1 Input Data: Hilti PROFIS Engineering 3.0.72

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

Hilti PROFIS Engineering 3.0.

72

www.hilti.com
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-RE 500 V3 + HIS-N B7 3/4
Item number: not available (element) / 2123401 HIT-RE 500 V3
(adhesive)
Effective embedment depth: hef,act = 8.071 in., hnom = 8.071 in.
Material: ASTM A 193 Grade B7
Evaluation Service Report: ESR-3814
Issued I Valid: 3/1/2021 | 1/1/2023
Proof: Design Method ACI 318-19 / Chem
Stand-off installation: eb = 0.000 in. (no stand-off); t = 0.750 in.

Anchor plate :
R lx x ly x t = 20.000 in. x 20.000 in. x 0.750 in.; (Recommended plate thickness: not calculated)

Profile: Round HSS (AISC), HSS10X.625; (L x W x T) = 10.000 in. x 10.000 in. x 0.625 in.
Base material: cracked concrete, 4000, fc' = 4,000 psi; h = 12.000 in., Temp. short/long: 32/32 °F
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: tension: present, shear: present; no supplemental splitting reinforcement present
edge reinforcement: > No. 4 bar

R
- The anchor calculation is based on a rigid anchor plate assumption.

Geometry [in.] & Loading [kip, ft.kip]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

1.1 Design results


Case Description Forces [kip] / Moments [ft.kip] Seismic Max. Util. Anchor [%]
1 Combination 1 N = 110.000; Vx = 0.000; Vy = 12.500; no 680
Mx = 0.00000; My = 0.00000; Mz = 0.00000;

2 Load case/Resulting anchor forces y

5
Anchor reactions [kip]
Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y
3 4
1 22.000 2.500 0.000 2.500
2 22.000 2.500 0.000 2.500 x
3 22.000 2.500 0.000 2.500 Tension
4 22.000 2.500 0.000 2.500
5 22.000 2.500 0.000 2.500
1 2
max. concrete compressive strain: - [‰]
max. concrete compressive stress: - [psi]
resulting tension force in (x/y)=(0.000/0.000): 110.000 [kip]
resulting compression force in (x/y)=(0.000/0.000): 0.000 [kip]

Anchor forces are calculated based on the assumption of a rigid anchor plate.

3 Tension load
Load Nua [kip] Capacity f Nn [kip] Utilization bN = Nua/f Nn Status
Steel Strength* 22.000 18.944 117 not recommended
Bond Strength** 110.000 16.184 680 not recommended
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Failure** 110.000 26.569 415 not recommended

* highest loaded anchor **anchor group (anchors in tension)

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

3.1 Steel Strength

Nsa = ESR value refer to ICC-ES ESR-3814


f Nsa ³ Nua ACI 318-19 Table 17.5.2

Variables
2
Ase,N [in. ] futa [psi]
0.33 120,039

Calculations
Nsa [kip]
29.145

Results
Nsa [kip] f steel f Nsa [kip] Nua [kip]
29.145 0.650 18.944 22.000

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

3.2 Bond Strength

Nag = (AA ) y
Na

Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ACI 318-19 Eq. (17.6.5.1b)
f Nag ³ Nua ACI 318-19 Table 17.5.2
ANa see ACI 318-19, Section 17.6.5.1, Fig. R 17.6.5.1(b)
2
ANa0 = (2 cNa) ACI 318-19 Eq. (17.6.5.1.2a)
t uncr
cNa = 10 da √ 1100
ACI 318-19 Eq. (17.6.5.1.2b)

( )
1
'
y ec,Na = eN £ 1.0 ACI 318-19 Eq. (17.6.5.3.1)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.0 a,min

Na
ACI 318-19 Eq. (17.6.5.4.1b)

= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-19 Eq. (17.6.5.5.1b)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-19 Eq. (17.6.5.2.1)

