Professional Documents
Culture Documents
4112 Dew Point Transmitter
4112 Dew Point Transmitter
Operations Manual
70-82-25-08
Rev. 2
2/99
Copyright, Notices, and Trademarks
Printed in U.S.A. – © Copyright 1999 by Honeywell Inc.
Revision 2 – 2/99
Honeywell
Industrial Automation and Control
Automation College
2820 West Kelton Lane
Phoenix, AZ 85023
(602) 313-5669
Abstract
This manual provides technical description and installation and maintenance instructions for the
Honeywell 4112 Moisture Instrument.
Included are all circuit adjustment instructions required to verify proper electrical functions of the
instrument as well as system calibration for ambient temperature and moisture.
Revision Notes
The following list provides notes concerning all revisions of this document.
0 9/30/96 This document is the initial release of the Honeywell version of the L&N
manual p/n 278159 Rev. A.
1 10/97 Additions were made in Chapter 3 for Ferrite Bead installation and in
Chapter 12 for CE approval information.
2 2/99 Additions were made for the cooler option and the S200 and S201 dip
switches.
References
Non-Honeywell Documents
The following list identifies select non-Honeywell documents that may be sources of reference for the
material discussed in this publication.
Contacts
The following list identifies important contacts within Honeywell.
1. INTRODUCTION....................................................................................................1
1.1 Overview.........................................................................................................................................1
Transmitter Functions........................................................................................................................1
1.2 Filters ..............................................................................................................................................1
3. INSTALLATION .....................................................................................................9
3.1 Storage and Shipment .....................................................................................................................9
3.2 Unpacking .......................................................................................................................................9
3.3 Rough Functional Check.................................................................................................................9
3.4 Dew Point and Wet Bulb Considerations .......................................................................................9
3.5 Mechanical Considerations...........................................................................................................10
3.6 Maintaining CE Mark Approval Procedure..................................................................................10
4. WIRING................................................................................................................13
4.1 Introduction...................................................................................................................................13
7. TROUBLESHOOTING.........................................................................................31
1. Introduction
1.1 Overview
Transmitter Functions
The Honeywell 4112 unit measures and digitally displays Ambient Temperature and a moisture
measurement. The moisture measurement can be in units of Dew Point Temperature, Relative Humidity,
Humidity Ratio or Wet Bulb temperature, depending on a customer’s requirements. In addition this
transmitter unit outputs two 4 mA to 20 mA current loops, proportional to Ambient Temperature and
moisture measurement. Figure 1-1 shows an exploded view of the 4112 assembly.
The unit is packaged in an explosion proof housing with a window to permit viewing the digital displays.
Connection for Transmitter operation is available by unscrewing (counterclockwise) the windowed housing
cover and exposing a barrier strip with screw terminals on an inside cover.
A label adjacent to the barrier strip screw terminals identifies connections for 120 VAC or low voltage DC
operation of the unit. Wiring should be routed through conduit inlets on the housing to the screw terminals
exposed by removal of the windowed explosion proof cap.
A green grounding screw is mounted to the housing adjacent to the internal cap for system grounding.
A metal swing away plate is affixed to the side of the unit below the explosion proof cap. This plate may be
loosened and swung away to expose adjustment controls for field calibration. These controls may be
accessed without violating the explosion proof integrity of the housing.
The sensor may be inserted into the application via 1/2” NPT male threads at the root of the sensor probe
just under the base of the housing.
The probe stainless steel shaft is 3/8” diameter and may optionally be inserted into the application via a 3/8”
compression fitting.
1.2 Filters
Included with each dew point transmitter are two threaded filters and a fluted shield .
One of the filters is mounted on the end of the sensing probe. The other filter and the shield are packed in a
small plastic bag. Following is a description of these three parts.:
condensing or wet conditions. It will help keep liquid moisture off the sensor itself, allowing it to more
quickly respond when conditions return to a non-saturated state.
Window
Window
Digital Display
Interface Cable Cap
Screw Terminals for
Temperature Sensor
Signal Conditioning
and Transmitter Ass’y
Co-Axial Connector
for Moisture Sensor
Neoprene O-Ring
1 1/4-16 UN-2A
to Have 8 Threads
Minimum Engagement
1/2-14 NPT Conduit with Housing
Material: 304 or 316 S.S.
1/2-14 NPT
Material: 300 Series S.S.
Sensor
a/n 23314
3/8"
INSTALLATION
Transmitter Housing: NEMA 4X, IP65 cast low-copper aluminum fully anodized with aliphatic
urethane finish. Weight approximately 4.4 lb. (2.0 kg).
Sensor Housing: Stainless steel probe; fluted shield; porous stainless steel filters.
