Professional Documents
Culture Documents
MDGF - New Feature For Emax 2 and New Tmax XT - June2020
MDGF - New Feature For Emax 2 and New Tmax XT - June2020
JUNE 2020
The challenge: Multi-sourced electrical system with a solidly grounded common neutral conductor
make ground fault protection very challenging. These systems are often found in double ended
substation and generation paralleling gear applications.
In these cases, it is not enough to use traditional zero sequence ground fault protection because it is
virtually impossible to isolate and identify the ground fault current.
The Emax 2 offers Modified Differential Ground Fault, or MDGF, protection to solve this paradigm.
The solution includes Emax 2’s Gext protection algorithm as well as some external hardware to
interconnect the system.
X2 X2
AH2
AX2
X1 AX1 X1
AH1
External phase current
Ge- AH2 AH2 Ge-
TRIP UNIT AX2 AX2 transformer
TRIP UNIT
Ge+ Ge+
AX1 AX1
AH1 AH1 External summing
current transformer
X2
X1
Ge+
Ge-
TRIP UNIT
TRIP UNIT Emax 2 trip unit with
MDGF terminal
LOADS LOADS
1 2
1 2
1 3 1
3
1 2
3
3
0 3
A B
3
CLOSE 0
3
3 CLOSE
0 1
1 1 1 2
1
C
3
June 2020
Slide 6
OPEN
Circuit Current
Action
Breaker Measured
— A 0 p.u. NO TRIP
MDGF
B 7 p.u. TRIP
C 7 p.u. TRIP
p.u. → per unit
4 3
4 3
5 1 2 1
7
4 3
7
7
0 7
A B
7
CLOSE 0
7
7 CLOSE
0 4
4 4 4 3
5
1
C
7
June 2020
Slide 7
CLOSE
Circuit Current
Action
Breaker Measured
— A 4 p.u. TRIP but it is still OPEN
MDGF
B 0 p.u. NO TRIP
C 4 p.u. TRIP
p.u. → per unit
3 1
3 1
3 4 3
4
3 1
4
4 0 0
A B
4
OPEN 4
0
0 CLOSE
4 1
3 1 1 1
3
4 C
June 2020
Slide 8
CLOSE
—
Documentation
Instruction sheet MDGF terminal Application wiring diagram Phase CTs and Summing CTs
LINK LINK LINK