SUB HEAD-14
Fire extinguisher
14.1.1 Supply & fixing the following capacities multi purpose ABC dry chemical
powder stored pressure type with manometer system fire extinguisher
suitable for repeated use complete with wall bracket, CO2 cartridge,
easy refilling system etc. as per sample accepted & approved by the
Engineer.
Mono Amonium Phosphate based 40% ABC dry chemical agent & has
a moisture-proof, anti-caking properties. Working pressure : 12 BAR
minimum & Test pressure : 25 BAR minimum. Proper fire rating (as per
NFPA 10) according to the capacity of the extinguisher. Manufacturerer
certificate shall have to be submitted if needed. Also sample of the dry
chemical powder will be tested by the proper authority in Bangladesh if
needed.
Carbon-Di-Oxide type
14.1.2 Supply & fixing the following capacities Carbon-di-Oxide type fire
extinguisher suitable for repeated use complete with wall bracket,
discharge nozzle etc. as per sample accepted & approved by the
Engineer.
Foam type
14.1.3 Supply & fixing the following capacity Foam type Fire Extinguisher
suitable for repeated use complete with wall bracket etc. as per
sampleaccepted/approved by the Engineer.
14.1.4 Providing & fixing the following parts of fire extinguisher as per sample
accepted/approved by the Engineer
Country of origin: CHINA / MALAYSIA or equivalent product
General :
14.2 Supply & installation of disel engine driven fire pump complete with all
related & essential accessores. The pump shall be designed and
installed in accordance with globally accepted international standard.
Each unit shall be tested and UL listed/FM approved.
Diesel engine :
Controller :
JOCKEY PUMP
(Pressure maintenance pump)
14.7 PUMP CONTROL PANEL FOR MOTOR DRIVEN FIRE & JOCKEY
PUMPS
Supply, installation of fire & jockey pump control panel complete with
MCCB / MCB / magnetic contactor / on-off push switch / indication lamp
for phase indication, run, trip mode / ampere meter / volt meter /
overload selector switch / phase failure protection device / dry operation
protection device / volt guard / connector block / bus-bar / CT of rated
capacity / ventilation fan / buzzer / cable lugs / and all other
accessories. The panel shall be well dressed in side for safety purpose
and for looking good.
The panel shall be suitable for 3-phase 400 ± 5% volt 50Hz power
supply. The panel shall with auto-manual mode to operate the pumps
controlled by pressure sensors. For fire pump the panel shall have
option to start the pump automatically by stop shall be manual. For
jockey pump the panel shall be suitable to start-stop the pump
automatically controlled by pressure sensor.
Encloser of the panel shall be made with 16 SWG sheet steel and shall
be painted with powder coating of red color approved as Fire code.
Door of the panel shall be swing type with locking arrangement. Knob of
main MCCB shall be extended in front screen. The panel shall be wall
mounted type with fixing arrangement properly.
14.8 Each 1½" dia fire hydrant unit shall be complete with the following
components and accessories.
Supply & installation of fire hose of 40mm dia 30 meter long with hose
rack frame & nipple suitable to install inside the hydrant cabinet. The
hose shall conforming to UL 19. The hose shall be UL Listed / FM
approved & burst pressure shall be not less that 600 psi and working
pressure 200 psi, shall be made with special quality EPDM rubber as
internal lining, suitable to withstand heat and polluted water, heat and
abrasion resistance, Jacketting shall be made up of 100% polyester for
extra sthrength. Hose shall be 30meter long in a single length and shall
be with male coupling in one end other end with female coupling.
Couplings shall be binded with hose with copper wire properly. Coupling
shall be available in NST or instantaneous couplings shall be made
with bronze / alluminium alloy, polished / hard anodized to confirm BS
336.
Supply & installation of jet / spray nozzle having 40mm dia male
instantaneous coupling. The nozzle shall be operable in three modes:
jet - spray - shut off. The nozzle shall be light weight and easy operable.
