Ieee The And: An American National Standard

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 216

ANSI/IEEE

Std 493-1980

An American National Standard


IEEE Recommended Practice for the
Design of Reliable Industrial and
Commercial Power Systems

Sponsor
Power System Technologies Committee
of the
IEEE Industry Applications Society

Approved December 20,1979


IEEE Standards Board

Approved June 28,1982


American National Standards Institute
Fourth Printing
March 1988

ISBN 0-47 1-0926 1-4


Library of Congress Catalog Number 80-83819

Copyright 1980 by

The Institute of Electrical and Electronics Engineers, Inc

No p a r t of this publication m a y be reproduced in any form,


in an electronic retrieval system or otherwise,
without the prior written permission of the publisher.
Approved December 20, 1979
IEEE Standards Board

Joseph L. Koepfinger, Chairman Irvin N. Howell, Jr., Vice Chairman


Ivan G. Easton, Secretary
G.Y.R. Allen Harold S. Goldberg J.E. May
William E. Andrus Richard J . Gowen Donald T. Michael*
C. N. Berglund H. Mark Grove R. L. Pritchard
Edward Chellotti Loering M. Johnson F. Rosa
Edward J. Cohen Irving Kolodny Ralph M. Showers
Warren H. Cook W. R. Kruesi J. W. Skooglund
R. 0. Duncan Leon Levy W. E. Vannah
J a y Forster B. W. Whittington

*Member emeritus
IEEE Standards documents are developed within the Technical Com-
mittees of the IEEE Societies and the Standards Coordinating Commit-
tees of the IEEE Standards Board. Members of the committees serve
voluntarily and without compensation. They are not necessarily mem-
bers of the Institute. The standards developed within IEEE represent
a consensus of the broad expertise on the subject within the Institute
as well as those activities outside of IEEE which have expressed an in-
terest in participating in the development of the standard.
Use of an IEEE Standard is wholly voluntary. The existence of an
IEEE Standard does not imply that there are no other ways to pro-
duce, test, measure, purchase, market, or provide other goods and ser-
vices related to the scope of the IEEE Standard. Furthermore, the view-
point expressed a t the time a standard is approved and issued is subject
to change brought about through developments in the state of the art
and comments received from users of the standard. Every IEEE Stan-
dard is subjected to review at least once every five years for revision
or reaffirmation. When a document is more than five years old, and has
not been reaffirmed, it is reasonable t o conclude that its contents,
although still of some value, d o not wholly reflect the present state of
the art. Users are cautioned to check to determine that they have the
latest edition of any IEEE Standard.
Comments for revision of IEEE Standards are welcome from any
interested party, regardless of membership affiliation with IEEE. Sug-
gestions for changes in documents should be in the form of a proposed
change of text, together with appropriate supporting comments.
Interpretations: Occasionally questions may arise regarding the mean-
ing of portions of standards as they relate to specific applications. When
the need for interpretations is brought to the attention of IEEE, the
Institute will initiate action to prepare appropriate responses. Since
IEEE Standards represent a consensus of all concerned interests, it is
important to ensure that any interpretation has also received the con-
currence of a balance of interests. For this reason IEEE and the mem-
bers of its technical committees are not able to provide an instant re-
sponse to interpretation requests except in those cases where the matter
has previously received formal consideration.
Comments on standards and requests for interpretations should be ad-
dressed to:
Secretary, IEEE Standards Board
345 East 47th Street
New York, NY 10017
USA
Foreword

(This Foreword is not a part of IEEE Std 493-1980, IEEE Recommended Practice for the Design of Re-
liable Industrial and Commercial Power Systems.)

The design of reliable industrial and commercial power systems is of considerable


interest to many people. Prior to 1962 a qualitative viewpoint was taken when at-
tempting to achieve this objective. The need for a quantitative approach was first
recognized in the early 1960s when a small group of pioneers led by W.H.Dickinson
organized a n extensive AIEE survey of the reliability of electric equipment in indus-
trial plants. The survey of AIEE taken in 1962 was followed by several IEEE relia-
bility surveys which were published during 1973 through 1979.
Tutorial reliability sessions on the design of industrial and commercial power sys-
tems were conducted at the 1971 and 1976 IEEE Industry and Commercial Power
Systems Technical Conferences. A need has existed for some time that the pertinent
tutorial reliability material, equipment reliability data, and cost of power outage
data be assembled into a single book that could be useful in the design of reliable in-
dustrial and commercial power systems.
Comments are invited on this recommended practice and also suggestions for addi-
tional material. These comments and suggestions should be addressed to:
Secretary
IEEE Standards Board
The Institute of Electrical and Electronics Engineers, Inc
345 E. 47th St
New York, NY 10017
This recommended practice was prepared by a working group of the Power Sys-
tems Reliability Subcommittee, Power Systems Support Committee, Industrial
Power Systems Department of the IEEE Industry Application Society.
At the time it recommended these practices the working group of the Power Sys-
tem Technologies Committee had the following members and contributors:

