Professional Documents
Culture Documents
7sj80 Overcurrent Relay For Transformer Protection
7sj80 Overcurrent Relay For Transformer Protection
SIPROTEC Compact
Overcurrent Protection SIPROTEC 7SJ80
Page
1
Description 4/3
2 Applications 4/5
10
You will find a detailed overview of the technical data
(extract of the manual) under:
http://www.siemens.com/siprotec
Description
The SIPROTEC 7SJ80 relays can be used for line/feeder
protection of high and medium-voltage networks with 1
grounded, low-resistance grounded, isolated or a com-
pensated neutral point. The relays have all the required
functions to be applied as a backup relay to a transformer
differential relay.
The SIPROTEC 7SJ80 features “flexible protection functions”. 2
Up to 20 additional protection functions can be created by
the user.
Therefore protection of change for frequency or reverse
power protection can be realized, for example.
The relay provides circuit-breaker control, further switching
3
LSP3.01-0022.eps
devices and automation functions. The integrated program-
mable logic (CFC) allows the user to add own functions, e.g.
for the automation of switchgear (interlocking). The user is
also allowed to generate user-defined messages.
Highlights 4
• Pluggable current and voltage terminals
• Binary input thresholds settable using DIGSI (3 stages)
• Secondary current transformer values (1 A / 5 A) settable
using DIGSI
Fig. 4/1 SIPROTEC 7SJ80 front view, housing
5
• 9 programmable function keys
• 6-line display
• Buffer battery exchangeable from the front
• USB front port 6
• 2 additional communication ports
• Integrated switch for low-cost and redundant optical
Ethernet rings
• Ethernet redundancy protocols RSTP, PRP and HSR for
highest availability
7
• Relay-to-relay communication through Ethernet with
IEC 61850 GOOSE
LSP3.01-0008.eps
10
9 Monitoring functions
–– MODBUS RTU
–– DNP3 TCP
• Operational measured values V, I, f –– PROFINET
• Energy metering values Wp, Wq –– Ethernet redundancy protocols RSTP, PRP and HSR
• Circuit-breaker wear monitoring • Ethernet interface for DIGSI 4 and extension up to two
• Minimum and maximum values SICAM I/O-Units 7XV5673
• USB front interface for DIGSI 4.
• Trip circuit supervision (74TC)
• Fuse failure monitor Hardware
• 8 oscillographic fault records. • 4 current transformers
The SIPROTEC 7SJ80 perform control and monitoring func- Operational indication
tions and therefore provide the user with a cost-effective
platform for power system management, that ensures
Event logs, trip logs, fault records and statistics documents
are stored in the relay to provide the user or operator with all 1
reliable supply of electrical power to the customers. The
the key data required to operate modern substations.
ergonomic design makes control easy from the relay front
panel. A large, easy-to-read display was a key design factor. Line protection
Control The SIPROTEC 7SJ80 units can be used for line protection
of high and medium-voltage networks with grounded, low-
2
The integrated control function permits control of discon-
resistance grounded, isolated or a compensated neutral point.
nect devices, grounding switches or circuit-breakers through
the integrated operator panel, binary inputs, DIGSI 4 or the Transformer protection
control or automation system (e.g. SICAM)
The relay provides all the functions for backup protection for
Programmable logic transformer differential protection. The inrush suppression
effectively prevents unwanted trips that can be caused by 3
The integrated logic characteristics (CFC) allow the user to
inrush currents. The high-impedance restricted ground-fault
add own functions for automation of switchgear (e.g. inter-
protection detects short-circuits and insulation faults on the
locking) or switching sequence. The user can also generate
transformer.
user-defined messages. This functionality can form the base
to create extremely flexible transfer schemes. Backup protection 4
Operational measured value As a backup protection the SIPROTEC 7SJ80 devices are
universally applicable.
Extensive measured values (e.g. I, V), metered values
(e.g.Wp,Wq) and limit values (e.g. for voltage, frequency)
provide improved system management.
Switchgear cubicles for high/medium voltage
All units are designed specifically to meet the requirements
5
of high/medium-voltage applications. In general, no separate
measuring instruments (e.g., for current, voltage, frequency,
…) or additional control components are necessary.
