Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

Overcurrent Protection 7SJ80

SIPROTEC Compact
Overcurrent Protection SIPROTEC 7SJ80

Page
1
Description 4/3

Function overview 4/4

2 Applications 4/5

Application sheets 4/6

Application examples 4/12

Selection and ordering data 4/18

3 Connection diagrams 4/21

Connection examples 4/27

Connection types 4/30

10
You will find a detailed overview of the technical data
(extract of the manual) under:
http://www.siemens.com/siprotec

4/2 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Description

Description
The SIPROTEC 7SJ80 relays can be used for line/feeder
protection of high and medium-voltage networks with 1
grounded, low-resistance grounded, isolated or a com-
pensated neutral point. The relays have all the required
functions to be applied as a backup relay to a transformer
differential relay.
The SIPROTEC 7SJ80 features “flexible protection functions”. 2
Up to 20 additional protection functions can be created by
the user.
Therefore protection of change for frequency or reverse
power protection can be realized, for example.
The relay provides circuit-breaker control, further switching
3

LSP3.01-0022.eps
devices and automation functions. The integrated program-
mable logic (CFC) allows the user to add own functions, e.g.
for the automation of switchgear (interlocking). The user is
also allowed to generate user-defined messages.

Highlights 4
• Pluggable current and voltage terminals
• Binary input thresholds settable using DIGSI (3 stages)
• Secondary current transformer values (1 A / 5 A) settable
using DIGSI
Fig. 4/1  SIPROTEC 7SJ80 front view, housing
5
• 9 programmable function keys
• 6-line display
• Buffer battery exchangeable from the front
• USB front port 6
• 2 additional communication ports
• Integrated switch for low-cost and redundant optical
Ethernet rings
• Ethernet redundancy protocols RSTP, PRP and HSR for
highest availability
7
• Relay-to-relay communication through Ethernet with
IEC 61850 GOOSE
LSP3.01-0008.eps

• Millisecond-accurate time synchronization through


Ethernet with SNTP (over Port A or Port B) 8
• Number of binary inputs and inary outputs by connection
from up to two SICAM I/O-Units extendable.

Fig. 4/2  SIPROTEC 7SJ80 rear view

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/3


Overcurrent Protection SIPROTEC 7SJ80
Function overview

Protection functions IEC ANSI No.


Definite and inverse time-overcurrent protection (phase/ground) I>, Ip, INp 50, 50N; 51, 51N
1 Directional time-overcurrent protection phase I>, I>>, I>>>, Ip 67
Directional time-overcurrent protection ground IE>, IE>>, IE>>>, IEp 67N 1)
Directional sensitive ground fault protection IEE>, IEE>>, IEEp 67Ns 1), 50Ns
Overvoltage protection, zero-sequence system V E, V 0> 59N 1)
2 High-impedance restricted ground-fault protection 87N
Inrush restraint
Trip-ciruit supervision TCS 74TC
Undercurrent monitoring I<, P> 37
Overload protection J> 49
3 Undervoltage/overvoltage protection V<, V> 27/59
Overfrequency/underfrequency protection f<, f> 81O/U
Circuit-breaker failure protection CBFP 50BF
Undervoltage controlled reactive power protection Q>/V<
4 Intermittent ground fault protection Iie>
Directional intermittent ground fault protection Iie dir> 67Ns 1)
Voltage dependent inverse-time overcurrent protection 51V
Unbalanced-load protection I 2> 46
5 Phase-sequence-voltage supervision LA, LB, LC 47
Synchrocheck Sync 25
Automatic reclosing AR 79
Fault locator FL FL 1)
6 Lockout 86
Forward power supervision, reverse power protection P<>, Q<> 32 1)
Power factor cos j 55 1)
Rate-of-frequency-change protection df / dt 81R
7 Rate-of-voltage-change protection dV/dt 27R, 59R

Table 4/1  Function overview

Control functions/programmable logic Communication interfaces

8 • Commands for the ctrl. of CB, disconnect switches


(isolators/isolating switches)
• System/service interface
–– IEC 61850 Edition 1 and 2
• Control through keyboard, binary inputs, –– IEC 60870-5-103 and IEC 60870-5-104
DIGSI 4 or SCADA system –– PROFIBUS-DP
• User-defined PLC logic with CFC (e.g. interlocking). –– DNP 3.0

9 Monitoring functions
–– MODBUS RTU
–– DNP3 TCP
• Operational measured values V, I, f –– PROFINET
• Energy metering values Wp, Wq –– Ethernet redundancy protocols RSTP, PRP and HSR
• Circuit-breaker wear monitoring • Ethernet interface for DIGSI 4 and extension up to two
• Minimum and maximum values SICAM I/O-Units 7XV5673
• USB front interface for DIGSI 4.
• Trip circuit supervision (74TC)
• Fuse failure monitor Hardware
• 8 oscillographic fault records. • 4 current transformers

10 • 0/3 voltage transformers


• 3/7/11 binary inputs (thresholds configurable using
software)
• 5/8 binary outputs (2 changeover/Form C contacts)
1) Not available if function package “Q” (synchrocheck, ANSI 25) • 1 life contact
is selected.
• Pluggable current and voltage terminals.

4/4 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Applications

The SIPROTEC 7SJ80 perform control and monitoring func- Operational indication
tions and therefore provide the user with a cost-effective
platform for power system management, that ensures
Event logs, trip logs, fault records and statistics documents
are stored in the relay to provide the user or operator with all 1
reliable supply of electrical power to the customers. The
the key data required to operate modern substations.
ergonomic design makes control easy from the relay front
panel. A large, easy-to-read display was a key design factor. Line protection
Control The SIPROTEC 7SJ80 units can be used for line protection
of high and medium-voltage networks with grounded, low-
2
The integrated control function permits control of discon-
resistance grounded, isolated or a compensated neutral point.
nect devices, grounding switches or circuit-breakers through
the integrated operator panel, binary inputs, DIGSI 4 or the Transformer protection
control or automation system (e.g. SICAM)
The relay provides all the functions for backup protection for
Programmable logic transformer differential protection. The inrush suppression
effectively prevents unwanted trips that can be caused by 3
The integrated logic characteristics (CFC) allow the user to
inrush currents. The high-impedance restricted ground-fault
add own functions for automation of switchgear (e.g. inter-
protection detects short-circuits and insulation faults on the
locking) or switching sequence. The user can also generate
transformer.
user-defined messages. This functionality can form the base
to create extremely flexible transfer schemes. Backup protection 4
Operational measured value As a backup protection the SIPROTEC 7SJ80 devices are
universally applicable.
Extensive measured values (e.g. I, V), metered values
(e.g.Wp,Wq) and limit values (e.g. for voltage, frequency)
provide improved system management.
Switchgear cubicles for high/medium voltage
All units are designed specifically to meet the requirements
5
of high/medium-voltage applications. In general, no separate
measuring instruments (e.g., for current, voltage, frequency,
…) or additional control components are necessary.
6
Busbar