Mounting: Can be mounted on pipe or wall
Sensor Operating Environment: -40oC to 185oC (-58oF to 365oF); to 150°C (300°F) for –110 option
Transmitter Operating Environment: -40oC to 80oC (-40oF to 176oF); Display:-30oC (-22oF)
Storage Environment: -55oC to 85oC (-67oF to 185oF)
Power Requirements: 115 VAC ± 10%, 60 Hz with Rlmax 500 Ohm or 11Vdc + (Rload x 0.02 A)
min. to 45 Vdc max. for dual 2-wire operation
Operation requires three wires, even if using only one signal
Intrinsic Safety Entity Parameters: V max = 30 volts; I max = 360mA; Ci = 0.1 µF; Li = mH
Signal Connection: Screw terminals
Sensor Mounting: 1/2” NPT; ¾” NPT (-110 option)
Pressure: 0 to 350 psi dew point at pressure; 0 to 2000 psi (-110 option)
SERVICEABILITY
Periodic Maintenance: Verify calibration periodically. Wash sensor as needed.
Adjustments: Vernier, non-interacting, multi-turn potentiometers for zero and span control
of Dry Bulb temperature. Momentary rotary action switches for Dew Point
Calibration. Adjustments are on the outside of the transmitter housing under
a swing-away plate.
Sensor Break Indication: Dry Bulb Sensor: upscale both output signals
Dew Point Sensor: downscale on dew point signal only
Over Temperature Indication: Dew Point output at 100oC when Dry Bulb > 192oC
Sensor Cleaning: Wash with detergent solution. Rinse with de-ionized water. Camel hair
(organic) brush may be used during cleaning when required.
TABLE IV – OPTIONS*
None 000 •
Pipe/Wall Bracket Kit 100 •
High Pressure Probe: up to 2000 psi 110 c
FM Intrinsically Safe (24 Volt only) 209 e
CE Compliant (24 Volt DC Power) 210 •
Stainless Steel Tag, up to 25 characters each of 3 lines 208 •
RESTRICTIONS
Restriction Letter Available Only With Not Available With
Table Selection Table Selection
c I 04, 12 IV 100, 104
II D3
d IV 110
e IV 210
f IV 209, 210
*See 4113 Accessories for coolers, insertion removal device, etc.
6.0
-10
FP
H 0°C
°C
-75
4.0 °C
FP
-50
°C
3.0
- 25
DP
DP
H
3% R
DP
2.0 -50
DP
°C
0°C
°C
°C
50
°C
25
75 DP
0°C
1 .5 10
RH
1 .0 10%
0.8
-25°C
0.6 0°C
0.5
0 25 50 75 100 125 150 175
Dry Bulb Ambient - °C a/n23315
FP
F)
4°
0.9 C
(1
0°
-1 P
)F
0.8 3 °F
it) (2
Lim °C
-5 DP
mA )
0.7 (4 2°F
(3
C
0° DP
°F)
(50
0.6 10°
DP
(68°F)
20°C
0.55
0 10 20 30 40
Dry Bulb Temperature, °C a/n 23326
) FP
4 6°F FP P FP
(-7 F) )F F)
C 8° 0°F 2°
0° (- 5 (-4 (- 2
-6 °C °C 0 °C
-5
0 -4
0
-3 FP
2 ° F)
(-4 FP
-2 0°C 14°
F)
P
0°C( 2°F) D
1 -1
0°C
(3
DP
20°C (68°F)
0.5
-40 -20 0 20 40
Dry Bulb Temperature - °C a/n 23327
3. Installation
3.2 Unpacking
Step Action
1 If there are visible signs of damage, do not remove the transmitter from its packing material. Notify
the carrier and Honeywell immediately.
2 If there is no visible damage, compare the contents with the packing list. Notify the carrier and
Honeywell immediately if there is a or shortage.
4 Carefully remove the Transmitter from its packing case and then remove any shipping ties on
packing material. Follow the instructions on any attached tags and then remove such tags.
1 Connect the “H2O”, “TEMP”, and “COM” screw The display should indicate ambient temperature and
terminals on the internal cap together. Apply dew point temperature.
120 VAC 60 Hz to the L1 and L2 screw
terminals.
2 Hold the sensor tip close to your open mouth Observe that the temperature display of ambient and
and breathe on it. dew point temperature responds.
The highest temperature at which water can exist as a liquid at one atmosphere of pressure is 100oC, hence
the maximum dew point range of the 4112 is 100oC or 212oF.
There is no theoretical practical upper limit of temperature at which water vapor can exist as a gas.
The real practical upper limit of gas ambient temperature for in situ dew point measurement is the 4112
sensor technology. This is limited to 185oC.
The 4112 calibrated upper limit of ambient temperature, sometimes referred to as dry bulb temperature, is
204.7oC.
Figure 2-3 illustrates the temperature range for which dew point measurements may be taken by the 4112.
