

Harsh Hlrpara Anuj Pratap Singh


Sr. Testing Engr. Executive Engineer ET & CD
AEPL,V.U/;NagaT. UPPTCL, Gr. Noida
F;QC;40, Rev; 10. dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

O) TRANSFORMER TEST REPORT Page : 8 OF 30


Customer s O.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW ' W.O. No.: AET 1291 Sr.No. ! 1291/90
9.3. NO LOAD LOSS AND MAGNETIZING CURRENT MEASUREMENT (at 110 % of Rated Voltage) At Tap No.: 5 :
CTR = 5/5 = 1 PTR = 33000/V3 / 1 lO/Va - 300 Frequency : (Hz) 50.000
Frequency correction applied

Note Frequncy Correction to feed rated Voltage for N.L.L. Measurement Grid Frequncy
x Rated Voltage
Rated Frequncy
50.000 K 69.859 69.589
50.000
_ 69.589 x 1.732 x 300 = 36160 instead of 36300 Volt
Vmean = 69.589 = 36159.51 Volt Vrms = 70.275 = 36515.96 Volt,

« Frequency : (Hz) 50.00


Frequency correction applied
110% Of Element V (rms) Watt
33.00 kV (Per Ph)
(1)RPhase 70.530 0.4924 33.855 W1
69.859 Rated (2) Y Phase 70.045 0.2729 17.708 W2
Volt at 50 Hz (3) B Phase 70.250 0.4416 27.240 W3
Average : 70.275 0.4023 78.303 W1+W2+W3
Measured Losses = 78.803 x1 x 300 = 23640.9 Watt
Corrected No Load Loss - 23407.85 Watt
Hence HV / LV Magnetizing Current is 0.057S % Of rated Current Of HV And LV.

9A. NO LOAD LOSS AND MAGNETIZING CURRENT MEASUREMENT (at 120 % of Rated Voltage) At Tap No?: 5 :

Note Frequncy Correction to feed rated Voltage for N.L.L. Measurement = Grid Frequncy
x Rated Voltage
Rated Frequncy
50.000 x 76.210 76.210
50.000
_ 76.210 x 1.732 x 300 = 39600 instead of 39600 Volt
Vmean = 76.210 = 39599.88 Volt Vrms = 77.094 = 400S9.22 Volt
Fr^ijuency : (Hz) 50.00
Frequency correction applied
120 % Of Element V (rms) Watt
33.00 kV (Per Ph)
(1) R Phase 77.224 0.S949 43.204 W1
76.210 Rated (2) Y Phase 76.889 0.3437 21.448 W2
Volt at 50 Hz (3)B Phase 77.169 0.5824 34.622 W3
Average : 77.094 0.5070 99.274 W1+W2+W3
. Measured Losses = 99.274 x1 x 300 = 29782.2 Watt
Corrected No Load Loss = 29436.7 Watt
Hence HV / LV Magnetizing Current is 0.0724 % Of rated Current Of KV And LV.

Pcrrected = Pm(l+d) , d = ( U" - UJ/U' , Where U' = Mean Volatge & U = RMS Voltage
FtdTI,"-.
Witnessed By : x
^rrQT)
Anuj Pratap Singh
Sr. Testing,Engr. Executive Engineer ET 86 CD
AEPL, V.U; Nagar. ,-v ,. UPPTCL, Gr. Noida
V*-
FiQC^O. Rev; 10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

TRANSFORMER TEST REPORT Pa-ee ! 9 OF 30


Customer : O.P,POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW |W.O. No.: |AET 1291 1291/90

10. TEST ON OLTC :


Test On OLTC Of Subject Transformer As Per IS 2026 is performed during NO Load test & Full Load test
and result found OK.
11. DIELECTRIC STRENGTH TEST ON TRANSFORMER OIL :

TEMP. OF OIL : 28.00 0C


RH: 44 %
FREQUNCY OF TEST VOLTAGE 50 HZ
SAMPLE DISCR1PATION: OIL SAMPLE TAKEN FROM THE BOTTOM OF THE TANK.
TYPE OF ELECTRODES: SPHERICAL
GAP BETWEEN ELECTRODES: . 2.5 mm
TEST STANDARD: IS 6792

OBSERVATIONS
READ 1 READ 2 READ 3 READ 4 READ 5 READ 6 AVG.
B.D.V. of Oil Sample in kV
88 82 76 72 74 80 79

•jtV N
Testfcd By :, Witnessed By :

Harsh Hir'para Anuj Pratap Sin


Sr. Testing_Engr.^ • C>> Executive Engineer ]£T & CD
AEPL, V.U.rNagar.'." UPPTCL, Gr. Noida
F:Qe:40, Rev: 10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

ei TRANSFORMER TEST REPORT Page : 10 OF 30


Customer : U.P.POWER TRANSMISSIOK CORPORATION LIMITED, LUCKNOW ]W.O. Ho.: |AET 1291 Sr.No. : 1291/90
12.1. LOAD LOSS & IMPEDANCE VOLTAGE MEASUREMENT : At Tap Mo.i S
CTR = 600/5 = 120 PTR = 22000/V3 / 1X0/V3 = 200 Frequency: (Hz) 50.033
Rated Current Element V (rms) Amp
(Per Ph) Watt
(1) R Phase 51.258 1.4390 1.603 W1
(2)Y Phase 51.778 1.4561 1.699
1.458 Amp. W2
(3)B Phase 52.316 1.4810 1.339 W3
Average : 51.784 1.4S87 4.641 W1+W2+W3
Measured Losses: 4.641 x 120 x 200 111384 Watt
Rated Current: 1.4580 x 120 = 174.96, Amp.
So Losses At Pull Load (Irated) = 111277 Watt at 39.20 0c
Impedance Voltage at Itest = S 1.7840 x 1.732 x 200 17938,50 Volt
Impedance Voltage Irated & 50 Hz = 51.7250 x 1.732 x 200 17918.07 Volt
Total Load Loss at 75 C = 122888 Watt Percentage Impedance at 75 C = 13.574 %
Guaranteed Temp.(T21: ( In0C)
Load Loss At 75 0C = 124.0 KW Max. Top : 39.90
Aux. Loss = l.SkW Max Bottom : 38.50
% Z = 13.75 % •+/- 3%' Tolerance) Avg. : 59,20
At Rated Current At Principal Tap at 75 0C.
12.2. LOAD LOSS & IMPEDANCE VOLTAGE MEASUREMENT : At Tap No.: 1
Frequency : (Hz) 50.000
Rated Current Element V (rms) Amp Watt
(Per Ph)
(1) R Phase 57.190 1.4463 1.794
W1
(2)Y Phase 57.384 1.4539 1.796
1.458 Amp. W2
(3)B Phase 57.895 1.4767 1.427 W3
Average : 57.490 1.4589 5.017 W1+W2+W3
Measured Losses : 5.017 x 120 x 200 120408 Watt
Rated Current : 1.4580 x 120 174.96 Amp.
So Losses At Pull Load (Irated) - 120259 Watt at 39.20 0c
Impedance Voltage at Itest = 57.4900 x 1,732 x 200 19915.12 Volt
Impedance Voltage Irated & 50 Hz = 57.4545 x 1.732 x 200 19902.82 Volt
Total Load Loss at 75 ''C = 132849 Watt Percentage Impedance at 75 0C = 15.078 %
12.3. LOAD LOSS 8s IMPEDANCE VOLTAGE MEASUREMENT : At Tap No.: 17
Frequency : (Hz) 49.921
Rated Current Element V (rms) Amp
(Per Ph) Watt
(1) R Phase 35.874 1.4372 1.276 W1
(2) Y Phase 36,225 1.4566 1.294 W2
1.458 Amp.
(3)B Phase 36.740 1.4833 1.104 W3
Average : 36.280 1.4590 3.674 W1+W2+W3
Measured Losses 3.674 x 120 x 200 88176 Watt
Rated Current ! 1.4580 x 120 174.96 Amp.
So Losses At Full Load (Irated) = 88055 Watt at 39.20 0C
Impedance Voltage at Itest ~ 36.2800 x 1.732 x 200 12567.76 Volt
Impedance Voltage Irated & SO Hz = 36.3100 x 1.732 x 200 12578.15 Volt
0
HV WTI CT Current : 1.490 Amp. LV WTI CT Current ; 1.240 Amp.
0
Total Load Loss at 75 C„='^ V C i 97310 Watt Percentage Impedance at 75 0C = 9.529
Tested By : Witnessed By :

\y Hirpara.„..
Harsh' :vw. • I /-/ Anuj PfatSp STirfih^
Sr. Testinj^Engrj^.-- o Executive Engineer ET & CD
AEPL, V.U^Nagar. UPPTCL, Gr. Noida
F:QC:40, Rev: 10. dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

TRANSFORMER TEST REPORT Page : 11 OF 30


Customer: U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKflOW )W.O. No.: AET 1291 Sr.No. : 1291/90
CALCULATION AT 75 Dcg. C OF FULL LOAD LOSS MEASUREMENT
13. RESULT AND CALCULATION SHEET :
Customer u.p.power TRANSMisstoN corporatiodi LIMITED, tUCKNOW Vector Group YNynO.
W.O. No. AET 1291 Tap No. 5
0
Sr. No. 1291/90 Temp. (Res!) (Tl) (In C) 39.20
KVA 40000 HV Amp. 174.96
HV Volt 132000 LV Amp. 699,84
2
LV Volt 33000 HV X R Loss at Tl Temp. ' 53471
2
HV Resl / Phase (Ohm) 0.5823 • LV I R Loss at Tl Temp. 4S948
2
LV Resi / Phase (m Ohm) 31.272 Total I R Loss at Tl Temp. 99419
0 2
Temp. (S/C Test) (T2) (In e) 39.20 Total I R Loss at T2 Temp. 99419
Meas. Voltage (Imp. Voltage) !- 51.7840
Calculated Imp. Volt at Irated & SO Hz 51.7250 Calculated Losses at T2 Temp Irated 111277
2
Watts (Wl) :• (Load Loss) 4.641 Total I R Losses at T2 Temp. 99419
C.T.R. 120 Stary Losses at T2 Temp :• 11858
2 0 if,
P.T.R..:- 200 Total 1 R Losses at 75 C 112399
0
W.M.M.F. !- 1 Stary Losses at 75 C 10489
0
Measured Amp. 1.45870 Total Load Losses at 75 C :• • 122888
Measured Loss at T2 Temp Itest 111384 Calculated Values i (% Impedance)
Calculated Loss at T2 Temp Irated 111277 Percehtage Impedance (% Z) T2 Temp. 13.574
HV Resi / Phase at 75 Deg. C ;• (Ohm) 0.6583 Percentage Resistance (% R) T2 Temp. 0.278
LV Resi / Phase at 75 Deg. C (m. Ohm) 35.3545 Percentage Reactance (% Xj 13,571
0
Percentage Resistance at 75 C (% R):- 0.307
0
Percentage Impedance at 75 C (% Z) 13.574
As Per GTP : (%Impedance)
Percentage Impedance at 75 0C (% Z) 13.750
Efficiency Calculated Values : Calculated Values
Efficiency at 100 % Load and Unity P.F 99.65
Efficiency at 75 % Load and Unity P.F 99.71
Efficiency at 50 % Load and Unity. P.F 99.76
Efficiency at 25 % Load and Unity P.F 99.75
Corrected No Load Loss 17091.40
C.T.R. :• 1 Efficiency Calculation: Calculated Values :
P.T.R. 300 Load at which maximum efficiency occurs (% of
full load) 37.29
W.M.M.F. 1 Maximum efficiency In % 99.77
Measured Amps 5- 0.3145 Calculated Values : Calculated Values :
Percentage Magnetizing Current 0.0449 % Regulation at Unity P.F;- 1.230
% Regulation at 0.8 P.F:- 8.9^0
Note : All tests arc carried out at 100 % Values, Values for other-Itjads are calculated.
^ .Y-GTR//-»,vV
/ v >- ^ - \
Test^l /' v \^<J\ .

Harsh Hirpji^tv ' j CJ


Sr. Testing Engn
AEPL, V.U. Nagar.. .. : /
F;QC:40, Rev; 10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

Q TRANSFORMER TEST REPORT Page : 12 OF 30


Customer: U.P.POWER TRANSMISSION CORPORATIOK LIMITED, LUCKNOW |W.O. No.: AET 1291 Sr.No. 1291/90
CALCULATION AT 75 Deg. C OF FULL LOAD LOSS MEASUREMENT
14. RESULT AND CALCULATION SHEET: (At Tap No.: 1 & 17)
Tap No.t 1 Tap No.: 17
Temp. (Resi) (TI) 39.20 Temp. (Resi) (T)(0C) 39.20
Temp. (Load Loss) (T2) 39.20 Temp. (L.L.) (T) (0C) 39.20
KVA 40000 KVA 40000
HV Volt :• 132000 HV Volt 132000
LV Volt 31350 LV Volt 37950
HV Amp. 174.96 HV Amp. 174.96
LV Amp. 736.67 LV Amp. 608.54
2 2
HV I R Loss at Tl Temp. (Watt) 55702 HV I R Loss at Tl Temp. (Watt) 44205
2 2
LV I R Loss at Tl Temp. (Watt) 50912 LV 1 R Loss at Tl Temp. (Watt) 34742
2 2
Total I R Loss at Tl Temp. (Watt) 107614 Total X R Loss at Tl Temp. (Watt) 78947
2 2
Total I R Loss atT2 Temp. (Watt) 107614 Total I R Loss at T2 Temp. (Watt) 78947

Measured Loss at T2 Temp. Itest (Watt) 120408 Measured Loss at T2 Temp. Itest (Watt) 88176
Measured Loss at T2 Temp. Irated (Watt) 120259 Measured Loss at T2 Temp. Irated (Watt) 88055
2 2
Total I R Loss at T2 Teirfp. (Watt) 107614 Total I R Loss at T2 Temp. (Watt) 78947
Stary Losses at T2 Temp. (Watt) 12645 Stary Loss at T2 Temp, (Watt) 9108
2 2
Total I R Loss at 75 Deg. C (Watt) 121664 Total I R Loss at 75 Deg. C (Watt) 89254
Stary Loss at 75 Deg. C (\yatt) 11185 Stary Loss at 75 Deg. C (Watt) 8056
Total Load Loss at 75 Deg. C (Watt) 132849 Total Load Loss at 75 Deg. C (Watt) 97310

Percentage Impedance (% Z) T2 Temp. 15.077 Percentage Impedance (% Z) :• T2 Temp. 9.529


Percentage Resistance j% R) T2 Temp. 0.301 Percentage Resistance (% R) :• T2 Tamp. 0.220
Percentage Reactance (% X) 15.074 Percentage Reactance j% X) 9.526
Percentage Resistance at 75 Deg.C (% R):- 0.332 Percentage Resistance at 75 Deg.C {% R);- 0.243
Pcrcentagc Impedance at 75 Deg.C (% Z) 15.078 Pcrcentage Impedance at 75 Deg.C (% Z) 9.529
*
HV Resi / Phase at T2 Temp. (Ohm) 0.6175 HV Resi / Phase at T2 Temp. (Ohm) 0.4814
LV Resi / Phase at T2 Temp. (m.Ohm) 31.2717 LV Resi / Phase at T2 Temp. (m.Ohm) 31.2717
HV Resi / Phase at 75 Deg. C (Ohm) 0.6981 HV Resi / Phase at 75 Deg, C (Ohm) 0.5442
LV Resi / Phase at 75 Deg. C (m.Ohm) 35.3545 LV Resi / Phase at 75 Deg. C (m.Ohm) 35.3545

Tested , .