6
Busbar
7
25 Synchrocheck
Commands/Feedbacks
Limits
V, f, P
74TC Trip circuit supervision
52 AND Mean value I, V, P, Q,
cos φ, f Flexible protection functions
86 Lock out min/max-memory P<>, Q<> cosφ df/dt dV/dt
27R
32 55 81R
Operation Communication module 59R
1) 1)
Metered energy: as counting pulses
8
RS232/485/FO/ f<, f> V> V<
Ethernet 81U/O 59 27
IEC 60870-5-103/4 Fault recording Fault Locator
Esc Enter IEC 61850
7 8 9 PROFIBUS-DP Directional supplement
4
1
5
2
6
3
DNP 3.0
Fn 0 . MODBUS RTU
DNP3 TCP FL 47 Phase sequence
1)
PROFINET
... I>, I>> I-
TOC
IN>, IN>>,
IN-TOC 9
67 67N
1)
INs>>
79 AR 67Ns-TOC VN>
67Ns 59N
50N 51N 87N 1) 1)
10
IN>>> Undervoltage
Contr.react.pow.protec.
Short inverse ●
6 Long inverse ● ●
Moderately inverse ●
Very inverse ● ●
Extremely inverse ● ●
Inrush restraint
If second harmonic content is detected during the energi-
(Sensitive) directional ground-fault detection Negative-sequence system overcurrent protection (ANSI 46)
(ANSI 59N, 67Ns, 67N) (contin.)
By measuring current on the high side of the transformer,
It has the following functions: the two-element phase-balance current/negative-sequence 1
• TRIP via the displacement voltage VE protection detects high-resistance phase-to-phase faults
and phase-to-ground faults on the low side of a transformer
• Two instantaneous elements or one instantaneous plus
(e.g. Dy 5). This function provides backup protection for
one user-defined characteristic
high-resistance faults through the transformer.
• Each element can be set to forward, reverse or non-
directional Directional intermittent ground fault protection (ANSI 67Ns)
2
• The function can also be operated in the insensitive mode The directional intermittent ground fault protection has to
as an additional short-circuit protection. detect intermittent ground faults in resonant grounded cable
systems selectively. Intermittent ground faults in resonant
grounded cable systems are usually characterized by the
following properties: 3
– A very short high-current ground current pulse (up to
several hundred amperes) with a duration of under 1 ms
– They are self-extinguishing and re-ignite within one
half-period up to several periods, depending on the power
system conditions and the fault characteristic. 4
– Over longer periods (many seconds to minutes), they can
develop into static faults.
Such intermittent ground faults are frequently caused by
weak insulation, e.g. due to decreased water resistance of old
cables. 5
Ground fault functions based on fundamental component
measured values are primarily designed to detect static
ground faults and do not always behave correctly in case
of intermittent ground faults. The function described here
evaluates specifically the ground current pulses and puts them 6
into relation with the zero-sequence voltage to determine the
direction.
High-impedance restricted ground-fault protection • Initiation of the ARC is dependant on the trip command
(ANSI 87N) selected (e.g. I2>, I>>, Ip, Idir>)
1 The high-impedance measurement principle is a simple • The ARC function can be blocked by activating a binary input
and sensitive method to detect ground faults, especially on • The ARC can be initiated from external or by the PLC logic
transformers. It can also be used on motors, generators and (CFC)
reactors when they are operated on a grounded network. • The directional and non-directional elements can either
2
When applying the high-impedance measurement principle, be blocked or operated non-delayed depending on the
all current transformers in the protected area are connected auto-reclosure cycle
in parallel and operated through one common resistor of • If the ARC is not ready it is possible to perform a dynamic
relatively high R. The voltage is measured across this resistor setting change of the directional and non-directional
(see Fig. 4/6). overcurrent elements.
The voltage is measured by detecting the current through
the (external) resistor R at the sensitive current measure- Flexible protection functions
3 ment input IEE. The varistor V serves to limit the voltage in
the event of an internal fault.
The SIPROTEC 7SJ80 enables the user to easily add up to
20 additional protection functions. Parameter definitions
It limits the high instantaneous voltage spikes that can are used to link standard protection logic with any chosen
occur at current transformer saturation. At the same time, characteristic quantity (measured or calculated quantity).
this results to smooth the voltage without any noteworthy
4 reduction of the average value.