Local/remote control CFC logic Operational measured values

7
25 Synchrocheck
Commands/Feedbacks
Limits
V, f, P
74TC Trip circuit supervision
52 AND Mean value I, V, P, Q,
cos φ, f Flexible protection functions
86 Lock out min/max-memory P<>, Q<> cosφ df/dt dV/dt
27R
32 55 81R
Operation Communication module 59R
1) 1)
Metered energy: as counting pulses

8
RS232/485/FO/ f<, f> V> V<
Ethernet 81U/O 59 27
IEC 60870-5-103/4 Fault recording Fault Locator
Esc Enter IEC 61850
7 8 9 PROFIBUS-DP Directional supplement
4
1
5
2
6
3
DNP 3.0
Fn 0 . MODBUS RTU
DNP3 TCP FL 47 Phase sequence
1)
PROFINET
... I>, I>> I-
TOC
IN>, IN>>,
IN-TOC 9
67 67N
1)

I>, I>>, IN>, IN>>, IN-TOC


I>>> I-TOC IN>>> I2> > SVS I<
InRush Intermitt. Additional Directional ground
50 51 50N 51N 46 49 51V
BLK ground fault 50BF 37 fault protection
INs>,
2_3_Visio-LSA4783b-us.pdf

INs>>
79 AR 67Ns-TOC VN>
67Ns 59N
50N 51N 87N 1) 1)

IN>, IN>>, IN-TOC REF

10
IN>>> Undervoltage
Contr.react.pow.protec.

AR Automatic reclosing I2> Unbalanced load protection


BF Breaker Failure Protection > Thermal overload protection
REF High-impedance ground fault differential protection I< Undercurrent monitoring

1) Not available if function package “Q” (synchrocheck, ANSI 25) is selected.

Fig. 4/3  Function diagram

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/5


Overcurrent Protection SIPROTEC 7SJ80
Application sheets

Protection functions Directional time-overcurrent protection (ANSI 67, 67N)


Directional phase and ground protection are separate
1 Overcurrent protection (ANSI 50, 50N, 51, 51N, 51V)
functions. They operate in parallel to the non-directional
This function is based on the phase selective measurement overcurrent elements. Their pickup values and delay times
of the three phase currents and the ground current (four can be set separately. Definite-time and inverse-time
transformers). Three definite time-overcurrent protection characteristics are
elements (DMT) are available both for the phase and the offered. The tripping characteristic can be rotated by ± 180
2 ground elements. The current threshold and the delay time degrees.
can be set in a wide range. By making use of the voltage memory, the directionality
Inverse time-overcurrent protection characteristics (IDMTL) can be determined reliably even for close-in (local) faults.
can also be selected and activated. The inverse-time func- If the primary switching device closes onto a fault and the
tion provides – as an option – voltage-restraint or voltage- voltage is too low to determine direction, the direction is
controlled operating modes determined using voltage from the memorized voltage. If no
3 Reset characteristics
voltages are stored in the memory, tripping will be accord-
ing to the set characteristic.
Time coordination with electromechanical relays are made For ground protection, users can choose whether the direc-
easy with the inclusion of the reset characteristics according tion is to be calculated using the zero-sequence or negative-
to ANSI C37.112 and IEC 60255-3 / BS 142 standards. When sequence system quantities (selectable). If the zero-sequence
4 using the reset characteristic (disk emulation), the reset pro- voltage tends to be very low due to the zero-sequence
cess is initiated after the fault current has disappeared. This impe-dance it will be better to use the negative-sequence
reset process corresponds to the reverse movement of the quantities.
Ferraris disk of an electromechanical relay (disk emulation).

5 Available inverse-time characteristics

Characteristics acc. to IEC 60255-3 ANSI / IEEE


Inverse ● ●

Short inverse ●

6 Long inverse ● ●

Moderately inverse ●

Very inverse ● ●

Extremely inverse ● ●

7 Table 4/2  Available inverse-time characteristics

Inrush restraint
If second harmonic content is detected during the energi-

8 zation of a transformer, the pickup of stages I>,Ip, I>dir


and Ip dir is blocked.
Fig. 4/4 Directional characteristics of the directional time-overcurrent
protection

Dynamic settings group switching


(Sensitive) directional ground-fault detection
In addition to the static parameter changeover, the pickup (ANSI 59N/64, 67Ns, 67N)
9 thresholds and the tripping times for the directional and
non-directional time-overcurrent protection functions can
For isolated-neutral and compensated networks, the
direction of power flow in the zero sequence is calculated
be changed over dynamically. As changeover criterion, the
from the zero-sequence current I0 and zero-sequence
circuit-breaker position, the prepared auto-reclosure, or a
voltage V0. For networks with an isolated neutral, the
binary input can be selected.
reactive current component is evaluated; for compensated
Directional comparison protection (cross-coupling) networks, the active current component or residual resistive
current is evaluated. For special network conditions, e.g.
It is used for selective instantaneous tripping of sections high-resistance grounded networks with ohmic-capacitive
fed from two sources, i.e. without the disadvantage of time ground-fault current or low-resistance grounded networks
delays of the set characteristic. The directional comparison
10 protection is suitable if the distances between the protection
with ohmic-inductive current, the tripping characteristics can
be rotated approximately
zones are not significant and pilot wires are available for ± 45 degrees (see Fig.4/5).
signal transmission. In addition to the directional compari-
Two modes of ground-fault direction detection can be
son protection, the directional coordinated time-overcurrent
implemented: tripping or “signalling only mode”.
protection is used for complete selective backup protection.

4/6 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Application sheets

(Sensitive) directional ground-fault detection Negative-sequence system overcurrent protection (ANSI 46)
(ANSI 59N, 67Ns, 67N) (contin.)
By measuring current on the high side of the transformer,
It has the following functions: the two-element phase-balance current/negative-sequence 1
• TRIP via the displacement voltage VE protection detects high-resistance phase-to-phase faults
and phase-to-ground faults on the low side of a transformer
• Two instantaneous elements or one instantaneous plus
(e.g. Dy 5). This function provides backup protection for
one user-defined characteristic
high-resistance faults through the transformer.
• Each element can be set to forward, reverse or non-
directional Directional intermittent ground fault protection (ANSI 67Ns)
2
• The function can also be operated in the insensitive mode The directional intermittent ground fault protection has to
as an additional short-circuit protection. detect intermittent ground faults in resonant grounded cable
systems selectively. Intermittent ground faults in resonant
grounded cable systems are usually characterized by the
following properties: 3
– A very short high-current ground current pulse (up to
several hundred amperes) with a duration of under 1 ms
– They are self-extinguishing and re-ignite within one
half-period up to several periods, depending on the power
system conditions and the fault characteristic. 4
– Over longer periods (many seconds to minutes), they can
develop into static faults.
Such intermittent ground faults are frequently caused by
weak insulation, e.g. due to decreased water resistance of old
cables. 5
Ground fault functions based on fundamental component
measured values are primarily designed to detect static
ground faults and do not always behave correctly in case
of intermittent ground faults. The function described here
evaluates specifically the ground current pulses and puts them 6
into relation with the zero-sequence voltage to determine the
direction.

