Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

Static converters,

dynamic
performance
GERHARD LINHOFER, PHILIPPE MAIBACH, NIKLAUS UMBRICHT – There are
Providing railway grids significant differences between railway electrification and national grids.
with the right frequency One of these is that AC-electrified railways generally use only a single
phase, whereas domestic grids generate, transmit and distribute
three-phase power. Furthermore, frequencies are in many cases different
from those of the national grid. Even when the same frequency is used,
this is not necessarily synchronized. Nowadays, large frequency
converters based entirely on power electronics are used to transfer
electricity between national and railway grids. ABB has installed
numerous 15 MW frequency converters, for example the railway power
supply to the new Swiss Lötschberg tunnel. Today, even larger power
classes are implemented, in particular the 413 MW station being built for
E.ON in Germany – the most powerful static converter so far.

42 ABB review 2|10


1 Single line diagram of a converter station

15 MW Standard converter ABB


Typical single line diagram

20 kV, 50 Hz Container
Network side 16.7 Hz
50 Hz 2 x 3-ph 4 x single phase transformer
transformer 3-level bridges 3-level bridges
3 3 1 110 kV, 16.7 Hz
Rail side

Grounding UZK- High- 33 Hz


measuring Limiter pass filter
filter

Cooling unit with fin fan 16.7 Hz filter

Other alternatives:
110 kV, 50 HzGrid connection
15 kV, 16.7 Hz Rail direct connection

mon mechanical shaft. In a more recent


development, frequency converters The compact
based on power electronics became
design led to the

E
lectric railways have a huge suitable for this purpose. In fact, the total
demand for power. In fact many
operate their own high-voltage
power of such static frequency convert-
ers taken into operation over the past 15
development of
power grids and some even years is about 1,000 MW. Approximately standardized
operate dedicated generating plants. two-thirds of these were supplied by
Few railways, however, are totally auton- ABB. Converters totaling more than converter mod-
omous: Power must be exchanged with 800 MW are presently being built or have
the national grids. Today, three main been ordered.
ules and permit-
power systems are used for electric ted converters of
mainline railways. From the point of view of the converter
– In countries or regions where railway (be it rotary or static), the interconnection various power
lines were electrified relatively recent- of a three-phase and a single-phase grid
ly, the catenaries are often fed from is more demanding than the intercon-
classes to be
the public grid at a frequency of 50 Hz
(or 60 Hz), mostly at a line voltage of
nection of two three-phase grids. One
principle reason for this is the fact that
built.
25 kV. the power in the single-phase grid oscil-
– In some countries, where railways lates at twice the grid frequency, whereas
were electrified much earlier, direct in the three-phase grid it is basically con-
current (DC) was chosen (typical line stant. In the case of rotary converters,
voltages are 1.5 and 3 kV). the ensuing torque and power fluctua-
– Other countries use single-phase tions are absorbed and damped by the
alternating current with a low supply rotating masses. The resulting vibrations
frequency. These include the East must however be absorbed by their me-
Coast of the United States, using chanical anchoring and foundations. This
25 Hz, and Norway, Sweden, Ger- leads to additional complexity in the de-
many, Austria and Switzerland, using sign of both the machine and its founda-
16.7 (formerly 16 2/3) Hz. tions.

In the past, rotary converters were used In the case of static frequency convert-
to exchange power between single- ers, the oscillation is filtered using a ca-
phase railway grids and three-phase na- pacitor bank and an inductance that are
tional grids. They basically consisted of tuned to twice the operating frequency
two electrical machines with a different of the railway grid.
number of pole pairs arranged on a com-

Static converters, dynamic performance 43


2 Converter container

Components of the converter container


– Space cooling system
– Converter and voltage limiter modules with
control electronics close to the converter
– DC-link bus bars and capacitors behind
the converter modules
– Bus bar feeders to the transformers
– Power distribution for auxiliary power and
instrumentation and control system
(control, measurement and protection)
– Uninterruptible power supply for the
instrumentation and control system
– Local operation using HMI and event
printer

