ET 200eco PN M12-L
Documentation Guide 1
Product overview 2
SIMATIC
Wiring 3
ET 200eco PN
Digital inputs/outputs 4
Parameters/address space
DIQ 16x24VDC/0.5A/2A M12-L
8xM12 (6ES7143-6BH00-0BB0) Interrupts/diagnostics
alarms 5
Equipment Manual
Technical specifications 6
Dimension drawing A
06/2021
A5E46571210-AB
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication
may be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Conventions
Also observe notes marked as follows:
Note
A note contains important information:
• On the product described in the documentation
• On handling the product
• On the part of the documentation to which particular attention is paid
Security information
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is
necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial
security concept. Siemens’ products and solutions constitute one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is necessary
and only when appropriate security measures (e.g. firewalls and/or network segmentation)
are in place.
For additional information on industrial security measures that may be implemented, please
visit (https://www.siemens.com/industrialsecurity).
Siemens' products and solutions undergo continuous development to make them more
secure. Siemens strongly recommends that product updates are applied as soon as they are
available and that the latest product versions are used. Use of product versions that are no
longer supported, and failure to apply the latest updates may increase customers' exposure to
cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS
Feed visit (https://www.siemens.com/industrialsecurity).
Preface ................................................................................................................................................... 3
1 ET 200eco PN M12-L Documentation Guide .......................................................................................... 6
2 Product overview ................................................................................................................................. 10
2.1 Properties .......................................................................................................................... 10
2.2 Operator controls and display elements.............................................................................. 13
3 Wiring .................................................................................................................................................. 14
3.1 Terminal and block diagram ............................................................................................... 14
3.2 Pin assignment .................................................................................................................. 15
4 Parameters/address space ................................................................................................................... 18
4.1 Parameters ........................................................................................................................ 18
4.2 Explanation of the parameters ........................................................................................... 19
4.3 Address space .................................................................................................................... 21
5 Interrupts/diagnostics alarms .............................................................................................................. 28
5.1 Status and error displays .................................................................................................... 28
5.2 Interrupts .......................................................................................................................... 31
5.3 Alarms ............................................................................................................................... 32
5.3.1 Diagnostics alarms ............................................................................................................. 32
5.3.2 Maintenance events........................................................................................................... 33
5.3.3 Hardware interrupts ........................................................................................................... 34
6 Technical specifications ....................................................................................................................... 35
A Dimension drawing ............................................................................................................................. 42
A.1 Dimension drawing ............................................................................................................ 42
Basic information
The system manual describes in detail the configuration, installation, wiring and
commissioning of the SIMATIC ET 200eco PN M12-L distributed I/O system. The STEP 7 online
help supports you in the configuration and programming.
Device information
Product manuals contain a compact description of the module-specific information, such as
properties, interfaces, wiring diagrams, display and operator control elements and technical
specifications.
General information
The function manuals contain detailed descriptions on general topics relating to the SIMATIC
ET 200eco PN M12-L distributed I/O system, e.g. diagnostics, communication and PROFINET.
You can download the documentation free of charge from the Internet
(https://support.industry.siemens.com/cs/de/en/view/109742718).
"mySupport"
With "mySupport", your personal workspace, you make the best out of your Industry Online
Support.
In "mySupport", you can save filters, favorites and tags, request CAx data and compile your
personal library in the Documentation area. In addition, your data is already filled out in
support requests and you can get an overview of your current requests at any time.
You must register once to use the full functionality of "mySupport".
You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/en).
Application examples
The application examples support you with various tools and examples for solving your
automation tasks. Solutions are shown in interplay with multiple components in the system -
separated from the focus on individual products.
You will find the application examples on the Internet
(https://support.industry.siemens.com/cs/ww/en/ps/ae).
PRONETA
SIEMENS PRONETA (PROFINET network analysis) allows you to analyze the plant network
during commissioning. PRONETA features two core functions:
• The topology overview automatically scans the PROFINET and all connected components.
• The IO check is a fast test of the wiring and the module configuration of a system.
You can find SIEMENS PRONETA on the Internet
(https://support.industry.siemens.com/cs/ww/en/view/67460624).