HarshMlirpara ■ -z^On
Sr. Testing Engr. / - ,j
AEPL, VIU. Nagar. . /r
s "
F:QC;40, Rev;10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

TRANSFORMER TEST REPORT Paee : 13 OF 30


Sr.No. ! 1291/90
Customer : U.P.POWER TRAKSMISSION CORPORATION'LIMITEQ, LUCKitOW "|W.O. Wo.! AET 1291
15. MEASUREMENT OF TAN DELTA & CAPACITANCE : At Tap No.: S
Temp.(T3): (In 0C)
Tan 5(%)
Test Capacitance, nF Top ; 39.90
Test Mode
•ft T3 "C 'a 20 °C Bottom : 38.50
Winding Avg. : 39.20
K Factor: 0.66 At temp 39
HV - LV 10 KV 4.S919 0.287 0.189

HV - E 10 KV 3.4951 0.606 0.400

LV - E 10 KV 8.7150 0.536 0.354

!IV Bushing. (Cl) Bushing Sr. No.

1U Phase 10 KV 210.02 0.293 1451006360


r, o

IV Phase 10 KV 201.03 0.274 1451006362

1W Phase 10 KV 210.38 0.276 1451006372

Note : For HV Bushing Uhit of Capacitance is pF 1


Note ;• The above tan5 values of windings are measured at = 39.20 "C (Approx C). To convert these Values at 20 °C,
it is multiplied by 0.66 (Conversion Factor).

16. MEASUREMENT OF ZERO PHASE SEQUENCE IMPEDANCE : (At Tap No.: 5. Measured From HV Side)
Rated KVA = 40000
Rated HV Voltage = 1320O0 Volt
Rated HV Current «= 174.96 Amp.
Applied Voltage Between Short Terminal HMV-IW and IN, LV winding Terminal Short 2U-2V-2W- 2N
CTR = 120 PTR = 60
Applied Measured 20 % 20
Voltage (Vra) Current (1m) (3 x Vm x PTR / Ira x CTR)

9.920 0.45190 57.031 13,092

Avg.
■ % ZO = 20 x Rated H.V. Amp. X 100 / Rated H.V.Pb. Volt.

TestediBy : Witnessed By :
\
15 Anuj Pratap Singh^
Harsh HirpaVa Executive Engineer ET & CD
Sr. Testing Engr. /,,■, j UPPTCL, Gr. Noida
AEPL. V.UNNaear.^
F;QC;40, Rev:10. dated 09-06-2018

ATLANTA BLECTRICALS PVT. LTD.

^4 IMPULSE TEST REPORT


Page : 14 OP 30
Customer: u.p.power transmission corporation limited, lucknow JW.O. No.: AET 1291 Sr. No.: 1291/90

17. LIGHTNING IMPULSE TEST.

Rating 40 MVA, 132 / 33 KV


Basic Ins. Level HV Side230 kVrms |LVSide:- 70 kVrms
Date Of Testing : 10.09.2018
Test Detail Lightening Impulse Test On All The Three Phases Of HV Terminals At 550 kVp And
On All The Three Phases Of LV" Terminals At 170 kVp.
Ref. Standard As Per IS : 2026 Pit - UI - 2009, Test Voltages Was Specified By The Customer And
Customer Technical Specification.

TEST ON HV TERMINALS :
Peak Magnitude (kVp)
ID - Phase (Tap No.: S) IV - Phase (Tap No.; I) 1W - Phase (Tap No.: 17)
Sr. No. Test Application Detail
Up (kVp) Page No. Up (kVp) Page No. Up(kVp) Page No.
1 Reduced Full Impulse Wave -378.1 15 -386,1 16 -387.3 17
2 100 % Full Impulse Wave -543.3 15 -550.6 16 -5S4;.9 17
3 100 % Full Impulse Wave -543.5 15 -550.5 16 -554.3 17
4 100 % Pull Impulse Wave -543.3 15 -550.1 16 -554.8 17

^ TEST OK LV TERMINALS :
Peak Magnitude (kVp)
Sr. No. Test Application Detail 2U - Phase 2V - Phase 2W - Phase
UP (kVp) Page No. Up (kVp) Page Wo. Up (kVp) Page No.
1 Reduced Full Impulse Wave -109.5 18 -111.6 19 -111.3 20
2 100 % Full Impulse Wave -166.2 18 -167.9 19 -168.3 20
■- 3 100 % Full Impulse Wave -167.6 18 -167.2 19 -168.2 20
4, 100 % Full Impulse Wave -168.4 18 -168 19 -166.7 20

Remarks : From the observation of enclosed osciliograohic records, it is concluded that the transformer Conforms to
the requirements of the above mentioned standards with respect to the test carried out.

Tn v.

Tested By : /■'' -Y Approved By: Witnessed By :

'lrrQt>
Cnirag Makavana, ^ Vacant Prajapati, Anuj Pratap Singh.
Asst. Manager Testing,AsstTManager Testing, Ebcecutive Engineer ET & CD
AEPL, V.U. Nagar. AEPL,,V.U. Nagar. UPPTCL, Gr. Noida
COMPANY: Atlanta Electricals Pvt Ltd., Gujarat.
CLIENT: UPPTCL, Lucknow. Date: 10.09.2018
Transformer Sr. No: AET1291/90 Transformer Rating: 40 MVA, 132/33kV.

Page:15 Of 30
1. REDUCED FULL IMPULSE WAVE 1U PHASE 3.100% FULL IMPULSE WAVE 1U PHASE

ISO ;.•*•• :>**-:-* • ... ,


,-:*,,.. j ... ^ ••• -•1 ^ -.r-T—
MO . . ; • .H -*..: 246* 'JJ'
12C ■ .*•.•; *. .vi.:• *.. :
7.ac- .*. v:..... .. ............ .^
;
Has, -125 ■ > •• ■: T* • •>
-2«5 5*
•■■r* *1 .2L •540
-3ia' ^ ...... .,4....... y;.., , ,'i :. .*
. . . , . , . ^. . . . - . ... « i... , . .;. . . . ^ .....
•Soc. : . ;; . .ft . . . : !
-Km. . - i"'v-. » . - ;• ; . ;: .tv'.-. 4 .■.. .. •.,
-720' -720 — ft ft—-ft——;-'ft—ft*'.:
5 ta M 3$ -48 • SC ?S. " S* as -.53 .iEo Q 4£ S4 as 43 SO 72 .24 35 IBS- 120
Upk^mikv, J1=1125S US, 12=50.1.1 uS IuS] Upk—643,5 kV, 11=1.249 u S, 72-49,97 uS luSJ
13S • •*•• •^..............,.... -■25, — '. . ;
*52 •• I • • • - ■ M • -,• •, - --.^V 5 ■ 5®
■JE . . ...... , v . . •. ;■ •.• , , ..2 .... , ; .■ ...... .• 4E '■ ;^:v • 'ft* . ..ft - ft/.ft. .-..ft"., v .•A. .v.
> yv , /\ '
-4S \pj -4S
2 ■as. V------ > : -T,... K • -• • • - -
-las.'. r --ft'ft •-••--.■ft -■
-1SS y
•2IS
-2TB
"3 20* se- so .0 as. £S ».
Apk=-84.64 Amp £US3 Apk=-121.7 Amp [uS]
seo • • • ••;• • ••••i- '*- ■• . .2. . . ; .
24®; : ■; ■ ... ... SMS f , ;. i . :■
520: :•■ •••; :•••:■
c
-f2b: ^2S
-240 ;••••• •:>

*20, ^vv...,T.
.*11 Si 35 ii SO *72* U 3S ■ 1C»: 120 ■O 12 2-4 "2 S4 m us
Upk=r543.3 kV, 11=1,258 y S, 12=49.96 uS - [US] Upk--543.3kV, 11=1.24803, 72=60.02 oS: im
its —TTTT— 7 ..
SB
A : :
.... ■*.5:
<
^5S* y. , . . .T ; > .1 . < ^..< ft ., v. ......... .11,,..
-530. . ........,.,.............
•22S- -KS
-2TC -220
0 SC.
A:pk=-121,9Amp [«S3 ftpk—121.5, Airtp [US]

2.100% FULL IMPULSE-WAVE 1U PHASE 4.100% FULL IMPULSE WAVE 1U PHASE

ft,- . , V vft
/gj
Tested By: Witnessed By:
COMPANY; Atlanta Electrlcals Pvt. Ltd., Gujarat.
MJ CLIENT: UPPTCL, Lucknow. Date: 10.09.2018
Transformer Sr. No: AET1291/90 Transformer Rating: 40 MVA, 132/33kV.

Page:16 Of 30
1. REDUCED FULL IMPULSE WAVE IV PHASE 3.100% FULL IMPULSE WAVE IV PHASE
3Sf
•as? —•—n SiEC-
lift .... : J4C
V - : ■ - *... *i - 12ft
.v- ■ ; > 0-
: > ■ ■ "■ • 1 ^25
S
- -JES
• ^esa n--^'
-5KJ,
-720 - • ' - - * -'JT ;.....;;, .j,.
■ ■. ••.. -7.23.
. ^ 4S so ?j 24 ' 35 '-OS 120
Upk=-38g.l kVs tl=.l,253 US, 72=48.92 aS
m ^ .. •;4 ^ ■« IE M JT
ilp^SSO.S kV. TiJ=1;242 uSj 12=48.81 uS
135
•" T. .i ri
.51?
"45 . ,.v * ^^ >
0
■■us--]
K
-135 ...1 ....... ^ ;■
-ISO- .........
-225 " ........
■47S ;
—- : *
^ BO so.
Apk=-7597 Amp |uS]
Apk=-1 Q7.8 Amp r«sj
35C
140
120

■'.20:
£ -s « -i-:s
£ -2®.

...
K
' ^ ~^—ir—w 110 O 12. 24
Upk=-S50.6kvt T1=1.242 u S, 72=48.84 tlS [tiS] 12i 120
•* " maj
IS
56
4S
0
rx fw
S .0 -45
•73S £ .3 i/y: -i- • • •
-ISO. itSS. ... * '
-IIS- -US® i. . v ^ .
--270 . -225 .7, . _ •■ '• ■•X ' V"
-270
"
Apk~1(Jf Amp 30
Eft SC
ApkM 07,6 Amp lusi

2.100% FULL IMPULSE-WAVE IV PHASE 4.100% FULL IMPULSE WAVE IV PHASE

^ ^ »,vrA/~
1 . if- ■

Witnessed By:
COMPANY: Atlanta Etectrlcals Pvt. Ltd., Gujarat.
CLIENT: UPPTCL, Lucknow. Date: 10.09.2018

Transformer Sr. No: AET1291/90 Transformer Rating: 40 MVA, 132/33kV.

Page: 17 Of 30
1. REDUCED FULL IMPULSE WAVE 1W PHASE 3.100% FULL IMPULSE WAVE 1W PHASE

140 -im ' '•> ■ ■ ' '• i'4 • ..... : ; -7 1


* *•».
■•20
126
■a ' "■ <; ;
'
^ -123 p'f' '• -f-
£
■•35B •■■■* • ... r........,•,.f• •..
HJS ■
-sas
■TIC
c :::!;
^ ^ ^ ^ ik' ^ 24 ae
kV, 11=1437 us. 12=47.73 us {usj 4S fiC T2 5,- as tea- •iw:
Opk-5S4.3 KV, 11=4.324 uSs 12=47,38 u S [USJ
135;
, . v . ... , , . ....
a? • '''' ' •'•■■■
r . 45 •■>.■> • ■■■
........
6 /. \ *._
-45
V/" ■ • /•■ . A.v ,. ;■
? ■•••
■25S
-276
;
35 £C -i?—J
Apk=-S8.21 Amp
Apk-126 Amp [US]
■ 3SC.
246.' •V
1SS v *. . i ^ . . . .v. ■ ;■
.c 6 ; ; •. " " ^ ' •; ■' ■ r
•Mi-
-:-4a '•• ■: i ."... ~v ^ r-T
•S-usa
-CM
-<5S
""' • f :... ■
■ssa
-3iB
;- • ■ • '•713 ■..
& iv 4 .
^ «• 8+ ~ ^0 12
Upk=r554.9kY Ti=1^29tiS, 12=47.32 uS •-.3S. «. ;5B- «• ¥4 9=- * ;6S 125
■ . Upk=-S54.8 kV, 71=1.329 uS, 72=47.36 uS [«S|
—rrr
•s© , ....
4= V ..... V ... . . .s .
, r\
-JS
rr..... .y.
•135 .. J .1. ,.....
-tSB -155
X,3........T, .-533
■5IS . . .• ._
-27C • -ISS
v.-4..;, »• .yvLv..., •. ■CsS V.'. .. vk
.w sa so. 35
Apk=.126.2 Amp 5C
["S3
Apk=-126.5 Amp

2.100% FULLJIVIPULSE WAVE 1W PHASE 4.100% FULL IMPULSE WAVE 1W PHASE

Tested, /,?/ Witnessed By:


COMPANY; Atlanta Electrlcals Pvt. Ltd., Gujarat.
CLIENT: UPPTCL, Lucknow. Date; 10.09.2018
Transformer Sr. No; AET1291/90 Transformer Rating: 40 MVA, 132/33kV.

Page:18 Of 30
1. REDUCED FULL IMPULSE WAVE 2U PHASE 3.100% FULL IMPULSE WAVE 2U PHASE

.5?

-TIE'
-225
■4?5 ■«S
« 3S <S' 9S .-71 ,,S4 «;•, 24 as 4S -so- is gjj •
Upk=.1Q9.5 kV. T1=0.994t uS, 12=44.08 uS Upk=-ie7.0kVs 11=0.9532n S, 12=44.02 uS
• -... 4 . . . <35
• ■ - y>

!
s
-1-SE -tss
-225

Apk=-72.Z9 Amp fuSJ Apk—110,1 Amp uSl

*
i35
•■.gc -533
-225 -22S.
i; -275
M
® v.''42 50
"2 34 5? -.£3 HQ ,A
'- ^ 25, <£ :EC 75
Upk=-1SS.2 kV( T4=0,9601 u S5 12=44,09 uS TuSJ 535 720
Upk=-168.4kV, 11=0.9515 u£, 12=44.04 uS
525 3

E .a
-fJS ■-E
■i - ■ • , ......
-s:s
<70 . ..... <70

Apk=-109.3 Amp [US] Apk=-110-7 Amp [uSJ

2. 100% FULL IMPULSE WAVE 2U PHASE 4.100% FULL IMPULSE WAVE 2U PHASE

is nK
Tested By : ■ V. Witnessed By :
COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat.

CLIENT: UPPTCL, Lucknow. Date: 10.09.2018


Transformer Sr. No: AET1291/90 Transformer Rating: 40 MVA, 132/33kV.

