1 System
1.1 Generals
1) Word definition of ARD
ARD: Automatic Rescue Device
1.2 Configuration
1[kOhm],100W
MCCB
3상 1 12
R1
FILTER
1[kOhm],100W
NOISE
S1
유도
C
Motor
U
12
V
W
T1
1[kOhm],100W 모터
12
DOC-100 DPP-100
PCB (주마이콤)
) PCB (IGBT (IGBT
Driving)
구동)
DPC-100
제어반
PCB
DOR-100
E/L
PCB (I/O) (인버터 제어,직렬 통신)
(INV control, Serial Comm.)
VD-1
VD-2
VD-4
VD-5
제어반
ARD
APC-1
APC-2
APC-3
APC-4
APC-5
APC-6
U U R
1 R U
R
S V V S
T S V
W W T
T W TR2
N
N
FAN SW2(MCCB)
C C C
B+ B- E U V W R S T
SW1(NFB)
ARD
function
E/L CP ARD CP
Serial Comm.
(RS-422)
DOC-PCB DPC- ARD
Operation Speed
MCU
control control
(8bit)
ARD operation & speed PROG.
E/L speed control PROG.
Parallel Comm.
(DPRAM)
2) Function
2) Function
Name Explanation Use voltage
Protects the commercial standard power
C9A input while the rescue operation is AC 110V
proceeding
Supply the battery power for the rescue
C9X DC 24 V
operation
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 6/55
FOD Part Application
Overseas Support Team Date Aug 2005
* External I/O Board (Service tool, communication input, external contact interface)
Pin Connector Function
1 APE Connector (16P) Connection to service tool
2 APK Connector (4P) Connect to sub contact of NFB
3 APC Connector (6P) Connect to communication line of elevator control panel
4 J1 Connector (6P) Connection to J3 connector of ARDP PCB
5 J2 Connector (2P) Connection to SW2
6 J3 Connector (5P) Connection to COM connector of ARDM PCB
7 J4 Connector (6P) Downloading connector of ATmaga162(LCD control)
program
8 PWR (switch) Power switch of ALPK PCB, whenever the service tool is
connected, this switch should be turned off.
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 15/55
FOD Part Application
Overseas Support Team Date Aug 2005
3 System
The ARD controller is consist of operation part, UPS control part, electric charge part and
electric power circuit part.
ARD Controller
Detection of P.F
Detection time: NO
3 secondsÇ?
Finish of Rescue
YES operation
Main power NO
YES is refreshed?
Level zone?
YES
NO
In case the power failure has happened under normal operation, the micro process of ARDM
PCB will detect the condition. If the power failure condition is maintained at least 3 seconds,
The ARD system will start to proceed rescue operation. The micro process of ARDM PCB
generates standard voltage and frequency to supply current power to elevator control panel.
The revived elevator controller by ARD checks the elevator that is under safe condition. If
the car position is level zone, the door is opened only to rescue passengers. Else if the
position is out of level zone, it compares the car and CWT weight. In case the car is heavier
than CWT, the car direction is downward. But if the CWT is heavier than car, the car
direction is upward. As the rescue operation is finished, the elevator control panel transmits
the signal to ARD controller. When the ARD controller receives the signal, it stops UPS
operation. And it displays the status of ARD controller and process of rescue operation until
main normal power is refreshed. As soon as the main normal power is refreshed, the
elevator control is returned to normal operation status.
NO
Power failure?
YES
NO NO
Charge operation Detection time:
possible? 3 secondsÇ?
YES
YES
UPS operation
Displays Charge operation
error
YES
Rescue operation finish?
Charging
NO
operation finish
NO
5 minutes passed?
YES
ARD operation stop
The above flowchart shows about operation of ARD controller. When the main power is
supplied to elevator system again, the ARD controller will start charge operation for battery.
If the power failure happens again, the recharge operation is stopped and mode is change to
rescue operation. As soon as the main normal power is refreshed, the elevator control is
returned to normal operation status.
If battery voltage is under DC192V, the low voltage error is detected, Else if battery voltage is
over DC225V, the high voltage error is detected.
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 22/55
FOD Part Application
Overseas Support Team Date Aug 2005
4 SERVICE TOOL
4.1 Function
-. Display of ARD status
-. Error log trace
TCD display A
ERROR mode
TCD re-display FFFF FFFF
Error clear DDDD
2) Description
-. R1: Displays charge operation mode.
-. R2: Displays the error that has just occurred.
-. R3: For the other signals, key in "FFFF".