Another challenge lies in the fact that the to the development of standardized con- 50 Hz converter
static converter not only has to act as a verter modules and permitted converters This converter consists of two standard
voltage and reactive power source, but of various power classes to be built. To- three-phase, three-level units. Two phas-
must also be able to handle – without in- day, more than twenty converters in the es are combined in one stack to form a
terruption – the transition from intercon- 15 to 20 MW range are in operation and double-phase module. The converter is
nected system operation to island opera- performing to the customers’ fullest sat- realized in a real 12-pulse configuration.
tion in case of disturbances in the grid. isfaction. Hence, only 12-pulse characteristic har-
Furthermore, it must be capable of act- monics (n = 12k ± 1; k = 1, 2, 3, 4 . . .) are
ing as the sole power supply to an iso- 15–20 MW: converter station for the generated.
lated section of railway, and be able to Lötschberg rail tunnel
subsequently resynchronize with the rest One of these deliveries was the Wimmis 16.7 Hz converter
of the railway grid after the disturbance converter station for the new Lötschberg This converter consists of four standard
has been cleared. rail tunnel (Switzerland) 1, through which two-phase, three-level units. Two phases
trains are able to operate at 200 km/h. In are combined in one stack assembly to
Long tradition of static converters 2005, ABB supplied four converter units form a double-phase module. The
ABB can draw on a long history of static for this railway. The customer was the 16.7 Hz converter is implemented in an
converter technology. The first railway Bernese Power Utility (BKW), which was eight-step configuration. The converter
at the time respon- output voltage levels are summed by
sible for providing means of series connection of the line-
The static converter not only electrical power to side transformer windings of the four
the railway. Each offset-pulsed three-level H-bridges.
has to act as a voltage and of the four con-

reactive power source, but verter blocks, with


a power of 20 MW,
Voltage limiter
Should the DC link voltage exceed an
must also be able to handle first converts the upper threshold, it is discharged via a re-
three-phase sup- sistor until a lower threshold is reached.
the transition from intercon- ply from the 50 Hz The voltage limiter control works inde-
network into DC pendently of the control system for the
nected system operation to (direct current). converter on the two-phase AC (railway-
island operation in case of a The energy is brief- side) and the three-phase AC (mains-
ly stored in a DC side). This ensures that the DC link volt-
disturbance. link before being age remains within the defined range at
changed by an in- all times.
power supply converters with powerful verter into a single-phase, alternating
turn-off semiconductors in the form of voltage with a frequency of 16.7 Hz. DC link
GTOs (gate turn-off thyristors) were tak- All double-phase modules of the con-
en into operation in Switzerland in 1994. The single line diagram of a complete verter are connected to each other on
Since then a new semiconductor ele- converter station such as the one in- the DC side by a common bus bar. This
ment, the integrated gate-commutated stalled for the Lötschberg tunnel in Swit- carries the individual converter module
thyristor (IGCT), was developed that fea- zerland is shown in ➔ 1. It features the connections for the directly coupled DC
tures a much more advanced switching following components:
capability, lower losses, and a low-in-
Footnote
ductance gate unit as an integrated 1 See also “Switzerland by rail” on page 31 of this
“component.” The compact design led edition of ABB Review.

44 ABB review 2|10


Supplied in a
weatherproof
container, the
converter and
the associated
control system
are fully wired
and tested.