Page: 19 Of 30
1. REDUCED FULL IMPULSE WAVE 2V PHASE 3.100% FULL IMPULSE WAVE 2V PHASE

5* ■
*• -so
-iSS'
-<SD -tas.
~fS3

14
as 4s: so n, ei
ppk=-tt1.6kVf T1=1.003 uS, 12=44.13 uS f"S| 103•
VpK—167,2 kV, 11=0.9536 uS, 12^44.03 US
135
,S&
-IS ■- - , . . . ..... . , _
•5 _• _ ■
-45 -A , : -
a. ^ , . , a.' ■30
"525 , . . ... . . ..I . . _
-tas
-!SS :. .■■■,... .....;....
-tss
-IIS -J25
' ...-
■ .SO:
Jf
' . sc
Apk=-73.77 Amp M APK=-109.8 Amp
-■ 5

* 30
-135
■f
-:;5
-a.-a -V7P
i- as AS £C 7, tea- sic
UpJcMSmV 11=0.9555 uS. 72=44.03 US 123 IflJ
[uS] Upk-ISSkV, 71=0.9466 «S, 72=44:03 uS fuSI
us

-135
:5
-3-0

Apk—110.4 Amp £uS]


Apk—110;3.Amp [US]

2. 100% FULL IMPULSE WAVE 2V PHASE 4.100% FULL IMPULSE WAVE 2V PHASE

Tested By: Witnessed By


COMPANY: Atlanta Electrlcals Pvt. Ltd., Gujarat.
CLIENT: IIPPTCL, Lucknow. Date: 10.09.2018

Transformer Sr. No; AET1291/90 Transformer Rating: 40 MVA, 132/33kV.

Page: 20 Of 30
1. REDUCED FULL IMPULSE WAVE 2W PHASE 3.100% FULL IMPULSE WAVE 2W PHASE
«as •• ...... - v..,:..:. •:v. X.v. v..
sc ••O" ,.
45-
' ■ ■ • X ' '■ - • • •.' ;• r - '
" ' P.
[• •• ^ " ■ ' i>
£
^SS'. " * * ' *V ' • i
-JM v- ' ■ - •. ..... ^. ..* . . . : r . . J .
.-2JS- ....., .■ . v.... _ V- • •. *-
<70 -»5:
: - • ■■
->= 7S U 9® tog' ' tSO" .® *£, a as 55
Upk^1113kV, 71=1,005 US, 72=44.05US [usj ' «« 35 133.-
Upk=-168.2 KV, 71=0.9479 uS, 72=44.6.1 US fuSJ

-3D E
-S3S:
-155
-JSC
•2Zi
-K5
so.
A:Pk=-f3.64 Amp [uS]
Apk--110,5 Amp [usj
«£" .....
36
4£ ■
C-'
— -«£': •. , , .;
£ 36 ■■■•.•.• .•.- ■ •:
1
£ -56
•iSS
-13S
-ISC .: ; iD
-335. •. . ;
' -s?o 4...... 175
■52 S,4 SS 42' so ■?2 3.4 ■SS tCJ 1-0. 3
II • 23. JB as SS St SE fsa -SJS
Upk=488^kV. 71=0.9553 uS, 72=44,03 US {uS| Upk—166.7 kVj 71=6.3539 uS; 12=44,02 uS fuSJ

o
<s
S -SB
1 .0
H8S
"135
-ISC.
-ISO
-OSS- •215
-270'
"370
Apk~110.5 Amp EC go
fuSJ Apk==-109.7 Amp [u Sj

2.100% FULL IMPULSE-WAVE 2W PHASE 4.100% FULL IMPULSE WAVE 2W PHASE


y'Y .X

111
Tested By: ^ V Witnessed By;
\ /
F:QC:40, Rev; 10, dated 09-06-2018
ATLANTA ELECTRICALS PVT. LTD.

TRANSFORMER TEST REPORT


Customer : U.P.POWER TRAjVSMI3S10K CORPORATION LIMITED. LUCKMOW 21 OF 30
IW.O.No.: |AET 1291" Sr.No. 1291/90

IS. SFRA TEST :

Page. No. Tap No. Source and reference Response Terminal Terminals Connected
(Vin) ( Vout) Earthed together
22 1 1U IN
23 1 IV IN ....
24 1 1W IN
25 1 2U 2N
26 2V 2N ....
27 1 2W 2N
28 1 1U IN .... 2U - 2V -2W
29 1 IV IN 20 • 2V .aw
30 1 1W IN .... 2U - 2V -2W

Note ; SFRA Qraphs are enclosed on Page 22 to 30

Tested By Witnessed By :

Harsh Hirpara . : Anuj Pratap Singh


Sr. Testing Engr. Executive Engineer ET & CD
AEPL, V.U. jf agar. UPPTCL, Gr. Hold a
COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat. Date: 11.09!2018

Q CLIENT; U.P, POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW.


Transformer Sr. No; AET 1291/90.
/ITLANTk
ELECTR1CALS PVT. LTD. Transformer Rating: 32/40 MVA, 132/33 kV.

Page No.: 22 OF 30

Transformer: Manufacturer: AEPL, Serial Number: 1291 90 - 1U- 1N , Tap No.: 1-Open Circuit_2018-09-11_ 13-50-25

-104

-20-|

-30 4

/ -so-;

-SO 4

-70-:

30-

-SS.S0&4
13 100 IK 10K 100K 1M 1.989.019
Frequency. Hz.

f ,v -

Tested By: I.J Witnessed By :


COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat. Date: 11,09.2018

01 CLIENT: U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW.


Transformer Sr. No: AET 1291/90.
ATLAKJOk
ELECTRICALS PVT. LTD. Transformer Rating: 32/40 MVA, 132/33 kV,

Page No.: 23 OF 30

Transformer: Manufacturer: AEPL, Serial Number: 1291 90 - 1V- 1N? Tap No.: 1-Op.en Circu!t_2018-09-11_J3-54-49
Magnitude;!- IV- TM Tap No. 1-Open Circuit 20184)9-1 > 1
i-,

-10

-20-:

-30-

-40-

■ cs
. "=■ -M) —

-50 i

-70-

-88.9C>6
13 K tOK 110 K 1M .1,989,019
Frequency. Hz

!VI .
^ y\\
Tested By: '^9d
Witnessed Byr

&
COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat. Date: 11.09.2018
Q CLIENT: U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW.
Transformer Sr. No: AET1291/90.
>4TLANTJv
ELECTR1CALS PVT. LTD. Transformer Rating; 32/40 MVA, 132/33 kV.

Page No. : 24 OF 30

Transformer: Manufacturer; A.EPL, Serial Number; 1291 90 - 1W- IN, Tap No. : 1 -Open Circuit_2018-09-11_13-59-17
Magnitude 1W-1N, T3p No. 1 -Open/€if6uit -20tS-.0&.11 13-53^17 . .

-10-

-20-

-30-

-40-

-50-

-G0-

-J

-&2.50S i
,100 IK 10K iODK 1M 1.939.019
Frequency. Hz

Witnessed By;
—4^ ^
COMPANY; Atlanta Electricals Pvt. Ltd., Gujarat, Date: 11.09.2018

0 CLIENT: U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNQW.


Transformer Sr. No: AET 1291/90.
/:TLA.4Tk
ELECTRiCALS PVT. LTD. Transformer Rating: 32/40 MVA, 132/33 kV.

Page No.: 25 OF 30

Transformer; Manufacturer: AEPL, Serial Number: 1291 90 - 2U - 2N , Tap No. ; 1-Open Circuit_2018-09-11_ 14-03-53
Magnitude. 2U - 2N Tap No l-Oj>eharcuii_20iS-Q9-11 j4-03r53

-10

-20-:

-30-i

-4Q-

-50-:
1
-60-i

-70-i

-50-

' . -SS.90& •
100 IK 10K 100K 1M 1,985,01 &
Frequency. Hz

>/*■ /x

. \.T
Tested By; Witnessed By :

<<i*y
COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat, Date: 11.09.2018
CLIENT: U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW.
Transformer Sr. No; AET1291/90.
/ITLANm
ELECTRICALS PVT. LTD. Transformer Rating; 32/40 MVA, 132/33 kV.

Page No.26 OF 30

Transformer; Manufacturer; AEPL, Serial Number; 1291 90 - 2V - 2N , Tap No. ; 1-Open Circuit_2018-09-11_14-08-01
2V ?N Tap No l-Opennrcoit 2013^09-11O4-0&01.
1 —:

-10

-20-

-30-

-40 —

t? -50-

-60-

•70-

-80-1

•£S.9C'6 i
13 100 IK 10K ICOK 1M 1.389.019
Frequency. Hz

T i.

■\ .7 \

Tested By ; Witnessed By
COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat. Date; 11.09.2018

Q CLIENT: U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW.


Transformer Sr. No: AET 1291/90.

ELECTRICALS PVT. LTD. Transformer Rating: 32/40 MVA, 132/33 kV.

Page No. : 27 OF 30

Transformer; Manufacturer; A,EPL, Serial Number: 1291 90 -- 2N, Tap No.:1-Open Circuit_2018-09-11_14-11-49
m--ZN. fap.No. l^oenUrcu!t±2Q184»-lV44^,M9;

-10H

-20-|

-30-j

-40-

-50-!

-50-i

70 "j

-83.9C6 i
13 100 IK 10K 100K 1M 1.989.019
Frequency. Hz

/-O''
V.,'-, \
N:
'^
r"!
■ ?■- ■
Tested By: I A':;.', WitnessecrBy
' v-1,
COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat. Date: 11.09.2018

ill CLIENT: U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW.


Transformer Sr. No: AET 1291/90.
JlTLANTk
ELECTRICALS PVT. LTD. Transformer Rating: 32/40 MVA, 132/33 kV.

Page No. : 28 OF 30

Transformer: Manufacturer: AEPL, Serial Number: 1291 90 - 1U - IN, Tap No.: 1-Shortcircuit_2018-09-11„14-16-50
r
|«syu IN ip No: I-Shortarcuit^MlS-OS: 11.^14-16-50
1

-1q4

-20-i

-30 J

-40-|

-50 J

-so^i

-70 ^

-80 J

•89.906 -
13 100 IK I OK ICC'K 1M 1.939.019
Frequency, Hz

WitnesseaBy:
COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat. Date: 11.09.2018
CLIENT: U.P,POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW.
Transformer Sr. No: AET 1291/90.

ELECTRICALS PVT. LTD. Transformer Rating: 32/40 MVA; 132/33 kV.

Page No.: 29 OF 30

Transformer; Manufacturer: AEPL, Serial Number: 1291 90 - 1V - IN, Tap No.:1 -Shor{circiiit_2018-09-11_14-21-13
T . -jN/WUfe;}-Shg^lt^l^liM-21/13
m

-io J

-2Q-:

-30-

-40-

cn
-50-
- ^
-60-

-70-

-30-:

5.506 - i
100 IK IQK 1COK 1M 1.529.019
Frequenc/. Hz

- T-nX

Tested By: Witnessed oy


V- j/.
COMPANY: Atlanta Electricals Pvt. Ltd., Gujarat. ■ Date: 11.09.2018

Q CLIENT: U.P.POWER TRANSMISSION CORPORATION LIMITED, LUCKNOW.


Transformer Sr. No: AET 1291/90.
ATLAHTX
ELECTR1CALS PVT. LTD, Transformer Rating; 32/40 MVA, 132/33 kV.

Page No.: 30 OF 30

Transformer: Manufacturer; AEPL, Serial Number; 1291 90 - 1W - IN, Tap No.; 1-Shortcircuit_2018-09-11_14-25-26
ite lNtTapiSio '-atorcuit Mm®* 14253®^

-10-

-20-

-30-

-40-j

I '2
r ^ -50s

-60-|

-70-1

-30-

-38.90&
i:< 100 IK 10K 100K 1M 1.%S,019
Frequency. Hs

a.\
Tested By: vr.— ■ '.n / Witnessed By
<J. NX1-::
I ATLANTA ELECTRICALS PVT LTD
PHYSICAL & DIMENTIONAL INSPECTION TEST REPORT
Date:-11 & 12.09.2018
Customer:- U.P. Power transmission corporation Ltd. Transformer W.O.: AET1291
bating:-40000 kVA, 132/33 kV Transformer. Transformer Sr.No.: 1291/90

SR.NO. CHECK POINTS [Remark


1 Punch mark of Serial Number on the jacking plate
1291/90
2 Check of all the bought out items as per approved GA Drawing.
Checked & Found As Per Approved Drawings.
3 Oil leakage Test. 10 PSI Pressure Maintained for 12 Hours. No leakage
found.
4 Clearance between PH to PH (H.V) Spe. 1430 mm 1555-1550 1U-1V&1V-1W
5 Clearance between PH to PH (L.V) Spe. 350 mm 605-600-600 2N-2U, 2U-2V & 2V-2W
6 Clearance between HV Phases to Earth. Spe. 1270 mm 1500
7 Clearance between LV Phases to Earth. Spe. 320 mm 390
8 Over all Dimension L Spe. 7760 mm 7630 +/■ 5% Tol.
9 Over all Dimension B Spe. 4900 mm 5045 +/- 5% Tol.
j. * Over all Dimension H Spe. 6000 mm 5825 +/- 5% Tol.
11 Plate thickness (Top & Bottom) Spe. 16,16 mm 16.10,16.50
12 Rail Gauge Oist. Spe. 1676 mm 1676