Undervoltage-controlled reactive power protection


Fig. 4/5 Directional determination using cosine measurements for
compensated networks The undervoltage-controlled reactive power protection pro-
7
tects the system for mains decoupling purposes. To prevent a
(Sensitive) ground-fault detection voltage collapse in energy systems, the generating side, e.g.
(ANSI 50Ns, 51Ns / 50N, 51N) a generator, must be equipped with voltage and frequency
For high-resistance grounded networks, a sensitive input
protection devices. An undervoltage-controlled reactive
power protection is required at the supply system connection
8
transformer is connected to a phase-balance neutral current
point. It detects critical power system situations and ensures
transformer (also called core-balance CT). The function can
that the power generation facility is disconnected from the
also be operated in the normal mode as an additional short-
mains. Furthermore, it ensures that reconnection only takes
circuit protection for neutral or residual ground protection.

Intermittent ground fault protection


place under stable power system conditions. The associated
criteria can be parameterized.
9
Intermittent (re-igniting) faults are caused by poor cable in- Breaker failure protection (ANSI 50BF)
sulation or water ingress into cable joints. After some time,
If a faulted portion of the electrical circuit is not disconnected
the faults extinguish automatically or they develop into
when a trip command is issued to a circuit-breaker, another
permanent short circuits. During the intermitting, neutral
trip command can be initiated using the breaker failure pro-
point resistances in impedance grounded systems can suffer
tection which trips the circuit-breaker of an upstream feeder.
thermal overload.
Breaker failure is detected if, after a trip command is issued
The normal ground fault protection is not capable of reliably and the current keeps on flowing into the faulted circuit. It
detecting and clearing the sometimes very short current
pulses. The required selectivity for intermittent ground
is also possible to make use of the circuit-breaker position 10
contacts for indication as opposed to the current flowing
faults is achieved by summing up the times of the individual through the circuit-breaker.
pulses and tripping after a (programmable) summation time
has been reached. The pickup threshold Iie> evaluates RMS
values referred to 1 system period.

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/7


Overcurrent Protection SIPROTEC 7SJ80
Application sheets

High-impedance restricted ground-fault protection • Initiation of the ARC is dependant on the trip command
(ANSI 87N) selected (e.g. I2>, I>>, Ip, Idir>)
1 The high-impedance measurement principle is a simple • The ARC function can be blocked by activating a binary input
and sensitive method to detect ground faults, especially on • The ARC can be initiated from external or by the PLC logic
transformers. It can also be used on motors, generators and (CFC)
reactors when they are operated on a grounded network. • The directional and non-directional elements can either

2
When applying the high-impedance measurement principle, be blocked or operated non-delayed depending on the
all current transformers in the protected area are connected auto-reclosure cycle
in parallel and operated through one common resistor of • If the ARC is not ready it is possible to perform a dynamic
relatively high R. The voltage is measured across this resistor setting change of the directional and non-directional
(see Fig. 4/6). overcurrent elements.
The voltage is measured by detecting the current through
the (external) resistor R at the sensitive current measure- Flexible protection functions
3 ment input IEE. The varistor V serves to limit the voltage in
the event of an internal fault.
The SIPROTEC 7SJ80 enables the user to easily add up to
20 additional protection functions. Parameter definitions
It limits the high instantaneous voltage spikes that can are used to link standard protection logic with any chosen
occur at current transformer saturation. At the same time, characteristic quantity (measured or calculated quantity).
this results to smooth the voltage without any noteworthy
4 reduction of the average value.
The standard logic consists of the usual protection elements
such as the pickup set point, the set delay time, the TRIP
If no faults have occurred and in the event of external or command, a block function, etc. The mode of operation for
through faults, the system is at equilibrium, and the voltage current, voltage, power and power factor quantities can be
through the resistor is approximately zero. In the event of three-phase or single-phase. Almost all quantities can be

5 internal faults, an imbalance occurs which leads to a voltage


and a current flowing through the resistor R.
operated with ascending or descending pickup stages (e.g.
under and overvoltage). All stages operate with protection
The same type of current transformers must be used and priority.
must at least offer a separate core for the high-impedance
Measured-value Standard protection logic
restricted ground-fault protection. They must have the Parameter

4_7_Visio-flexProFunc-us.pdf
processing (simplified diagram)

6
Current I measured
same transformation ratio and approximately an identical 4
V measured Time
Pickup

knee-point voltage. They should also have only minimal 3I0, I1, I2
t
TRIP
command
3V0, V1, V2
measuring errors. Voltage
3 P,Q Threshold

cos φ
Function 1
f
Function 2
df/dt
Function 20
dV/dt

7
Fig. 4/7  Flexible protection functions

Protection functions/stages available are based on the avail-


able measured analog quantities:
8 Function ANSI
I>, IE> 50, 50N
V<, V>, VE> 27, 59, 59N

9 3I0>, I1>, I2>, I2 / I1>, 3V0>, V1> <, V2 > < 50N, 46, 59N, 47
LSA4115-de.ai

P> <, Q> < 32


cos j 55
f>< 81O, 81U
Fig. 4/6 High-impedance restricted ground-fault protection df / dt > < 81R
dV/dt 27R/59R
Table 4/3  Available flexible protection functions
Automatic reclosing (ANSI 79)
Multiple re-close cycles can be set by the user and lockout For example, the following can be implemented:

10 will occur if a fault is present after the last re-close cycle.


The following functions are available:
• Reverse power protection (ANSI 32R)
• Rate-of-frequency-change protection (ANSI 81R)
• 3-pole ARC for all types of faults • Rate-of-voltage-change protection (ANSI 27R/59R).
• Separate settings for phase and ground faults
• Multiple ARC, one rapid auto-reclosure (RAR) and up to
nine delayed auto-reclosures (DAR)
4/8 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4
Overcurrent Protection SIPROTEC 7SJ80
Application sheets

Synchrocheck, synchronizing function (ANSI 25) Undervoltage protection (ANSI 27)


When closing a circuit-breaker, the units can check The two-element undervoltage protection provides protec-
whether two separate networks are synchronized. Voltage-, tion against dangerous voltage drops (especially for electric 1
frequency- and phase-angle-differences are checked to machines). Applications include the isolation of generators
determine whether synchronous conditions exist. or motors from the network to avoid undesired operating
conditions and a possible loss of stability. Proper operating
Trip circuit supervision (ANSI 74TC) conditions of electrical machines are best evaluated with
One or two binary inputs can be used for monitoring the the positive-sequence quantities. The protection function is 2
circuit-breaker trip coil including its incoming cables. An alarm active over a wide frequency range (45 to 55, 55 to 65 Hz).
signal is generated whenever the circuit is interrupted. Even when falling below this frequency range the function
continues to work, however, with decrease accuracy. The
Lockout (ANSI 86) function can operate either with phase-to-phase, phase-
to-ground or positive phase-sequence voltage, and can be
All binary output statuses can be memorized. The LED reset
key is used to reset the lockout state. The lockout state is
monitored with a current criterion. Three-phase and single-
phase connections are possible.
3
also stored in the event of supply voltage failure. Reclosure
can only occur after the lockout state is reset. Frequency protection (ANSI 81O/U)
Thermal overload protection (ANSI 49) Frequency protection can be used for overfrequency and
To protect cables and transformers, an overload protection
underfrequency protection. Electric machines and parts
of the system are protected from unwanted frequency
4
function with an integrated warning/alarm element for
deviations. Unwanted frequency changes in the network
temperature and current can be used. The temperature is
can be detected and the load can be removed at a specified
calculated using a thermal homogeneous body model (per
frequency setting. Frequency protection can be used over
IEC 60255-8), it considers the energy entering the equip-
ment and the energy losses. The calculated temperature is
a wide frequency range (40 to 60 (for 50 Hz), 50 to 70 (for
60 Hz)). There are four elements (individually set as over-
5
constantly adjusted according to the calculated losses. The
frequency, underfrequency or OFF) and each element can
function considers loading history and fluctuations in load.
be delayed separately. Blocking of the frequency protection
Settable dropout delay times can be performed by activating a binary input or by using an