C.R. Heising, Chairman


C. E. Becker A. D. Patton
P. E. Gannon C. Singh
D. W. McWilliams S. J. Wells

Other contributors to the nine IEEE Committee Reports on equipment reliability


in the Appendixes are:
J. W. Aquilino D. Kilpatrick
M. F. Chamow R. T. Kulvicki
W. H. Dickinson P. O’Donnell
B. G. Douglas R. W. Parisian
I. Harley W. J. Pearcet
M. D. Harris W. L. Stebbins
H.T. Wane
1. Introduction

1.1 Objectives and Scope. The objective ysis by probability methods


of this book is t o present the funda- (2) Fundamentals of power system
mentals of reliability analysis as it ap- reliability evaluation
plies t o the planning and design of (3) Economic evaluation of reliability
industrial and commercial electric power (4) Cost of power outage data
distribution systems. The text material (5) Equipment reliability data
is primarily directed toward consulting (6) Examples of reliability analysis
plant electrical engineers. In addition, discussion and informa-
The design of reliable industrial and tion are provided on:
commercial power distribution systems (1) Emergency and standby power
is important because of the high costs (2) Electrical preventive maintenance
associated with power outages. There is (3) Evaluating and improving relia-
a need to be able t o consider the cost of bility of existing plant
power outages when making design de- A quantitative reliability analysis in-
cisions for new power distribution sys- cludes making a disciplined evaluation of
tems and to be able t o make quantitative alternate power distribution system de-
cost versus reliability tradeoff studies. sign choices. When costs of power out-
The lack of credible data concerning ages at the various building and plant
equipment reliability and the cost of locations are factored into the evalua-
power outages has hindered engineers tion, the decisions can be based upon
in making such studies. total owning cost over the useful life o f
The authors of this book have at- the equipment rather than simply first
tempted t o provide sufficient informa- cost of the system. The material in this
tion so that reliability analyses can be book should enable engineers t o make
performed on power systems without more use of quantitative cost versus
need for cross references t o other texts. reliability tradeoff studies during the
Included are: design of industrial and commercial
(1) Basic concepts of reliability anal- power systems.

15
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

1.2 IEEE Reliability Surveys of Indus- wish to start with Chapter 2 and not
trial Plants. From 1973 through 1979 wish t o attempt to fully understand
the Power Systems Reliability Subcom- the derivation of the statistical formulas
mittee of the Power Systems Support given in 2.1.9,Table 1.
Committee, Industrial Power Systems The most important parts of planning
Department, IEEE Industry Applications and design are covered in 2.1 and 2.2 on
Society, conducted and published the fundamentals of power system relia-
results of extensive surveys of the relia- bility evaluation and on the economic
bility of electrical equipment in indus- evaluation of reliability. Chapter 7 gives
trial plants and also the cost of power six examples using these methods of anal-
outages for both industrial plants and ysis. These examples cover some of the
commercial buildi'ngs. The results from most common decisions that engineers
these surveys have been published in are facing when designing a power distri-
nine IEEE committee reports. The most bution system. Some discussion on the
important results from these surveys are limitations of reliability and availability
summarized in Chapters 2, 3 and 5 of predictions are given in the latter part
this book. In addition, the nine IEEE of 7.1.
committee reports are reprinted in Those wishing to obtain equipment
Appendixes A, B, C, D, and E. reliability data should go t o Chapter 3.
The IEEE survey reliability data pro- Those wishing t o obtain data on the cost
vide historical experience t o those who of electrical interruptions to industrial
have not been able to collect their own plants or commercial buildings should
data. Such data can be an aid in analyz- consult 2.2. Any data on costs may need
ing, designing, or redesigning a power t o be updated to take into account the
distribution system and can provide a effects of inflation.
basis for quantitative cost comparisons The importance of electrical preventive
between alternate designs. maintenance in planning and design is
covered in 2.3 and 2.4. Chapter 5
discusses the subject in further detail
1.3 How to Use This Book. This book is and contains data showing the effect
primarily directed toward consulting of maintenance quality on equipment
engineers and plant electrical engineers failure rates.
and covers the fundamentals of relia- Many reliability studies need t o be
bility analysis as it applies t o the plan- followed up by considerations for emer-
ning and design of industrial and gency and standby power. This subject is
commercial electric power distribution covered in Chapter 6 and may also be
systems. The methods of reliability anal- considered part of planning and design.
ysis are based upon probability and An approach to evaluating and upgrad-
statistics. Some users of this book may ing the reliability of an existing plant is
wish to read Chapter 8 on basic prob- presented in Chapter 4. Some users of
ability concepts before reading Chapter 2 this book may wish to start with this
on planning and design. Other users may Chapter.

