M2Seu2: Wu=1.2 (1.50) +1.6 (3.25) =7 K Ft Mu= Wul Wa=1.50+ 3.25=4.75 K Ft M Mn Ω Wa=4.75+0.076=4.83 K Ft Ma= Mn Ω
M2Seu2: Wu=1.2 (1.50) +1.6 (3.25) =7 K Ft Mu= Wul Wa=1.50+ 3.25=4.75 K Ft M Mn Ω Wa=4.75+0.076=4.83 K Ft Ma= Mn Ω
CE134P-2/A4
Engr. Rolando Quitalig
M2SEU2
Using both LFRD and ASD, select the most economical sections, with Fy = 50 ksi,
unless otherwise specified, and assuming full lateral bracing for the compression
flanges. Working or service loads are given for each case, and beam weights are not
included.
1.
LRFD ASD
k k
Wu=1.2 ( 1.50 )+ 1.6 ( 3.25 )=7 Wa=1.50+ 3.25=4.75
ft ft
2 2 2
Wu L 7 ( 28 ) 4.75 ( 28 )
Mu= = =686 ft−k M a= =465.5 ft−k
8 8 8
From AISC Table 3-2 From AISC Table 3-2
W 24 x 76 , ∅ Mn=750 ft−k Mn
W 24 x 76 , =499 ft−k
k Ω
Wu=7+1.2 ( 0.076 ) =7.09
ft k
2 Wa=4.75+0.076=4.83
7.09 ( 28 ) ft
Mu= =694.9 ft−k ≤ ∅ Mn
8 4.83 ( 28 )2 Mn
Ma= =472.9 ft −k ≤
Use W24 x 76 8 Ω
Use W24 x 76
2.
LRFD ASD
k k
Wu=1.2 ( 1.0 )+ 1.6 (1.5 )=3.6 Wa=1.0+ 1.5=2.5
ft ft
Pu=1.2 ( 1.6 )=19.2 K Pa=12k
2
3.6 (20) 19.2(20) 2.5 ( 20 )2 12 ( 20 )
Mu= + =276 k Ma= + =185 I k
8 4 8 4
From AISC Table 3-2 From AISC Table 3-2
W 18 x 40 , ∅ Mn=294 K Mn
W 18 x 40 , =196 I k
k Ω
Wu=1.2(1.04)+1.6 ( 1.5 )=3.65
ft k
2 Wa=1.04 +1.5=2.54
3.65 ( 20 ) 19.2 ( 20 ) ft
Mu= + =278.4 k ≤ ∅ Mn=294 k
8 4 2.54 ( 20 )2 12 ( 20 ) Mn
Ma= + =187 I k ≤ =196I k
Use W18 x 40 8 4 Ω
Use W18 x 40
3.
LRFD ASD
Wu=self weight only Wa=self weight only
Pu=1.2 ( 12 )+ 1.6(20)=46.4 K Pa=12+20=32 k
Mu=Pu a=46.4 ( 8 ) =371.2 ft−k Ma=32 ( 8 )=256 ft−k
From AISC Table 3-2 From AISC Table 3-2
W 21 x 48 , ∅ Mn=398 ft−k Mn
W 21 x 48 , =265 ft −k
k Ω
Wu=1.2(0.048)=0.058 k
ft Wu=0.048
0.058 ( 24 ) 2 ft
Mu=46.4 (8)+ =375.4 I k ≤ ∅ Mn=398I k 0.048 ( 24 )2 Mn
8 Ma=32(8)+ =259.5I k ≤ =265I k
Use W21x 48 8 Ω
Use W21 x 48
4.
LRFD ASD
k k
Wu=1.2 ( 1.5 )+ 1.6 (1.5 )=4.2 Wa=1.5+ 1.5=3.0
ft ft
Pu=1.2(20)=24 k Pa=20 k
Mu=600.0 ft −k Ma=444.9 ft−k
W 24 x 68 , ∅ Mn=664 ft−k Mn
W 24 x 76 , =499 ft−k
k Ω
Wu=1.2 ( 1.568 )+ 1.6(1.5)=4.282
ft k
Wa=1.576+ 1.5=3.08
Mu=609.1 ft−k ≤ ∅ Mn=664 ft −k ft
Use W24x 68 Mn
Ma=453.3 ft−k ≤ =499 ft−k
Ω
Use W24 x 68
5. The accompanying figure shows the arrangement of beams and girders that are
used to support a 5 in. reinforced concrete floor for a small industrial building.