The standard logic consists of the usual protection elements
such as the pickup set point, the set delay time, the TRIP
If no faults have occurred and in the event of external or command, a block function, etc. The mode of operation for
through faults, the system is at equilibrium, and the voltage current, voltage, power and power factor quantities can be
through the resistor is approximately zero. In the event of three-phase or single-phase. Almost all quantities can be
4_7_Visio-flexProFunc-us.pdf
processing (simplified diagram)
6
Current I measured
same transformation ratio and approximately an identical 4
V measured Time
Pickup
knee-point voltage. They should also have only minimal 3I0, I1, I2
t
TRIP
command
3V0, V1, V2
measuring errors. Voltage
3 P,Q Threshold
cos φ
Function 1
f
Function 2
df/dt
Function 20
dV/dt
7
Fig. 4/7 Flexible protection functions
9 3I0>, I1>, I2>, I2 / I1>, 3V0>, V1> <, V2 > < 50N, 46, 59N, 47
LSA4115-de.ai
10
10 circuit current
Commissioning
Commissioning could not be easier and is supported by
DIGSI 4. The status of the binary inputs can be read individu- 1
ally and the state of the binary outputs can be set individu-
ally. The operation of switching elements (circuit-breakers,
disconnect devices) can be checked using the switching
functions of the relay. The analog measured values are
represented as wide-ranging operational measured values. 2
To prevent transmission of information to the control center
during maintenance, the communications can be disabled
to prevent unnecessary data from being transmitted. During
commissioning, all indications with test tag for test pur-
poses can be connected to a control and protection system.
Test operation 3
During commissioning, all indications with test tag can be
passed to a control system for test purposes.
10
Radial systems
1) Auto-reclosure Infeed
General hints:
1 The relay at the far end (D) from the
(ANSI 79) only with
overhead lines Transformer protection
infeed has the shortest tripping time. 2) Unbalanced load
Relays further upstream have to be protection (ANSI 46)
time-graded against downstream as backup protection
A 52
against asymmetrical
relays in steps of about 0.3 s.
2 faults Busbar
3 Busbar
C 52
*
I>t IN>t I2>t
4
51 51N 46
Load
Busbar
5 * D 52
4_9_LSA4839-en.pdf
I>t IN>t I2>t
51 51N 46
6 Load Load
7
Earth-fault detection in isolated or
compensated systems
1) The sensitive current Infeed
8 In isolated or compensated systems,
an occurred earth fault can be
measurement of
the earth current
should be made by a
easily found by means of sensitive zero-sequence current
directional earth-fault detection. transformer
Busbar
9
52
I>> I>t
50 51
4_10_LSA4840a-en.pdf
1) 67Ns
60/1
10 Load
Ring-main cable
With the directional comparison
protection, 100% of the line can be Infeed Infeed
1
protected via instantaneous tripping 52
in case of infeed from two sources
(ring-main cable). 52 52
51
IN>t
51N
υ>t
49
I2>t
46 Direct.Compar.Pickup
2
with a simple definite-time overcur-
rent protection. Therefore, the Overhead line Overhead line Protection as in
directional definite-time overcurrent or cable 1 or cable 2 the case of line
or cable 1
protection must be used. A non- I>t IN>t dir. I>t IN>t
67 67N 51 51N
52 52
6
52
4_11_LSA4841a-en.pdf
52 52
7
I>t IN>t υ>t I2>t
51 51N 49 46
Load Load
10
2 50/50N 51/51N
52
t0 = 50 ms
Busbar
52 52 52
3 I>>
4_12_LSA4842a-en.pdf
I>> I>t I>t I>> I>t
50/50N 51/51N 50/50N 51/51N 50/50N 51/51N
4
Fig. 4/12 Busbar protection via overcurrent relays with reverse interlocking
5
Line feeder with load shedding
In unstable power systems (e.g.
solitary systems, emergency
6 power supply in hospitals), it may
be necessary to isolate selected Busbar
consumers from the power system in
order to protect the overall system. V< f<
The overcurrent-time protection 52
7
27 81U
functions are effective only in the
case of a short-circuit.Overloading of I>, I>>, IN>,
the generator can be measured as a I>>> IN>> I>, Ip INTOC
50 50N 51 51N
frequency or voltage drop.