If the relays are used in conjunction with electromechanical


undervoltage element. 6
relays, in networks with intermittent faults, the long dropout Fault locator (ANSI 21FL)
times of the electromechanical relay (several hundred mil-
The integrated fault locator calculates the fault impedance
liseconds) can lead to problems in terms of time coordination/
and the distance to fault. The results are displayed in Ω,
grading. Proper time coordination/grading is only possible if
the dropout or reset time is approximately the same. This is
kilometers (miles) and in percent of the line length. 7
why the parameter for dropout or reset times can be defined Customized functions (ANSI 51V, 55 etc.)
for certain functions, such as overcurrent protection, ground
short-circuit and phase-balance current protection. Additional functions, which are not time critical, can be im-

Undercurrent monitoring (ANSI 37)


plemented using the CFC measured values. Typical functions
include reverse power, voltage controlled overcurrent, phase 8
angle detection, and zero-sequence voltage detection.
A sudden drop in current, which can occur due to a reduced
load, is detected with this function. This may be due to shaft
that breaks, no-load operation of pumps or fan failure.

Overvoltage protection (ANSI 59)


9
The two-element overvoltage protection detects unwanted
network and machine overvoltage conditions. The function
can operate either with phase-to-phase, phase-to-ground,
positive phase-sequence or negative phase-sequence volt-
age. Three-phase and single-phase connections are possible.

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/9


Overcurrent Protection SIPROTEC 7SJ80
Application sheets

Further functions Circuit-breaker wear monitoring/


circuit-breaker remaining service life
1 Measured values
Methods for determining circuit-breaker contact wear or
The r.m.s. values are calculated from the acquired current the remaining service life of a circuit-breaker (CB) allow CB
and voltage along with the power factor, frequency, active maintenance intervals to be aligned to their actual degree of
and reactive power. The following functions are available for wear. The benefit lies in reduced maintenance costs.
measured value processing:
2 • Currents IL1, IL2, IL3, IN, IEE
There is no exact mathematical method to calculate the
wear or the remaining service life of a circuit-breaker that
• Voltages VL1, VL2, VL3, V12, V23, V31 takes arc-chamber’s physical conditions into account when
the CB opens.
• Symmetrical components I1, I2, 3I0; V1, V2, 3V0
This is why various methods of determining CB wear have
• Power Watts, Vars, VA/P, Q, S (P, Q: total and phase selec-
evolved which reflect the different operator philosophies.
tive)
To do justice to these, the relay offers several methods:
3 • Power factor cos j (total and phase selective)
• SI
• Frequency
• SIx, with x = 1..3
• Energy ± kWh, ± kVarh, forward and reverse power flow
• Si2t.
• Mean as well as minimum and maximum current and
4 voltage values
• Operating hours counter
The devices also offer a new method for determining the
remaining service life:
• Two-point method
• Mean operating temperature of the overload function
The CB manufacturers double-logarithmic switching cycle
• Limit value monitoring
diagram (see Fig. 4/8) and the breaking current at the time
5 Limit values can be monitored using programmable logic
in the CFC. Commands can be derived from this limit value
of contact opening serve as the basis for this method. After
CB opening, the two-point method calculates the remaining
indication.
number of possible switching cycles. Two points P1 and P2
• Zero suppression only have to be set on the device. These are specified in the
In a certain range of very low measured values, the value CB’s technical data.
6 is set to zero to suppress interference.
All of these methods are phase-selective and a limit value
Metered values can be set in order to obtain an alarm if the actual value falls
below or exceeds the limit value during determination of
For internal metering, the unit can calculate an energy me- the remaining service life.
tered value from the measured current and voltage values. If
7 an external meter with a metering pulse output is available,
the SIPROTEC 7SJ80 can obtain and process metering pulses
through an indication input. The metered values can be dis-
played and passed on to a control center as an accumulated
value with reset. A distinction is made between forward,
8 reverse, active and reactive energy.

Binary I/O extension with SICAM I/O-Unit 7XV5673


To extend binary inputs and binary outputs for SIPROTEC
7SJ80 up to two SICAM I/O-Units 7XV5673 can be added.
9 Each SICAM I/O-Unit 7XV7653 is equipped with 6 binary
inputs and 6 binary outputs and an Ethernet switch for
cascading. The connection to the protection device can be
either through the DIGSI Ethernet service interface Port A or P1: Permissible number
through IEC 61850 GOOSE on Port B (System interface with of operating cycles
EN100 module). at rated normal
current
P2: Permissible number
of operating cycles
at rated short-

10 circuit current

Fig. 4/8  Permissible number of operating cycles as a function of


breaking current

4/10 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Application sheets

Commissioning
Commissioning could not be easier and is supported by
DIGSI 4. The status of the binary inputs can be read individu- 1
ally and the state of the binary outputs can be set individu-
ally. The operation of switching elements (circuit-breakers,
disconnect devices) can be checked using the switching
functions of the relay. The analog measured values are
represented as wide-ranging operational measured values. 2
To prevent transmission of information to the control center
during maintenance, the communications can be disabled
to prevent unnecessary data from being transmitted. During
commissioning, all indications with test tag for test pur-
poses can be connected to a control and protection system.

Test operation 3
During commissioning, all indications with test tag can be
passed to a control system for test purposes.

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/11


Overcurrent Protection SIPROTEC 7SJ80
Application examples

Radial systems
1) Auto-reclosure Infeed
General hints:
1 The relay at the far end (D) from the
(ANSI 79) only with
overhead lines Transformer protection
infeed has the shortest tripping time. 2) Unbalanced load
Relays further upstream have to be protection (ANSI 46)
time-graded against downstream as backup protection
A 52
against asymmetrical
relays in steps of about 0.3 s.
2 faults Busbar

Further power supply B 52

I>t IN>t I2>t AR


51 51N 46 79
2) 1)

3 Busbar

C 52
*
I>t IN>t I2>t

4
51 51N 46

Load
Busbar

5 * D 52

4_9_LSA4839-en.pdf
I>t IN>t I2>t
51 51N 46

6 Load Load

Fig. 4/9 Protection concept with time-overcurrent protection

7
Earth-fault detection in isolated or
compensated systems
1) The sensitive current Infeed
8 In isolated or compensated systems,
an occurred earth fault can be
measurement of
the earth current
should be made by a
easily found by means of sensitive zero-sequence current
directional earth-fault detection. transformer
Busbar

9
52

I>> I>t
50 51
4_10_LSA4840a-en.pdf

7XR96 IN>t dir.