Construction of the nozzle shall be of brass or alluminium & nylon.
Working pressure shall be not less than 7Kg / Cm². Flow shall be not
less than 100 lpm @ 7kg / cm². Nozzle shall be install inside the
cabinet.
14.9 Each 2½" dia fire hydrant unit shall be complete with the following
components and accessories.
Supply of fire hose of 2½" (63mm) dia 30 meter long with hose rack
frame & nipple suitable to install inside the hydrant cabinet. The hose
shall conforming to UL 19 . The hose shall be UL listed / FM approved &
burst pressure shall be not less than 600 psi and working pressure 200
psi, shall be made with special quality EPDM rubber as internal lining,
suitable to withstand heat and polluted water, heat and abrasion
resistance, jacketting shall be made up of 100% polyester for extra
sthrength. Hose shall be 30 meter long in a single length and shall be
with male coupling in one end other end with female coupling.
Couplings shall be binded with hose with copper wire properly. Coupling
shall be available in NST or instantaneous couplings shall be made with
bronze / alluminium alloy, polished / hard anodized to confirm BS 336.
Supply & installation of jet / spray nozzle having 2½" (63mm) dia male
instantaneous coupling. The nozzle shall be operable in three modes:
jet - spray - shut off. The nozzle shall be light weight and easy operable.
Construction of the nozzle shall be of alluminium and nylon. Working
pressure shall be not less than 7Kg / Cm². Flow shall be not less than
150 lpm @ 7kg / cm². Nozzle shall be installed inside the cabinet.
PILLAR HYDRANT
14.1 Supply and installation of cast Iron body double deaded pillar hydrant
complete with 2 (two) nos. cast brass made controllable outlet of 65mm
dia with female instanteneous outlet, Inlet shall be 100mm dia flanged
end. The hydrant shall be suitable to withstand test pressure of 300 psi
(minimum). Color of the unit shall be red / approved by the
manufacturer or as per code. Piller hydrant Shall be BS standard.
STEEL CABINET
14.11 Fabrication, supply & installation of hydrant cabinet of suitble size (as
per site measurement and requirement / recommended by the
Engineering to accommodate landing valve, hose, nozzle and coupling.
The cabinet shall be with swing type door with or without breakable
tempered glass. The cabinet shall be made with 18 SWG sheet steel,
powder coated of red color.
14.11.i Class - I cabinet ( for 2.5'' hose rack assembly) each Tk. 12,678.00
14.11.ii Class - II cabinet ( for 1.5'' hose rack assembly) each Tk. 12,678.00
14.11.iii Class - III cabinet ( for 1.5'' hose rack assembly & 2.5 hose angle valve) each Tk. 12,678.00
14.11.iv Outdoor hydrant box for pillar hydrant each Tk. 13,886.00
14.12 Supply and installation of black steel pipe ASTM A53 ERW, 40
schedule. The pipe work shall be included with welded type tee, elbow,
reducer etc. and also hangers / supports etc completed. Pipe work (over
ground) shall be painted with red oxide primer. Underground pipes
should be layed after wrapping with PVC tape after using approved
priver. Pipe wall thickness shall be as per mentioned for different
diameters.
Country of origin : AUSTRALIA / CHINA / INDIA / JAPAN / SOUTH
KOREA / VIETNAM.