16
2. Planning and Design

2.1 Fundamentals of Power System Re- The quantitative reliability evaluation


liability Evaluation methods presented here permit reli-
2.1.1 Reliability Evaluation Funda- ability indexes for any electric power
mentals. Fundamentals necessary for a system t o be computed from knowledge
quantitative reliability evaluation in elec- of the reliability performance of the
tric power systems include definitions of constituent components of the system.
basic terms, discussions of useful meas- Thus, alternative system designs can be
ures of system reliability and the basic studied t o evaluate the impact on service
data needed t o compute these indexes, reliability and cost of changes in com-
and a description of the procedure for ponent reliability, system configuration,
system reliability analysis including com- protection and switching scheme, or
putation of quantitative reliability in- system operating policy including main-
dexes. tenance practice.
2.1.2 Power System Design Considera- 2.1.3 Definitions. The definitiok pre-
tions. An important aspect of power sented here include those used in the sur-
system design involves consideration of vey of the reliability of electric equipment
the service reliability requirements of in industrial plants.[l] The defini-
loads which are t o be supplied and the tions presented are not exhaustive, but
service reliability which will be provided d o provide much of the required nomen-
by any proposed system. System reli- clature for discussions of power system
ability assessment and evaluation reliability.
methods based on probability theory
which allow the reliability of a proposed availability. This term may apply either
t o the performance of individual compo-
system t o be assessed quantitatively are
finding wide application today. Such nents or to that of a system. Availability
methods permit consistent, defensible, is defined to be the long-term average
and unbiased assessments of system reli-
Numbers in brackets refer to the references
ability which are not otherwise possible. listed in 2.5.

17
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

fraction of time that a component or repaired or replaced. The terms failure


system is in service satisfactorily perform- and forced outage are often used synon-
ina its intended function. An alternative ymously.
an> equivalent definition for availability failure rate (forced outage rate). The
is the steady-state probability that a mean number of failures of a component
component or system is in service. per unit exposure time. Usually exposure
component. A piece of equipment, a line time is expressed in years and failure
or circuit, or a section of a line or circuit, rate is given in failures per year.
or a group of items which is viewed as an forced unavailability. The long-term
entity for purposes of reliability evalua- average fraction of time that a compo-
tion. nent or system is out of service due to
expected interruption duration. The ex- failures.
pected, or average, duration of a single interruption. The loss of electric power
load interruption event. supply to one or more loads.
exposure time, The time during which interruption frequency. The expected
a component is performing its intended (average) number of power interruptions
function and is subject t o failure. to a load per unit time, usually expressed
failure. Any trouble with a power as interruptions per year.
system component that causes any of
the following to occur: outage. The state of a component or sys-
tem when it is not available to properly
(1) Partial or complete plant shut- perform its intended function.
down, or below-standard plant operation repair time. The repair time of a failed
(2) Unacceptable performance of component or the duration of a failure is
user’s equipment the clock time from the occurrence of the
(3) Operation of the electrical protec- failure t o the time when the component
tive relaying or emergency operation of is restored t o service, either by repair of
the plant electrical system the failed component or by substitution
(4)Deenergization of any electric cir- of a spare component for the failed
cuit or equipment component. It is not the time required
A failure on a public utility supply to restore service t o a load by putting
system may cause the user t o have either alternate circuits into operation. It in-
of the following: cludes time for diagnosing the trouble,
locating the failed component, waiting
(1) A power interruption or loss of for parts, repairing or replacing, testing,
service and restoring the component t o service.
(2) A deviation from normal voltage The terms repair time and forced outage
or frequency of sufficient magnitude or duration are often used synonymously.
duration
scheduled outage. An outage that results
A failure on an in-plant component when a component is deliberately taken
causes a forced outage of the compo- out of service at a selected time, usually
nent, that is, the component is unable t o for purposes of construction, mainte-
perform its intended function until it is nance, or repair.