Design the beams and girders assuming that they are simply supported. Assume
full lateral support of the compression flange and a live load of 80 psf. Concrete
weight is 150 lb/ft3.
a. Design of Beams
Neglect self-weight of beam - check after selection
5 500lbs
Concrete Slab ¿ ( 150 ) (8) ¿ =W DL
12 ft
Live Load = 80(8) lbs
¿ 640 =W ¿
ft
LRFD ASD
k k
Wu=1.2 ( 0.50 ) +1.6 ( 0.64 ) =1.62 Wa=0.50+0.64=1.14
ft ft
1.62 ( 30 )2 1.14 ( 30 )2
Mu= =182.7 ft −k Ma= =128.3 ft−k
8 8
From AISC Table 3-2 From AISC Table 3-2
W 16 x 31 , ∅ Mn=203 ft−k Mn
W 16 x 31 , =135 ft−k
k Ω
Wu=1.2(0.53)+1.6 ( 0.64 )=1.66
ft k
2 Wu=0.53+0.64=1.17
1.66 ( 30 ) ft
Mu= =186.9 ft−k ≤ ∅ Mn=203 ft−k 2
8 1.17 ( 30 ) Mn
Ma= =131.7 ft−k ≤ =135 ft −k
Beam – W16 x 31 8 Ω
Beam – W16 x 31
b. Design of Girders
LFRD ASD
30 30
Pu=1.66 ( )(2)=49.84 k
2
Pa=1.17 ( ) 2
( 2 ) =35.13 k
Mu=49.84 ( 8 )=398.7 ft−k Ma=35.13 ( 8 )=281.0 ft−k
W 21 x 50 , ∅ Mn=413 ft−k Mn
k W 21 x 55 , =314 ft −k
Wu=1.2 ( 0.050 )=0.060 Ω
ft k
2 Wa=0.055
0.06 ( 24 )
Mu= + 49.84 ( 8 ) =403.0 ft−k ≤ ∅ Mn=413 ft−kft 2
8 0.055 ( 24 ) Mn
Girder – W21x 50 Ma= +35.13 ( 8 ) =285 ft−k ≤ =314 ft−k
8 Ω
Girder - W21 x 55
LFRD ASD
W18 X 55 ∅ M p=420 I k Mp I
W18 X 55 =279 k
Zone 2 L p=5.90 I Lv=17.6 I Ω
BF=13.8 Lb =15I Zone 2 L p=5.90 I Lv=17.6 I
∅ Mn=1.14 [ 420−13.8 ( 15−5.9 ) ] ≤ 420 BF=13.8 Lb =15I
∅ Mn=335.6 ft−k Mn
=1.14 [ 279−9.15 ( 15−5.9 ) ] ≤ 279
Wu L2 Ω
Mu=Pu a +
( ) ≤ ∅ Mn
8
1.2 ( 0.055 ) Mn
Pu (5 )+ ( 15 )2=335.6 =223.1 ft−k
8 Ω
Pu=66.75 kips Wa L2 M n
66.75 Ma=Pa+ ≤
P¿ = =41.7 K 8 Ω
1.6 ( 0.055 )
Pu (5 )+ (15 )2=223.1
8
P¿ =44.3 kips
( 12 )( 15 θ ) + Pu(15 θ)
Span1
{M u 4 θ=( 30 W u )
( 12 ) ( 20 θ )
Span2
{ M u 4 θ=( 40 W u )
Mu=100 W u =(100)(6.0)
Mu=600 ft−k ( controls )
( 12 ) ( 17.58 θ )
Span3
{ M u (3.414 θ)=( 30 W u )
Mu=77.24 W u=(77.24)( 6.0)
Mu=463.4 ft−k
Use W 21 X 68 ( AISC Table 3−2 ) . ∅b M p=600 ft −k =M u=600 ft −k
b. Analyzing beam for service loads
4k
w a=1.0+3.0=
ft
Pa=15+ 20=35 k
Maximum negative moment for design
¿ ( 0.9 ) (−505 )=−454.5 ft −k ( controls )
Maximum positive moment for design
1 505+505
¿+295+ ( )( 10 2 ) =+345.5 ft−k
Mp
Use W 24 X 76 ( AISC Table 3−2 ) . =499 ft−k > M a =454.5 ft−k
Ω