PWD E/M Schedule -2018 SH - 14 Page No :-10
14.12.i 200 mm (8 inch) dia, wall thickness: 8.2mm ft. Tk. 2,717.00
14.12.ii 150 mm (6 inch) dia, wall thickness: 7.1mm ft. Tk. 2,415.00
14.12.iii 100 mm (4 inch) dia, wall thickness: 6.0mm ft. Tk. 1,962.00
14.12.iv 80mm (3 inch) dia, wall thickness: 5.5mm ft. Tk. 1,449.00
14.12.v 65 mm (2½ inch) dia, wall thickness: 5.2mm ft. Tk. 966.00
14.12.vi 50 mm (2 inch) dia, wall thickness: 3.9mm ft. Tk. 604.00
14.12.vii 40 mm (1½ inch) dia, wall thickness: 3.7mm ft. Tk. 507.00
14.12.viii 32 mm (1.25 inch) dia, wall thickness: 3.6mm ft. Tk. 440.00
14.12.ix 25 mm (1inch) dia, wall thickness: 3.4mm ft. Tk. 423.00
14.12.x 20 mm (3/4 inch) dia, wall thickness: 2.9mm ft. Tk. 302.00
14.12.xi 12 mm (1/2 inch) dia, wall thickness: 2.8mm ft. Tk. 193.00
GATE VALVES
Supply & installation of valves & fittings complies with ANSI, flange /
groove type, temperature range: 00C-800C; working pressure: 200 PSI
minimum, valve body as per ASTM A536, 65-45-12 standard, UL / FM
approved.
14.15 Y-STRAINERS
FLEXIBLE JOINT :
14.17 Supply & installation of flexible joint complies with ANSI, temperature
range: 00C-800C ; working pressure: 200 PSI minimum, valve body as
per ASTM A536, 65-45-12 standard, UL / FM approved.
14.18 Supply & installation of ball valves complies with ANSI, temperature
range: 00C-800C ; working pressure: 200 PSI minimum, valve body as
per ASTM A536, 65-45-12 standard, UL / FM approved.
14.19 Supply and installation of 3.5'' - 4” dial type pressure gauges including
supply of all accessories and consumable. The range shall be 0-250
psi. UL/FM approved.
PRESSURE SWITCH
14.20 Supply, installation and testing of pressure switch complete with
sensing element, enclosure material, 15 mm NPT pressure connection,
direct mounting electrical connection, other material etc. accepted /
approved by the Engineer
14.22 Supply & installation of auto air vent valve of 1 inch (25mm) dia of 1"
dia inlet BSP, bronze made with rubber ball and seat. The valve shall be
suitable to release air from the fire hydrant pipes. Shall be suitable to
withstand pressure upto 10kg/cm².
FLOW SWITCH
14.23 Supply & installation of 50-100 mm dia flow switch of leaf type suitable
for installation within 65mm and 40mm dia water hydrant pipe. The flow
shall sense flow of water within pipe and send signal to water flow
monitoring panel. Flow switch shall be under control of water flow
supervisory panel to ensure the hydrant operation. Power supply shall
be 24VDC. The flow switch shall be UL listed.
14.24 Supply & installation of pressure reducing valve of 1½" (40mm) dia,
brass body, screwed end type, shall be used with 40mm dia internal
hydrant unit (where to reduce high pressure is necessary). Valve body
shall be made with hot pressed brass, seat of stainless steel ANSI304
shall be suitable for 80°C. Initial pressure shall be 15 bar, adjustable
final pressure shall be 0.5bar (min), 7bar (max)
PWD E/M Schedule -2018 SH - 14 Page No :-13
SPRINKLAR HEAD
14.26 Supply & installation of sprinklar alarm check valve (wet riser type) The
valve shall be actuated by breaking of sprinklar glass bulb. The valve
shall be UL listed / FM approved
14.27 Supply & installation of zone control valve to to get the notification of
water flow from any fire zone on a combination of butterfly valve with
tamper switch, flow switch, pressure gauge and test & drain valves. UL
listed / FM approved.
14.28 Supply & installation of water flow monitoring panel to monitor water
flow of hydrant units. After receiving close contact through flow switches
indication will be at panel and buzzer will be activated. Power supply:
230VAC ± 10%. Netwoork power shall be 24VDC. The panel shall be
conventional type, complete with LED indication, keypad, trickle
charger, rechargeable batteries etc.