4_13_LSA2216b-en.pdf
8
> I2> Final trip
79M 49 46 86
10
Automatic reclosing
The Automatic reclosing function (AR)
has starting and blocking options. In the
52
Stage can
be blocked
Stage get slower executes the
than the fuse or reclosing for
1
opposite example, the application of the
lower protection the hole feeder
blocking of the high-current stages is devices graduated
represented according to the reclosing
cycles. The overcurrent protection is
2
ON
52 52
graded (stages I, Ip) according to the TRIP
4_14_LSA2219d-en.pdf
function is installed in the incoming 50 51
supply of a feeder, first of all the complete IN>t, IN>>t,
feeder is tripped instantaneously in case IN>> INTOC AR
50N 51N 79
of fault. Arc faults will be extinguished
independently of the fault location. Other
protection relays or fuses do not trip
3
(fuse saving scheme). After successful
Automatic reclosing, all consumers are
supplied with energy again. If there is 52 Fuse opens by
4
unsuccessful reclosing
a permanent fault, further reclosing
cycles will be performed. Depending on I>t, Ip
the setting of the AR, the instantaneous 67
Circuit-breaker opens
by unsuccessful reclosing
tripping stage in the infeed is blocked in
the first, second or third cycle, i.e., now
the grading is effective according to the
grading plan. Depending on the fault Fig. 4/14 Auto-reclosure 5
location, overcurrent relays with faster
grading, fuses, or the relay in the infeed
will trip. Only the part of the feeder with
the permanent fault will be shut down
definitively.
6
Reverse power protection with parallel Infeed Infeed
infeeds A B
10
Synchrocheck
Where two system sections are inter-
1 connected, the synchrocheck
Busbar
4_16_LSA4114-us.pdf
Transformer control
by means of a programmable angle VT1
2
1)
3 Infeed G
Synchrocheck can be used for
auto-reclosure, as well as for control
functions (local or remote). 1)
Synchrocheck
2)
Automatic reclosing
Busbar
5 Protection of a transformer
The high-current stage enables a cur- 59-1 PU ,t
High-voltage
59
rent grading, the overcurrent stages
work as backup protection to subordi-
nate protection devices, and the I>, I>> I>t, I>>t, Ip >t I2>t, I2>>t
6
TRIP
overload function protects the 52 50 51 49 46
9 52
Busbar
Medium-voltage
TRIP
52 52 52 52
4_17_LSA2203b-us.pdf
typical Feeder
10
Unbalanced fault
Undervoltage-controlled reactive
power protection (QV Protection)
When connecting generating units 1
to the medium-voltage power
system of the operator, a protective Power transformer
4_18_Visio-QU-Schutz-en.pdf
stored when connecting after a short with V>>, V<, V<<, f>, f< functionen
10
2
Housing 1/6 19"; 4 x I, 7 BI, 8 BO (2 Changeover/Form C), 1 life contact 2
Housing 1/6 19"; 4 x I, 3 x V, 3 BI, 5 BO (2 Changeover/Form C), 1 life contact 3 see
Housing 1/6 19"; 4 x I, 3 x V, 7 BI, 8 BO (2 Changeover/Form C), 1 life contact 4 next
page
Housing 1/6 19"; 4 x I, 11 BI, 5 BO (2 Changeover/Form C), 1 life contact 7
Housing 1/6 19"; 4 x I, 3 x V, 11 BI, 5 BO (2 Changeover/Form C), 1 life contact 8
Measuring inputs, default settings
Iph = 1 A/5 A, IE = 1 A/5 A 1
3 Iph = 1A / 5A, IEE (sensitive) = 0,001 to 1,6A / 0,005 to 8A 2
Auxiliary voltage
DC 24 V / 48 V 1
DC 60 V / 110 V / 125 V / 220 V / 250 V, AC 115 V, AC 230 V 5
4 Construction
Surface-mounting case, screw-type terminal B
Flush-mounting case, screw-type terminal E
Region specific default and language settings
Region DE, IEC, language German (language changeable), standard front A
51V
Basic functionality + Directional sensitive ground fault, voltage and frequency protection
Voltage dependent inverse-time overcurrent protection
F B 4)
4
67N Directional time-overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
67Ns1) Directional sensitive ground fault protection, IEE>, IEE>>, IEEp
64/59N Displacement voltage
27/59 Under/Overvoltage
81U/O
47
Under/Overfrequency, f<, f>