18
IEEE
PLANNING AND DESIGN Std 493-1980

scheduled outage duration. The period terruption duration can be used to com-
from the initiation of a scheduled outage pute other indexes which are also useful:
until construction, preventive mainte- (1) Total expected (average) interrup-
nance, or repair work is completed and tion time per year (or other time period)
the affected component is made avail- (2) System availability or unavailabil-
able t o perform its intended function. ity as measured at the load supply point
in question
scheduled outage rate. The mean number
(3) Expected demanded, but unsup-
of scheduled outages of a component per
plied, energy per year
unit exposure time.
It should be noted here that the
switching time. The period from the time disruptive effect of power interruptions
a switching operation is required due t o is often non linearly related t o the dura-
a component failure until that switching tion of the interruption. Thus, it is often
operation is completed. Switching opera- desirable t o compute not only an overall
tions include such operations as: throw- interruption frequency but also fre-
over t o an alternate circuit, opening or quencies of interruptions categorized by
closing a sectionalizing switch or circuit the appropriate durations.
breaker, reclosing a circuit breaker
following a trip out due to a temporary 2.1.5 Data Needed for System Reli-
fault, etc. ability Evaluations. The data needed for
quantitative evaluations of system reli-
system. A group of components con-
ability depend to some extent on the
nected or associated in a fixed configura-
tion to perform a specified function of nature of the system being studied and
distributing power. the detail of the study. In general,
however, data on the performance of
unavailability. The long-term average individual components together with the
fraction of time that a component or times required to perform various
system is out of service due to failures switching operations are required.
or scheduled outages. An alternative System component data which are
definition is the steady-state probability generally required are summarized as
that a component or system is out of f 0110ws :
service. Mathematically, unavailability = (1) Failure rates (forced outage rates)
-
( 1 availability). associated with different modes of com-
ponent failure
2.1.4 System Reliability Indexes. The (2) Expected (average) time to repair
basic system reliability indexes [2], or replace failed component
[ 31 , which have proven most useful and (3) Scheduled (maintenance) outage
meaningful in power distribution system rate of component
design are: (4) Expected (average) duration of a
(1) Load interruption frequency scheduled outage event
(2) Expected duration of load inter- If possible, component data should be
ruption events based on the historical performance of
These indexes can be readily computed components in the same environment as
using the methods which will be de- those in the proposed system being
scribed later. The two basic indexes of studied. The reliability surveys con-
interruption frequency and expected in- ducted by the Power Systems Reliability
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

Subcommittee [ 13, [ 41 provide a source the appropriate service interruption


of component data when such specific definition or definitions.
data are not available. These data have (2) Perform a failure modes and
been summarized in Chapter 3. effects analysis identifying and listing
The needed switching time data in- those component failures and combina-
clude : tions of component failures that result
(1) Expected times t o open and close in service interruptions and which con-
a circuit breaker stitute minimal cut-sets of the system.
(2) Expected times to open and close (3) Compute the interruption fre-
a disconnect or throwover switch quency contribution, the expected inter-
(3) Expected time t o replace a fuse ruption duration, and the probability of
link each of the minimal cut-sets of step (2).
( 4 ) Expected times t o perform such (4) Combine the results of step (3) t o
emergency operations as cutting in clear, produce system reliability indexes.
installing jumpers, etc These steps will be discussed in more
Switching times should be estimated detail in the sections that follow.
for the system being studied based on 2.1.7 Service Interruprtion Definition.
experience, engineering judgment, and The first step in any electric power
anticipated operating practice. system reliability study should be a
2.1.6 Method for System Reliability careful assessment of the power supply
Evaluation. The method for system reli- quality and continuity required by the
ability evaluation which is recommended loads which are t o be served. This
and presented here has evolved over a assessment should be summarized and
number of years [2], [ 5 ] , [ 8 ] . The expressed in a service interruption defini-
method, called the minimal-cut-set tion which can be used in the succeeding
method, is believed to be particularly steps of the reliability evaluation pro-
well suited t o the study and analysis of cedure. The interruption definition spec-
electric power distribution systems as ifies, in general, the reduced voltage level
found in industrial plants and com- (voltage dip) together with the minimum
mercial buildings. The method is sys- duration of such a reduced voltage period
tematic and straightforward and lends which results in substantial degradation
itself to either manual or computer or complete loss of function of the load
computation. An important feature of or process being served. Frequently reli-
the method is that system weak points ability studies are conducted on a con-
can be readily identified, both numeri- tinuity basis in which case interruption
cally and non numerically, thereby definitions reduce to a minimum dura-
focusing design attention on those tion specification with voltage assumed
sections of the system that contribute t o be zero during the interruption.
most t o service unreliability. See Chapter A further discussion of interruption
8 for a derivation of the minimal cut-set- definitions together with examples of
method. such definitions is given in 7.1.2.
The procedure for system reliability 2.1.8 Failure Modes and Effects Anal-
evaluation is outlined as follows: ysis. Failure modes and effects analysis
(1) Assess the service reliability re- (FMEA) for power distribution systems
quirements of the loads and processes amounts t o the determination and listing
which are t o be supplied and determine of those component outage events or