Checked iSyf- 'j":1 '-•/-}/


Witnessed by:-
- w:
Ni
Anuj Pratap Sing,
Engr. (QG)k
Executive Engineer ET & CD,
AEPL, V.U. Nagar. '/
UPPTCL, Gr. Noida.
■l- 12-v no
i\-}. PRECIMEASURE CONTROLS PV LTD
vfwvf.precuneastae.com
TEST CERTIFICATE
hodne1. ■THB Date: 24/07/2018 Serial Number FunnatNo. QA-FM-17
P1804222.1
Purchase Order Order Date
AT1MJTA EIXCTRICALS PVT.LTD. lJOD/RM/1819/eOB41 04/07/2018
BeJetcnce Master Cctlificaic aombci. 49407 Due date 14.0848
Product Doscriptian
Specification Type Specification Descriplion
MODEL
!IANGE
NO. OF SWITCH
TYBRID ADD ON 1
SWITCH TYPE :016A .
HAL GRADUATION 1
ACCURACY OF INDICATION tl% OF FSD
SWITCH RATING
SWITCH DIFFERENTIAL i TO 9'C f6±3'0 FOR SI & S2.8 TO 40'C FOR S3.S4.SS & S6
STANDARD THERMOMETER READING IN *0 40 60 80 100 129 us
INSTRUMENT READING IN'C FORWARD | 40 60 60 100 120 140 I
INSTRUMENT BEADING IN *0 REVERSE . (j j 61 | 101 j (
REMOTE INDICATOR BEADING IN "C •i 40.3 | 60.2 80,3 100.2 1202 j 139.8
CURRENTOUTPUT-i IN mA ((831 | 10.43 | 12.59 14.70 16,84 j 18.93
CURRENT OUTPUT-2 IN mA !Mi ! 10,43 12.59 14.70 16.84 .( 18.93
CURRENT OUTPUT-3 IN m A . j) • _J
CURRENT OUTPUt-4 IN mA 1
?.W|TC!J 21 | 52 . S2 Si S3 | SI
[switch SETTING IN 'C jioa |100 60 80 j| |
jSWITCH DIFF. SETfiKG IN "C 1(6 1® 10 j 10 if il ' . i
(SWITCH ON IN'C 1190 |ioi 60 | 70 j 80 (1 ' j
(SWITCH OFF IH'C ifSS (96 so ( 60 |™ 11 1
(SWITCH DIFF. OBSERVED IN 'C 06 (s • 10 ( 10 1 10 [j
GRAOIENTREADMS
G1UPIEKT SI 22 52 Si ss
i SECOWDARY CURRENT IN AMPS
jREQ. TEMP. RISE OVER OIL IN 'C
jvm BEADING in
REMOTE INDICATOR READING
CUBBEKT OUTPirr-l IN mA
ICURRENT 01HPUT-2 IN mA '
ICURRENT OtnPUr-3 M m A"
CURRENT OUTPUT-4 IN mA
RV, HV2 HV4
INSTRUMENT on/vm OTi/vm OTE INDICATOR
TEST VOLTAGE REMOTE INDICATOR
WITHSTOOD SOOV AC, SO WITHSTOOD 2,5 KV AC; 50 D SOOV AC, 50 WITHSTOOD ifiKV AC;
HZ/60H2 HZ/60HZ 50 HZ/WHS
TERMINAL DETAILS 12 514 TERMINALS TO AU. OTHER TERMINALS 4 & 9,10 TERMINALS TO 14 & 16 TERMINALS TO
EARTH FOR ONE TO EARTH FOR ONE WIH FOR ONE MINUTE EARTH FOR 0MB
MINUTE MINUTE ' KflNUTE
IrfSCLATlON RESISTANCE TEST
INSTRUMENT 0T1/WTI/REM0TE INDICATOR
[IEST VOLTAGE 500VDC
(TERMINAL DETAILS ALL TERMINALS TO EARTH
MEASURED VALUE BEFORE & AFTER H.V,TESt GREATER THAN 20M OHMS
RESULT n PASS
■TEST CONDITIONS
L CONTINUCa/SLY STORED OIL BATH USED,
2. OIL TEMPERATURE READINGS WERE TAKEN AFTER 5 MINUTES THE RATH REACHES STEADY TEMPERATURE.'
3. wn UD (COVER) CLOSED WHILE TESTING, HATH TEMPERATURE f4AINTAINED AT 60/75"C WHILE CHECKING GRADIENT.
FOR CHECKING GRADIENT iwri) IS 40 MINUTES, AFTER CONTINUOUS PASSING CONSTANT CURRENT THROUGH THE HEATER CIRCUtT
LINDICATIOH ACCURACY FOUND WITHIN ilti OF FSD,
2. SVflTCH OPERATION IS FOUND WITHIN iZS'Q.
3. REMOTE INDICATOR / PSU READING FOUND WITHIN ii\ OF FSD.
RematAs
Tested &>" ' Umesh Approved By: Madbusudaa
This Is an electronically generated certificate and does not require any signature.
PRECIMEASURE CONTROLS PVT. LTD,
www.precmieasure.com
TEST CERTIFICATE
•■iOdllC! |-PHB )ate: 11/09/2018 Serial Number Format No: QA-FM-17
P1802030.ll
Customer Infotmation
Name Purchase Order Order Date
ATLANTA ELECTRICALS PVTJ.TD, POD/RM/1718/01301 06/08/2013
Reference Master Ceitificutc number; SC067 Due Dt. 03-08-19
Product Oescripl
SpecilicatioQ Type __Sj>ecification Descri£tio^__
dODEL 005AH
IANGE I-ISO'C
JTl/WTI vn
TO. OF SWITCH is
JAPPILARY LENGTH ;m
iYBRID ADDON 15HT2 80-17
SWITCH TYPE :016A
NAL GRADUATION •c
ACCURACY OF INDICATION :1% OF FSD
SWITCH RATING SAMPS CONTINUOUS 250VAC, 0.5AMPS 25QVDC FOR MAKE OR BREAK
WITCH DIFFERENTIAL 1 TO 9'C (6t3*C) FOR SI & S2.8 TO 40*C FOHS3.S4.SS&S6
TEMPERATURE READING
| STANDARD THERMOMETER READING IN "0 43 m fill 100 120 HQ
[INSTRUMENT READING IN 'C FORWARD 40 1 60 80 100 120 139
[INSTRUMENT BEADING IN 'C REVERSE 1 61 101
jREMOTE INDICATOR BEADING IN 'C 40.1 60.0 79.8 99.8 19.8 139.0
[CURRENT OUTPUT! IN mA 8.31 j 0.41 12.51 14.66 6.80 18-92
[CURRENT OUTPUT-Z IN mA 6.31 041 1251 14.66 6.80 18.92
[CURRENT OUTPUT-3 IN mA Zl
[CURRENT OUTPUT-4 IN mA 1
SWITCH READING
SWITCH SI S2 S3 SA 35 35
[switch setting in 'C 90 100 50 70 [80
[switch diff. SETTING IN "C 6 6 10 10 lio
[SWITCH ON IN *0 90 100 60 70 [so
[SWITCH OFF IN-C 85 95 50 50 i 70
[switch diff. OBSERVED IN 'C S 5 10 10 110
GRADIENT GRAPH
GRADIENT READING
GRADIENT £1 £2 1 C3 SA 35
[CT SECONDARY CURRENT JN AMPS 0 15
■REQ. TEMP. RISE OVER OIL IN 'C 0 16
[WTI READING 60 76
[REMOTE mriCATOH READING 60.0 75.8
[current OUIPUT-I IN mA 10,41 1L9T
[CUHHENT OUTPUT-Z IN mA 10,41 1L97
[CURRENT OUTPUT-3 IN raA II
[CURRENT OUTPUT-4 IN mA II
HIGH VOLTAGE BREAKDOWN TEST
HV1 HV2 HV3 HV4
INSTRUMENT on/wn OTt/wn REMOTE INDICATOR REMOTE INDICATOR
TEST VOLTAGE WITHSTOOD SOOV AC, 50 WITHSTOOD Z5 KV AC; 50 WITHSTOOD SOOV AC, SO WITHSTOOD 2£ KV AG,
HZ/60HZ HZ/60H2 HZ/60HZ 50HZ/60HZ
TERMINAL DETAILS 12 & 14 TERMINALS TO ALL OTHER TERMINALS 1-4 & 940 TERMINALS TO 14 & 16 TERMINALS TO
EARTH FOR ONE TO EARTH FOR ONE EARTH FOR ONE MINUTE EARTH FOR ONE
MMUIE MINUTE MINUTE
1.R, TEST mi
INSTRUMENT [OTl/WTI/REMOTE INDICATOR
TEST VOLTAGE [500VDC
TERMINAL DETAILS [ALL TERMINALS TO EARTH
MEASURED VALUE BEFORE & AFTER H.V.TEST [GREATER THAN 20M OHMS
RESULT [PASS
L CONTINUOUSLY STIRRED OH. BATH USED,
2. OR. TEMPERATURE READINGS WERE TAKEN AFTER 5 MINUTES THE BATH REACHES STEADY TEMPERATURE.
3. wn LID (COVER) CLOSED WHILE TESTING. BATH TEMPERATURE MAINTAINED AT 60/7S*C WWLE CHECKING GRADIENT.
4. TIME ALLOWED FOR CHECKING GRADIENT (WT1) IS 40 MINUTES, AFTER CONTINUOUS PASSING CONSTANT CURRENT THROUGH THE HEATER CIRCUIT.
TEST RESULTS
L INDICATION ACCURACY FOUND WITHIN ±1% OF FSD,
2. SWITCH OPERATION IS FOUND WITHIN 12.5*C.
3. REMOTE INDICATOR / PSU BEADING FOUND WITHIN il% OF FSD.
Remarks
Tected By. Umesh Approred By. Madhusudan
This is an electronically generated certificate and does not require any signature.
rPRECIMEASURE CONTROLS PVT. LTE
www.precimeasure.com
TEST CERT1RCATE
^PHB jJa'": J?! fena! Number
P1802030.12
Customer Iniorrration
Name Purchase Ordei Order Date
ATLANTA ELECTRICALS PVTXTO, POD/RM/1718/01301 06/08/2018
HeSerence Masiej Cctttficatesumber, S0067 Due Dt. 03-08-19
Pfoaucl Description
^^Spedlication Description
MODEL
RANGE
yn/wn

IYBR1D ADD ON

STANDARD THERMOMETER READING IN -C "48 SO 1D0 12Q 132


IlNSTHUMENT READING IN 'G FORWARD 40 tT" [80 100 120 139
[INSTRUMENT READING IN 'C REVERSE 161 101
[REMOTE INDICATOR READING IN *C 40.0 59.9 [79.8 99.9 119,8 139.4
[CURRENT OUTPUT-l M mA e.30 10,41 [1ZS0 14.66 le.si 18.95
[CURRENT DUTPtJr-2 IN mA 830 b.41 (12.50 14.66 16.81 18,95 j
[CURRENT OUTPUT-3 IN mA
IcURRENT OUTPUr-4 IN mA
SWITCH READING
SWITCH SI S2 £3 1 Si 1 ss Si
[SWITCH SETTING IN-C 90 [100 60 It70 |8()
[SWITCH DIFF. SETTING IN "C ||6 1® 10 II10 |lQ
[switch on IN *C [[go [100 59 1170 jso
[switch off in-c |)eg |9S 50 ||60 [70
[SWITCH DIFF. OBSERVED IN 'C )js Is Jl9 ||10 [10
GRADIENT READINO
1 GRADIENT SI S2 sa Si ss
|CT SECONDARY CURRENT IN AMPS Q 1,5
[HEO. TEMP. RISE OVER OIL IN 'C 0 16
|WTI READING 60 76
(REMOTE INDICATOH HEADING 59.9 76.1
(CURRENT OUTPUT-l IN mA 10.41 12.11
ICURRENT OinPUT-2 IN mA 10.41 1ZU
ICURRENT OUTPUT-3 IN mA
CURRENT OUTPUT-4 IN m A
flOH VOLTAGE BREAKDOWN TEST
1 ffifl HV2 HV3 HV4
INSTRUMENT jon/wn on/wn REMOTE INDICATOH (REMOTE INDICATOR
TEST VOLTAGE I WITH STOOD 500V AC. 50 WITHSTOOD 2.5 KV Ad SO WITHSTOOD 500V AC, SO | WITHSTOOD 2.5 KV AC, |
jH2/60HZ HZ/60HZ HZ/60HZ SO HZ/60HZ
FERMINAL DETAILS 12 & 14 TERMINALS TO ALL OTHER TERMINALS 1-4 S 9,10 TERMINALS TO 14 & 16 TERMINALS TO |
EARTH FOR ONE TO EARTH FOR ONE EARTH FOR ONE MINUTE EARTH FOR ONE
MINUTE MINUTE ■MtNUTE |
NSULAIIDN RESISTANCE TEST
i.R.T^?r mi
(jon/WTl/REMOTH INDICATOR
[TEST VOLTAGE | SOOVDC
[TERMINAL DETAILS [[ALL TERMINALS TO EARTH
[MEASURED VALUE BEFORE & AFTER HV.TEST jjGHEATER THAN 20M OHMS
[RESULT ([PASS
I CONTINUOUSLY STIRRED OIL BATH USED.
. 2. OIL TEMPERATURE READINGS WERE TAKEN AFTER 5 MINUTES THE BATH REACHES STEAOY TEMPERATURE.
3. WTI LID (COVER) CLOSED WHILE TESTING. BATH TEMPERATURE MAINTAINED AT 60/75-0 WHILE CHECKING GRADIENT.
4. TIME ALLOWED FOR CHECKING GRADIENT (WTI) IS 40 MINUTES, AFTER CONTINUOUS PASSING CONSTANT CURRENT THROUGH THE HEATER CIRCUIT.
TEST RESULTS
1. INDICATION ACCURACY FOUND WITHIN 11% OF FSD.
2. SWITCH OPERATION IS FOUND WITHTK 12.5*0.
3. REMOTE INDICATOR / PSU READING FOUND WITHIN ±1% OF FSD.
Remarhc
TeMedBjr. Umesh Approved By; Madhuaudan
This is an electronically generated certificate and does not require any signature.
TEST REPORT / CERTIFICATE Document No:
V2:QS:02:11:312116 Rev 0

PRODUCT FAMILY PRESSURE RELIEF VALVE (T6)


MODEL T5-1 (0.42) •SIZE 150 mm
SERIAL MO 1846 EV Report No. T1846
Customer Name ATLANTA ELECTRICALS P.O. No- POD/RM/1819/00857 Date Oo-Jul-
PVT LTD 18
Invoice cum Challan No. VIAT2.1020.1819 Challan Date 13-Jul-18
Operating Pressure 2
0.42 kg/cm

Accessories
Gasket Semaphore Shroud
YES NA NA

Test Name and specification Acceptance criteria OBSERVATION


Porosity Test
Porosity Test at 3 Kg/cmJ(294 KPa, 42,6 PSI) for 2 minutes • No leakage Passed
Measurement of cracking/operating pressure using compressed Cracking pressure Tolerance Result
air.
The device should operate when subjected to cracking pressure as Upto0.90 Kg/cm2 ±0.07Kg/cm2 0.42 kg/cm2
per the tolerance given in acceptance criteria.
Above 0.90 & 2
upto 1.4 Kg/cm ±0.14 Kg/cm2
Switch operation check (Switched models only) In switched models, switches should reverse Passed
contacts when the device operates.
Flag operation check (optional) Flag should move to 'up' position after device Passed
operation.
Leakage test of finished material at slow rate of pressure rise No leakage up to 80% of specified cracking pressure Passed

Short duration dielectric test (Switched models only)


Between circuits and earth; 2kV RMS AC for 50 sec. No leakage of current detected during any test. Passed
Between contacts in open position: IkV RMS AC for 60 sec.
Type Test;
Enclosure Protection class Exposure to dust and water as per Below Conforms
classification of
EN 60529-1992
Without Shroud Material: IP 65
With Shroud Material : IP 67
GOODS APPROVAL CONFORMANCE TO TEST STANDARD CONFORMS

*******
\ Compliance This is to state and certify that our products were manufactured, calibrated, tested and accepted conforming to your purchase order, the test f
standard referred to in this document, and all relevant work instructions, drawings and procedures. We further certify that the onit(s) have been J
I Statement tested and meet all operational and product performance specifications. \

Product supervisor Quality manager

Distributed / Sold By: Viat Instruments Pvt Ltd (Unit-II) Viat Instrument Pvt Ltd(Unit-l) Vta.-
6, Neelkanth Estate, Module 2701 To 2704, Phase II, Shilpangan
Village-iyava, Block 181, Sector III, Salt Lake - ~ INSTBOMeNTS
S3nand-382110 Kolkata - 700098
AHMEDA8AD INDIA INDIA
Phone; (91) 7575804174/28 Phone (91) 9903805104 / (91-33) 23352925
TEST REPORT / CERTIFICATE Document No;
V2:Q5;02:11 (V106<N)Rev 1

Product Family MAGNETIC OIL LEVEL GAUGE (MOLG) ATMS TYPE


Model MOG SOS-ATMS (15D) Size 150mm
Serial No SSV02495 Report No. 18-19/SSV02495
Customer Name ATLANTA ELECTRICALS P.O. No. POD/RM/1819/00883 Date 07-Jul-
PVT LTD 18
Invoice cum Challan No. V1AT2.1212.1819 Challan Date 04-Aug-18

Test Name and specification Acceptance criteria OBSERVATION


Porosity Test
The body is placed under liquid with the transformer side No sweating or leakage through the body. , Passed
exposed to pressure of 3 kg/cm2 maintained for 60 seconds
Calibration Test Switch position and needle operation should Passed
A float arm length (FAL) as per conservator diameter at half be within +5%-0% of conservator dia when
scale marking is used to calibrate the needle position w.r.t the float is falling or rising.
the float levels.
Movement check of needle & float
The Float is moved manually to check if the both the float Free & continuous movement of float. Passed
and needle move smoothly and continuously.
High Voltage Test
2kV RMS, 50Hz AC voltage is applied between live terminals No leakage of current observed in each case. Passed
of the MOLG and the body.
Insulation Resistance Test
The insulation resistance (1R) is measured with megger < insulation resistance >20 MQ. >20 MQ
between the terminal and earthed body at 500 V DC. Meets the requirement.