When choosing a site for sensor installation within a system consideration should be given to select a point
where the gas will be the coolest without the formation of condensation.
The reason for the above consideration is that accuracy is dependent on the difference of temperature
between the ambient or dry bulb and dew point temperature (see accuracy chart Figure 2-1). This
temperature difference is referred to as temperature depression.
ATTENTION
This conduit connection can not exceed 30”.
Step Action
1 These installation notes apply to CE marked direct current loop powered units only (option code –
210). The ferrite bead is not required for CE marked AC line powered units (option –212). The ferrite
bead is not required for any units not bearing the CE mark.
2 Install the 4112 per the installation instructions. Before connecting the field wires to the terminal
block, slip the supplied ferrite bead over all wires. The ferrite bead is installed inside the threaded
explosion-proof housing of the 4112 unit.
3 Push the ferrite bead over the field wires as far as possible to the lower part of the enclosure.
4 Secure a plastic cable tie around the field wires just above the ferrite bead to retain the ferrite bead (
the exact location of the ferrite bead is not critical to its function.).
5 Connect the field wires to the terminal block per the installation instructions.
4.4
4.6" Dia (111.8mm)
7.3
(116.8mm) (185.4mm)
ZSD
1/2" NPT
Optional Pipe/Wall Mount
12" Hardware Kit
(305mm)
STD
4.4
4.6" Dia (111.8m
7.3
(116.8mm) (185.4mm)
ZSD
3/4" NPT
12"
(305mm)
STD
Figure 3-2-b 4112 Transmitter with High Pressure Probe (option –110)
Mounting Configuration
4. WIRING
4.1 Introduction
The 4112 has two transmitter outputs and an internal 120 VAC 60 Hz power supply to power these two
transmitters.
The two transmitters are internally connected together at their (+) positive terminals and when powered by
120 VAC 60 Hz can drive a maximum wire and load resistance of 500 ohms.
Should 120 VAC 60 Hz operation not be desired the 4112 may be powered by an external low voltage DC
power supply.
ATTENTION
The intrinsically safe model is DC powered only.
The above values are derived from the relationship 11 Vdc + (Rload x 0.02A) = Vdc loop min..
11 Vdc is required to keep the transmitter in regulation while the load(resistor + lead wires) creates the
balance of the voltage drop incurred at the 20 mA level.
ATTENTION
Determine load resistor values and mounting location per the requirements of your readout device(s).
REFERENCE
Figure 1-1, screw terminal label on inner cap.
CAUTION
Both outputs must be connected to the negative side of the power supply even if no 4-20 mA input device is
used for one or both outputs.
3 Connect one end of the Dew Point load Maximum load resistance for ac powered
resistor to the H2O Terminal, and wire to the transmitters is 500 ohms, 250 ohms per channel.
Positive Terminal of the readout device.
5 Connect one end of the Dry Bulb load resistor If Dry Bulb read out is not used, use a jumper
to the TEMP Terminal, and wire to the Positive between TEMP and COMM in place of the
Terminal of its readout device. resistor and disregard step 6 below. See Figure 4-
2.
4112
Terminal
Block
L Hot (Black)
1
120 VAC Power
L
Neutral (White) 4 - 20 mA
2 Input Device
_
Com Loop Com
(-)
H2 O
AI 1
{ + Dew Point
4 - 20 mA
Input
+
Temperature
Temp 4 - 20 mA
AI 2
{ _
Input
Gnd Jumper
Water Pipe
Load Resistors
if Required
a/n 23317
Note: Always consult the manual of these devices for correct jumper configuraiton and wiring connections.
4112
Terminal
Block
L Hot (Black)
1
120 VAC Power
L
Neutral (White) 4 - 20 mA
2 Input Device
_
Com Loop Com
H2 O
(-)
AI 1
{ + Dew Point
4 - 20 mA
Input
Jumper
+
Load Resistors Temperature
Temp if Required 4 - 20 mA
{
AI 2 _
Input
Gnd
Water Pipe
Note: Always consult the manual of these devices for correct jumper configuraiton and wiring connections.
5 Connect one end of the Dry Bulb load resistor If Dry Bulb read out is not used, use a jumper
to the TEMP Terminal, and wire to the Positive between TEMP and power supply Negative in
Terminal of its readout device. place of the resistor and disregard step 6 below.
See Figure 4-4.
Current Loop
Power Supply
H20
AI 1
{ Dew Point
+ 4 - 20 mA
Input
+
Temperature
Temp 4 - 20 mA
AI 2 { _
Input
Note: Always consult the manual of these devices for correct jumper configuraiton and wiring connections.
H2O
AI 1
{ + Dew Point
4 - 20 mA
Input
Temp
Load Resistor
If Required
Gnd
Water Pipe
Note: Always consult the manual of these devices for correct jumper configuraiton and wiring connections.