20
IEEE
PLANNING AND DESIGN Std 493-1980

combinations of component outages 3 of this book. A minimal cut-set is


which result in an interruption of service defined t o be a set of components which,
at the load point being studied according if removed from the system, results in
to the interruption definition which has loss of continuity t o the load point being
been adopted. This analysis must be investigated and which does not contain
made considering the different types and as a subset any set of components which
modes of outages which components is itself a cut-set of the system. In the
may exhibit and the reaction of the present context the components in a
system’s protection scheme to these cut-set are just those components whose
events. Component outages may be cate- overlapping outage results in an interrup-
gorized as: tion according to the interruption
(1) Forced outages or failures definition adopted.
(2) Scheduled or maintenance outages An important non quantitative benefit
(3) Overload outages of the failure modes and effects analysis
Forced outages or failures may be (FMEA) is the thorough and systematic
further categorized as : thought process and investigation that
(1) Permanent forced outages it requires. Often weak points in system
(2) Transient forced outages design will be identified before any
Permanent forced outages require re- quantitative reliability indexes are com-
pair or replacement of the failed compo- puted. Thus, the failure modes and
nent before it can be restored to service, affects analysis (FMEA) is a useful reli-
while transient forced outages imply no ability design tool even in the absence of
permanent damage t o the component, the data needed for quantitative evalua-
thus permitting its restoration t o service tion.
by a simple reclosing or refusing opera- The FMEA and the determination of
tion. Additionally, component failures minimal cut-sets is most efficiently con-
may be categorized by physical mode or ducted by considering first the effects of
type of failure. This type of failure outages of single components and then
categorization is important for circuit the effects of overlapping outages of in-
breakers and other switching devices creasing numbers of components. Those
where failure modes such as the follow- cut-sets containing a single component
ing are possible and have varying im- are termed first-order cut-sets. Similarly
pacts on system performance: cut-sets containing two components are
termed second-order cut-sets, etc. In
(1) Faulted, must be cleared by back- theory the FMEA should continue until
up devices all the minimal cut-sets of the system
(2) Fails t o trip when required have been found. In practice, however,
(3) Trips falsely the FMEA can be terminated earlier
(4) Fails to re-close when required since high-order cut-sets have low prob-
The primary result of the failure ability compared to lower order cut-sets.
modes and effects analysis (FMEA) as A good rule of thumb is to determine
far as quantitative reliability evaluation minimal cut-sets up t o order n + 1 where
is concerned is the list of minimal cut- n is the lowest order minimal cut-set of
sets it produces. The use of the minimal the system. Since most power distribu-
cut-sets in the calculation of system tion systems have at least some first-
reliability indexes is described in Chapter order minimal cut-sets, the analysis can
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

usually be terminated after the second- (3) Components are not taken out of
order minimal cut-sets have been found. service for maintenance or other defer-
2.1.9 Computation of Quantitative rable work if other components are on
Reliability Indexes. Computation of re- forced outage, but forced outages of
liability indexes may proceed once the components may occur during the
minimal cut-sets of the system have been scheduled outage of a component.
found. The first step is t o compute the (4)Components which act in parallel
frequency, expected duration, and ex- t o carry load are fully redundant. That
pected down time per year of each is, any one component of the parallel
minimal cut-set. Note that the expected combination is capable of carrying the
down time per year is just the product of entire load of the parallel combination
the frequency expressed in terms of without overload. (Methods for treating
events per year and the expected dura- overload outages are given in 2.1.12).
tion. If the expected duration is ex- Once the frequencies and expected
pressed in years, the expected down time durations have been computed for each
will have the unit of years per year and minimal cut-set, the system reliability
may be regarded as the relative propor- indexes at the load point in question
tion of time or the probability the sys- are determined.
tem is down due t o the minimal cut-set
in question. More commonly the ex- f, = interruption frequency
pected duration is expressed in hours,
= fCSi
and the expected down time has the unit min
of hours per year. cut-sets