SINETPLAN
SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and
networks based on PROFINET. The tool facilitates professional and predictive dimensioning of
your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports
you during network optimization and helps you to exploit network resources optimally and to
plan reserves. This helps to prevent problems in commissioning or failures during productive
operation even in advance of a planned operation. This increases the availability of the
production plant and helps improve operational safety.
The advantages at a glance
• Network optimization thanks to port-specific calculation of the network load
• Increased production availability thanks to online scan and verification of existing systems
• Transparency before commissioning through importing and simulation of existing STEP 7
projects
• Efficiency through securing existing investments in the long term and the optimal use of
resources
You can find SINETPLAN on the Internet (https://www.siemens.com/sinetplan).
Article number
6ES7143-6BH00-0BB0
Figure 2-1 View of the I/O device DIQ 16x24VDC/0.5A/2A M12-L 8xM12
Properties
The I/O device has the following technical properties:
• 16 digital inputs/digital outputs, depending on configuration and parameter assignment
– 8 DIQ signals connected to 1L+ (non-switched)
– 8 DIQ signals connected to 2L+ (switched)
• M12 sockets for connection of sensors or actuators
• Digital inputs:
– 24 V DC supply voltage
– Configurable input delay 0.05 to 20 ms (per channel)
– Configurable diagnostics can be set for each channel
– Configurable hardware interrupt can be set for each channel
– Suitable for switches and proximity switches
• Digital outputs:
– Rated load voltage 24 V DC
– Configurable diagnostics can be set for each channel
– Output current per output 0.5 A at X10 to X13
total current max. 2 A for group X10 to X13
– Output current per output 2 A at X14 to X17
total current max. 6 A for group X14 to X17
– Suitable for solenoid valves, DC contactors, and indicator lights
• Integrated switch with 2 ports
• Dual assignment of the sockets
• Dimensions 45 x 200 mm
The I/O device supports the following functions:
• Firmware update
• Identification and maintenance data I&M0 to I&M3
• Value status (Quality Information)
• Module-internal Shared Input/Output (MSI/MSO)
• Shared device
Accessories
The following components are included in the I/O device package:
• Identification labels
Other components
The following component can be ordered as spare part:
• Identification labels
The following components can be ordered as accessories:
• Mounting rail
• Connectors and cables
• M12 sealing cap
See also
You can find additional information on the accessories in the ET 200eco PN M12-L distributed
I/O system system manual.
See also
Technical specifications (Page 35)
① Bus interface with integrated 2-port switch 1L+ Supply voltage 1L+ (non-switched)
② Monitoring 1M Ground 1M (non-switched)
③ DIQ circuit (1L+, 1M) 2L+ Load voltage 2L+ (switched)
④ DIQ circuit (2L+, 2M1) 2M Ground 2M (switched)
⑤ Internal supply voltage 2M1 Ground with reverse polarity protection, divert-
ed from 2M (switched)
⑥ Configured as inputs: 2-wire connection 1US 24 V encoder supply (from 1L+)
⑦ Configured as input: 2-wire connection 2US 24 V encoder supply (from 2L+)
⑧ Configured as output DIQn Input/output signal
⑨ Configured as inputs: 3-wire connection RN/NS RUN/network status LED (green)
⑩ Configured as input: 3-wire connection ER/MS ERROR/module status LED (red)
⑪ Configured as outputs MT/IO MAINT/IO status LED (yellow)
X10 to X17 Channels 0 to 15 P1 LK Link port 1 LED (green)
X80 Infeed of supply and load voltage P2 LK Link port 2 LED (green)
X81 Loop-through of supply and load voltage DIQ Channel status/channel error LED (green/red)
X1 P1R PROFINET interface X1 port 1 PWR LED load voltage 2L+ (green)
X1 P2R PROFINET interface X1 port 2
Figure 3-1 Terminal and block diagram
Assignment X1 P2 R
1 Yellow RXP
2 White TXP
3 Orange RXN
4 Blue TXN
Thread Functional earth FE
NOTICE
24 V encoder supply 1US
Use only the 24 V encoder supply 1US provided by the I/O device to supply power to the
encoders.
NOTICE
24 V encoder supply 2US
Use only the 24 V encoder supply 2US provided by the I/O device to supply power to the
encoders.