Continuity Test for low level alarm contact The lamp should operate each time the Passed
The contact positions at low level are checked 20 times needle is at low level.
with a continuity test lamp
Type Test; (Performed/Not Performed)
Contact rating
5 A at 240 V AC No failure. Conforms
0.5 A at 240 V DC
1 A at 127 V DC

Compliance This is to state and certify that our products were manufactured, calibrated, tested and accepted confotming to your
purchase order, the test standard referred to in this document, and all relevant work instructions, drawings and procedures.
Statement- We further certify that the unitfs) have been tested and meet all operational and product performance specifications.

Product supervisor Quality manager

6, Neelkanth Estate, Module 2701 To 2704, Phase II, Shilpangan


Village - lyava, Block LB1, Sector III, Salt Lake Via-
Sanand-382110 Kolkata - 700098
AHMEDABAD INDIA INDIA INSTflUMCNTS
Phone: (91) 7575804174/28 Phone (91) 9903 80S 104 / (91-33) 23352925
TEST REPORT / CERTIFICATE Document Mo;
® V2:QS:02:11 MOG(N)Rev 1

Product Family MAGNETIC QIC LEVEL GAUGE (MOLG) NORMAL TYPE


Model MOG 506 (15D) Size 150mm
Serial No SV02254 Report No. 18-19/SV002254
Customer Name ATLANTA ELECTRICALS PVT P.O. No. POD/RM/1819/00883 Date 07-Jul-18
LTD
Invoice cum VIAT2.1212.1819 Challan Date 04-Aug-18
Challan No.

Test Name and specification Acceptance criteria OBSERVATION


Porosity Test
The body is placed under liquid with the transformer side No sweating or leakage through the body. Contlrms
exposed to pressure of 3 kg/cm2 maintained for 60 seconds
Calibration Test Switch position and needle operation should Confirms.
A float arm length (FAL) as per conservator diameter at half be within ± 10 mm of specified float position.
scale marking is used to calibrate the needle position w.r.t
the float levels.
Movement check of needle & float
The Float is moved manually to check if the both the float Free & continuous movement of float. Confirms
and needle move smoothly and continuously.
High Voltage Test
2kV RMS, 50Hz AC voltage is applied between live terminals No leakage of current observed in each case. Confirms
of the MOLG and the body.
Insulation Resistance Test
The insulation resistance (IR) is measured with megger Insulation resistance >20 MO. >20 MO
between the terminal and earthed body at 500 V DC. Meets the requirement.

Continuity Test for low level alarm contact The lamp should operate each time the
The contact positions at low level are checked 20 times needle is at low level. Confirms
with a continuity test lamp
TypeTest: (Performed/NotPerformed)
Contact rating
5 A at 240 V AC n No failure. Confirms
0.5 A at 240 V DC
1 A at 127 V DC

Compliance This is to state and certify that our products were manufactured, calibrated, tested and accepted conforming to your ■
purchase order, the test standard referred to in this document, and al! relevant work instructions, drawings and procedures,
Statement We further certify that the unit(s) have been tested and meet all operational and product performance specifications,

Product supervisor Quality manager

6, Neelkanth Estate, Module 2701 To 2704, Phase II, Shiipangan


Village - lyava, Block LB1, Sector 111, Salt Lake
Sanand-382110 Kolkata - 700098
AHMEDABAD INDIA INDIA INSTRUMCNTS
Phone: (91) 7575804174/28 Phone (91) 9903805104 / (91-33) 23352925
r

CTR MmrsemDn indssthies ltd. is—^


W B Hv FAX : 91(020} 26633425
WEBSITE; www.ctr.in

WARRANTY NR : 1840262

We certify that product(s) indicated hereunder meets specification shown in our


catalogue(s) and/or specification sheet(s) unless specifically agreed to
othervyise. We warrant that the product(s) is free from defects in workmanship
and material. Any product claimed to be defective can be returned to us with
prior intimation observing Central Excise formalities, quoting warranty number
n indicated above, during validity of this warranty. This warranty does not cover
damage resulting out of incorrect use or improper handling. We are not liable
for consequential damages.

Customer ATLANTA Product : 1NTANK TAPCHANGER

Order POD/RM/1819/00606 Spec. : SN/500L2/350/300/16 O


16.06.2018

W.O. AET-1291/08 Qty, 1NR.

18
Validity : Months from the Serial : 1840262
date of sale or 12
months from the date
of commissioning
/ whichever is earlier
O

MKOAA 18:40060 MKQAA :1840262

Date . 31.08,2018
AUTHORISED SIGNATORY

REGISTERED OFFICE : NAGAR ROAD. PUNE 411014. INDIA.


CIN U29299MH1964PLC013087
PAAD. 1113.R1
NAGAR ROAD
PUNE 411014 INDIA
PHONE : 91(020) 26633402/05
MR mFSE'MIHG iiusms LTD. FAX : 91 (020) 26633425
WEBSITE: www.ctr.in

TEST CERTIFICATE NUMBER: 1801177

OLTC Sr.Nr. 1840262 OLTC Type : SN/500L2/350/300/16 O


Customer ATLANTA WO Nr. AET-1291/8 MKOAA Nr. 18:40060
Max. Phase Max.Step
Vector Group YNynO 174.95 A 989.77 V
Current Voltage

Upper Part Diverter Selector


1841205 Switch 1841192 Switch 1841199
Assembly Nr.
Assembly Nr. Assembly Nr.
D.M.Box Counter
1841185 5380
Assembly Nr. Reading

SR. ROUTINE
NR. TESTS SPECIFIED OBSERVED

Supply voltage +10%M5% 484 V AC


440 V AC
1. to Drive 374 V AC
Mechanism 23 0 +10/ 20%
- v DC NA
2. Nr.of steps 16 Steps 16 Steps
With the Tapchanger fully
assembled but without the
Mechanical contacts energized 10 complete 5380 Tap chanaes done and
3.
Test cycle of operation 1320 tap no failure observed.
changes shali be performed
without failure
Accelerated Internal and
Pressure Test
4. External Pressure Test at 22 PSI NO Leakages Found.
of oil
for 2 hours with oil and at 15 PSI
compartment
for 1 hour with air.
5. Auxiliary Circuit Withstood 2 KV for 60 sec
2KV for 60 second
insulation Test
4.36 Q
4.29 n
Transition
6. +/ 5% 4.33 Q
Resistance 4.3 - Q x 06 Nrs.
Value 4.34 n
4.30 O
4.26 O
Reference
IS8468 / IEC60214
Standards

Date:31.8.2018 Prepareoby Checlcedby Qualit / Control Manager.

MADidrk
REGISTERED OFFICE; NAGAR ROAD, PUNE 411 014. INDIA.
CIN U29299MH1964PLC013087
AAD.1115.R3
test report / certificate
Document No:
V2:QS:02:11:3002 CTR T3 Rev 0

"PRODUCT FAMILY
MODEL
SERIAL NO ~ TsSF- rsoW
1496 DCV Report No.
Customer Name 71496
CTR MANUFACTURING P.O. NoT"
WDS. LTD (ITD) 1741620 Date
Invoice cum Challan No 16-Oct-17
VIAT2.1387.1819 Challan Date
Operating Pressure 25-Aug-18
0.56 kg/cm
Accessories
Gasket
YES
Test Name and specification
Porosity Test atTKite?(294kPM2lm^: ^ Acceptance criteria
No bubbling of air observed Passed/Value

PASSED

2 treS voIume
rate of pressure
ofDres ^ 0fmin
^ nse >0.035 - 2 I,per
Kg/cm ' sec. ^" Opto 0.90 ko/rw ±0.07 kg/cm2
Above 0.90 & 0.59 kg/cm'
±0.14 kg/cm2
Leaka8e test Upto 1.4 kg/cm;

SWITCH (TpERATroisf PASSED


A
' Contact PrKitmn
Before Operation After Operatinn
3-4 Normally Open 3-4 Normally Close
1
1 - 2 Normally Close -2 Normally Open CONFORMS
Contact
Manual
C. Switch RaRntr- PASSED
20 OrERATIONS
10.0 Amps 300V-AC CONFORMS
6 Amps 24V - nr
Switches reverse contacts when the PRV
operates.
PASSED
_jjag at "70°-9Q0 to horhnntnl
Between circuits and earth: 2k V RMS AC fnr i™- ♦ No leakage of current detected during any

PASSED
Goods approval
Conformance to test stanH^M
PASSED
| Compliance •j-h* • . —,—-M/ ——
| Statement ;ted and accepted conforming
tested and meet all operational and product prrforanwfplXTti^ the test
have been
T>w
Product supervisor
Quality manager

6. Meelkanth Estate,
Viilage-iyava,
Sanand-382110 Block LBl, sector (II, Salt lake VlA,
AHMEDABAO INDIA Kolkata - 700098
Phone: (91} 7575804174/28 INDIA
Phone (91} 9903805104/(91.33) 23352925
TEST REPORT/ CERTIFICATE
Document No;
V2;QS;02:ll:172l GOR RevO
(SFT (MERCURY) RO)
—}^^|^SlRgALY(MgRCURY^Wffcm
"Y~"^ * ■ ~ -NO-
SERIAL SIZE
DVQI226 ~ 25mm
Customer Name Report No.
18-19/DV01226
^XbamnufactT/ring RONoT"
r
INOS. LTD (ITD) 1741620 Date
Invoice cum Challan No. 16-Oct-17
"VIAT2.1387.1819 Challan Date
25-Aug-i8

TEST NAME AND SPFnF( CAT i II,0n


n
Porosity ^ 1 •— a , at o^ Kg/cm-air
and element
k.^.irIV^M ny
-—■»—-—-pressure for 5 ACCEPTANCE CRITERIA
mmutes under fluid at room temperature P
"2 No leakage or sweating through housing! PASSED / VALUE

Passed
through relay at angle of 5° ascending towards
SIZE STANDARD
25mm 103cm/sec
70-130 cm/s
(cm/s)

^eL Standard -
"7;—-—:—- i^oo
r Contarnty test for contacts manually withlAdT Passed
Switches operate when test lock screw is
rotated in required direction
Surface condition check (Visual) Passed
"Surface should be free of porosity and
surface irregularities
Mercury switch rating Passed
5/2 AMPS at 250 Volts AC/DC
respectively.
Internal resistance < 0.1 ohms Conforms
Pressure test at 3 kg/cm2 for 24 hrs.

No leakage of current detected during any

llKZi*^posiiion for imi"- Passed

IR > 20 MD
> 20 MC>
Meet The Requirements
Goods approval
Passed
Conformance to test standard
PASSED

| Compliance
f Statement

Product supervisor
Quality manager

6, Neelkanth Estate,
Village-lyava, 1 j 27
Sanand-382110 IThT.
Block ° 111,Eli=i
LSI, Sector Salt Lake
AHMEDABAD INDIA Kotkata - 700098 Via-!*•
Phone: (91) 7575804174/28 INDIA
Phone (91) 9903805104 / (91-33) 2335292 INSTRUMENTS
Document No:
TEST REPORT / CERTIFICATE V2:CiS:02:ll:1723 GOR MER.
SWITCH Rev 0

rKUUUU 1 r AMIL T
MODEL GOR-3 SIZE 80mm
SERIAL NO MPV03117 Report No. 18-19/MPV03117
P.O. No. POD/RM/1819/00869 Date 06-Jul-
Customer Name ATLANTA ELECTR1CALS
18
PVT LTD
Invoice cum Chalian No. VIAT2.1218.1819 Chailan Date 04-Aug-18

Acceptance criteria OBSERVATION


Test Name and specification
No sweating or leakage through the housing, Conforms
Porosity Test and Elements test At 3kg /cm
(CL NO. 7.2 and 7.4) 15:3637-1966 M/Swt or any joints.
Gas volume test with transformer oil at angle of 5" 1.The volume of air/gas collected shall be
ascending towards conservator within
SIZE REQUIREMENT(CC) Result (cc)
(CL NO. 7.5) 15:3637-1966 240CC
25 MM 90-165
50 MM 175-225
80 MM 200-300
2.Trip device should not operate.
SIZE REQUIREMENTJ cm/sec) Results (cm/sec)
Equivalent steady oil flow velocity for sudden surge with
25MM 70-130 104cm/sec
transformer oil at angle of 5 degree ascending towards
conservator. 50MM 75-140
80MM 90-160
(CL. NO. 7.6) 15:3637-1966 Conforms
The oil level shall be dropped to the bottom of the pipe The trip device shall operate.
bore.
(CL. NO. 7.6) 15:3637-1966 Conforms
Surface condition (Visual) Free from all surface defects.
Both alarm and trip device operates. Conforms
Continuity test for contacts manually with test lock screw
with relay at 5 degree. Conforms
Switch Rating
i) 5/2 amps at 250 volts AC/DC respectively applied. i) Internal resistance should be <0.1 ohm.
(3 A 110 V DC) i) No. breakage of or damage to switch.
ii) Pressure tested 3 kg/cm2 for 72 hrs.
No leakage of current detected. Conforms
High voltage Test 2kV at 50 Hz for 60 seconds,
(CL NO. 7.3) 13:3637-1966
Insulation resistance > 10 MQ >10Mn
Insufetion Resistance Test 500 V meggar.
Meets the requirement
(CL NO. 7.3) 13:3637-1966
Type' Te st; (Pe rfo rm ed/ N ot P e rfo rm ed)
No mechanical failure of housing. Conforms
Mechanical Strength test 8 kg/cm2for 60 seconds.
(CL. NO. 7.7) 15:3637-1966
SIZE REQUlREMENT(cm/sec) Results (cm/sec)
Velocity calibration Test At an angle of 1, 5 and 9 .
(CL. NO. 7.8) 15:3537-1966 25 MM 70-130
50 MM 75-140 Conforms
.80 MM 90-160

our
■oducts were manufactured, calibrated, tested and ccepted conforming to v
' CompHante to ow p ed to in this document, and all relevant work instructic ns, drawings and procedures,
purchase order, the test standard referr
Statement We further certify that the unit(s) have b een tested and meet all operstfbnal and product perfor mance specifications.
X-
Product superviso Quality m anager

6, Neelkanth Estate , Module 2701 To 2704, Phase II, Shilpangan


Village - lyava, Block LB1, Sector 111, Salt Lake
Safiand-382110 Kolkata - 700098
INDIA INSTBOMeNTS
AHMEDA8AD INDIA
Phone: (91) 7575801174/28 Phone (91) 9903805104/(91-33) 2335292
CG Power and Industrial Solutions Limited
(Formerly Crompton Greaves Limited)
Swilchgear Division: Power Systems
A-3 MIDC, Ambad, Nasbik 422 010, Maharashtra. India o
T: +91 253 238 2271-75 F: +91 253 2381247 Smart solutions.
Strong relationships.