Approximate expressions for the fre-


quency and expected duration of the rs = expected interruption duration
most commonly considered interruption
= fCSi rcsJfs
events associated with first-, second- min
and third-order minimal cut-sets are cut-sets

given in Table 1. These are discussed in


more detail in Chapter 8. fsrs = total interruption time per time
Note that expressions are given for period
forced outages (failures) and for forced
outages overlapping a maintenance out- 2.1.10 Example: Sample System
age. The basic assumptions made in Evaluation . The reliability evaluation
deriving the expressions of Table 1 are method which has been described will
as follows: now be illustrated through a simple
(1) Component failure and repair example. More detailed examples using
events are statistically independent. typical data are given in Chapter 7.
(2) Component up times are much Consider the simple system of Fig 1.
larger than down times. That is, the Here, for the sake of simplicity, only the
probability that a component is up is components labeled 1, 2, and 3 will be
much larger than the probability that it considered fallible, and only permanent
is down. forced outages and scheduled outages
IEEE
PLANNING AND DESIGN Std 493-1980

Table 1
Frequency and Expected Duration Expressions for Interruptions
Associated with Minimal Cut-Sets

Forced Outages

First-Order Minimal Cut-Set Second-Order Mznimal Cut-Set Third-Order Minimal Cut-Set


fcs = A 1 f,,= h , h J ( r l + r J ) fc,= h , hJ rJ+r,rk+rJrk)

TCS = rt rcs = r, rJ I (rl+rJ) rcs = r,rJrk i (r, r J + r , r k + r J r k )

Forced Outages Overlapping Scheduled Outage

Second-Order Minimal Cut-Set Third-Order Minimal Cut-Set


fcs= A +B +C

fcs = frequency of cut-set event where.


rcs = expected duration of cut-set event
hi = forced outage r a t e of ith component
r, + rJ r, + rk
A, = scheduled outage rate of zth component
r, = expected repair or replacement time of
ith component rJrl r~r k
I +-
r, = expected scheduled outage duration of rJ + r, rJ + rk
ith component

Note 1: The time units of r and A in expressions for f,, must be the same.
Note 2: If service can be restored to the affected load point by a switching operation, set rcs= expected
switching time. Note t h a t this assumes t h a t switching times a r e short compared to repair or replacement
times.

23
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Fig 1
Sample System

Table 2
Sample System Evaluation

Minimal Cut-Sets f cs TCS f csrcs

Forced Outages:
Component 1 A1 rl hl'l

Component 2/Component 3 h3h2(r3 + r2) r3r2(r3 + r2) A 3' 2r3r2

Forced/Scheduled Outages:

Totals c f csrcs

System indices:

f , = Cfcs
rd = Cfc,rcs/fs

24
IEEE
PLANNING AND DESIGN Std 493-1980

will be assumed possible. Additionally, time to repair or replace failed com-


scheduled outages of component 1which ponents. Thus when computing the
would result in interruptions t o the load frequency and duration of a system
are assumed t o be taken during periods interruption event (minimal cut-set), the
of plant maintenance shutdown and are frequency is computed as outlined in
not treated in the reliability analysis. All Tables 1 and 2, but the duration be-
circuit breakers are assumed to be nor- comes simply the switching time (assum-
mally closed and are coordinated t o ing that the switching time is short com-
minimize system disruption due t o a pared to the repair or replacement
component failure. time).
The load is assumed not to be sensitive The procedure is most easily described
t o voltage dips limited t o the time through use of a simple example. Con-
required t o clear a fault, but any loss of sider the system of Fig 2 in which power
continuity from source t o load consti- is supplied from a source t o a load over
tutes an interruption t o the load. Using two parallel circuits with the sectionaliz-
this definition of an interruption, the ing scheme shown. Assume for the pur-
minimal cut-sets of the system are shown poses of the example that only the
in Table 2. Also shown in Table 2 are the circuits are subject t o failure and that
expressions needed for the calculation of each circuit has a failure rate of hi and
the system reliability indexes. an average repair time of r i . Assume
2.1.11 Post Fault Switching. Power further that the sectionalizing switches
systems are frequently designed with a t the load point can be opened in a time
protective and switching schemes that t , t o isolate a faulty circuit and that all
allow restoration of service through circuit breakers and switches are normally
some switching action following one or closed.
more component failures. The key point If the definition of system failure is
in such cases is that the duration of the loss of continuity from source to load,
interruption event is the time to perform the general reliability evaluation pro-
the switching operation rather than the cedure yields the results given in Table 3.