When the monitoring device supplies power for the 4112 Transmitter, both loops must be activated. This is
necessary for the proper operation of the instrument. Wiring diagrams covering monitoring devices with
internal power supplies are shown in Figures 4-5, 4-6 and 4-7.
4 - 20 mA
Input Device
4112
Terminal + 24VDC
Block Internal
- Supply
-
Loop Com
Com
(+) Jumper
H2 O
AI 1
{ +
Dew Point
4 - 20 mA
Input
+
Temperature
Temp 4 - 20 mA
Note: Always consult the manual of these devices for correct jumper configuration and wiring connections.
Two inputs are needed for proper operation. Both outputs must be connected to the negative side of
the power supply, whether one or both outputs are used. If 2 inputs are not available call the
Technical Assistance Center (T.A.C.) @ 1-800-343-0228 for assistance..
Figure 4-5 DC Wiring Diagram with Internal Supply for Dew Point
and Temperature 4-20 mA Current Loops Monitored
4 - 20 mA
Input Device
4112
Terminal + 24VDC
Block Internal
- Supply
Jumper
Com -
(+)
H 2O
AI 1
{ +
Dew Point
4 - 20 mA
Temp Input
Load Resistor
Gnd Water Pipe If Required
Note: Always consult the manual of these devices for correct jumper configuration and wiring connections.
Two inputs are needed for proper operation. Both outputs must be connected to the negative side of
the power supply, whether one or both outputs are used. If 2 inputs are not available call the
Technical Assistance Center (T.A.C.) @ 1-800-343-0228 for assistance..
Figure 4-6 DC Wiring Diagram with Internal Supply for Dew Point only
4-20 mA Current Loops Monitored
Com - + V-
-
(+) AI 1
+ V+
H2 O
Excitation
Voltage
AI 2
Temp - +
-
Note: Always consult the manual of these devices for correct jumper configuration and wiring connections.
Two inputs are needed for proper operation. Both outputs must be connected to the negative side of
the power supply, whether one or both outputs are used. If 2 inputs are not available call the
Technical Assistance Center (T.A.C.) @ 1-800-343-0228 for assistance.
Figure 4-7 DC Wiring Diagram with Internal Supply for Dew Point
and Temperature 4-20 mA Current Loops Monitored
5. System Operation
5.1 Introduction
Figure 5-1 Simplified System Block Diagram shows transmitter connections labeled L1, L2, COM, H2O
and Temp.
EO +5.0
+
DC to DC
Convertor
5.0 VDC RTD
-
+ COMM
+ Digital Display
Temp CCT
Zero Span 204.7°C
-104.7°C
Temp. D.P.
24 VDC A to D RH OSC
I2 Freq
6.9 Zero Span
F101 CR VDC RV301 RV302
T 100 C101 RV300 Moisture
100
Sensor
VR
-
BR100 402
D.P.
F100 D to A S-201
-
EO -6.9
MICROPROCESSOR
Display °C/°F
Zero Span
4 mA Temp. RV200 RV201 Cal Protect
I1 I3 4 mA D.P. I4
Scale H.B./D.P.
Not Used
RV400
RV202
Ext.
Micro
Interface
Conn.
E ² Memory
Set Zero RH + DP Look Up
AC Powered Function/Mode Ta ble
Connections Switches
Down Up
DC Powered See S-200
Connections Figure 4-1 DP Calibration
See
Figure 4-2
a/n 23319
5.4 A to D Conversion
Once the current output is calibrated a voltage in the temperature circuit proportional to output current
calibration is routed to 12 bit A to D converter circuitry that digitizes the temperature signal to the
microprocessor.
This digitized value is displayed on a microprocessor controlled LCD display.
Calibration of the A to D converter is accomplished by RV301 and RV302, zero and span controls.
As moisture levels change and the capacitance of the moisture sensor changes, the RH oscillator changes
frequency.
This frequency change is monitored by the microprocessors timer input and provides digitized moisture
information to the microprocessor.
6.1 Introduction
Two single – pole, single – throw DIP switch packs are mounted on the microprocessor board and
interfaced to the microprocessor. S-200 consists of two switches and S-201 consists of four switches.
The location of the S-200 and S-201 on the dew point assembly is shown in Figure 6-3
S-200
DIP switch S-200 contains two switches and is located on the microprocessor board perpendicular to the
display board and directly behind the upper display (dry bulb temperature). S-200 has the letters D.P.
inscribed in white letters directly beside it (see Figure 6-3). Figure 6-1a illustrates the correct method for
configuring the switches of DIP switch S-200 in the off position. Each individual switch is OFF when it is
pointing up toward the white dot and the word OFF located on the DIP switch block. Figure 6-2b illustrates
the correct method for configuring the switches of DIP switch S-200 in the ON position. The switch is ON
when it is pointing down toward the switch numbers inscribed on the DIP switch block.