Doc. No.EfT7004/R2

CONDENSER BUSHING ROUTINE TEST REPORT

Date of Test: 29/07/2018

Unit Sr.No. SI 451006360 Rated Current; 800/1250A Rated Voltage : 145 kV

Type: COT 650 kV BCT: 100 mm

1. Test for Leakage of Internal filling (Pressure Test).


Gauge Pressure 1.6 kg/sq.cm. Maintained for 12 hours - OK.

2. Power Frequency Dry Withstand Voltage Test for Tap 2 kV (rms) for 1 min.-: WITHSTOOD

3. Measurement of Capacitance, Tangent delta at ambient temperature and Partial Discharge


Levels before and after HV Test (Dry)

Voltage Before HV Test After HV Test


kV Cap.(pF) Tan-Deita PD (pC) Cap.(pF) Tan-Delta PD (pC)
10 277.18 0.00320 277,37 0.00330
0.3 Un 43.5 277.20 0.00324 2 277.39 0.00333 3
0.6 Un 87 277.21 0.00324 3 277.41 0.00333 3
0.85 Un 123 277.24 0.00330 3 277.44 0.00333 3
Un 145 277.31 0.00333 3 277.48 0.00335 3

4. High Voltage Power Frequency Test (Dry) 305 kVrms for 1 min. - WITHSTOOD

5. Measurement of Capacitance, Tangent delta of Test Tap with respect to Flange at 1.0 kV

Capacitance 201.2 pF Tan Delta 0.0062

6. Ambient Temperature: 24 deg.Celsius


7. All dimensions as per relevant drawing Found OK
8. Minimum Creepage Distance: 25 mm/kV

This is to certify that the above condenser bushing has been tested for routine tests in accordance with the relevant
clauses of IS 2099 (2003) / iEC 60137 (2008) In so far as they are applicable and passed the tests successfully.

Tested By:

3*4.

Test Engineer, QA
SI Division, CG
Nashik

Registered Office:
CG House, 6th Floor, Dr Annie Besant Boad, Worli, Mumbai 400 030, India
T: +91 22 2423 7777 F: +91 22 2423 7733 W; www.cgglobal.com o
Corporate Identity Number: L99999MH1937PLC002641 AVANTHA
GROUP COMPAMY
CG Power and Industrial Solutions Limited
(Formerly Crompton Greaves Limited)
Switchgear Division: Power Systems
A-3 M1DC. Ambad, Nashik422 010, Maharashtra, India o
T; +91 253 238 2271-75 F: +91 253 2381247 Smart solutions.
Strong relationships.

Doc. NO.EIT/004/R2
CONDENSER BUSHING ROUTINE TEST REPORT

Date of Test: 31/07/2018


Unit Sr.No. S1451006362 Rated Current: 800/1250A Rated Voltage : 145 kV
Type: COT 650 kV BCT: 100 mm

1. Test for Leakage of Internal filling (Pressure Test).


Gauge Pressure 1.6 kg/sq.cm. Maintained for 12 hours - OK.
2. Power Frequency Dry Withstand Voltage Test for Tap 2 kV (rms) for 1 min.-: WITHSTOOD
3. Measurement of Capacitance, Tangent delta at ambient temperature and Partial Discharge
Levels before and after HV Test (Dry)

Volt age Before HV Test After HV Test


kV Cap.(pF) Tan-Delta PD(pC) Cap.fpF) Tan-Delta PD (pC)
10 290.15 0.00350 290.31 0.00350
0.3 Un 43.5 290.16 0.00350 3 290.32 0.00353 3
0.6 Un 87 290.17 0.00353 3 290.34 0.00354 3
0.85 Un 123 290.19 0.00354 3 290.38 0.00355 3
Un 145 290.22 0.00355 3 290.42 0.00355 3
4. High Voltage Power Frequency Test (Dry) 305 kVrms for 1 min. - WITHSTOOD
5. Measurement of Capacitance, Tangent delta of Test Tap with respect to Flange at 1.0 kV

Capacitance 200.45 pF Tan Delta 0.0070


6. Ambient Temperature: 24 deg.Celsius
7. All dimensions as per relevant drawing Found OK
8. Minimum Creepage Distance: 25 mm/kV

This is to certify that the above condenser bushing has been tested for routine tests in accordance with the relevant
clauses of IS 2099 (2003) / IEC 60137 (2008) In so far as they are applicable and passed the tests successfully.

Tested By:

^-

Test Engineer, OA
S1 Division, CG
Nashik

Registered Office;
CG House. 6th Floor. Dr Annie Besant Road. Worli, Mumbai 400 030, India
T: +91 22 2423 7777 F: +91 22 2423 7733 W: www.cggl0bal.com o
Corporate Idenfity Number: L99999MH1937PLC002641
Avantha
GROUP COM PAUY
CG Power and Industrial Solutions Limited
(Formerly Crompton Greaves limited)
Switchgear Division: Power Systems
A-3 MiDC, Ambad, Nasliik422 010, Maharashtra, India o
T: +91 253 238 2271-75 F: +91 253 2381247 Smart solutions.
Strong relationships.

Doc. NO.EIT/004/R2
CONDENSER BUSHING ROUTINE TEST REPORT

Date of Test: 29/07/2018


Unit Sr.No. S1451006372 Rated Current: 800/1250A Rated Voltage : 145 kV

Type: COT 650 kV BCT: 100 mm

1. Test for Leakage of Internal filling (Pressure Test).


Gauge Pressure 1.6 kg/sq.cm. Maintained for 12 hours - OK.

2. Power Frequency Dry Withstand Voltage Test for Tap 2 kV (rms) for 1 min.-; WITHSTOOD

3. Measurement of Capacitance, Tangent delta at ambient temperature and Partial Discharge


Levels before and after HV Test (Dry)

Voltage Before HV Test After HV Test


kV Cap.(pF) Tan-Delta PD (pC) Cap.(pF) Tan-Delta PD (pC)
10 274.33 0.00310 274.50 0.00315
0.3 Un 43.5 274.35 0.00310 2 274.52 0.00315 2
0.6 Un 87 274.37 0.00310 2 274.55 0.00315 2
0.85 Un 123 274.38 0.00315 2 274.57 0.00315 2
Un 145 274.40 0.00315 2 274.58 0.00315 2
4. High Voltage Power Frequency Test (Dry) 305 KVrms for 1 min. - WITHSTOOD
5. Measurement of Capacitance, Tangent delta of Test Tap with respect to Flange at 1.0 kV

Capacitance 214.33 pF Tan Delta 0.0094


6. Ambient Temperature: 25 deg.Celsius
7. All dimensions as per relevant drawing Found OK
8. Minimum Creepage Distance: 25 mm/kV

This is to certify that the above condenser bushing has been tested for routine tests in accordance with the relevant
clauses of IS 2099 (2003) / IEC 60137 (2008) In so far as they are applicable and passed the tests successfully.

Tested By:

Test Engineer, OA
S1 Division, GG
Nashik

Registered Office:
CG House, 6th Floor, Dr Annie Besant Road. Worli, Mumbai 400 030, India
T: +91 22 2423 7777 F: +91 22 2423 7733 W: www.cgglobai.com o
Corporate Identity Number: L99999MH1937PLC002641 Avantha
A. S. INSULATORS
ISO 9001:2003 OGSctJ
TEST CERTIFICATF

T.C. No.ASI/00107/18-19 Date: 21/07/2018

1 Customer's Name ATLANTA ELECTRICALS PVT LTD.


2 P.O. No. and Date POD/RM/1819/00689 Date : 25/06/2018
3 Item • Porcelain Bushing 36 KV/1000 A
4 Drawing No./Rel IS:8603
5 Specification 18:2099/1986 & IS 5621/1980
6 Quantity 21 NOS.
7 Invoice No. & Date ASI/00107/18-19 Date: 21/07/2018

Sr. ROUTINE / ACCEPTANCE


No. TEST OBSERVATION
cv
Visual Inspection
All the pieces are visually checked and found
1 IS: 5621/1980 clause 3.2
OX
IS: 2099/1986 clause 4.1

Electrical Routine Test


2 Withstood, 70 kV for one minute.
■ IS: 5621/1980 clause 3.3

Verification of Important
Dimension All the important dimensions are within the
3
15:2099/1986 clause 4.1 tolerance limit.
IS: 5621/1980 clause 3.4
Porosity Test
4 IS: 5621/1980 clause 3.5 No dye penetration observed.
15:2099/1986 clause 4.1
cv
Temperature Cycle Test
5 IS: 5621/1980 clause 3.6 No glaze and body crack observed.
IS :2099/1986 clause 11.7

ENGINEER- (QUALITY CONTROL)


A. S. INSULATORS

/jVDIK
Plot No. 355, Padra-Jambusar Highway, Vill: Dabhasha, Tal. Padra, Vadodara-331440.
Phone: (91) 9376224628 Email; info@asinsulators.com
o«n«»rt /tnn ping/ p«t. Up.
Corporate Office & .works: Gujarat Spun Pipe Compound, Padra Road, P.O. Samiala- 391410. Tal. & Dist Vadodara
India Tel.: +91-265-3923200, +^1-265-3923211. fax: +91-265-3923226 e-mail: man@-amodstamn.rnm
wvyw.ampdstamp.com

ROUTINE TEST CERTIFICATE OF CURRENT TRANSFORMER ^AS PER IS-2705)

SR. NO. fLS p<y ctTf CLcTved


ORDER NO. fotD i RM | (^r IT / oo9"2-3- 44- 2.ol t
DESIGN NO.
\j-CS3
MODEL LT cT V ctrf i ' S K ed,
SYSTEM.VOLTAGE D* WV-
RATIO l7 5/i'3
BURDEN l-o V/f|
CLASS
5
INSULATION CLASS t
QUANTITY 3 rw
TOTAL PAGES

ROUTINE TEST :

1) VERIFICATION OF TERMINAL MARKING AND POLARITY


O.K
T
2) HIGH VOL AGE POWER-FREQUENCY TEST ON
3 KV FOR 1 MIN. -
PRIMARY WINDINGS
withstood
3) HIGH VOLTAGE POWER-FREQUENCY TEST ON
3 KV FOR 1 MlN
' SECONDARY WINDINGS
WITHSTOOD
4) OVER VOLTAGE INTER-TURN TEST FOR ONE
O.K,
MINUTE

5) DETERMINATION OF ERROR ACCORDINGS TO


AS PER ATTACH
ACCURACY CLASS
SHEET
AMOD STAMPINGS PVT. LTD
DATE ; (-7.-7.^0) r
GUJARAT SPUN PiPE COMPOUND,
AT. & PO. SAMIALA. PADRA ROAD
DIST. VADODARA-391 410. " TESTED

TESTING IN-CHARGE ; ;

CiN: U17119GJ1995PTC025300
*o,to : Opp. Pramulch Oxygen Company, Nr. Bhenslore Distillery, Daman- A TUVRheinland8'
Kuntej Road,Daman-396210,India. "• . Precisely Right.
omodi sl^Mpliiga. pwL ltd.
Corporate Office & Works: Gujorot Spun Pip© Compound.,Podro Rood, P.O. SQmiQto-391410. Tol, & Dist, Vododoro, India.
Tel, : +91-265-39S3200, +91-265-3923211, Fox: .+91-26S-2923:226 6-mQil: friolt@QmodstQmp,com UJeb : ujujuj.QmodstQmp,cpm %

CORE RATED RATED %AGE OF BURDEN %AGE PHASE


MO. PRIMARY SECONDARY RATED RATIO DISPLACEMENT
CURRENT CURRENT PRIMARY VA COS 0 ERROR MINUTES
CURRENT (LAG)

SR.MO l" JT 120 10 0.8 -on r


4-TS~
50 10 0.8
120 5 0.8 -V-c
50. 5 0,8 + fc '3 ^

CORE RATED RATED %AGE OF BURDEN %AGE PHASE


NO. PRIMARY SECONDARY RATED . RATIO DISPLACEMENT
CURRENT CURRENT PRIMARY VA COS 0 ERROR MINUTES
CURRENT (LAG)
t-'JT 120 10 OiS —O»9-%
J-7 S""
50 10 0..8 -X '3o
120 5 0.8 •F0-7V —
50 5 OS T0.3S

CORE RATED RATED %AdE OF BURDEN. %AGE PHASE


^ NO. PRIMARY SECONDARY RATED RATIO DISPLACEMENT '
CURRENT CURRENT PRIMARY VA COS0 ERROR MINUTES

i £"1 25 </ 17 r 120 10 0.8 — 0'<ri


60 10 0.8 -1.^7 ' —
120 5 . 0.8 0 . 7 i.
SO tt 0.8 40 •k0
A
w
L r-m momkm mm ti t >• mfio mpuommi
cumWNt auiWNT ■ VA com MINUTHI
mm&m (IA&)

lt\2& Vl ^ m io OS — 0 < gro •—


so 10 0.8 -
120 6 0.8
50 5 0,8 40.33 ■—

LTD. • DATE
GUJARAT SPUN PIPE COWIPOUND,
AT. & PC. SM/I1ALA, PADRA ROAD, TESTED'BV^
DIST. VADODARA- 391 440,

CIN: U171151 G./1i}«5PTC025300 a TUVRheinland^


ajoms ■ Opp PramulihOxuciw cumwinu. Ni OiienMorw iJKlilluru. IJunicm-Kuhln Hand DnmMn.Wrt &IU inHm /zz* Priicisely Right.
9/10/201,8 New Doc 2018-09-08 16.17.21 .jpg

rsu.
®ffia©di pivl.
Corporate Office & works: Gujarat Spun Pips Compound, Padra Road, P.O. Samiafa- 391410. Tal, & Dist, Vadodara,
India Tel.; +91.265-3923200, +91-265.3923211, fax; +91-255-3923226 e-mail: mall@amodstamp.cofn web;
www.am od stamp.com

ROUTINE TEST CERTIFiCATE OF CURRENT TRANSFORMER (AS PER IS-2705)

SR.NO. 0-5 aw sKee-H-


ORDER NO. PolD / Rjvi { l<£r |«T I 00
DESIGN NO.
MODEL LT c-r Vcw THi" K e d -
SYSTEM VOLTAGE oj 01 o UV'
RATIO 7Lto I i' 5
BURDEN . ioV/j
CLASS 5"
INSULATION CLASS E
QUANTITY 3
TOTAL PAGES L
1
r
ROUTINE TEST :
REMARK
1) VERIFICATION OF TERMINAL MARKING AND POLARITY
O.K.
2) HIGH VOLTAGE POWER-FREQUENCY TEST ON
PRIMARY WINDINGS l tbT ON 3 KV FOR 1 MIN, -
WITHSTOOD
3)
c/SlVOlTAGE poWER-FREQUENCY TEST
1 tST ON
3 KV FOR 1 MSN
SECONDARY WINDINGS
WITHSTOOD
4) miWte0LTA^inter-turn test for one O.K.