Table 3
Sample System Evaluation
Considering Post-Fault Switching

Minimal-Cut Frequency Dura tion Probability


Failure of circuit 1 11 4 A1 4
Failure of circuit 2 A2 tS A24
r1r2
Failure of both circuits A,A2(rl + 7-21 A ,A 2 r1r2
(rl + r2)
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

NC CIRCUIT 1 NC
I- '-I

ClRCUlT 2
SOURCE

Fig 2
Example of Post-Fault Switching

Note that failure of both circuits is not, 2.1.12 Incomplete Redundancy. A


strictly speaking, a minimal cut-set since common method of improving the reli-
failure of either circuit alone constitutes ability performance of a system is
a system failure and load interruption. through component redundancy, for ex-
The justification for including failure of ample, more than one transformer in a
both circuits is the desire t o give fre- substation. Typically, each component
quency, duration, and probability in- of the redundant set has sufficient capac-
formation on both short-duration in- ity, perhaps based on an emergency
terruptions which are terminated by rating, t o carry the peak load that the
switching actions and long-duration system may be asked to deliver. Such
interruptions which are terminated by full redundancy is effective in improving
repair or replacement efforts. In the system reliability performance but is
event that load sensitivity is such that usually quite expensive. If the load of
differences in power supply interruption the system is variable, the opportunity
durations are not important, failure of exists to cut costs by reducing the
both circuits could have been omitted capacity of redundant components t o
and only the frequency of minimal levels less than that required t o carry
cut-sets calculated. In general system system peak load. Such component ca-
failure, frequency and probability are pacity reductions admit the possibility
obtained by summing the frequency and that one component of the redundant
probability columns, respectively. If it is set might be called upon to carry system
desired t o separate short- and long- peak load and would thereby suffer an
duration interruption performance, these overload outage. An overload outage
summations are carried out with due might result in an actual interruption of
regard to the average durations of the load or perhaps only some loss of life in
various cut-sets. Average interruption the overlqaded component, depending
duration is given by system failure prob- on the protection scheme in service.
ability divided by system failure fre- A method exists [ 9 ] , [lo] for com-
quency. puting the frequency, average duration,
IEEE
PLANNING AND DESIGN Std 493-1980

0.9-
0.8 -

0.7 -
0.6 -
0.5 -
0.4 -
0.3 -
0.2 -
0.1 -
0
0 0.1 0.2 0.3 0.4 0,5 0.6 0.7 0.8 0.9 1.0

PER U N I T L O A D

Fig 3
Typical Load-Duration Characteristic

PTR UNIT LOAD

Fig 4
Typical Load-Frequency Characteristic

27
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

and probability of overload outage 2.2 Costs of Interruptions; Economic


events as a function of component Evaluation of Reliability
capacities and load characteristics. This 2.2.1 Cost of Interruptions Versus
method, which is compatible with the Capital Cost. The type and extent of
general reliability evaluation procedure new or rehabilitated electric systems for
outlined earlier, can be used to evaluate industrial plants or commercial buildings
the cost-reliability tradeoffs of incom- must carefully balance the costs of
plete redundancy. The method is briefly anticipated interruptions to electrical
presented hereafter. service against the capital costs of the
Consider a system possessing incom- systems involved. Each instance requires
plete redundancy, and consider the a separate analysis taking into account
forced outage of some set i of the special production and occupancy needs.
components of this system. Let the fre- Because of the many variables involved,
quency and probability of this forced one of the most difficult items to obtain
outage event be fi and Pi. Then the fre- is the cost of the electrical interruptions.
quency, probability, and average dura- 2.2.1.1 What is an Interruption?
tion of overloading events that are Economic evaluation of reliability begins
precipitated by loss of the components with the establishment of an interrup-
in set i are given approximately by: tion definition. Such a definition specifies
the magnitude of the voltage dip and the
minimum duration of such a reduced-
foL = fi - P (load Z capacity of re-
voltage period which result in a loss of
maining components)
production or other function for the
+Pi o f (load Z capacity of re- plant, process, or building in question.
maining components) Frequently, interruption definitions are
given only in terms of a minimum dura-
PoLi = Pi .P (load 2 capacity of re-
tion and assume that the voltage is zero
maining components)
during that period.
DOL '= POL/ ~ O L IEEE surveys, [ 121 [ 131, [ 141 , have
revealed a wide variation in the minimum
In the above expressions P (load Z x) or critical service loss duration. Table 4
is called the load-duration characteristic summarizes results for industrial plants
and is simply the probability of propor- and Table 5 gives results for commercial
tion of time that the load is greater than buildings. It is clear from these tables
or equal to X . A typical load-duration that careful attention must be paid to
characteristic for utility load is shown in choosing the proper interruption defini-
Fig 3. Similarly, f (load Z X ) is called tion in any specific reliability evaluation.
the load-frequency characteristic and is Another important consideration in
the rate with which events (load 2 X ) the economic evaluation of reliability is
occur. A typical load-frequency char- the time required to restart a plant or
acteristic is shown in Fig 4. The reader process following a power interruption.
is referred to [ l o ] for additional discus- An IEEE survey [121, (shown in Table
sion of the load-duration and load- 6) indicates that industrial plant restart
frequency characteristics. time following a complete plant shut-

28
IEEE
PLANNING AND DESIGN Std 493-1980

Table 4
Critical Service Loss Duration for
Industrial Plants*
(Maximum length of time a n interruption of electrical service will not stop plant production.)