1) 67Ns
60/1

10 Load

Fig. 4/10  Protection concept for directional earth-fault detection

4/12 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Application examples

Ring-main cable
With the directional comparison
protection, 100% of the line can be Infeed Infeed
1
protected via instantaneous tripping 52
in case of infeed from two sources
(ring-main cable). 52 52

For lines with infeed from two sour-


ces, no selectivity can be achieved
I>t

51
IN>t

51N
υ>t

49
I2>t

46 Direct.Compar.Pickup
2
with a simple definite-time overcur-
rent protection. Therefore, the Overhead line Overhead line Protection as in
directional definite-time overcurrent or cable 1 or cable 2 the case of line
or cable 1
protection must be used. A non- I>t IN>t dir. I>t IN>t

directional definite-time overcurrent 67 67N 51 51N

protection is enough only in the


corresponding busbar feeders. The
3
52 52
grading is done from the other end
respectively. 52
Advantage: 100% protection of the
line via instantaneous 52 52
4
tripping, and easy
setting. 67 67N 51 51N
Direct.Compar.Pickup
Disadvantage: Tripping times increase I>t IN>t dir. I>t IN>t

towards the infeed. Overhead line


or cable 3
Overhead line
or cable 4
Protection as in
the case of line
or cable 3
5
I>t IN>t dir. I>t IN>t

67 67N 51 51N

52 52
6
52

4_11_LSA4841a-en.pdf
52 52

7
I>t IN>t υ>t I2>t

51 51N 49 46

Load Load

Fig. 4/11 Protection concept of ring power systems

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/13


Overcurrent Protection SIPROTEC 7SJ80
Application examples

Busbar protection by overcurrent


relays with reverse interlocking
1 Applicable to distribution busbars Infeed

without substantial (< 0.25 x IN) Reverse interlocking


backfeed from the outgoing feeders.
I>>t0

2 50/50N 51/51N

52
t0 = 50 ms

Busbar

52 52 52
3 I>>

4_12_LSA4842a-en.pdf
I>> I>t I>t I>> I>t
50/50N 51/51N 50/50N 51/51N 50/50N 51/51N

4
Fig. 4/12 Busbar protection via overcurrent relays with reverse interlocking

5
Line feeder with load shedding
In unstable power systems (e.g.
solitary systems, emergency
6 power supply in hospitals), it may
be necessary to isolate selected Busbar
consumers from the power system in
order to protect the overall system. V< f<
The overcurrent-time protection 52

7
27 81U
functions are effective only in the
case of a short-circuit.Overloading of I>, I>>, IN>,
the generator can be measured as a I>>> IN>> I>, Ip INTOC
50 50N 51 51N
frequency or voltage drop.
4_13_LSA2216b-en.pdf

8
> I2> Final trip
79M 49 46 86

Fig. 4/13 Line feeder with load shedding

10

4/14 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Application examples

Automatic reclosing
The Automatic reclosing function (AR)
has starting and blocking options. In the
52
Stage can
be blocked
Stage get slower executes the
than the fuse or reclosing for
1
opposite example, the application of the
lower protection the hole feeder
blocking of the high-current stages is devices graduated
represented according to the reclosing
cycles. The overcurrent protection is
2
ON
52 52
graded (stages I, Ip) according to the TRIP

grading plan. If an Automatic reclosing I>, I>>, I>>> I>t, I>>t, Ip

4_14_LSA2219d-en.pdf
function is installed in the incoming 50 51
supply of a feeder, first of all the complete IN>t, IN>>t,
feeder is tripped instantaneously in case IN>> INTOC AR
50N 51N 79
of fault. Arc faults will be extinguished
independently of the fault location. Other
protection relays or fuses do not trip
3
(fuse saving scheme). After successful
Automatic reclosing, all consumers are
supplied with energy again. If there is 52 Fuse opens by

4
unsuccessful reclosing
a permanent fault, further reclosing
cycles will be performed. Depending on I>t, Ip
the setting of the AR, the instantaneous 67
Circuit-breaker opens
by unsuccessful reclosing
tripping stage in the infeed is blocked in
the first, second or third cycle, i.e., now
the grading is effective according to the
grading plan. Depending on the fault Fig. 4/14 Auto-reclosure 5
location, overcurrent relays with faster
grading, fuses, or the relay in the infeed
will trip. Only the part of the feeder with
the permanent fault will be shut down
definitively.
6
Reverse power protection with parallel Infeed Infeed
infeeds A B

If a busbar is supplied by two parallel 7


4_15_LSA4116a-en.pdf
infeeds and there is a fault in one of the
infeeds, the affected busbar shall be
selectively shut down, so that supply to
52 52
the busbar is still possible through the
remaining infeed. To do this, directional
devices are required, which detect a
67 67N 32R 67 67N 32R
8
short circuit from the busbar towards the 52
infeed. In this context, the directional
time-overcurrent protection is normally 52 52
adjusted over the load current. Low-cur-
rent faults cannot be shut down by this
9
protection. The reverse power protection
can be adjusted far below rated power, Feeder Feeder
and is thus also able to detect reverse
power in case of low-current faults far Fig. 4/15 Reverse power protection with parallel infeeds
below the load current. The reverse
power protection is implemented through
the “flexible protection functions”.

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/15


Overcurrent Protection SIPROTEC 7SJ80
Application examples

Synchrocheck
Where two system sections are inter-
1 connected, the synchrocheck
Busbar

determines whether the connection V2


is permissible without danger to Closing Signal
the stability of the power system. In 52
1
the example, load is supplied from
2 a generator to a busbar through a
transformer. The vector group of
Local/remote
the transformer can be considered

4_16_LSA4114-us.pdf
Transformer control
by means of a programmable angle VT1
2
1)

adjustment, so that no external 25 SYN


2)
adjustment elements are necessary. 81 AR

3 Infeed G
Synchrocheck can be used for
auto-reclosure, as well as for control
functions (local or remote). 1)
Synchrocheck
2)
Automatic reclosing

4 Fig. 4/16  Measurement of busbar and feeder voltage for synchronization

Busbar

5 Protection of a transformer
The high-current stage enables a cur- 59-1 PU ,t
High-voltage

59
rent grading, the overcurrent stages
work as backup protection to subordi-
nate protection devices, and the I>, I>> I>t, I>>t, Ip >t I2>t, I2>>t

6
TRIP
overload function protects the 52 50 51 49 46

transformer from thermal overload. IN>, IN>>


IN>t, IN>>t,
INTOC
Low-current, single-phase faults 50N 51N Inrush blocking

on the low-voltage side, which are


reproduced in the opposite system
7 on the high-voltage side, can be de-
tected with the unbalanced load pro-
52

tection. The available inrush blocking


prevents pickup caused by the inrush 87

currents of the transformer.