O FF O FF
A. B.
OFF ON
2 2
1 1
OFF 2 sec, back Switch S-200-1 OFF only when performing a zero %RH
to ON calibration. When switch 1 of S200 is turned OFF and then
back ON, the transmitter assumes a zero %RH standard is
being applied to the sensor and stores this data in memory.
Note: Switch 3 of DIP switch S-201 must be in the ON
position to allow the transmitter to store the zero calibration
data. If this switch is in the OFF position when activating
switch 1 of S-200, the lower display will quickly 0.0% RH for
approximately one second, and then continue displaying the
value observed before configuring switch 1 of S-200.
S-201
DIP switch S-201 contains 4 switches and is labeled S201and is located on the reverse side of the
microprocessor board than S200. See Figure 6-3. Figure 6-2 illustrates the correct method for configuring
the switches of DIP switch S-201 on and off. Figure 6-2a illustrates the correct method for configuring the
switches of DIP switch S-201 in the off position. Each individual switch is OFF when it is pointing up
toward the white dot and the word OFF located on the DIP switch block. Figure 6-2b illustrates the correct
method for configuring the switches of DIP switch S-201 in the on position. The switch ins ON when it is
pointing down toward the switch number inscribed on the DIP switch block.
O FF
A. B. O FF
OFF ON
4 4
3 2 3
2
1 1
D1, D2, D3, W1, R1 Switch 1 of S-201 comes configured in the OFF position from
the factory for models D1, D2, D3, W1 & R1. The position of
switch 1 for these models has no effect on the transmitter
reading/output.
1 OFF H1, H2, H3 When in the OFF position and switch 2 of S-201 is in the ON
position, the transmitter moisture display and output scaling
units are lb/lb. When switch 2 of S-201 is in the OFF position,
switch 1 of S-201 has no effect on the transmitter
reading/output.
OFF D1, D2, D3, H1, H2, H3, W1 When switch 2 of S-201 is in the OFF position, the moisture
display and output scaling are proportional to Dew Point
temperature.
ON D2, D3, H1, H2, H3 When switch 2 of S-201 is in the ON position and switch 1 of S-
201 is in the ON position, the transmitter moisture display and
output scaling units are grains/lb. When switch 2 of S-201 is in
the ON position and switch 1 of S-201 is in the OFF position,
the transmitter moisture display and output scaling units are
lb/lb.
4 ON ALL Dry Bulb and Dew Point/Wet Bulb Displays are in degrees
Fahrenheit on the transmitter.
OFF Dry Bulb and Dew Point/Wet Bulb Displays are in degrees
Celsius on the transmitter.
S201 4 Display On = °F
S200 Off = °C
1 Zero = Cal 3 Cal Prot. On = Fact
Off = Oper Off = Usr
RTD Temperature
2 Scale On = W.B.
Sensor Locations
Off = D.P.
Span RV201 1 Not Used
Zero RV200
2 Display On = D.P. RV400 4mA Temp
Off = %RH
DP Loop 4mA
Dew Point Up/Down Span
RV202
Counts Pushbuttons
RTD Card
External Micro
Span Temp 20mA
Interface Connector
Mother Card
a/n 23320
Table 6-3 can be used to convert the 4112 transmitter from one model type to another. For example, if we
take a D1 model type transmitter, the table shows that it can be converted to an R1 or H1 unit by
appropriately configuring DIP switches S-200 and S-201.
Table 6-3 Switch Selectability of Output Units for the 4112 Transmitter
Model Type D1 D2 D3 D4 H1 H2 H3 R1 W1
D1 X — — — X — — X —
D2 — X — — — X — *X —
D3 — — X — — — X *X —
D4 — — — X — — — *X —
H1 X — — — X — — X —
H2 — X — — — X — *X —
H3 — — X — — — X *X —
R1 X — — — X — — X —
W1 X — — — — — — X X
NOTE: *X indicates a non-temperature compensated relative humidity output signal which is provided
only for purposes of calibration against a relative humidity reference at room temperature. RH is always 0-
100% over 4-20 mA. Dry bulb temperature ranges always remain fixed.
ATTENTION
• The RH output is temperature compensated only if the instrument is configured with D1, W1, H1 or R1
output options.
• With other ranges, RH output reads low above room temperature, and high below room temperature.
