Subject : GROUNDING / Voltage - Grounding system in Factory

Dear Mr Mardini ,

The theoretical resistance of the Ground-pin;

Re = 25 / Inom

The maximum nominal current of the EVO = 210 Amp.

Re = 25 / 210 = 0,12 Ohms.

You have mentioned that the Re of your groundpin is 2 Ohms.

This is the groundpin of your whole factory (?).

When there is only 1 groundpin in your factory, then the value of 2 Ohms is high.

Stork Prints B.V. (Trade Registry Oost Brabant, The Netherlands, nr. 16032034) is part of the Stork Prints Group. Stork Prints B.V. its General Delivery Conditions apply to all
offers and all agreements to be made and/or services to be rendered by Stork Prints B.V. concerning deliveries of capital goods and parts. Stork Prints B.V. its General Delivery
Conditions for Consumables apply to all offers and all agreements to be made concerning deliveries of consumables by Stork Prints B.V. Said general delivery conditions have
been deposited under number 106/2002 respectively 107/2002 with the court registry of the ’s-Hertogenbosch District Court, The Netherlands. Upon your first request, you will
be sent a copy, free of charge. These general delivery conditions each include a restriction of our liability. Any other terms and conditions are hereby explicitly excluded.
Stork Prints B.V.

In a TN earthing system, one of the points in the generator or transformer is connected with earth, usually
the star point in a three-phase system. The body of the electrical device is connected with earth via this
earth connection at the transformer.

TN-S

TRANSFORMER

PRIMARY / SECUNDARY
DELTA / STAR

L1
L2
L3

Neutral
Ground

Secundary side of

-2-
Stork Prints B.V.

SECTION of electrical drawings

Grounding connections between Ground Pin and machine frame parts.

-3-
Stork Prints B.V.

TRANSFORMER in FACTORY

PRIMARY / SECUNDARY
DELTA / STAR

High Voltage Net


(main supply)

In order to realize a better grounding,


an additional ground pin in the area of the machine can be made.

EVO

-4-
Stork Prints B.V.

Measure Factory Ground Pins resistance – Check with your local installer –
Resistance depends on Soil-type.

DELTA / STAR

High Voltage Net


(main supply)

DISCONNECT
DURING TEST

The distance between the reference pins must be


15-30 meters, in order to measure a correct value.

RESISTANCE
GROUND_TESTER = Re < 1 Ohm
PD LINE MACHINE

EVO Printing Machine

-5-
Stork Prints B.V.

The Test distance between groundpins should be large enough.

Usuallly a distance of 20 – 50 meters is sufficient.

This depends in soil type – Contact your local installation-engineer.

When ground pins are too close to eachother they should be seen as ‘1 pin’.

Sometimes several pins are used close to eachother, in order to create 1 good grounding-pin.

Also wire-grids can be used as ground ( as long it is not steel concrete wire grid which will rust away )

Ground pins can be made out of Galvanised Steel, or Copper-plated Steel ( pipes / grids )

Check you local supplier for specific knowledge.

PIN 1 / Bad grounding PIN 2 / Good grounding

Dry Soil / High Resistance

Moist Soil / Low Resistance

Met vriendelijke groet / With kind regards,