Previous mode will be reset by "FFFF".
-. R4: Displays voltage of batteries and charging condition.
(HCC; High Constant-current Charge, LCC; Low Constant-current Charge,
CV; Constant-voltage Charge)
of 2nd row.
5 Trial run
5.1 Preparation
1) To be prepared
-. Perform trial run of ARD system after normally finishing installation of the elevator.
(ARD system may unnecessarily operate, because switching power is frequently
required while installing the elevator.)
-. Pay attention to electric shock.
-. Speed of rescue operation is 10 m/min.
-. ARD system will be activated in case of power failure. Therefore, follow the below
procedure when switching off power.
Commercial
Power
EMI
Motor
power Stack
E/L CP
ARD CP
Battery
C9X Power
Stack
C9A
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 28/55
FOD Part Application
Overseas Support Team Date Aug 2005
After connections of ARD, switching off MCCB in control panel in case that the work is
required on the control panel (elevator side).
If switch on builder's switchboard were turned off, the elevator would be operated by the
power of ARD system (3Φ 380V).
Electric hazard would be exposed around control panel & electric equipment even if main
switch were turned off.
[Special Note]
¾ Switching off MCCB of elevator makes switching off ARD system.
¾ High volts would be still exposed on terminal (R, S, T, U, V, W, B+, B-) even if SW1
(NFB) of ARD controller were turned off.
¾ If any service is required on ARD controller side, do not switch off SW1 (NFB) of ARD
The elevator, which is connected with ARD controller, may have emergency stop.
Switch off MCCB of elevator in order to perform the service of ARD controller.
¾ The trouble on ARD controller has no relation with elevator operation.
¾ If term of rescue operation exceeds 5 minutes, ARD controller stops UPS.
¾ ARD controller stops UPS after finishing rescue operation then ARD system will be at
the rest mode.
* If commercial standard power is not established within 1 minute after stoppage of UPS,
the power of ARD system will be off.
(2) Instruments
* Multi meter (impedance: 1MΩ, Min. volt: 10mV)
* Hook meter (For current)
* Megger tester
* Speed meter
* Analog tester
# All instruments must be certified by the quality engineering authority.
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 29/55
FOD Part Application
Overseas Support Team Date Aug 2005
5.2 Inspection
1) Elevator
* Inspect if all landing doors is closed and locked.
* Inspect if the elevator touches with any equipment in hoistway during operation.
* Inspect if safety line is normal.
* Inspect if the elevator is normally operated.
2) Control panel
* Inspect if control panel is cleanly arranged.
* Inspect if the connection between ARD controller & control panel is correct.
3) Battery
* Inspect if there is any abnormal issue on batteries.
MCCB
Sub
contact
Shield cable
Serial
Commun
ication
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 31/55
FOD Part Application
Overseas Support Team Date Aug 2005
3) Measurement
Perform megger test and inspect if measured value is within the standard
4) Fuses
Inspect if the capacity of fuses on ARDP PCB is correct.
(F1, F2: 250V 1A, F3: 250V 3A)
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 33/55
FOD Part Application
Overseas Support Team Date Aug 2005
5.5 Adjustment
1) Adjustment for detecting battery voltage
Adjust VR1 resistor on ARDP PCB so that the voltage of batteries becomes the value
on annunciator. (Allowance: ±2V)
Power on - Builder
MCCB on - CP
SW1 (NFB) on - ARD
---CHARGE MODE---
The initial screen display?
ERRO-NO:
on service tool
MOD-NO:
VALUE: 207Vb <HCC
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 35/55
FOD Part Application
Overseas Support Team Date Aug 2005
Commercial
Power failure
standard power ARD power
Power condition
of E/L controller
Normal operation
E/L speed
Rescue operation
1) Control function (When the E/L controller goes under rescue operation mode)
2) Operation function
6 Regular Inspection
7 Part List
7.1 ARD controller
1) Picture
Part ARD-022, 030
ARD System Ctrl. No. OST-PA-12-0
Page 40/55
FOD Part Application
Overseas Support Team Date Aug 2005
* The trouble code in this document can apply to ARD of DI Elevator (60~150m/min) in
common
* The TCD number is classified from 10~70.
* In case a TCD has occurs, the operating condition of ARD is controlled and managed as
followings.
TCD = 25, 50 : Unable to operate UPS & charge
TCD = 10, 16, 21,23, 30,34,40,45,70 : Unable to operate UPS
TCD = 51, 60 : Unable to operate charge