INITIATING DEVICES
smoke detector
14.31 Supply and installation of smoke detector complete with base. Shall be
UL listed / FM approved / LPCB approved. Integrated alarm LED.
Remote LED connection. Power supply shall be 24VDC.
Heat Detector
14.32 Supply and installation of heat detector complete with base. Shall be
UL listed / FM approved / LPCB approved. Integrated alarm LED.
Remote LED connection. Power supply shall be 24VDC.
PWD E/M Schedule -2018 SH - 14 Page No :-15
14.33 Supply and installation of conventional type manual call point like break
glass switch or single action pull station complete with back box and all
other accessories and consumables. Power supply shall be 24V DC.
shall be UL listed / FM approved approved
14.34.i Supply and installation of conventional type fire alarm bell of 150mm dia
, red color, shall be UL listed / FM approved / LPCB approved. Power
supply shall be 24VDC. Sound level shall be not less than 92 dBA @
3meter. Color of the bell shall be red.
Horn
14.34.ii Supply and installation of conventional type horn for notification purpose
suitable to produce electronic sound level of 87 to 95 dBA @ 3 meter
complete with back box, red color, shall be UL listed / FM approved /
LPCB approved. Power supply shall be 24VDC. Color of the device
shall be red.
14.35 Balancing, testing & commissioning of fire detection & alarm system by
the compitant engineer, technical personels and provide training to the
PWD personels to operate the sytem perfectly and safely.
14.36 Supply & installation of addressable type fire alarm control panel
complete with following basic options. Master controller assembly / CPU
shall be suitable with port to add voice alarm system / fire fighter
telephone system / Printer / remote annunciator etc. FACP must be
comply with internationally accepted standard. Control units for fire
-protective signaling systems.
Loss of primary power shall sound a trouble signal at the FACP. FACP
shall indicate when the system is operating on an alternate power
supply.
Product data sheets for system components highlighted to indicate the
specific products, features, or functions required to meet this
specification. Alternate or as-equal products submitted under this
contract must provide a detailed line-by-line comparison of how the
submitted product meets, exceeds, or does not comply with this
specification.
System power and battery charts with performance graphs and voltage
drop calculations to assure that the system will operate per the
prescribed backup time periods and under all voltage conditions per UL
and NFPA standards.
Alarm silence, system reset and priority to reset global and individual
point acknowledge. Set system time and date and clear event log,
individual point access for control or parameter revisions.
14.36.i FACP (Fire alarm control panel) up to 150 devices (maximum.) each Tk. 301,862.00
14.36.ii FACP 151-250 devices (maximum) each Tk. 350,763.00
14.36.iii FACP 251-500 devices (maximum) each Tk. 450,981.00
14.36.iv FACP 501-750 devices (maximum) each Tk. 526,145.00
14.36.v FACP 751-1000 devices (maximum) each Tk. 601,309.00
14.36.vi FACP 1001-1500 devices (maximum) each Tk. 701,527.00
14.36.vii FACP 1501-2000 devices (maximum) each Tk. 851,854.00
The LCD shall display the following information relative to the abnormal
condition of a point in the system:
Each sensor base shall contain an LED that will flash each time it is
scanned by the control Unit (once every 4 seconds). In alarm condition,
the sensor base LED shall be on steady.
Removal of the sensor head for cleaning shall not require the setting of
addresses.
14.4 Supply & installation of addressable type heat detector / thermal sensor:
combination fixed-temperature and rate-of-rise unit with plug-in base
and alarm indication lamp; 135° F fixed-temperature setting except as
indicated.
PWD E/M Schedule -2018 SH - 14 Page No :-21
14.41 Supply & installation of addressable type manual call station of red
LEXAN, with molded, raised-letter operating instructions of contrasting
color. Station will mechanically latch upon operation and remain so until
manually reset by opening with a key common with the control units.
Activation of the MCS will required a firm downward pull to activate the
alarm switch. The pull lever latches into the alarm position and remains
extended out of the housing to provide a visible indication.