8 e.g.
7UT61
52
*

IN>, IN>> IN>t, IN>>t, INTOC


50N 51N

9 52

Busbar
Medium-voltage
TRIP
52 52 52 52
4_17_LSA2203b-us.pdf

I2>>t, I2>t I>, I>> I>t, I>>t, Ip


46 50 51

typical Feeder

10
Unbalanced fault

Fig. 4/17 Typical protection concept for a transformer

4/16 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Application examples

Undervoltage-controlled reactive
power protection (QV Protection)
When connecting generating units 1
to the medium-voltage power
system of the operator, a protective Power transformer

disconnection device is required


which takes into account frequency Busbar
and voltage and also evaluates the
Circuit breaker at the power-system connection point
2
reactive power direction. When the Further *
generating unit draws reactive power I>, I>> I-TOC IN>, IN>> IN-TOC
feeders
50 51 50N 51N
from the operator's power system,
Undervoltage-controlled reactive 52 V>, V>> V< f>, f> Q>/ V<
1)
1) Undervoltage
power protection (Q> & V<) links the Tripping
59 27 81
controlled reactive
reactive power with all three phase-
to-phase voltages falling below a Medium-voltage busbar
power protection
3
limiting value using a logical AND
operation.
This ensures that generating units
disconnect from the power system
which additionally burden the power
Generator step-up transformers
4
system during a short circuit or Bus coupler circuit-breaker
prevent that the power system is re- 52 52 52 Decoupling protection

4_18_Visio-QU-Schutz-en.pdf
stored when connecting after a short with V>>, V<, V<<, f>, f< functionen

circuit. The monitoring of the voltage


support also fulfills this function.
5
Using the criteria mentioned above G
3~
G
3~
G
3~ Generators
the QV protection disconnects the
generating unit from the power
system after a programmable time.
Fig. 4/18 Application directional intermittent ground fault protection
6
The QV protection furthermore
allows releasing the re-connection
after the fault has been located and
cleared in the power system and the
system voltage and frequency are 7
stable again.

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/17


Overcurrent Protection SIPROTEC 7SJ80
Selection and ordering data

Product description Order No. Short code


1 2 3  4  5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

1 Overcurrent Protection SIPROTEC 7SJ80 V4.74 7SJ80 - - +

Measuring inputs, binary inputs and outputs


Housing 1/6 19"; 4 x I, 3 BI, 5 BO (2 Changeover/Form C), 1 life contact 1

2
Housing 1/6 19"; 4 x I, 7 BI, 8 BO (2 Changeover/Form C), 1 life contact 2
Housing 1/6 19"; 4 x I, 3 x V, 3 BI, 5 BO (2 Changeover/Form C), 1 life contact 3 see
Housing 1/6 19"; 4 x I, 3 x V, 7 BI, 8 BO (2 Changeover/Form C), 1 life contact 4 next
page
Housing 1/6 19"; 4 x I, 11 BI, 5 BO (2 Changeover/Form C), 1 life contact 7
Housing 1/6 19"; 4 x I, 3 x V, 11 BI, 5 BO (2 Changeover/Form C), 1 life contact 8
Measuring inputs, default settings
Iph = 1 A/5 A, IE = 1 A/5 A 1
3 Iph = 1A / 5A, IEE (sensitive) = 0,001 to 1,6A / 0,005 to 8A 2
Auxiliary voltage
DC 24 V / 48 V 1
DC 60 V / 110 V / 125 V / 220 V / 250 V, AC 115 V, AC 230 V 5

4 Construction
Surface-mounting case, screw-type terminal B
Flush-mounting case, screw-type terminal E
Region specific default and language settings
Region DE, IEC, language German (language changeable), standard front A

5 Region World, IEC/ANSI, language Englisch (language changeable), standard front


Region US, ANSI, language US-English (language changeable), US front
B
C
Region FR, IEC/ANSI, language French (language changeable), standard front D
Region World, IEC/ANSI, language Spanish (language changeable), standard front E
Region World, IEC/ANSI, language Italian (language changeable), standard front F

6 Region RUS, IEC/ANSI, language Russian (language changeable), standard front


Region CHN, IEC/ANSI, language Chinese (language not changeable), Chinese front
G
K
Port B (at bottom of device, rear)
No port 0
IEC60870-5-103 or DIGSI4/Modem, electrical RS232 1

7 IEC60870-5-103 or DIGSI4/Modem, electrical RS485


IEC60870-5-103 or DIGSI4/Modem, optical 820nm, ST connector
2
3
PROFIBUS DP Slave, electrical RS485 9 L 0 A
PROFIBUS DP Slave, optical, double ring, ST connector 9 L 0 B
MODBUS, electrical RS485 9 L 0 D

8 MODBUS, optical 820nm, ST connector


DNP 3.0, electrical RS485
9
9
L 0 E
L 0 G
DNP 3.0, optical 820nm, ST connector 9 L 0 H
IEC 60870-5-103, redundant, electrical RS485, RJ45 connector 9 L 0 P
IEC 61850, 100Mbit Ethernet, electrical, double, RJ45 connector 9 L 0 R

9 IEC 61850, 100Mbit Ethernet, optical, double, LC connector


DNP3 TCP + IEC 61850, 100Mbit Ethernet, electrical, double, RJ45 connector
9
9
L 0 S
L 2 R
DNP3 TCP + IEC 61850, 100Mbit Ethernet, optical, double, LC connector 9 L 2 S
PROFINET + IEC 61850, 100Mbit Ethernet, electrical, double, RJ45 connector 9 L 3 R
PROFINET + IEC 61850, 100Mbit Ethernet, optical, double, LC connector 9 L 3 S
IEC 60870-5-104 + IEC 61850, 100Mbit Ethernet, electrical,double, RJ45 connector 9 L 4 R
IEC 60870-5-104 + IEC 61850, 100Mbit Ethernet, optical, double, LC connector 9 L 4 S
MODBUS TCP + IEC 61850, 100 Mbit Ethernet, electrical, double, RJ45 connector 9 L 5 R
MODBUS TCP + IEC 61850, 100 Mbit Ethernet, optical, double, LC connector 9 L 5 S

10 Port A (at bottom of device, in front)


No port 0
With Ethernet interface (DIGSI, I/O-Unit connection, not IEC61850), RJ45 connector 6
Measuring / Fault recording
With fault recording 1
With fault recording, average values, min/max values 3
You will find a detailed overview of the technical data (extract of the manual) under: http://www.siemens.com/siprotec
4/18 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4
Overcurrent Protection SIPROTEC 7SJ80
Selection and ordering data

ANSI No. Product description Order No. Short code


1 2 3  4  5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Overcurrent Protection SIPROTEC 7SJ80 V4.74 7SJ80 - - +
1
3)
Basic version F A
50/51 Time-overcurrent protection, phase I>, I>>, I>>>, Ip
50N/51N Time overcurrent protection, ground IE>, IE>>, IE>>>, IEp
50N(s)/51N(s)1) Sensitive ground fault protection IEE>, IEE>>, IEEp
Intermittent ground fault protection
2
2)
87N High impedance REF
49 Overload protection
74TC Trip circuit supervision
50BF Circuit-breaker failure protection
46 Negative-sequence system overcurrent protection
37 Undercurrent monitoring
86 Lockout
Parameter changeover
3
Monitoring functions
Control of circuit breaker
Flexible protection functions (current parameters)
Inrush restraint