Variables
t k,c,uncr [psi] da [in.] hef [in.] ca,min [in.] aoverhead t k,c [psi]
2,013 1.090 8.071 6.806 1.000 1,148

ec1,N [in.] ec2,N [in.] cac [in.] la


0.000 0.000 17.175 1.000

Calculations
cNa [in.] ANa [in. ]
2
ANa0 [in. ]
2
y ed,Na
14.679 806.00 861.93 0.839

y ec1,Na y ec2,Na y cp,Na Nba [kip]


1.000 1.000 1.000 31.732

Results
Nag [kip] f bond f Nag [kip] Nua [kip]
24.898 0.650 16.184 110.000

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

3.3 Concrete Breakout Failure

Ncbg = (AA ) y
Nc

Nc0
ec,N y ed,N y c,N y cp,N Nb ACI 318-19 Eq. (17.6.2.1b)
f Ncbg ³ Nua ACI 318-19 Table 17.5.2
ANc see ACI 318-19, Section 17.6.2.1, Fig. R 17.6.2.1(b)
2
ANc0 = 9 hef ACI 318-19 Eq. (17.6.2.1.4)

( )
1
'
y ec,N = 2 eN £ 1.0 ACI 318-19 Eq. (17.6.2.3.1)
1+
3 hef

y ed,N = 0.7 + 0.3 (1.5h


c
) £ 1.0 a,min

ef
ACI 318-19 Eq. (17.6.2.4.1b)

= MAX(
c ) £
c 1.5h a,min ef
y cp,N , 1.0 ACI 318-19 Eq. (17.6.2.6.1b)
c ac ac
1.5
Nb = kc l a √ '
fc hef ACI 318-19 Eq. (17.6.2.2.1)

Variables
hef [in.] ec1,N [in.] ec2,N [in.] ca,min [in.] y c,N
5.333 0.000 0.000 6.806 1.000

'
cac [in.] kc la fc [psi]
17.175 17 1.000 4,000

Calculations
ANc [in. ]
2
ANc0 [in. ]
2
y ec1,N y ec2,N y ed,N y cp,N Nb [kip]
716.92 256.00 1.000 1.000 0.955 1.000 13.243

Results
Ncbg [kip] f concrete f Ncbg [kip] Nua [kip]
35.425 0.750 26.569 110.000

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

4 Shear load
Load Vua [kip] Capacity f Vn [kip] Utilization bV = Vua/f Vn Status
Steel Strength* 2.500 15.054 17 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength controls)** 12.500 34.858 36 OK
Concrete edge failure in direction y+** 12.500 11.592 108 not recommended

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel Strength

Vsa = ESR value refer to ICC-ES ESR-3814


f Vsteel ³ Vua ACI 318-19 Table 17.5.2

Variables
2
Ase,V [in. ] futa [psi]
0.33 120,039

Calculations
Vsa [kip]
25.090

Results
Vsa [kip] f steel f Vsa [kip] Vua [kip]
25.090 0.600 15.054 2.500

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

4.2 Pryout Strength (Bond Strength controls)

Vcpg =kcp [(AA ) y


Na

Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ] ACI 318-19 Eq. (17.7.3.1b)
f Vcpg ³ Vua ACI 318-19 Table 17.5.2
ANa see ACI 318-19, Section 17.6.5.1, Fig. R 17.6.5.1(b)
2
ANa0 = (2 cNa) ACI 318-19 Eq. (17.6.5.1.2a)
t uncr
cNa = 10 da √ 1100
ACI 318-19 Eq. (17.6.5.1.2b)

( )
1
'
y ec,Na = eN £ 1.0 ACI 318-19 Eq. (17.6.5.3.1)
1+
cNa

y ed,Na = 0.7 + 0.3 (cc ) £ 1.0 a,min

Na
ACI 318-19 Eq. (17.6.5.4.1b)

= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-19 Eq. (17.6.5.5.1b)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-19 Eq. (17.6.5.2.1)

Variables
kcp aoverhead t k,c,uncr [psi] da [in.] hef [in.] ca,min [in.] t k,c [psi]
2 1.000 2,013 1.090 8.071 6.806 1,148

ec1,N [in.] ec2,N [in.] cac [in.] la


0.000 0.000 17.175 1.000

Calculations
cNa [in.]
2
ANa [in. ] ANa0 [in. ]
2
y ed,Na
14.679 806.00 861.93 0.839

y ec1,Na y ec2,Na y cp,Na Nba [kip]