Phase rotation
5
Flexible protection functions (current and voltage parameters)): Protective function for voltage,
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change
4)
Basic functionality + Directional phase & ground overcurrent, F C
6
directional sensitive ground fault, voltage and frequency protection
51V Voltage dependent inverse-time overcurrent protection
67 Directional time-overcurrent protection, phase, I>, I>>, I>>>, Ip
67N Directional time-overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
67Ns1) Sensitive ground-fault protection, IEE>, IEE>>, IEEp
64/59N Displacement voltage
7
27/59 Under/Overvoltage
81U/O Under/Overfrequency, f<, f>
47 Phase rotation
Flexible protection functions (current and voltage parameters): Protective function for voltage,
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change
4)
Basic functionality + Directional phase & ground overcurrent, directional sensitive F F
ground fault, voltage and frequency protection + Undervoltage controlled reactive
power protection + Directional intermittent ground fault protection 8
51V Voltage dependent inverse-time overcurrent protection
67 Directional overcurrent protection, phase, I>, I>>, I>>>, Ip
67N Directional overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
67Ns1) Directional sensitive ground fault protection, IEE>, IEE>>, IEEp
67Ns2)
64/59N
27/59
Directional intermittent ground fault protection
Displacement voltage
Under/Overvoltage
9
81U/O Under/Overfrequency, f<, f>
Undervoltage controlled reactive power protection, Q>/V<
47 Phase rotation
Flexible protection functions (current and voltage parameters)): Protective function for voltage,
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change
see
next
page
1) Depending on the ground current input the function will be either sensitive (IEE) or non-sensitive (IE)
2) Function only available with sensitive ground current input (Position 7=2)
10
3) Only if position 6 = 1, 2 or 7
4) Only if position 6 = 3, 4 or 8
5)
Basic functionality + Directional phase overcurrent, voltage and FQ
frequency protection + synchrocheck
51V Voltage dependent inverse-time overcurrent protection
2 67
27/59
Directional time-overcurrent protection, phase, I>, I>>, I>>>, Ip
Under/Overvoltage (phase-to-phase)
81U/O Under/Overfrequency, f< ,f>
47 Phase rotation
25 Synchrocheck
Flexible protection functions (current and voltage parameters)):
Protective function for voltage, rate-of-frequency change, rate-of-
27R/59R/81R voltage change
3 Automatic Reclosing (AR), Fault Locator (FL)
Without 0
79 With automatic reclosure function 1
FL With FL (only with position 6 = 3, 4 or 8) 2
Conformal Coating
for 7SJ801, 7SJ803 Z Y 1 5
10
5) Only with position 6 = 3 or 4 and position 16 = 0 or 1
You will find a detailed overview of the technical data (extract of the manual) under: http://www.siemens.com/siprotec
1
F1 IA BO1 C11
C9
F2 C10
F3 I B, IN2
BO2 C14
F4
F5 IC
C13
C12 2
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E4
BO5 E5
E6
3
C3
C4
BI1
4
C5 BI2
C6
C7 BI3 Life Contact E10
C8
5
E8
E7
= + C1
Power Supply (~)
=
- C2
Port B
6
B
e.g. System interface
Port A
A
7
Contacts, Ceramic, 2.2 nF,
Ethernet interface
Interference Suppression
Capacitors at the Relay
USB-DIGSI-Interface
4_19_LSA4784us.pdf
10
1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
2 F4
F5 IC
C13
C12
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E4
3 BO5 E5
E6
BO6 D9
D10
BO7 D11
C3
4 C4
BI1
BO8
D12
D13
C5 BI2 D14
C6
C7 BI3
C8 Life Contact E10
5 D1 BI4
E8
E7
D2
= + C1
D3 BI5 Power Supply (~)
D4 =
- C2
6 D5
D6
BI6
Port B
D7 B
BI7 e.g. System interface
D8
Port A
7 A
Contacts, Ceramic, 2.2 nF,
Ethernet interface
Interference Suppression
Capacitors at the Relay
USB-DIGSI-Interface
4_20_LSA4785us.pdf
10
1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
F4
F5 IC
C13
C12
2