51V
Basic functionality + Directional sensitive ground fault, voltage and frequency protection
Voltage dependent inverse-time overcurrent protection
F B 4)
4
67N Directional time-overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
67Ns1) Directional sensitive ground fault protection, IEE>, IEE>>, IEEp
64/59N Displacement voltage
27/59 Under/Overvoltage
81U/O
47
Under/Overfrequency, f<, f>
Phase rotation
5
Flexible protection functions (current and voltage parameters)): Protective function for voltage,
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change
4)
Basic functionality + Directional phase & ground overcurrent, F C

6
directional sensitive ground fault, voltage and frequency protection
51V Voltage dependent inverse-time overcurrent protection
67 Directional time-overcurrent protection, phase, I>, I>>, I>>>, Ip
67N Directional time-overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
67Ns1) Sensitive ground-fault protection, IEE>, IEE>>, IEEp
64/59N Displacement voltage

7
27/59 Under/Overvoltage
81U/O Under/Overfrequency, f<, f>
47 Phase rotation
Flexible protection functions (current and voltage parameters): Protective function for voltage,
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change
4)
Basic functionality + Directional phase & ground overcurrent, directional sensitive F F
ground fault, voltage and frequency protection + Undervoltage controlled reactive
power protection + Directional intermittent ground fault protection 8
51V Voltage dependent inverse-time overcurrent protection
67 Directional overcurrent protection, phase, I>, I>>, I>>>, Ip
67N Directional overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
67Ns1) Directional sensitive ground fault protection, IEE>, IEE>>, IEEp
67Ns2)
64/59N
27/59
Directional intermittent ground fault protection
Displacement voltage
Under/Overvoltage
9
81U/O Under/Overfrequency, f<, f>
Undervoltage controlled reactive power protection, Q>/V<
47 Phase rotation
Flexible protection functions (current and voltage parameters)): Protective function for voltage,
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change
see
next
page

1) Depending on the ground current input the function will be either sensitive (IEE) or non-sensitive (IE)
2) Function only available with sensitive ground current input (Position 7=2)
10
3) Only if position 6 = 1, 2 or 7
4) Only if position 6 = 3, 4 or 8

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/19


Overcurrent Protection SIPROTEC 7SJ80
Selection and ordering data

ANSI No. Product description Order No. Short code


1 2 3  4  5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

1 Overcurrent Protection SIPROTEC 7SJ80 V4.74 7SJ80 - - +

5)
Basic functionality + Directional phase overcurrent, voltage and FQ
frequency protection + synchrocheck
51V Voltage dependent inverse-time overcurrent protection
2 67
27/59
Directional time-overcurrent protection, phase, I>, I>>, I>>>, Ip
Under/Overvoltage (phase-to-phase)
81U/O Under/Overfrequency, f< ,f>
47 Phase rotation
25 Synchrocheck
Flexible protection functions (current and voltage parameters)):
Protective function for voltage, rate-of-frequency change, rate-of-
27R/59R/81R voltage change
3 Automatic Reclosing (AR), Fault Locator (FL)
Without 0
79 With automatic reclosure function 1
FL With FL (only with position 6 = 3, 4 or 8) 2

4 79/FL With automatic reclosure function and FL


(only with position 6 = 3, 4 or 8)
3

Conformal Coating
for 7SJ801, 7SJ803 Z Y 1 5

5 for 7SJ802, 7SJ804, 7SJ807, 7SJ808 Z Y 1 6

10
5) Only with position 6 = 3 or 4 and position 16 = 0 or 1
You will find a detailed overview of the technical data (extract of the manual) under: http://www.siemens.com/siprotec

4/20 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Connection diagrams

1
F1 IA BO1 C11
C9
F2 C10
F3 I B, IN2
BO2 C14
F4
F5 IC
C13
C12 2
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E4
BO5 E5
E6
3

C3
C4
BI1
4
C5 BI2
C6
C7 BI3 Life Contact E10
C8
5
E8
E7

= + C1
Power Supply (~)
=
- C2

Port B
6
B
e.g. System interface

Port A
A
7
Contacts, Ceramic, 2.2 nF,

Ethernet interface
Interference Suppression
Capacitors at the Relay

USB-DIGSI-Interface
4_19_LSA4784us.pdf

Grounding on the case 8


250 V

Fig. 4/19 Multifunction protection SIPROTEC 7SJ801

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/21


Overcurrent Protection SIPROTEC 7SJ80
Connection diagrams

1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
2 F4
F5 IC
C13
C12
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E4

3 BO5 E5
E6
BO6 D9
D10
BO7 D11
C3
4 C4
BI1
BO8
D12
D13
C5 BI2 D14
C6
C7 BI3
C8 Life Contact E10
5 D1 BI4
E8
E7

D2
= + C1
D3 BI5 Power Supply (~)
D4 =
- C2

6 D5
D6
BI6
Port B
D7 B
BI7 e.g. System interface
D8
Port A
7 A
Contacts, Ceramic, 2.2 nF,

Ethernet interface
Interference Suppression
Capacitors at the Relay

USB-DIGSI-Interface
4_20_LSA4785us.pdf

8 Grounding on the case


250 V

Fig. 4/20 Multifunction protection SIPROTEC 7SJ802

10

4/22 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Connection diagrams

1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
F4
F5 IC
C13
C12
2
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E9 Q2 VA, VAB, Vph-n E4
E11
E12
VB, VBC BO5 E5
E6
3
E13 VC, VN, Vsyn, VX
E14

C3
C4
BI1
4
C5 BI2
C6
C7 BI3
C8 Life Contact E10
E8
E7 5
= + C1
Power Supply (~)
=
- C2

Port B
6
B
e.g. System interface

Port A
A
7
Contacts, Ceramic, 2.2 nF,

Ethernet interface
Interference Suppression
Capacitors at the Relay

USB-DIGSI-Interface
4_21_LSA4786us.pdf

Grounding on the case 8


250 V

Fig. 4/21 Multifunction protection SIPROTEC 7SJ803


9

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/23


Overcurrent Protection SIPROTEC 7SJ80
Connection diagrams

1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
2 F4
F5 IC
C13
C12
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E9 Q2 VA, VAB, Vph-n E4

3 E11
E12
VB, VBC BO5 E5
E6
E13 VC, VN, Vsyn, VX BO6 D9
E14 D10
BO7 D11
C3
4 C4
BI1
BO8
D12
D13
C5 BI2 D14
C6
C7 BI3
C8 Life Contact E10
5 D1 BI4
E8
E7
D2
= + C1
D3 BI5 Power Supply (~)
D4 =
- C2

6 D5
D6
BI6
Port B
D7 B
BI7 e.g. System interface
D8
Port A
7 A
Contacts, Ceramic, 2.2 nF,

Ethernet interface
Interference Suppression
Capacitors at the Relay

USB-DIGSI-Interface
4_22_LSA4787us.pdf

8 Grounding on the case


250 V

Fig. 4/22 Multifunction protection SIPROTEC 7SJ804


9

10

4/24 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Connection diagrams

1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
F4
F5 IC
C13
C12
2
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E4
BO5 E5
E6
3