7. Troubleshooting
Table 7-1 Troubleshooting
Symptom Probable Cause Action
Transmitter does not function. Incorrect connections, reversed Review Figure 4-1and
Display is blank. polarity
Figure 4-3. Try reversing the
polarity
Humidity output is locked at 20ma, Water vapor has condensed on Withdraw sensor from process. Dry
dew point reading tracks at or very the sensor and or the filter the filter *. Use the sintered
close to dry bulb temperature stainless steel filter with
reading. Display reads HHH.H. hydrophobic coating
Mechanical damage of the Visible scratches, abrasion, etc. Use screens or baffles to deflect
sensor surface high flow rates, greater than 30 high speed airborne particulate,
m/sec (100 fps) relocate transmitter.
Damaged sensors must be replaced
and the transmitter recalibrated.
Humidity output is locked Break in the electrical Return transmitter to Honeywell for
permanently, typically at 4ma. connection between the sensor service.
and the transmitter electronics:
Dew point reading does not agree Reference dew point value is Convert each reading to the
with the reading from another referenced to atmospheric equivalent humidity ratio (mixing
reference instrument. pressure, while the transmitter’s ratio) value and then compare the
sensor is reading the gas at humidity ratio values **
elevated pressure
* After an hour or so, depending on the amount of condensation, the unit output should be between 4 and 20ma.
One way to speed the drying of the sensor and filter is to spray them with an isopropyl alcohol solution from a
simple plastic pump spray bottle.
** The partial vapor pressure of a compressed gas mixture is higher than the partial vapor pressure of the same
gas mixture at atmospheric pressure. Because dew point is directly related to vapor pressure, the dew point of a
compressed gas will also be higher than the dew point of that same gas at atmospheric pressure. One way to
compare two dew point readings of the same gas but at different pressures is to convert each reading to the
equivalent humidity ratio (mixing ratio) value and then compare the humidity ratio values. Given total pressure
and dew point, the humidity ratio can be calculated. The humidity ratio is commonly expressed as pounds of
H2O per pound of dry air, grains per pound, kilogram per kilogram, etc.
Sensor Cleaning
The surface of the sensor may be coated with a film or with a heavy layer of contaminants. This is usually,
though not always, evident by visual inspection of the sensor surface. The sensor surface is green in color and
normally appears shiny, sometimes iridescent depending on lighting. A good procedure for cleaning the sensor
is as follows: Obtain three simple pump spray bottles, Fill the first with a solution of distilled water and mild
detergent like Ivory soap. Fill the second with distilled water, and the third with a solution of water and
isopropyl alcohol. Spray the sensor directly with the soap solution, and follow that with distilled water spray to
rinse it off. Finally a spray of alcohol will help to dry out the sensor quickly. As an alternative to the three
bottles, the alcohol alone will often be adequate to clear the sensor of surface contaminants. Avoid touching the
sensor surface directly as it is possible to scratch the sensor’s top protective layer. If necessary, a soft camel hair
brush may be used to help remove surface dirt.
For convenience, the sensor may be removed from the end of the probe before cleaning. The sensor connects to
the probe via four gold-plated pins. When reinstalling the sensor assembly, be sure to match up the notch on the
sensor assembly housing with the machined flat at the end of the probe.
REFERENCE
(Table 6-1 , 6-2 ), Fig. 1-1 , Fig. 6-3, Fig 8-3, and Fig. 9-1
1 Obtain a screwdriver, suitable power supply, The Calibration Kit provides the necessary
Calibration Kit or alternate 0% and 75.3% RH standards. Near 0% RH can also be obtained
standards. from bottled Nitrogen gas. A 75.3% RH standard
may be made by mixing a saturated solution of
sodium chloride in a suitable container.
3 Remove inner cover from the transmitter. Loosen mounting screws(3) and one ground
screw.
4 Power the transmitter Make sure terminals are covered with black shield
5 Set S-200-2, labeled DP-2 to OFF; make sure Bottom display of transmitter will display %RH
S-201-3 is ON
7 Insert the probe into the canister with the Let stand for 30 to 60 minutes. RH reading should
attached compression fitting, and fasten the be 0 to 0.1 % after time has elapsed. If so, go to
fitting around the probe end. step 9. If higher, go to step 8.
8 Activate DIP switch S-200-1,labeled DP-1 to S-200 is on the top edge of the microprocessor
OFF position for approximately 2 seconds then board in Figure 6-3. The display should be
return to ON position. reading 0.0% RH.
Note: Factory calibration values can be restored by setting DIP switch S-201-3 to OFF, while power is applied to
transmitter.
2 Add distilled water (about 10 ml) to form a Slush/slurry appearance, salt crystals should be
saturated solution. visible in solution Avoid wetting the plastic filter in
the bottle.
3 Insert the probe via the plastic filter fitting. Let stand for approximately two hours. The lower
Insert the bottle into a temperature stable transmitter display should read 75.3% RH @
environment, see Figure 9-1 Calibration Setup 75°F/24°C after the two hours.