link capacitors, the DC link filter banks 16.7 Hz transformer Line filter
and voltage measurements. The transformer of the 16.7 Hz converter On the 16.7 Hz side, a filter is used to
is used to add up the four partial voltag- reduce the very low harmonic distortion
The DC link forms the connection be- es to a nearly sinusoidal single-phase caused by the converter to even lower
tween the 50 Hz and 16.7 Hz converters. voltage with a rated frequency of 16.7 Hz. values. On the 50 Hz side, this is also re-
It consists of the following main compo- The transformer consists of four single- quired in some cases.
nents: phase units. The rectangular partial volt-
– Directly coupled capacitor bank as ages are generated from a DC voltage Remote control
energy storage In the case of the static converters at the
– 33.4 Hz filter to absorb the power Swiss Lötschberg project, the whole
fluctuation from the railway grid The world’s larg- system is remotely controlled by an ABB
– High-pass filter to absorb the higher system-control computer, known as
frequency harmonics from the railway est rail converter ALR 2, which captures and analyzes the
grid, in particular the distinct third and
fifth harmonics of the railway grid
station is now data from the four 20 MW converters and
the two rotary converters via standard-
under construc- ized interfaces. The ALR continually cal-
Converter container culates the optimum use of the available
Supplied in a weatherproof container, the tion in Datteln, production units (static and rotary con-
converter and the associated control verters) on the basis of the power de-
system are fully wired and tested. The
North Rhine West- mand in the railway network or based on
cooling system is located in a separate falia, Germany. manual settings. Thus, the necessary
container. Both containers are mounted power reserve can be connected to or
onto a common support base. A cross- disconnected from the network by the
sectional view of the converter container source (DC link) with the help of four sin- control computer within a matter of sec-
is shown in ➔ 2. gle-phase IGCT converter bridges using onds.
the pulse-width modulation method and
50 Hz transformer are fed to the four valve-side windings All control, regulation and safety func-
The transformer of the 50 Hz converter of the transformer. The adding up and tions are equipped with the proven, fully
feeds the two IGCT-based three-phase adaptation to the railway grid voltage digital power-electronic control system 3
bridges. A three-phase transformer con- occurs in the high-voltage winding. A fil-
sists either of a three-limb core in dou- ter is connected to the series-connected Footnotes
ble-tier design with intermediate yoke or tertiary windings or to the railway grid. 2 ALR is an abbreviation for Anlageleitrechner
(system control computer).
of two three-limb cores contained in one
3 On earlier installations: PSR (Programmierbarer
tank. Schneller Rechner), on current installations:
AC 800 PEC.

Static converters, dynamic performance 45


3 The Wimmis converter station for the new The two × 30 MW converter station in Timelkam, Austria
Lötschberg rail tunnel

from ABB. This system is designed for tions. Two or more 30 MW units can be
The ALR continu- use in precise and very fast servo loops combined in parallel to achieve higher
for converter/inverter systems. The op- power ratings per station.
ally calculates the erator workstations of the ABB Mi-

optimum use of croSCADA power control system in the


central control room guarantee the reli-
30 MW: converter station Timelkam
At the end of 2007, the Austrian Railway
the available pro- able display of the measured values and System ÖBB ordered a new rail convert-
calculations as well as the operation of er station for installation near the town of
duction units the supervisory circuits and sequences Timelkam in the province of Upper Aus-
of all parts of the system. Hot standby tria. The station comprises two indepen-
(static and rotary operation of the supervisory power con- dent 30 MW converter stations, which
converters) on trol system components (ALR and oper- are fed from the national grid at 50 Hz
ator workstations) guarantees very high / 110 kV and convert this to 16.7 Hz
the basis of the availability of the system. / 110 kV. A total of 60 MW of electric
power is thus available for the railway
power demand The installation is shown in ➔ 3. The grid with no transportation losses thanks
in the railway 50 Hz transformer can be seen on the
left-hand side, including the 50 Hz filter
to its proximity to the power generation
facility. The first 30 MW converter went
network or of circuit above the transformer (mounted into commercial operation in July
on a portal). The single phase 16.7 Hz 2009 ➔ 4.
manual settings. transformer is on the right-hand side and
the converter container is in the middle 413 MW: Datteln converter station
between the transformers. The world’s largest rail converter station
is now under construction in Datteln,
Increase of unit power to 30 MW North Rhine Westfalia, Germany. The
Due to the modular design, other power station was ordered by the German pow-
classes can be implemented very easily er supplier E.ON in 2007 and will provide
(in steps of 15 MW). The additional con- a power rating of 413 MW. It will replace
verter modules are connected in parallel. existing 16.7 Hz generators of the power
This converter generation sets new stan- plants Datteln 1–3, which have reached
dards in terms of performance, footprint the end of their economic and technical
and short erection and commissioning lifespans. The converter station will re-
times. Positive feedback shows that ceive power at 50 Hz from the new near-
ABB’s standardized railway converter is by Datteln 4 power station and feed
well suited to meet customer needs. power at 16.7 Hz into the 110 kV network
of the German Railways (DB). The Dat-
Following the successful introduction of teln node is one of the most important
the 15–20 MW converters, customers “supply points” of DB’s grid. A very high
sought a further increase of unit power. availability is therefore required of the
ABB thus developed another standard converter station. ABB is responsible for
frequency converter for 30 MW with op- the entire engineering of this project, ie,
tional overload capability, depending on the design of the converter system,
application and environmental condi- specification of all the components and

