Professional Documents
Culture Documents
Pump Operation Assessement
Pump Operation Assessement
Note: The following retro-commissioning Review the TAB report, including flow, impeller
information was taken directly from PECI’s size, and motor volt/amp measurements.
functional testing guide (www.peci.org/ftguide/) and
modified for this energy assessment training. Control Accuracy and Stability
Verify proper control sequence and integration
Constant Volume Systems over all components (such as setpoints, start-
The performance of a constant flow water system is up/shut-down procedures, and time delays).
acceptable if it meets the design intent and specified – This includes verification of proper stand-by
operating sequence. In some instances, witnessing pump operation in the case of a lead pump
the flushing and pressure testing of individual coils failure. Temperature control strategies
and/or distribution piping may be required. impact water flow through the system and
pump staging, which can cause system
Actuation and Sequencing instability. Typically, testing entails
Verify proper stroke for control valves to ensure verifying that the proportional integral
that they open and close completely (coil derivative (PID) control loop generates the
valves, isolation valves, etc.). proper control signal based on the setpoint.
– Control valve leakage testing reveals no Testing should also verify the setpoints are
detectable leakage when valve is optimized for the system or recommend
commanded closed. modifications, if necessary.
Verify proper distribution pump staging per the
sequence of operations. Valve leakage tests and tests that are targeted at
– Frequently, water and air temperature reset verifying valve stroke, spring range, and sequencing
strategies are not coordinated; this can result should be conducted with the pumping system
in the unnecessary staging of distribution operating at its peak differential pressure. The
pumps in the on position. Optimizing differential pressure across the valve plug can have a
various reset strategies, during both initial significant impact on the close-off rating and shift
system set up and commissioning, will the operating spring range of the valve. These tests
improve system control and minimize should be performed prior to temporary system
pumping energy. operation to ensure that equipment will not be
damaged during functional testing.
SAVING ENERGY IN COMMERCIAL BUILDINGS | Pump System Assessment Guidelines