5 Remove the Honeywell nameplate from the Moisture display increments up or down. CAL is
face of the transmitter. displayed until actuator is released. After
adjustment, CCC.C appears in the display.
Use a flathead screwdriver to rotate slot D
clockwise to increase, counter clockwise to
decrease display of %RH until lower displays
read 75.3% RH.
6 Momentarily press and release again. If CCC.C does not clear, the switch button is
stuck, or there is an internal fault. Have the
transmitter serviced.
7 Set S-200-2 back to the ON position. The Do not turn OFF S-201-3 or the original factory
calibration is complete. span and zero calibration will be restored.
N.C. L1
120 VAC R1 R2
N.C. L2 60 Hz DVM DVM
Comm Comm
H2 O H2 O
Temp Temp
INC
Z S D
a/n 23321
CAUTION
• Do not attempt this procedure unless temperature bath can be measured and controlled to 0.01deg c via
NIST traceable standards.
• Do not remove the P.C. assemblies from the lower housing as this affects calibration
REFERENCE
(Table 6-1, 2 ), Fig. 1-1 , Fig. 6-1, fig 8-1, and Fig. 9-1
1 Obtain a power supply, resistance decade Connections are shown in Fig. 8-1, electrical test
box(0-5000 ohms, settable to .01 ohm), load set up
resistors and DVM. Also tip cover( Honeywell
part number 225-0158)
5 Connect resistance box to RTD block Set for zero ohms(or short box terminals)
7 adjust RV-400 trimpot on the RTD Board Temperature Channel output of 3.98 to 4.00
milliamps cutoff
8 adjust RV-301on the A to D Board Temperature Display reading of 000.0. Dew Point
display should now read -104.7.
9 adjust RV-200 trimpot on the Microprocessor 0.000 millivolts output +/- 50 microvolts at pins 1
Board and 2 of U-200 IC
10 adjust RV-202 trimpot on the Microprocessor Dew Point Channel output of 3.98 to 4.00
Board milliamps cutoff.
12 adjust the Zero trimpot on the Mother Board for slightly over 4 milliamps Temperature Channel
output and then slowly back to 4.00 milliamps
13 adjust RV-301 trimpot on the A/D board Temperature Display reading of 000.0.
15 adjust the SPAN trimpot on the Mother Board 20.00 milliamps output on the Temperature
Channel
16 adjust trimpot RV-302 located on the A/D Temperature Display to read 204.7.
Board
18 adjust RV-201 trimpot on the Microprocessor for Dew Point channel 20.00 milliamps output
Board
22 Place protective tip cover on end of probe prevents water/oil Sensor contamination
24 adjust the Zero trimpot located on the Mother for slightly over 4 milliamps Temperature Channel
Board output then slowly back to 4.00 milliamps output.
26 adjust the Span trimpot located on the Mother for the Temperature Channel milliamps output by
Board using the following transfer equation:
o
milliamps output = (( Bath Temp C / 204.7 ) x 16
mA )) + 4 mA.
30 using screw driver slot switch activator D (Fig. read 75.3 % RH.
8-1), increment or decrement the Display
N.C. L1
120 VAC
N.C. L2 60 Hz
Comm Comm
H 2O H 2O
Temp Temp
Jumper
INC
Z S D
Ambient Temp. Zero
(±Multiturn Pot.) Dew Point
Cal. Actuator
(±10° multiturnOnly)
Ambient Temp. Span
(±Multiturn Pot.)
Any Container
Fine Gravel
Thermal Mass
(I.E. Aquarium Gravel)
3"
Solution with
Sodium Chloride
2" min Crystals in a
Saturated Solution
a/n 23322
10.1 Introduction
The Dew Point Transmitter has a maximum sensor operating temperature of 185°C. The optional Cooler
allows the safe operation of the sensor at process temperatures of up to 540°C (1000°F).
The Cooler surrounds the Dew Point probe with a jacket of flowing external air. Customer supplied air is
directed through the inlet port on the Cooler. The air is vented through a muffler on the outlet port. A safe
operating temperature can be maintained by controlling the air pressure.
Table 10-1 Cooler Performance, shows the cooling capability of the cooler. The data was obtained by
inserting the Dew Point Transmitter and Cooler into an oven in still air. The table lists sensor temperatures
for various oven temperatures and inlet pressures. For example, with oven temperature at 427°C and inlet
pressure at 20 psig, the dew point sensor temperature is 109°C, well below the 185°C maximum sensor
rating.
50 ----- ----- 89 62 49 37
40 23 3 102 74 53 39
30 16 2.3 120 88 60 43
20 10 2 152 109 75 50
CAUTION
Maximum sensor temperature is 185°c. exceeding this temp. will damage the sensor and void the warranty.