C3
C4
BI1
4
C5 BI2
C6
C7 BI3
C8 Life Contact E10

D1 BI4
E8
E7 5
D2
= + C1
D3 BI5 Power Supply (~)
D4 =
- C2
D5
D6
BI6
Port B
6
D7 B
BI7 e.g. System interface
D8
D9 BI8 Port A
D10 A
7
Contacts, Ceramic, 2.2 nF,

BI9 Ethernet interface


Interference Suppression

D11
Capacitors at the Relay
4_23_Visio-kl-uebers-7sx807-us.pdf

D12 BI10
D13 USB-DIGSI-Interface
BI11
D14

Grounding on the case 8


250 V

Fig. 4/23 Multifunction protection SIPROTEC 7SJ807


9

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/25


Overcurrent Protection SIPROTEC 7SJ80
Connection diagrams

1
F1 IA BO1 C1 1
F2 C9
C10
F3 I B, IN2
BO2 C1 4
2 F4
F5 IC
C13
C12
F6
BO3 E1
F7 I N, INS
E2
F8
BO4 E3
E9 Q2 VA, VAB, Vph-n E4

3 E11
E12
VB, VBC BO5 E5
E6
E13 VC, VN, Vsyn, VX
E14

C3
4 C4
BI1

C5 BI2
C6
C7 BI3
C8 Life Contact E10
5 D1 BI4
E8
E7
D2
= + C1
D3 BI5 Power Supply (~)
D4 =
- C2

6 D5
D6
BI6
Port B
D7 B
BI7 e.g. System interface
D8
D9 BI8 Port A
7 D10 A
Contacts, Ceramic, 2.2 nF,

BI9 Ethernet interface


Interference Suppression

D11
Capacitors at the Relay
4_24_Visio-kl-uebers-7sx808-us.pdf

D12 BI10
D13 USB-DIGSI-Interface
BI11
D14

8 Grounding on the case


250 V

Fig. 4/24 Multifunction protection SIPROTEC 7SJ808


9

10

4/26 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Connection examples

Connection of current
and voltage transformers
1
A
B
Standard connection C

For grounded networks, the ground 52 52 52


Surface-/Flush Mounting Housing
current is obtained from the phase
currents by the residual current IA

2
F1 F2

4_25_LSA4789-en.pdf
circuit. F3 IB F4

F5 IC F6
P2 S2

IN
P1 S1 F7 F8

A B C SIPROTEC

Fig. 4/25 Residual current circuit without directional element


3

A
B
C
4
A

a
5
Surface-/Flush Mounting Housing

E9 VA-N

E11 VB-N E12


52 52 52
E13 VC-N E14 6
IA
F1 F2

4_26_LSA4791-en.pdf
IB
F3 F4
IC
F5 F6

7
L l

IN
K k F7 F8

A B C SIPROTEC

Fig. 4/26 Residual current circuit with directional element


8
A

9
B
For power systems with small earth C

currents, e.g. isolated or compen- Surface-/Flush Mounting Housing


52 52 52
sated systems, the earth current is IA
F1 F2
measured by a zero-sequence current IB
F3 F4
transformer. IC
F5 F6
L l

K k
4_27_LSA4790a-en.pdf

INs
A B C F8 F7

L l
SIPROTEC 10
K k

Fig. 4/27 Sensitive ground current detection without directional element

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/27


Overcurrent Protection SIPROTEC 7SJ80
Connection examples

Connection for compensated


networks A

1 The figure shows the connection of


A
B
C
two phase-to-ground voltages and
the VE voltage of the broken delta B

winding and a phase-balance neutral da

current transformer for the ground


2
dn
a
current. This connection maintains
maximum precision for directional b

ground-fault detection and must be


Surface-/Flush Mounting Housing
used in compensated networks.

LSA4792a-en.pdf
E9 VA-B

E11 VC-B E12

3 52 52 52 E13 VN E14

IA
F1 F2
IB
F3 F4
IC
F5 F6
L l

4 K k

A B C
F8 INs F7

L l

5
SIPROTEC

K k

Fig. 4/28 Sensitive directional ground-fault detection with directional


element for phases

6
A
Sensitive directional ground-fault B
detection. C
A

7 B

da

dn Surface-/Flush Mounting Housing

52 52 52 VN
E13 E14

8 F1

F3
IA

IB
F2

F4
IC
F5 F6
L l

9
K k
4_29_LSA4793a-en.pdf

A B C
F8 INs F7

L l SIPROTEC

K k

Fig. 4/29 Sensitive directional ground-fault detection

10

4/28 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4


Overcurrent Protection SIPROTEC 7SJ80
Connection examples

Connection for the synchrocheck


function A

If no directional earth-fault protection


B
C
1
A B
is used, connection can be done with a b Surface-/Flush Mounting Housing
just two phase current transformers. 52 52 52
VA-B
For the directional phase short-circuit E9

2
A a
protection, the phase-to-phase
E12
voltages acquired with two primary B
A
b
a

transformers are sufficient. B b E11


VC-B

VSyn
E14
E13

F1
IA
F2
3

4_30_LSA4858-en.pdf
IB
F3 F4

F5 IC F8
L l

K k F7 IN F8 4
A B C SIPROTEC

Fig. 4/30 Measuring of the busbar voltage and the outgoing feeder


voltage for synchronization 5

10

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4 4/29


Overcurrent Protection SIPROTEC 7SJ80
Connection types

Overview of connection types


Type of network Function Current connection Voltage connection

1 (Low-resistance) grounded
networks
Time-overcurrent protection
phase/ground non-directional
Residual circuit, with 3 phase-
current transformers required,

phase-balance neutral current


transformers possible
(Low-resistance) grounded Sensitive ground-fault protection Phase-balance neutral current –

2 networks
Isolated or compensated Overcurrent protection phases
transformers required
Residual circuit, with 3 or 2 phase- –
networks non-directional current transformers possible
(Low-resistance) grounded Directional time-overcurrent Residual circuit, with 3 phase- Phase-to-ground connection or
networks protection, phase current transformers possible phase-to-phase connection
Isolated or compensated Directional time-overcurrent Residual circuit, with 3 or 2 phase- Phase-to-ground connection or
networks protection, phase current transformers possible phase-to-phase connection
3 (Low-resistance) grounded
networks
Directional time-overcurrent
protection, ground-faults
Residual circuit, with 3 phase-
current transformers required,
Phase-to-ground connection
required
phase-balance neutral current
transformers possible
Isolated networks Sensitive ground-fault protection Residual circuit, if ground current 3 times phase-to-ground

4 > 0.05 IN on secondary side,


otherwise phase-balance neutral
connection or phase-to-ground
connection with broken delta
current transformers required winding
Compensated networks Sensitive ground-fault protection Phase-balance neutral current 3 times phase-to-ground
cos j measurement transformers required connection or phase-to-ground
connection with broken delta
5 winding

Table 4/4  Overview of connection types

10

4/30 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 4

You might also like