NOTICE
Reverse polarity protection
To guarantee reverse polarity protection, use the ground 2M1 supplied by the I/O device at
pin 3 of the respective socket.
Reverse polarity protection is suspended for a connection of 2M and 2M1.
Pin assignment of the connector for infeed of the supply voltage (M12 L-coded)
The table below shows the pin assignment of the M12 L-coded connector for infeed of the
supply voltage.
Pin assignment of the socket for loop-through of the supply voltage (M12 L-coded)
The table below shows the pin assignment of the M12 L-coded socket for loop-through of the
supply voltage.
Note
This diagnostics is only available for channels supplied with 2L+ voltage.
Diagnostics: Short-circuit
Enable diagnostics:
• for short-circuit of the encoder supply to ground.
• for short-circuit of the output to ground.
• for short-circuit of the output to 1L+ or 2L+.
Note
• This diagnostics is only available for channels configured as inputs.
• Influence on the value status:
If the parameter is deactivated, wire break detection is switched off. A wire break does not
have an effect on the value status.
Input delay
This parameter can be used to suppress signal interference. Changes to the signal are only
detected if they are present consistently for longer than the set input delay time.
For input channels with longer input delays, the read-in time is moved accordingly. This
means individual channels can be assigned input delays, if necessary, without having a
negative impact on the possible cycle time.
Configuration mode
Specifies whether the channel operates as digital input (DI) or digital output (DQ).
Configuration Short designation/ Configuration software, e.g., with STEP 7 (TIA Portal)
device name in the Integrated in hardware GSD file in
GSD file (device view in catalog STEP 7 STEP 7 (TIA Portal) V11 or
the configuration soft- (TIA Portal) higher or STEP 7 V5.5 SP4
ware) HF1 or higher
1 x 16-channel DIQ 16x24VDC DIQ 16x24VDC/0.5A/2A V16 or higher with HSP X
0299
1 x 16-channel DIQ 16x24VDC QI DIQ 16x24VDC/0.5A/2A, QI V16 or higher with HSP X
0299
1 x 16-channel DIQ 16x24VDC DIQ 16x24VDC/0.5A/2A, V16 or higher with HSP X
MSI/MSO MSI/MSO 0299
2 x 8-channel DIQ 16x24VDC S DIQ 16x24VDC/0.5A/2A, S - X
Figure 4-1 Address space for configuration as 1 x 16-channel DIQ 16x24VDC without value status
Figure 4-2 Address space for configuration as 1 x 16-channel DIQ 16x24VDC QI with value status
The following figure shows the assignment of the address space with submodules 1 and 2
and the value status.
Figure 4-3 Address space for configuration as 1 x 16-channel DIQ 16x24VDC MSI/MSO with value
status (basic submodule)
Figure 4-4 Address space for configuration as 1 x 16-channel DIQ 16x24VDC MSI/MSO with value
status (MSI/MSO submodule)
Figure 4-5 Address space for configuration as 2 x 8-channel DIQ 16x24VDC S without value status
Reference
You can find information on the functionality Module-internal Shared Input/Shared Output
(MSI/MSO) in the STEP 7 online help or in the function manual SIMATIC PROFINET with STEP
7 (https://support.industry.siemens.com/cs/ww/en/view/49948856).
LED displays
The figure below shows the LED displays (status and error displays) of the I/O device DIQ
16x24VDC/0.5A/2A M12-L 8xM12.
Behavior of the LEDs RN/NS (RUN/network status), ER/MS (ERROR/module status) and MT/IO
(MAINT/IO status) on PROFINET
PWR LED
P1 LK and P2 LK LEDs
Table 5- 4 Status and error display of the channel status/channel error LEDs
LEDs Meaning
Channel sta-
tus/channel
error
Process value = 0
Off
Process value = 1
On
Channel diagnostics
On
5.2 Interrupts
The I/O device digital inputs DIQ 16x24VDC/0.5A/2A M12-L 8xM12 supports diagnostic and
maintenance interrupts.