0
t accuracy
A™T^\ !i9F
class
ERR0R
ACCORD,NGS TO AS PER ATTACH -
SHEET
AMOD STAMPINGS PVT LTD
GUJARAT SPUN PIPE COMPOUND date :
AT. & PO. SAMIALA, PADRA ROAn' n 7-
D
L DIST. VADODARA- 391 410 ' TESTED by T^,

TESTING in-charge ; •

ON: U17119GJ1995PTC025B00
Works 0pp. Pramukh Oxygen Company, Nr. Bhenslore Distillery, Daman- ^ TUVRheinland'"
vUnt:a
HOad,Daman-396210,lnd!a. Precisely flight.

https://mail .google.com/mai I/u/0/#in box?projector= 1 1/1


steiSi|»tMgs
Corporate Office S UJorl«s: Gujarat Spun Pipe Compound, Podro Rood, P.O. SomlolQ-391410. Tal, & Dist. Vododoro India
Tei.: +91-265-3923200. +91-265-3923211. Pox; +91.265-3.923226 .e-mail mQiI@omodstQmp.com UJeb : ujujaj.amodstQmp.com

GORE RATED RATED % AGE OF BURDEN %-AG€ PHASE


NO. PRIMARY SECONDARY RATED RATJO DISPLACEW1ENT
CURRENT CURRENT PRIMARY VA CO&0 iRROR MINUTES
CURRENT (LAG)

SR. NO 7HD 1'5" 120 10 O.S - o. g- 2-


50 10 0.8 - 1. 2-0.
120 5 0.8
60 5 0.8 •V o «'■V O

CORE RATED RATED %AGE OF BURDEN %AGE PHASE


( NO. PRIMARY SECONDARY RATED RATIO DISPLACEMENT
CURRENT CURRENT PRIMARY" VA COS0 ERROR MINUTES
CURRENT (LAG)
7ti0
120 10 0i8 ~W3
50 10 0,8 y

120 5 0.8 . 4 0 «77


50 5 0v8

CORE RATED RATED %AOE OF BURDEN: %AGE PHASE


NO. PRIMARY SECONDARY RATED RATIO DISPLACEMENT
CURRENT CURRENT PRIMARY VA COS0

120 10 0.8 -6. gri-


is-ja&o . *7110
50 10 0.8
120 5 0.8 +-O»79
§0 ft 0.8 •V o» U 1

»»„. WAflU IUTID HAOBOH UUKOSN %Al38 j»HA88


C •f) (inlMAftY 01300NOAKY «ATiD HATIO DlWUAOBMBN'f
OUHRiNT CUrUVBNT PRIMARY VA COS 13 CiRROft M ■JUTSS
(ua»

120 10 0.8 2v "■


'7U0 60 10 0.8 - X - 2~c] —
120 5 0.8
50 5 0.8 + ^.'33 ^

PVT. LTD. DATE. : 1-7.7-<2,01^


GUJARAT SPUN PIPE COIV1POUND,
At. & PO. SAMIALA, PADRA ROAD, Tested'EYT" sc,;^
01 ST, VAD033ARA - 391 410. .1
■ss /
TESTING iN'CHARGE

iJi/nfiGJiaDsprco^ssoo A Fi) VRh81nland


UOOIN Opj., Promukh C>WtJ«n <:.OMU)U/tU, N( Bh«(lSloiv+i)kllliuiU hnrhnnJlunln HnnH IVumU.- AlMO H. te"-* ^Wisely Rifint,
HVi ^^mUSTRIgSLTD
'n iCudK K
' fWage.D ANHmelt
&h(Wa-39(!230
'A +91-360.2630282
... fa +91-260.2630961
* •+91-260-2630960

(Page / Of I)
r:™
batch NO.: SIT0240818
QTY: f0<
batch start date- ^ lVKL
18.08.2018
26.08.2018
28.08.2018
TANKER NO: DN-09-G-9949
SR. UBSRNO: 1952
CHARAi;i ERISTICS BATE OF ISSUE; 28.08^2018
Appearance TEST ^iSFiEnS^ ^Sagazro-27«/.B..n
METHOn
Visual TEST VALUES
Clear, transparent &
^mzM29.5'a
,QUV T J free from suspended Ckar, transparent &
hr——
SSHillle ^>vQSity r.Qf (S> 27 ® f IS: 1448 ii6) matter A $edimenfc "5® from suspended
t—g^SfeltCTsion. N/m^ _ 0.89
Flash ^oint (PM^1 ■ ■■ ■■" — IS: 1448
kourPofn^ °c IS. 6104 27 Mav QM* "—
IS: 14480>.?i 0.04 Mm 13.56
iNeutralizatioa Value IS: 1448 (P,}n 140 Mj'n 0.049
8) Total Acidity. mgiCOH / go, -6 Max 148
3SIVe Sulnhiir fnf lo L_j L— .'T: K: 1448 (p.2) <•18
— 0.03 Max.
c Nil _ o.ooi?
v0 New imun ouicreo
filtered oil Non - Cnn-rtciyf Nil
After Filtration. IS: 6792 Nop - Cormci.N.
MSfr^Breakd0wa ^Itagc 30 Mia.
60Miti. 67.00
10 d) 0d
Oil tempeiraturc :27n<y
:27 n°r- 68,70,66,68,62,68
factor (T^Xi^TT 90 "C
IS: 6262
a)® Oft'r-
a)@90*C IS: 6103
f b).@27»C
O^U^n oubiJrty I64hrs@ loFc 35* I0!JMih
2)
+) oluqge content ^% mg KOH/gm ^ ANmdjRBC ■Lsooxio^g. 1250x10"
OFIS:335 12690x10"
0.4 Max.
IS: 12177 0-1 Max 0.072
») Sp. Reite (ResistRfyj ota^ M,c _0.0080
I4ETHOD-A
IS; 6103 2s
f" ^ IteiS'a"« C^viW @ 90.c
x 10" Min.
D eIec!n c 0 IS: 6103 356 xlO'2
1°) ' " Bissipation Factor @90 C 0.2 x I0,J Min.
(d) Total Acidity, mgKOH/nn IS: 6262 124x10"
|e) Total sludge Wt. % 0,2 Max.
IS: 1448 (p.2) 0.0056
Presence ot Oxidation inhibitoT ANNEX. A OF 0.05 Max.
/V IS: 12177 0-05 Max. 0,0044
L ppm
content, pnm — I IS:13631 0.0022
llis oil shau not contain"
antioxidanf
.30 Max.
F«r ^'{age gradtent in the samnte u 13.3
Fluency of applied voltage- 50M it
iS^0f room 27«.
iSSgSg&Milo-r3'

IS:33S

CM/t.najjj, Authorised by
Shatri/njaypar
Officer (Q.c)
0
|FAX:+9l -22-25246326 ^TeI;+91-22- 252243400,
1509001:2015.
ISO 14001:20104,
OHSAS 18001:2007
Certified Conmany
:'<■/-
< i',:
ik-
IB:
V-tSSS! Level , !'■ V
D'
TRANS PARES LIMITED No. ;'j 2
m ; . Date. | 1/04/07
■M.
f :
■ tr [Doc No.325/18 19] Dt.30.08.2018

Name of the party : ATLANTA ELECTRICALS PVT.LTD.

P.Q.NO. ; POD/RM/1819/01366 DATE : 08.08.2018


I
Item
: Pressed Steel Radiators

Specification & Mounting: IEEMA 9:1990

Size 2000 X 26 SEC X 520

Quantity 10 Nos.

Material used ; 1.2 mm thickness CRCA sheet


(
Pairit shade Shade No 631 of IS:5

Section Width 520mm ± 5mm

Center Distance 2000mm ± 2mm

Skew Within ± 3mm in ail Direction

Plumb i ±2mm

Leak Test : Tested Individualiy Under Water at an Air Pressure


Of 2 Kg/cm2 for period SOmin and found O.K.

Internal Coating : Varnish (10 to 15 Micron)

Surface Cleaning by Shot : Found Ok


Blasting of radiator Header

Paint Thickness : Above 11Q p

Adhesion test : No peel off found

Internal Cleaning &


Visual check
for any foreign material : Found Qk

Flange No. : 2787 TO 2796

FOIV^^|gp^RES LIMITED
?•.
//>
<?• /■
(Qua [jaj^fn e n t)
rzrr/T0

aVINAYAK

Engineering Co

Manufacturer of: Transformar Tank, Machinery Parts and Heavy Precision Fabricated Items
369, G.I.D.C. Phase-2, Dediyasan, Mehsana-2 (Guj.)
E-mail; vinayak.msn@gmail,com I Mo.: 9375283520

Ref.: Date:

Test Report No.- VEC/AEPL/04 Date : -05/08/2018.


Invoice No. - fot3' Wt.
Name of Customer: ■ Atlanta Electricals Pvt.Ltd.
P.O.No.;- POD/R1VI/18-19/00686. Date-25/06/2018.
identification No.: V4-1291-V
Drg.liStNa:- AT02/4495
W.O.No. - AET -1291/ (32/40 MVA) 132/33 KV.
Material Used: - Mild Steel Plates of Different Sizes as per IS 2062.
Material Origtn:-
Top Plate Thk. ISmrn TCNo: 1712652
Side Plate Thk/ 3mm TCNO; A92196
Bottam Plate Thk. 16mm TCNO:. 1712552
Stiffener Thk. 6mm TCNO; B88795

Used Welding Electrode: - RATNA-6013XX.


Joint Details: As Per Drawing.
Test Carried Out:-
DP Test Not any disabnormality observed (Test carried out, during process and in Presence
Of customer after completion).
Leakage Test After ceiling of all the joints, leakage test carried out by applying pressure
And liquid soap solution over all the joints during test not any leakage observed.
Pressure Test : Applied On a First Unit and Found OK.
Test Result : N.A.
Radiography Test N.A
Weight Test on Lifting Lugs and Jacking Pads : N.A.
O Visual Check; Uniform welding with proper back chipping. Not any spatters, dent crack or pin hole
Observed at outer surface.
Dimensional.: All the accessories completely fitted as per GA Org NO.AT09/1541Q/A1. AS PER DRG
Check . • Critical dimension taken in presence of AEPL representative and results submitted.
Special Remarks:
1) All the critical joints welded by Qualified Welders..
2) Jacking pads, lifting Lugs, inspection windows, bushing flanges & Etc welded from both
the sides
■1) Ali Sharpe corners grinded properly
4) Pressure calibration due date.

7/
LTD.
T'est uttout
Doc. No.QC-F-06

Date.09.08.-2018
M/sATIANTA electricals pvt. ltdKsao
Mate rial w
flexible SEPARATOR ^
Reference No.
NCPL/ F AS/20l8-d9/fi^gg"
Invoice Number & Date
SIG-003438. 09.Q«.7nig
P.O. Numbers Date
—Ziz
s^e Of Flexible Separator ^Rp^ooSiCDiiid^T^
X=3061 MM
x=^np.-s rv.irwi r:~~ ^ V^tg.
j Quantity Y=16ia IVIM G=l450 MM
1 No.

|DescnpIjor7 ~ " r-u • -


Specified ^
Inspection
Standard
Appearance -■ • • tool •••
Shall be free •••'-v.:: '
Visual Surface is free
from Pits, Satisfactory
from pit marks,
marks,Wnnkles
r
and surface M wrinkles, surface
| damage
damage
'Dimension:
|L Measuring
3061 -f 1.5% Satisfactory
|W tape 3053 mm
1611 -f 1.5%
(G 3 1620 mm
-A3Q%lOmrn
1450 mm
Product Corn pressed
No leakage or No leaKage or Satisfactory
performance test air
ply separation separation
I inflation test @0.105
should fae noticed
L-g/cm2 For IDtimp^
observed
Pressure test- SeparatoF
VVater No leakage and
should be Satisfactory
manometer seepage noticed
inflated at 0.105
kg/cm2 and after 24 hrs;

kept for 24 hrs.


no leakage or
seepage should
3e noticed

s- -
>
; ?
: 4^ X&SM'
'i ..
P i'<R
..jm mm

Ajay Kumar ^RNU-CORK PRODU^Tc To

{Testing incharge) Ajit Kumar


XI (Quality Officer)
i^RHCOjnd Area, Bhiwadi, Rajasthan
Grindbecfc
(^n ISO 9001:2015 Go
J-255/1, GIDq. Indl. Are^, Umhergaon -396171,Dist - Valsadj Gujarat
Tel j 0260 -r 25^$|8 / 25^i72B;. ? f v S fox
feinail: respbnse@grindbeckcork.com \Veb:www.grindbeckcnrk.rnni

TEST REPORT

TO, -;v. , REPORT NO.195/2018-2019


ATLANTA ELECTRICALS PVT. LTD DATE • 28.07.2018
TOSTGEtOTFIdMl^:
iS-4253( PART 2 ) 2008 GRADE: ( RC-TO-C )
INV, NO.227/2018-26l9 Dt28.07.2018
^TTHAL UD YOG NAGAR ANAND PURCHASE ORDER NO. 906 /1146 /1169
DTr 09.07.2018 / 21.07.2018 / 24.07.2018
SAMPLE DESGRIPTIGN IDENTIFICATION BATCH NO. DATE
RUBBERISED CORK SHEET "ZEBRA BRAND,,
SIZE 11- 1000X 2000X16 MM GRADE : GCS-II 192/193 26.07.2018
II- 1000X1000X6.0 MM (RC-70-C) 27.07.2018
II- 1000X1000X10.0 MM
IE 1000X1000X16 MM

NO. TEST DETAILS


REQUIREMENT OBTAIN
VALUE AS PER VALUE
4253 ( PART 2)
2008
HARDNES, IRHD
70 ±5 73
DIMENSIONAL CHARGES,% MAX,
1.5 1,3
TENSILE STREGNTH, KPA. MIN.
1750. 1765
/
0
L COMPRESSIBILITY AT 2800 KPA,. /o 20-30 28
RECOVERY AT 2800 KPA, % MIN 80 83
FLEXIBILITY ( NO BREAKAGE THROUGH THE
NO BREKAGE NO BREKAGE
: ; grAnualot
OBSERVED
SEPAKATIQ^ OF GIO^NU^ )
. FLUID RESISTANCE TEST,
MAX. 8 +7.5
% CHANGE IN VOLUNffiT TR^ on.)
COMPRESSION SET, PERCENT M^ 85 ,82

FOR GRINDBECK
CO
o
co CM
CM U>
^r
CM O o: ;>* o
< CO
CM H- o CO
03 LU
o CO > r-z
CC
z D 2 cr
a: "M" TO CO
» CO CO o o "O
N- a
S o h- ro Z
< CO Z)
"D
D)
§ O fin ,i S2 CO
1 2 Q_ i lii "N" >
O co CO CM ro LT
h- < o= O
CO o CL
LU o
CD o
o Qi y>
-*-•
CO c
03
< E
03
CO o
CO '5
o >» E' ; 'v. ^ cr
CC. X) 03
>_
Oi "T
c LJ LL CQ CM 03
>- x:
X to
CO i2
O CO 03
03
CO £
CO CD
CO Q 03
CO >- UJ "2
CD o
< Ei cc x>
O O «c a>
c
z: H < CO o
-y CD O CO c „
c o (U CO 03 CO
h- TJ LU ^ O
o> CD < g CN
O CQ CO o s
« E -Q
o c >
C O CO w ^ C&
o <J> a. « CM
LU m-: ~ 03*
Q_ CO CM CO •*£
fit. 03 CO
CO CO o>
CD CO X3
CO CO N "O
CO 03
UJ Si CO CL
CO ID CQ < D_ Q.
CO CM cr 3
0 o CD t/i
c V)
o o o ■c
CO
< CO CO ^ ffi
CO o CO CO 00 o
>-
3 :»2»wa»K s
g ^ CO
o CL < <
u DC -» ra LU
LU > a. < V): < 11
O « CD co
■c CO LU
X a O o CO S
£ o
<D -a. CO CO
3 z is
o o o «=
C cc o
LD H D- <
-C CQ Z oo <
a O) o O
TJ
m V) c - LL. ■s "S
CO aj LU LU a
£V - s
> O CD CO D_
03.i CO 1 I
CO " ft ; I S
T—
o m'
&; ; :5p;M
a>r
(N ^ o: o o
co O 8 H H-
-E: O > >
< ^.
2- CO
d Jr S M- a> lu
i O > rr:
cc
Z Q C3> CO J3
tn "^T" H LL 03 CO

PHYSICAL PROPERTIES
O CO or- o>
t— h- <
; rali 1^ O "O Z> Q
c O ^ ■*3-
< ~ CO i CJ>
•o r" — 43/ CO CM
cr 00
?4jifig3V LU c S2
S 2 a. ii .2 >
O co wi. ' co <3 Q:
h- < < co CO if= o
O) CO < o
CO Mi : a.
UJ i|:• i CO
h- o
o to
W: c
0
" ^ ■? E
CO 11. ^ ;Q.i co '5
o ■f cr
q: o; £
c Q m
.... 0
>- 4=
X CO
Ll_ w
O ipl 0
CD a>
CO wi § E
CO CO V-ft-.
w >- a>
| LU E
o 5 < o
</} < < X3
^2 Hi d'. 0)
UJ § < c
o
•z. s J- •J=J
Z) o d z 0 c _
o a. 0} 00
.o c o CO
h- a: s o
<D i ? 0. V- gj cm4
O <
:?!
-o E a DC#5 ^ CQ < o
O o _Q s
o E > S § cn CO 00
8 o CO 0 T CO T-
< o .£
UJ ^ ■ o> X
o o co
Q_ m CO
; § 0>
O) ra
CO CO to
m (0 T)
CO ; IO N •o
1 <1>
Si I,;. ; a.
co CQ o.
3
0 "O co£ <o
c zr co
"L- UJ o "C
*4—1 co
CO § § c 1 o3 O
3 Li- .o w g
g> vi
"O S ra LU .3- i 5! : — &
LU w in ra S
c O J2 5 & o co
W S a> <3 s
Q £ o
S r- O
5 -3> a> -li_ 0
3 < UJ £ 0 O i: ^ c
C 3 -2
< c Vi ra uj
^ '",'i h C
O >*
-C Q — C co o -Q
HEAT NO.