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E9 Q2 VA, VAB, Vph-n E4
E11
E12
VB, VBC BO5 E5
E6
3
E13 VC, VN, Vsyn, VX
E14
C3
C4
BI1
4
C5 BI2
C6
C7 BI3
C8 Life Contact E10
E8
E7 5
= + C1
Power Supply (~)
=
- C2
Port B
6
B
e.g. System interface
Port A
A
7
Contacts, Ceramic, 2.2 nF,
Ethernet interface
Interference Suppression
Capacitors at the Relay
USB-DIGSI-Interface
4_21_LSA4786us.pdf
10
1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
2 F4
F5 IC
C13
C12
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E9 Q2 VA, VAB, Vph-n E4
3 E11
E12
VB, VBC BO5 E5
E6
E13 VC, VN, Vsyn, VX BO6 D9
E14 D10
BO7 D11
C3
4 C4
BI1
BO8
D12
D13
C5 BI2 D14
C6
C7 BI3
C8 Life Contact E10
5 D1 BI4
E8
E7
D2
= + C1
D3 BI5 Power Supply (~)
D4 =
- C2
6 D5
D6
BI6
Port B
D7 B
BI7 e.g. System interface
D8
Port A
7 A
Contacts, Ceramic, 2.2 nF,
Ethernet interface
Interference Suppression
Capacitors at the Relay
USB-DIGSI-Interface
4_22_LSA4787us.pdf
10
1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
F4
F5 IC
C13
C12
2
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E4
BO5 E5
E6
3
C3
C4
BI1
4
C5 BI2
C6
C7 BI3
C8 Life Contact E10
D1 BI4
E8
E7 5
D2
= + C1
D3 BI5 Power Supply (~)
D4 =
- C2
D5
D6
BI6
Port B
6
D7 B
BI7 e.g. System interface
D8
D9 BI8 Port A
D10 A
7
Contacts, Ceramic, 2.2 nF,
D11
Capacitors at the Relay
4_23_Visio-kl-uebers-7sx807-us.pdf
D12 BI10
D13 USB-DIGSI-Interface
BI11
D14
10
1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
2 F4
F5 IC
C13
C12
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E9 Q2 VA, VAB, Vph-n E4
3 E11
E12
VB, VBC BO5 E5
E6
E13 VC, VN, Vsyn, VX
E14
C3
4 C4
BI1
C5 BI2
C6
C7 BI3
C8 Life Contact E10
5 D1 BI4
E8
E7
D2
= + C1
D3 BI5 Power Supply (~)
D4 =
- C2
6 D5
D6
BI6
Port B
D7 B
BI7 e.g. System interface
D8
D9 BI8 Port A
7 D10 A
Contacts, Ceramic, 2.2 nF,
D11
Capacitors at the Relay
4_24_Visio-kl-uebers-7sx808-us.pdf
D12 BI10
D13 USB-DIGSI-Interface
BI11
D14
10
Connection of current
and voltage transformers
1
A
B
Standard connection C
2
F1 F2
4_25_LSA4789-en.pdf
circuit. F3 IB F4
F5 IC F6
P2 S2
IN
P1 S1 F7 F8
A B C SIPROTEC
A
B
C
4
A
a
5
Surface-/Flush Mounting Housing
E9 VA-N
4_26_LSA4791-en.pdf
IB
F3 F4
IC
F5 F6
7
L l
IN
K k F7 F8
A B C SIPROTEC
9
B
For power systems with small earth C
K k
4_27_LSA4790a-en.pdf
INs
A B C F8 F7
L l
SIPROTEC 10
K k
LSA4792a-en.pdf
E9 VA-B
3 52 52 52 E13 VN E14
IA
F1 F2
IB
F3 F4
IC
F5 F6
L l
4 K k
A B C
F8 INs F7
L l
5
SIPROTEC
K k
6
A
Sensitive directional ground-fault B
detection. C
A
7 B
da
52 52 52 VN
E13 E14
8 F1
F3
IA
IB
F2
F4
IC
F5 F6
L l
9
K k
4_29_LSA4793a-en.pdf
A B C
F8 INs F7
L l SIPROTEC
K k
10
2
A a
protection, the phase-to-phase
E12
voltages acquired with two primary B
A
b
a
VSyn
E14
E13
F1
IA
F2
3
4_30_LSA4858-en.pdf
IB
F3 F4
F5 IC F8
L l
K k F7 IN F8 4
A B C SIPROTEC
10
1 (Low-resistance) grounded
networks
Time-overcurrent protection
phase/ground non-directional
Residual circuit, with 3 phase-
current transformers required,
–
2 networks
Isolated or compensated Overcurrent protection phases
transformers required
Residual circuit, with 3 or 2 phase- –
networks non-directional current transformers possible
(Low-resistance) grounded Directional time-overcurrent Residual circuit, with 3 phase- Phase-to-ground connection or
networks protection, phase current transformers possible phase-to-phase connection
Isolated or compensated Directional time-overcurrent Residual circuit, with 3 or 2 phase- Phase-to-ground connection or
networks protection, phase current transformers possible phase-to-phase connection
3 (Low-resistance) grounded
networks
Directional time-overcurrent
protection, ground-faults
Residual circuit, with 3 phase-
current transformers required,
Phase-to-ground connection
required
phase-balance neutral current
transformers possible
Isolated networks Sensitive ground-fault protection Residual circuit, if ground current 3 times phase-to-ground
10