REFERENCE
Data Developed using a 12 in. probe and cooler with 5 (0.187 dia.) vent holes. Actual sensor temperatures
depend upon actual process ambient (moving vs static air) and inlet process air temperature.
.700
90 o Street Elbow
1.25" 304 SST
DIA.
10.3 Installation
CAUTION
Installation must not permit exceeding the 185°C sensor limit or the 80°C max electronics operating limit. To
protect the sensor, the air supply must be reliable and over -temp and loss of air alarms are recommended.
Step Action
1 Obtain a pressure regulator and gauge capable of delivering 5 scfm @ 50 psig., suitable tubing to
connect the air supply to the ¼ “ NPT inlet port, and a means to measure the cavity temperature.
2 Remove the Cooler from the transmitter. Loosely plug the ½” NPT mounting port temporarily.
4 Install the pressure regulator and gauge from the air supply to the Cooler inlet.
6 When the process temperature is at its hottest, allow 30 minutes for the Cooler cavity to reach its
maximum.
7 Measure the cavity temperature. Make sure it does not exceed 185°C.
8 For best performance, adjust the pressure to make the cavity temperature about 25 deg. above the
normal process dew point. See
11.1 Introduction
The Honeywell model 4112 Dew Point Transmitter is approved by Factory Mutual:
Case: NEMA 4X, approved units have FM labeling.
Explosion proof: Class I, Division 1, Groups B, C, and D; dust-ignition proof for Class II, Division 1,
Groups E, F, and G indoor and outdoor locations.
Intrinsically Safe: Class I, Division 1, Groups A, B, C, and D; dust-ignition proof for Class II, Division 1,
Groups E, F, and G indoor and outdoor locations in accordance with Drawing No. A-21008, Rev 4-7-94
3 Positive
2 Loop Barriers
24V (40 mA MIN) (Notes 3 & 4)
DC Supply
0.1A 8-40 mA
Fuse
COM
Notes:
Power Supply Ground 1. Vmax must be greater than Vt of the FMRC approved
4-20 mA + barrier combination.
H2 O
Imax must be greater than It of the FMRC approved
Alternate Load Resistor
Location (Note 2) barrier combination.
4-20 mA + Ci plus interconnecting wiring must be less than C0 of the
TEMP FMRC approved barrier combination.
2. Preferred location of 2500 load resistor is for high
CAT 4112 impedence receiver input circuit for less than 250k Ohm
Signal Common Dew Point/ input impedance move load resistor to receiver terminals.
Temperature This adds barrier resistance to transmitter load.
1-5V Receiver Transmitter 3. Install in accordance with manufacturers instructions and
Input Terminals (Note 1) NEC Article 504 and ANSI/ISA RP12.6.
Dew Point 4. Typical connections are shown to barrier unit terminals.
Alternate Load Resistor Maximum fault voltage in any circuit connected to barrier
Location (Note 2) Preferred Load terminals must not exceed 250V RMS or 250VDC.
Resistor Location 5. A Approved transmitters:
(Note 2) 4112 02-D1.d2-C-100 207
to D3H1-f-104 208
Signal Common 60 H3W1 209
1/4 X 1 3/4 Copper Bus Bar B See sheet 2 of this drawing for Stahl barrier system
1-5V Receiver and sheet 3 for MIL barrier system.
for Mounting Barriers. Must 6. Use only NRTL listed dust tight fitting or threaded conduit
Input Terminals Have 2 Earth Ground
Temperature Connections. Bus Bar to for installation in Class II, Division I, Groups E, F, and G.
Ground Resistance 1 Ohm
Maximum.
Intrinsic Safety Entity Paramters:
NONHAZARDOUS LOCATION Vmax = 30 volts
HAZARDOUS LOCATION
Class I, II, III Imax = 360 mA
Division 1 Ci = 0.1uF
Groups A, B, C, D, E, F, G Li = mH
OPTION I
I S Ground
HAZARDOUS LOCATION
NONHAZARDOUS LOCATION
Class I, II, III
Div 1
Groups C, D, E, F, G
12. CE Approvals
Introduction
The following statements covers the subject of CE approvals for the 4112 Dew Point Transmitter.
CE conformity: This product is in conformance with the protection requirements of the following
European Council Directive: 89/336/EEC, the EMC directive. Conformance of this product with any
other “CE Mark” Directive(s) shall not be assumed.
Attention
The emission limits of EN 50081-2 are designed to provide reasonable protection against harmful
interference when this equipment is operated in an industrial environment. Operation of this equipment in a
residential area may cause harmful interference. This equipment generates, uses, and can radiate radio
frequency energy and may cause interference to radio and television reception when the equipment is used
closer than 30 meters to the antenna(e). In special cases, when highly susceptible apparatus is used in close
proximity, the user may have to employ additional mitigating measures to further reduce the
electromagnetic emissions of this equipment.