RK8, RK88 RK2, RK22 RK82 Universal P Controllers: Types

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

381

RK8, RK88
3
RK2, RK22
RK82
Universal P controllers

Electronic proportional controllers in


the analogue control range, CLASSIC,
for the control of temperature, RK..
humidity, air quality, pressure etc.
One or two output sequences: Types
• Proportional output sequence(s) to
drive valves, damper actuators etc. RK8 Universal controller with one proportional output sequence
and/or RK88 Universal controller with two proportional output sequences
• 2-point output(s) for on/off control RK2 Universal controller with one on/off output
of pumps, compressors, electric RK22 Universal controller with two on/off outputs
heating coils etc. RK82 Universal controller with one proportional output sequence and
one on/off output

Technical data
Supply voltage Extra low voltage (SELV)
Nominal voltage AC 24 V +15/–10 %; 50 ... 60 Hz
Power consumption 4 VA (without output peripheral devices)
Signal inputs
Control sensor x1
– Temperature T1 sensor
– Humidity etc. DC 0 ... 10 V, Ri >10 MΩ
External setpoint adjuster w1
– Temperature Setpoint adjuster, type BSG-T..
– Humidity etc. Setpoint adjuster, type BSG-100
Outputs (Factory setting)
Proportional outputs
Y1 (RK8, RK88, RK82), Y3 (RK88) DC 0 ... 10 V, max. 1.5 mA (source)
– Cut-in point xa –10 ... 10 K (0 K)
– Proportional band xp 1 ... 10 K (3.5 K)
– Adaptation to peripheral devices "universal"/"magnetic" ("magnetic")
– Mode of operation Heating/cooling (Y1 heating, Y3 cooling)
On/off outputs
Y2 (RK2, RK22), Y4 (RK22, RK82) Volt-free relay contact
– Kontaktbelastung Max. AC 250 V
Max. 5 A resistive
Max. 2 A inductive (cosϕ ≥0.4)
Min. admissible load: 10 mA at DC 5 V
– Max. voltage against earth 250 V
– Switch-off point xoff –10 ... 10 K (0 K)
– Switching differential xd 1 ... 10 K (3,5 K)
– Mode of operation Heating/cooling (Y2 heating, Y4 cooling)
Controller data
Control algorithm P
Internal setpoint
– Temperature 5 ... 32 °C
– Humidity etc. 10 ... 90 %
External setpoint adjusters
Temperature BSG-TC Comfort 10 ... 30 °C
BSG-TZ Supply air 20 ... 60 °C
BSG-TK Refrig. –20 ... 20 °C
BSG-TH Heating 30 ... 110 °C
Humidity BSG-100 DC 0 ... 10 V (0 ... 100 %)
Optional digital indicator BA-RK
Connection terminals Plug-in screw terminals 2 x 1.5 mm2
Weight 0.45 kg
Dimensions (W x H x D) 108 x 122 x 52 mm

Landis & Staefa CA1N3381E June 1997 1/2


General ambient conditions
Conditions of use For installation in control panel
Temperature range
– Operation 5 ... 45 °C
– Transport/storage –25 ... 70 °C
Ambient humidity 10 ... 90 %rh, non-condensing
Mounting Snap-mounted on DIN rail (EN50022-35x7.5)
or screwed to a flat surface
Safety:
Product safety EN 60730
– Overvoltage category II; transient overvoltages up to 2500 V
Output sequences – Contamination level 2; normal non-conductive contamination
Electrical safety SELV-E (PELV to IEC364-4-41)
Proportional (RK8, RK88, RK82)
Conformity Meets the requirements for marking
y [V] y [V]
m u 94.0274

xp xp
xa
8 10 Principle of operation
The CLASSIC electronic universal P controller is suitable for the control of
A B temperatures, relative humidity, air quality, pressure etc.
4 2 The controller compares the measured value x1 with the setpoint w1
x [°C] (internally or externally defined) and generates an output based on the
w1
difference between these two values and the programmed sequence
On/off (RK2, RK22, RK82) parameters.
Relais
94.0281
For further details, see Technical manual Q1.
xd xd
xoff

on
Mounting and installation
A B
– The connection terminals must be freely accessible.
off – Adequate air circulation must be provided, to dissipate the heat
x [°C]
generated during operation
w1 95 40818

y Output signal
1 4
x Measured value Rail type:
w1 Setpoint EN50022-35 x 7.5

xa Offset between heating/cooling


sequence cut-in point and setpoint
121

x p Proportional band
109

82 82
RK RK

x off Switch-off point


x d Switching differential
A Heating sequence max. ø 4,5 mm
B Cooling sequence 52
108

u "universal" for DC 0 ... 10 V


2 3
controlled devices
m "magnetic" for magnetic valves Rail mounting Surface mounting

Terminal layout
RK8, RK88, RK82 RK2, RK22
60073 94.0329
0 TE Functional earth 0 TEFunctional earth
1 NS Secondary neutral conductor 1 NSSecondary neutral conductor
2 LS Secondary phase conductor 2 LSSecondary phase conductor
AC 24 V +15/–10 % AC 24 V +15/–10 %
11 x1 Sensor (T1 / DC 0 ... 10 V) 11 x 1 Sensor (T1 / DC 0 ... 10 V)
12 HGND T1 sensor ground 12 HGND T1 sensor ground
13 w1 External setpoint adjuster 13 w 1 External setpoint adjuster

60 Yt (used internally) 71
61 Y1 Proportional output signal DC 0 ... 10 V 72 Y2 On/off relay, volt-free, AC 230 V/5(2)A
62 (Y3) Proportional output signal DC 0 ... 10 V 73
(RK88 only)
76 76
77 (Y4) On/off relay, volt-free, AC 230 V/5(2)A 77 (Y4) On/off relay, volt-free, AC 230 V/5(2)A
78 (RK22 only) 78 (RK22 only)

NS = System ground (Common)

© 1997 Landis & Gyr (Europe) Corp.

2/2 CA1N3381E June 1997 Landis & Staefa