Diagnostic interrupt
The I/O device generates a diagnostic interrupt on the following events:
• Wire break
• Internal module fault
• Parameter error
• Hardware interrupt lost
• 2L+ missing or too low
• Short-circuit
Maintenance alarm
The I/O device generates a maintenance alarm on the following event:
• Undervoltage at 1L+
Hardware interrupt
The I/O device generates a hardware interrupt on the following events:
• Rising edge
• Falling edge
5.3 Alarms
Note
Wiring two outputs in parallel
For parallel connection of two outputs for redundant control of a load, deactivate the channel
diagnostics "Wire break" and "Short-circuit to L+".
Uncouple the parallel switched outputs via external diodes.
Product function
• I&M data Yes; I&M0 to I&M3
• Isochronous mode No
Engineering with
• STEP 7 TIA Portal configurable/integrated from STEP 7 V17 or higher with HSP 0299
version
Operating mode
• DI Yes
• Counter No
• DQ Yes
• MSI Yes
• MSO Yes
Supply voltage
Load voltage 1L+
• Rated value (DC) 24 V
Input current
Current consumption (rated value) 90 mA; without load
from load voltage 1L+ (unswitched voltage) 12 A; Maximum value
from load voltage 2L+, max. 12 A; Maximum value
Encoder supply
24 V encoder supply
• Short-circuit protection Yes; Group-by-group for 2 channels, electronic
Power loss
Power loss, typ. 9.7 W
Address area
Address space per module
• Inputs 2 byte; + 4 bytes for QI information
• Outputs 2 byte
Hardware configuration
Submodules
• Number of configurable submodules, max. 2
Digital inputs
Number of digital inputs 16; Parameterizable as DIQ
• in groups of 8
Input current
• for signal "1", typ. 2.4 mA
Digital outputs
Number of digital outputs 16; Parameterizable as DIQ
• in groups of 8; 2 load groups for 8 outputs each
Current-sourcing Yes
Short-circuit protection Yes; per channel, electronic
• Response threshold, typ. 0.5 A: 1 A / 2 A: 3 A
Limitation of inductive shutdown voltage to 0.5 A: Type 1L+ (-70 V) / 2 A: Type (-18 V)
Controlling a digital input Yes
Switching capacity of the outputs
• with resistive load, max. 0.5 A / 2 A
• upper limit 4 kΩ
Output voltage
• for signal "1", min. 1L+ (-0.8 V) / 2L+ (-0.8 V)
Output current
• for signal "1" rated value 0.5 A / 2 A
Switching frequency
• with resistive load, max. 0.5 A: 100 Hz / 2 A: 40 Hz
Cable length
• unshielded, max. 30 m
Encoder
Connectable encoders
• 2-wire sensor Yes
• Number of ports 2
Protocols
• PROFINET IO Device Yes
Interface types
M12 port
• Autonegotiation Yes
• Autocrossing Yes
Protocols
Supports protocol for PROFINET IO Yes
PROFINET IO Device
Services
– IRT Yes; 250 µs to 4 ms in 125 µs frame
– on S7-1500R/H Yes
– on S7-400H Yes
Media redundancy
– MRP Yes
Open IE communication
• TCP/IP Yes
• SNMP Yes
• LLDP Yes
Interrupts/diagnostics/status information
Substitute values connectable Yes
Alarms
• Diagnostic alarm Yes; Parameterizable
Diagnoses
• Diagnostic information readable Yes
– parameterizable Yes
• Wire-break Yes; DI, input current < 0.3 mA, per channel
Potential separation
between the load voltages Yes
between Ethernet and electronics Yes
• between the channels and the power supply 8 channels are non-isolated and 8 channels are
isolated from supply voltage 1L+
of the electronics
Isolation
tested with
• 24 V DC circuits 707 V DC (type test)
• Test voltage for interface, rms value [Vrms] 1 500 V; According to IEEE 802.3
Ambient conditions
Ambient temperature during operation
• min. -40 °C
• max. 60 °C
Derating trend
The following figure show the load current derating with mounting clearance observed,
depending on the ambient temperature.
The minimum clearance of the I/O devices is 2 cm around the I/O device.
Note
Adherence to the minimum clearance
The I/O devices may be used at an installation distance of 2 cm up to max. 60 °C ambient
temperature.
If the installation distance to other devices or objects is less than 2 cm, the ambient
temperature must be reduced by 5 K (for example, 60 °C ⇒ 55 °C). This also applies to the
derating trend.