46 ABB review 2|10


4 30 MW converter station 5 One of the four converter units (103 MW)

16.7 Hz transformer Cooling unit


380 kV/50 Hz
Control transformer
30 MW Converter unit
container 50 Hz transformer

Control/cooling Heat exchangers


container
33 Hz filter reactors
33 Hz inductor 2 x 55 kV/16.7 Hz
Heat exchargers transformer
4 x 30 MW converter containers

development of control and protection flexible response to various power re-


software. Since it is a turnkey project, in- quirements. In coming years there will be
stallation and commissioning is also part an increased demand for 15 MW con-
of the project scope. verter units as many rotary converters
reach the end of their lifespan. ABB is
The scope of supply for ABB includes committed to following up on its recent
four independent converter stations each successes by further advancing this
with a rated power of 103 MW, obtained technology.
from four standard 30 MW converters.
The built-in overload capability allows
the customer to still receive the nominal
power of 413 MW even if one of the four
converter stations is not in service. Each Gerhard Linhofer
converter unit has the following main Philippe Maibach
components: Niklaus Umbricht
– One converter transformer on the ABB Automation Products
50 Hz side Turgi, Switzerland
– Four converter containers including gerhard.o.linhofer@ch.abb.com
intermediate circuit filters philippe.maibach@ch.abb.com
– One control container niklaus.umbricht@ch.abb.com
– One cooling container (housing the
cooling system)
– Four water/air heat exchangers References
– Two series connected converter [1] Gaupp, O., Linhofer, G., Lochner, G., Zanini, P.
Powerful static frequency converters for
transformers on the 16.7 Hz railway transalpine rail routes. ABB Review 5/1995,
side 4–10.
[2] Lönard, D., Northe, J., Wensky, D. Statische
Apart from the technical challenge pre- Bahnstromrichter – Systemübersicht aus-
geführter Anlagen. Elektrische Bahnen 6/1995,
sented by this major project, logistics 179–190.
and good planning are essential to en- [3] Mathis, P. Statischer Umrichter Giubiasco der
able the equipment to be delivered on Schweizerischen Bundesbahnen. Elektrische
time. The long contract duration (com- Bahnen 6/1995, 194–200.
[4] Steimer, P., Grüning, H., Werninger, J., Dähler,
pletion is scheduled for 2011) accompa- P., Linhofer, G., Boeck, R. Series connection of
nied by a rigid timetable is a distinctive GTO thyristors for high-power static frequency
feature. This project may also pioneer converters. ABB Review 5/1996, 14–20.
further applications: Four converter [5] Steimer, P., Grüning, H.P., Werninger, J.,
Carroll, E., Klaka, S., Linder, S. IGCT – a new,
blocks with 103 MW each set a new
emerging technology for high-power, low-cost
standard in terms of power for static fre- inverters. ABB Review 5/1998, 34–42.
quency converters ➔ 5. [6] Meyer, M., Thoma, M. Netzkompatibilitätsstudie
und -messungen für die Umrichteranlage Wim-
mis. Elektrische Bahnen 12/2006, 567–574.
Outlook
[7] Jampen, U., Thoma, M. Statische Frequen-
ABB is market leader for this type of sys- zumrichteranlage Wimmis. Elektrische Bahnen
tem. The modular approach allows a 12/2006, 576–583.

Static converters, dynamic performance 47

You might also like