Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

SAVING ENERGY IN COMMERCIAL BUILDINGS

Pump System Assessment Guidelines


General Pumping System Assessment Procedure  Verify that three-way control valves modulate
correctly.
1. Get copies of mechanical drawings (determine – This will help to ensure that simultaneous
pumping system specifications). heating and cooling does not occur. For
2. Get copies of pump engineering specification example, a leaky hot water valve on a pre-
sheets (head versus flow rate for various heat or heating coil will add unwanted heat
impeller sizes). to the air stream, which can cause the chilled
3. Fill out pumping system data collection forms water valve to modulate open. This wastes
and sketch out the pump system configuration. heating and cooling energy.

Note: The following retro-commissioning Review the TAB report, including flow, impeller
information was taken directly from PECI’s size, and motor volt/amp measurements.
functional testing guide (www.peci.org/ftguide/) and
modified for this energy assessment training. Control Accuracy and Stability
 Verify proper control sequence and integration
Constant Volume Systems over all components (such as setpoints, start-
The performance of a constant flow water system is up/shut-down procedures, and time delays).
acceptable if it meets the design intent and specified – This includes verification of proper stand-by
operating sequence. In some instances, witnessing pump operation in the case of a lead pump
the flushing and pressure testing of individual coils failure. Temperature control strategies
and/or distribution piping may be required. impact water flow through the system and
pump staging, which can cause system
Actuation and Sequencing instability. Typically, testing entails
 Verify proper stroke for control valves to ensure verifying that the proportional integral
that they open and close completely (coil derivative (PID) control loop generates the
valves, isolation valves, etc.). proper control signal based on the setpoint.
– Control valve leakage testing reveals no Testing should also verify the setpoints are
detectable leakage when valve is optimized for the system or recommend
commanded closed. modifications, if necessary.
 Verify proper distribution pump staging per the
sequence of operations. Valve leakage tests and tests that are targeted at
– Frequently, water and air temperature reset verifying valve stroke, spring range, and sequencing
strategies are not coordinated; this can result should be conducted with the pumping system
in the unnecessary staging of distribution operating at its peak differential pressure. The
pumps in the on position. Optimizing differential pressure across the valve plug can have a
various reset strategies, during both initial significant impact on the close-off rating and shift
system set up and commissioning, will the operating spring range of the valve. These tests
improve system control and minimize should be performed prior to temporary system
pumping energy. operation to ensure that equipment will not be
damaged during functional testing.
SAVING ENERGY IN COMMERCIAL BUILDINGS | Pump System Assessment Guidelines

Test Conditions, Considerations, and Cautions Setpoints and Reset Controls


The following points should be noted to avoid  Verify the system operates and maintains
testing complications: chilled and hot water supply temperature
 Rapid stroking of valves during a test process setpoints and discharge air temperature setpoints
can cause water hammer problems in the piping in all modes including morning warm-up,
systems. occupied mode, and night low-limit mode.
 Consider stroking each valve in stages to  Verify VFD control loops generate the proper
prevent slamming valves open or closed, giving setpoint based on the reset parameters, if
the system time to respond appropriately. applicable. Reset parameters are optimized for
the system.
Functional Testing Field Tips—Variable Flow  Verify the differential pressure reset control
Actuation and Sequencing strategy.
 Verify two-position control valves associated – Frequently, the discharge pressure setpoint
with the respective equipment open fully upon is reset based on dynamic load requirements
start-up and close fully upon shutdown. This is to reduce pump energy even further. Various
typical for water-source heat pumps and water- indicators can be used to signify reduced
cooled process equipment. load on the system, one example being valve
 Verify proper distribution pump staging and position. In this control strategy, the system
variable frequency drive (VFD) control, if pressure setpoint is reset higher or lower in
applicable, per the sequence of operations. order to maintain one chilled water valve at
– Typically, distribution pumps in variable a preset position (95% open, for example).
flow systems utilize a VFD to modulate  Verify proper coordination between individual
pump speed in order to deliver water flow setpoints and reset strategies.
that matches system loads. VFD staging and – Resetting the chilled water supply
modulation control is normally based on temperature warrants close attention.
maintaining a constant differential pressure Without coordination between chilled water
either across the distribution pumps temperature reset and discharge air
themselves or out in the loop. The temperature reset, the air handler may be
differential pressure setpoint is based on the trying to make colder air than is possible
pressure required to provide adequate flow with the chilled water supply temperature.
through the worst case load (for example, This situation will result in distribution
the load with the highest overall pressure pumps operating at full flow even though
drop piping losses and device requirements) there is no load on the system, wasting
at full load. Often, the setpoint (either significant pumping energy.
specified by the design engineer or
estimated by the controls contractor, if not
provided) is set artificially high, wasting
pumping energy for the life of the building.
The actual system pressure setpoint should
be determined during the initial system setup
and commissioning to improve system
control and minimize pumping energy.

NREL/FS-7A20-50131 • June 2011

You might also like