14.41.i Addressable manual pull station : Single action each Tk. 6,514.00
14.41.ii Addressable manual pull station : Double action each Tk. 8,519.00
14.42 Supply & installation of addressable type audible horn for notification
purpose shall contain an electronic module and a selectable address
setting. A visible LED on each appliance shall provide verification of
communications.
The device shall be suitable to program the high / low setting of the
audible (horn) appliances by channel from the addressable controller.
The horn shall be red color with "FIRE" lettering.
14.44 Supply & installation of addressable type horn with strobe for audible &
visible application, combination of audible & visible (A/V) notification
appliances shall be listed to UL . The strobe light shall consist of a
xenon flash tube and associated lens / reflector system. Provide a label
inside the strobe lens to indicate the listed candela rating of the specific
strobe. The horn shall have a minimum sound pressure level of 83 to 89
dBA @ 24VDC. The audible / visible enclosure shall mount directly to
standard single gang, double gang or 4" square electrical box, without
the use of special adapters or trim rings.
Addressable modules
14.45 Supply & installation of addressable type isolator / fault Isolator module
shall be used in the field wiring between the devices (contractor shall
propose the quantity and location in the system required) to detect &
isolate the devices at the time short cirtuit in SLC.
14.47 Supply & installation of addressable relay / control module shall be used
in the field wiring to connect the conventional Initiating devices with the
addressable FACP interfaces to control / operate dampers, motors or
similar appliances on receiving signal from the FACP as when as
required (configured by the service provider).
The device shall be suitable for indoor use only and shall be with back
box.
Shall be suitable to temperature range : 0° to 50° C
Humidity range: Up to 90% RH at 35°C)
Approvals: UL listed / FM approved.
14.48.i FACP for up to 150 addressable devices (max.) each Tk. 120,745.00
14.48.ii FACP for 151-250 addressable devices (max.) each Tk. 144,894.00
14.48.iii FACP for 251-500 addressable devices (max.) each Tk. 181,117.00
14.48.iv FACP for 501-750 addressable devices (max.) each Tk. 205,266.00
14.48.v FACP for 751-1000 addressable devices (max.) each Tk. 229,415.00
14.48.vi FACP for 1001-1500 addressable devices (max.) each Tk. 253,564.00
14.48.vii FACP for 1501-2000 addressable devices (max.) each Tk. 277,713.00
ANNEXURE - 14
OCCUPANCY CLASSIFICATION :
All buildings shall be classified according to their use or by considering the character of their occupancy. For the
purpose of this Code, the occupancy classification groups shall be as follows:
Occupancy A : Residential
Occupancy B : Educational
Occupancy C : Institutional
Occupancy D : Health Care
Occupancy E : Assembly
Occupancy F : Business and Mercantile
Occupancy G : Industrial
Occupancy H : Storage
Occupancy I : Hazardous
Occupancy J : Miscellaneous
The details of occupancy classification of buildings are provided in Sec 2.1 of Part 3.
Notes:
Note The standpipe shall be located in noncombustible enclosure such that it will be able to provide hose stream
to the most remote area of the floor served.
Up to 5 Up to 17 75*
Up to 10 Up to 33 100
10 to 20 33 to 63 150
20 to 54 63 to 165 200
* This size may be used only for occupancy groups A1, A2 and A4
Note The hose shall be connected to the standpipe within 1.5 m from the floor. Hose stations shall be
easily accessible for inspection and testing.
Up to 5 Up to 17 75*
PWD E/M Schedule -2018Up to 10 Up to 33 SH - 14 100 Page No :-27
10 to 20 33 to 63 150
ltem.no. 20 to 54 63 toof165
Description item 200 Unit Unit rate
* This size may be used only for occupancy groups A1, A2 and A4
Note The hose shall be connected to the standpipe within 1.5 m from the floor. Hose stations shall be
easily accessible for inspection and testing.
Material Standard