C >» ■o
CO ?< L JQ Q
1 i a> O
^ I 2 LU o ^ 4: O
> yo m iE O) Q.
% ;< 0 co
c
CO
•? 'igj,
O to
CN <!);•
m
p 1
< O)
; P ^ CO
0}
> LU
0 »— oo o CU
z Q a> -Q 1— I
» ^7 <0 CO
■a 3
CD Q
1 O <g Z
< h- w "£5 3
tn 2
CO 2
CO CO
li £ c
CO o .9 >
,^ f •> CO CU
" y Co o
H < !*= o
LU
i— o
<u
CO o.
to
LU SI CO M—
o
o to
c
a)
E
<B
k-
CO '3
o cr
W (U
. A> '' i_
c O cQ.j. 1 <u
£
■n sBi ■fS
"ra
u. to
o ipL <5
CD
r— c::- a>
CO i ' E
CO CO few I k_
w <u
s 111 ■a
CM in o
o .<- 5?v | TD
Z § S2 < COl ■f<trSnav' CD
C
o
1 S H- z c
d b <D 00
b >. c 0 .0): |
E o
H ~ 0) ;c
fl o o
CQ, fe ■ - ••: > CM
-o c "o 1 o
XJ
> LU CD co s
c o CO -j 'to p
o> LU CO c 0)
LU CM <0 -JS
CL CO O) <0
CO co mm CT> (0 "D
CO CO •o
CO CO CO 0)
LU 0) CO a.
CO N CQ < a.
W DC =3
0 'O CQ 09
c s: LU <0
LU o O ■c
CO CO
CL
CO O :: CO o® p
w s
13 Q> en
rv S (0 LU < CO eti
■O LU -i z
< 5 g
c O J2 LU •*-* Cj
V) S LU
o CO IM
Q
0 -LU CO E
3 2^
< LU E 0
C Z ^ ra^ (— c
< c ^
L—LU
m 2 o
o
-C Q -B >» ■o
a X3
■ CO i": 11 cu 0)
fel £ LU x: o a>
> ss m £ Q> Q.
5 to c
Jin CST No. 24692200674 Dt. 05-05-2005
Subject to Vadodara Jurisdiction
• Tin GST No. 24192200674 Dt. 05-05-20C

electromech
?
MANUFACTURERS S SUPPLIER OF ELECTRICAI iTRANSFORMER PARTS
1
Factory
Cto^ : Plot No.264,
No 264 G.I.D.C.
U in r Estate. Waahorilp,
u ^
n,., ^ ^bFORMER PARTS
^^ERPARTS

Ret Ho. — " 98796117276ST124AAQFGQ121N1ZF


Date:

Ref. GE/ AEPL/56/18-19


21.06.2018

IggI££SI
^IEFOR RADIATOR VA,
Name of Customer
[ M/s. ATLANTA ELECTRICALS PVT. LTD
Purchase Order No.
Your P.O. No. AEPL/RM-170/17-18 Dt.30.11.17
Invoice No. & Date
Our Tax Invoice No. 56 / 18-19 Dt. 21/06/2018
Material Specification
80mm Butterfly Valve (Radiator Valve)
No of Products
^ 300 Nos.

Make
: R1NU
Details of Test Result
1. Construction & Dimension ■ i ^
and found correci
3 Mechanical Operation Test •
3.» no, _ «on _ ^

Va,Ve in 0PEN
the following is ensured^AS POSTION ana

' eakage through Body ■ m;,


Ker®ka9,e'hr0U9hPressure nut Nil
(Around the fop)
On Normal liquid filling test
Leakage through Flap

Mfg. / Batch NO. Month of Mfgf


Rosalee/134/01 18
Dry film thickness of primer 60 to 70 Microns
Time and Date of application

Por, Gajanan Electromech

1333
Subject to flhmedabad Jurisdiction

Rmu TRANSCO

' MFG. ELECTRICAL TRANSFORMERS PARTS,

Rei RT/ AEPL/18-19/SGB TC-146 Date: 25/07/2018

TEST CERTIFICATE FOR SlUCA-GEL BREATHER

Name of Customer : M/s. ATLANTA ELECTRICALS PVT. LTD.


Purchase Order No. : POD/RM/1819/00876 Dt. 07/07/2018
Invoice No. .& Date : OurTax Invoice No.GST 146 /18-19 Dt. 25/07/2018
Description of Item : Silica-Gel Breather -
Visual inspection : Checked Ahd Found ok.

Sr. Item Capacity Suitable for Pipe Type of Breather Quantity


No. (GelCont.) Connection,..
V'BSP with 85 PCD
1. Silica-Gel Breather 2 Kg. Clear view Type 41 Nos.
• Flanged
Gv2. 1"BSP witj^ PCD
Silica-Gel Breather 5 Kg. Clear view Type 41 Nos.
, Flanged

TEST PARTICULARS OBSERVATIONS


Performance Test
Oil Cup at Bottom of Breather was filled with Oil up to ^Pdevebin cup went up and there after Air escaped by
line mark, Air under pressure of 5PS! slowly Rubbling through Oil from rim of Bottom Lid towards
introduced through top Lid. Breathingrholes of the Oil Cup
Pressure Test '■ _ ■
During the Performance Test as mentioned •above Airdidrhbt leak through any joints or through any
any leakage of Air from any portion of Breather|A/as ; portiom'df the Breather
checked
Oil Leakage Test Oil did not leaK through any portion of the Oil Cup
During the Performance Test as stated above
leakage of Oil from any portion of the Oil Cup wajif m . ' ■ "■ ''
checked. v Deep Blue Colour of Silica-Gel changes to Pinkish
Moisture Absorption / Evaporation Test iWhitew
A'smail quantity of Silica-Gel was subjected:to
Pinkish
rijmw White colour of Silica-Gel changes to Deep
moisture. Wet Silica-Gel was uniformly dried in oven
Blue
at 200 Degree Calais Temperature 4' •

SPECIFICATIONS OF SILICA GEL TESTED & APPROVED BY


1. Loss of Drying 3.50%
2. Absorption capacity 29;00 %{Approx.)
3.. Ph value 5.5 .
4. Chlorides 0.30%
5. Cobalt (as Cocl2) 0.55%
6. Ammonium (as NH3) Nil
7. Sulphates (as Na2S04) 0.35
8. Color of silica gel Blue (Indicating type)

Factory2; Chirag Estate, B|h. Bevabhal Estate, Sureliya Estate Road, Amraiwadi, Ahmedabad-3B0 026. (Gujarat) INDIA, (F) +91-79-2586012f
• E-mail: pratik@rinutransco.coni • E-mail: nl!esh@rinutransco.com • Visit us: www.rinutran$GO.com
VIJA^ INDUSTRIES
Mfg Of: Ail Type Of OCB Main Contact & Spare Parts,
All Type Of Gun Metal and Aluminum Clamp Conductor Suitable For
11 KV to 400 KV Subs taUons
Opp.Aryodaya Ginning Mill, Hartpura Road, Asarwa, Ahmedabad-380016 (Gujarat)
Mobile: 9601885559 f E-mail: viiavind.drp@amail.com
Date: 17/08/2018

Test Report

Name of the Item. Bimetallic Connector for HV


Quantity 27 Nos.
Project N/A
Purchaser Atlanta Eleetricals Pvt. Ltd.
Order Reference POD/RM/1819/01035, Date:18/07/2018
Item Code BMC01291 HV
Drawing Reference AT10/1025Q( VI/AEPl/02/2018-19}
Relevant Standard IS 5561-1970
Indian Standard Specification for Electric Power Connectors

Following Routine Tests, were conducted on the finished pieces and the results / observations are as
noted alongside

Name of the test : Requirements Result

Visual Inspection : Should be free from visual defects like cuts, burrs or blow Meets the
holes. Finish should be smooth with no sharp edges requirement
Dimensional ; Dimensions shall be as per the approved drawing within Meets the
Check the permissible tolerance requirement

All Clamps are manufactured as per Drawing Specification Provided. Clamps are made from EC Grade
Aluminum Material from Flats Bar and Supplied with Necessary SS 304- Bolt, Nut, and MS-Zinc
Washers & Bimetal Sleeve (CU+AI)

Conclusion: Satisfactory

Tested by

For, Vijay Industries


VIJAY industries
Mfg Of: All Type Of OCB Main Contact & Spare Parts,
All Type Of Gun Metal and Aluminum Clamp Conductor Suitable For
11 KV to 400 KV Substations
Opp.Aryodaya Ginning Mill, Haripura Road4 ASarwa, Ahmedabad-380016 (Gujarat)
Mobile: 9601886559 / E-mail: viiavind.rim@fimaii nnm
Date: 17/08/2018

Test Report

Name of the Item Bimetallic Connector for LV


Quantity 20 Nos.
Project N/A
Purchaser Atlanta Electricals Pvt. Ltd.
Order Reference POD/RM/1819/010B5, Date:18/07/2018
Item Code BMC01291 LV
Drawing Reference AT10/1026Q( VI/AEPL/03/2018-19}
Relevant Standard IS 5561-1970
Indian Standard Specification for Electric power Connectors

Following Routine Tests, were conducted on the finished pieces and the results / observations are as
noted alongside

Name of the test : Requirements Result


Visual Inspection ; Should be free from visual defects like cuts, burrs or blow
Meets the
holes. Finish should be smooth with no sharp edges
requirement
Dimensional : Dimensions shall be as per the approved drawing within
Meets the
Check the permissible tolerance
requirement

All Clamps are manufactured as per Drawing Specification Provided, Clamps are made from EC Grade
Aluminum Material from Aluminum Flats Bar, Tube. And Supplied with Necessary MS-HDG - Bolt,
Nut, and MS-Zinc Washers & Bimetal Plate (CU+AI)

Conclusion: Satisfactory

Tested by

For, Vijay Industries


iMG_20180910_141202137 .jpg
2/2018

H %
•ffiB
,wf iPiS
Hi mj

m sid'iiiiisSf
m 1
iafiV! /-w y-s#-■'yW'.jp*>>*tTTtiitTARUi3yiiKW4i*i*^w•
ill 1
Siiif
^SKfiPifs ,; mmf-
BHIMB I !! wiiW?mmm ¥ 'W elilfiffliSbW
mlfr
•ijjaii/5L ^ Viiz'.'&'M Sitfii wn ww s-Sii
id .c
•im<s HIW ;lss M m
■VJIP Sisals Iw'S
srJKP A'ti 5«K«
;jii..I .i,i m
•^w - feiurrii'
ii'S' wi^'aB
;tfCi ttwli ASBpiS
,iS" ^iK! «!sp %
11M' Wit!
Mmi Iwlik m
;f'M» !t }HHffi(lliS3»;?V<h,ullQif2/' (uttfni !!•'>»
Mai
«RHiS
WSKmmfmt
LmJ JXkV'lS ffl'l Kwi m v$m
afe-sss ■' *T£r,'2 iiil
iwWWwM? i !■
IKmm
' assgss**^^ iiS'/inii!' «pih'i
mi
jtlilwj .m s^^Esa '..i fe* M 111,1
ahESffi jtk It PW®
ili in
m
w, m m
mm .E-ds
m ifJsilij
Mtoll
ivjfl m
sns ;. ; m Sti
31 i&m
illii
tm
m :■ m fSiil
m
liii
mt
■ ■.:■■■■■■ :
im njnJi

hUKlimJiliiftle,con,/m|§/0fflinbo^165cd0365585^3?proJec1o,= ^aifeO#Par.ld=0.1
9/12/2018 IMG_20180910_161240652_BURST001.jpg

isippsp»g immi
mm IliwiSilwMSBS
I PI
fL'a% RS PfcwiB^ * ■

ft jm! m

m 'SWi
;
^- ! wM-
'r-■SSWffrfStear
■■Mn^.EKjr^jll^RfcSLw
&'' " ""
f'fi 'i.'A /,•'..}„.•j »•f. 2ii1LS?:'.: v9i• a.M
r.,r.„rrT.rrV-«;, ■■
.a::::.,..J'l~ ® «*2Iwl
ll.Ul.Ujin- •jtm
XminS SSSSIISi
rww; Jmrnmrnz?
iaiw ^ zm. iiH
•*tn m

fimfSf
«?i
MH r* '*%>■a»S
%%!& SpiBlpS
Sfti
^ ,' v.
•■.v '®s^, iu-w... asgfe j^F Vfr"'^
alii _.. PPHRHpRII^H^HpilllHip

mmm »ri •w* li IBnvp


•■la ■An»iE^2£v>
^MS|p' ill
•» zm 118^
Ifi w£i'A\^ m
:»w;
m £
r4il
» '■■mm
PM:
Hi

mmsm
<•Srr'.'fcAJ'AKW W.1-J/+H?>v Wi'Itny

https;//mail.google.com/fnail/u/0/#inbox/165cd0365585ece3?projector=1&messagePartld=0.1 1/1
-.i

KtERii^

miw
',|p'!4
^i Z &Jifei
««'P^si]
PSS p|
-.sJlil &1!iii!?fS !'!'^;f#;:
'„. -•v.'- |^li%

iM 5^ *«
«««»»,

!;.i!r;i;r^:!lf:?!Si!iSiCi!

You might also like