1.000 1.000 1.000 31.732

Results
Vcpg [kip] f concrete f Vcpg [kip] Vua [kip]
49.797 0.700 34.858 12.500

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

4.3 Concrete edge failure in direction y+

Vcb = (AA ) y
Vc

Vc0
ed,V y c,V y h,V y parallel,V Vb ACI 318-19 Eq. (17.7.2.1a)
f Vcb ³ Vua ACI 318-19 Table 17.5.2
AVc see ACI 318-19, Section 17.7.2.1, Fig. R 17.7.2.1(b)
2
AVc0 = 4.5 ca1 ACI 318-19 Eq. (17.7.2.1.3)

y ed,V = 0.7 + 0.3


ca2
1.5ca1 ( ) £ 1.0 ACI 318-19 Eq. (17.7.2.4.1b)

y h,V = √1.5ca1
ha ³
1.0 ACI 318-19 Eq. (17.7.2.6.1)
1.5
Vb =9la √ '
fc ca1 ACI 318-19 Eq. (17.7.2.2.1b)

Variables
ca1 [in.] ca2 [in.] y c,V ha [in.] le [in.]
8.000 13.463 1.200 12.000 8.071

'
la da [in.] fc [psi] y parallel,V
1.000 1.090 4,000 1.000

Calculations
AVc [in. ]
2
AVc0 [in. ]
2
y ed,V y h,V Vb [kip]
288.00 288.00 1.000 1.000 12.880

Results
Vcb [kip] f concrete f Vcb [kip] Vua [kip]
15.456 0.750 11.592 12.500

5 Combined tension and shear loads, per ACI 318-19 section 17.8
bN bV z Utilization bN,V [%] Status
6.797 1.078 1.000 657 not recommended

bNV = (bN + bV) / 1.2 <= 1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

6 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2018, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering calculates
the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions explained above. The
proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be checked for
agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the potential
concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or where pullout
or pryout strength governs.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-19,
Section 26.7.

Fastening does not meet the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

9
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 10
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

7 Installation data
Anchor type and diameter: HIT-RE 500 V3 + HIS-N B7 3/4
Profile: Round HSS (AISC), HSS10X.625; (L x W x T) = 10.000 in. x 10.000 in. Item number: not available (element) / 2123401 HIT-RE
x 0.625 in. 500 V3 (adhesive)
Hole diameter in the fixture: df = 0.812 in. Maximum installation torque: 0.10031 ft.kip
Plate thickness (input): 0.750 in. Hole diameter in the base material: 1.250 in.
Recommended plate thickness: not calculated Hole depth in the base material: 8.071 in.
Drilling method: Hammer drilled Minimum thickness of the base material: 10.600 in.
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required

3/4 Hilti HIS-N Carbon steel anchor rod with Hilti HIT-RE 500 V3

7.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required accessories • Dispenser including cassette and mixer
• Properly sized drill bit to blow from the bottom of the hole • Torque wrench
• Proper diameter wire brush

y
10.000 10.000
3.000

5
10.000
4.837

3 4

x
7.826

10.000

1 2
4.337

3.343 2.543 4.114 4.114 2.543 3.343

Coordinates Anchor [in.]


Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -4.114 -5.663 10.543 17.577 8.000 20.663 4 6.657 2.163 21.314 6.806 15.826 12.837
2 4.114 -5.663 18.771 9.349 8.000 20.663 5 0.000 7.000 14.657 13.463 20.663 8.000
3 -6.657 2.163 8.000 20.120 15.826 12.837

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

10
Hilti PROFIS Engineering 3.0.72

www.hilti.com
Company: Page: 11
Address: Specifier:
Phone I Fax: | E-Mail:
Design: CIR-5 Date: 9/7/2021
Fastening point:

8 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each
case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data
or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2021 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

11