Average Plant
Outage Time
for Equipment
Failure Between
25th 75th 1- and 10-Cycle
Percentile Median Percentile Duration

10.0 10.0 15 1.39


cycles seconds minutes hours

'55 plants in the United States and Canada reporting; all industry.

Table 5
Critical Service Loss Duration for Commercial Buildings*
(Maximum length of time before a n interruption to electrical service is considered critical.)

Service Loss Duration Time

1 2 8 1 5 30 1 12
cycle cycles cycles second minutes minutes hour hours
% % % % % % % %
~~

3 6 9 15 36 64 74 100

*Percentage of buildings with critical service loss for duration less t h a n or equal to time indicated (54
buildings reporting).

down due to a power interruption aver- critical factor must be carefully explored
ages 17.4 hours. The median plant res- prior t o assigning a cost t o the interrup-
tart time was found to be 4.0 hours. tion. That 15% of the commercial
Clearly, specific data on plant or process buildings reported the critical service loss
restart time should be used if possible duration time to be 1 second or less is
in any particular evaluation. probably attributable to the fact that
Many industrial plants reported that computer installations were involved.
1 to 10 cycles were considered critical Further data from [12] graphically
interruption time, as compared t o 1.39 h , illustrates the time required t o start an
required for startup, (plant outage industrial plant after an interruption.
time being considered equal t o plant Step 1 of the cost analysis thus be-
startup time). This indicates that the comes the selection of the critical dura-

29
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 6 accomplishing economic evaluations. For


Plant R e s t a r t Time* quick order-of-magnitude or Is it worth
(After service is restored following a failure that further investigation ? type of evalua-
has caused a complete plant shutdown.) tions, cost data from [121, [141 can be
used. Caution must be exercixed how-
Average Median ever, since these data are very general
(hours) (hours) in nature, and wide variations are possi-
17.4 4.0
ble in individual cases. Some of the
‘43 plants in the United States and Canada re- more commonly accepted methods for
porting; all industry. economic analyses are:

tion time of the outage and the plant (1) Revenue requirements (RR)
startup time, including equipment repair (2) Return on investment (ROI)
or replacement time required because of (3) Life cycle costing (LCC)
the interruption. It is not the intent t o stipulate here
2.2.12 Cost of an Electrical Service the method to be used nor the depth
Interruption. With the establishment of t o which each analysis is t o be made.
expected downtime per interruption, These are considered t o be the preroga-
costs are assigned t o all individual items tive of the engineer and will depend
involved, including but n o t limited to: heavily on management choice and the
(1) Value of loss production time less time available for the analysis. The
expenses saved (expected restart time is revenue requirements (RR) method is
used along with the repair or replacement given in this chapter as an example.
time) 2.2.2 “Order of Magnitude” Cost of
(2) Damaged plant equipment Interruptions. IEEE surveys, References
(3) Spoiled or off-specification prod- [21, 141, presented general data on the
uct cost of interruptions to industrial plants
(4) Extra maintenance costs and commercial buildings. The reader is
(5) Cost for repair of failed component again cautioned that such general data
If possible, the cost for each inter- should be used only for “order of magni-
ruption of service should be expressed tude” evaluations where data specific to
in a short interruption plus an amount the system being studied is not avail-
of dollar per hour for the total outage able. A review of the reliability data
time in order t o utilize the reliability can probably best be used in adjudicat-
data and analysis presented. ing the type of utility company service
2.2.1.3 Economic Evaluation of which should be provided.
Reliability . There are many methods The costs based on the kW inter-
of varying degrees of complexity for rupted and the kWh not delivered to
IEEE
PLANNING AND DESIGN Std 493-1980

industrial plants are presented in weaknesses, especially when comparing


Tables 7 and 8. design alternatives in contrast to
Interruption costs based on kWh not overall projects. The RR method is
delivered and reflecting the relationship “mathematically rigorous and quantita-
to duration of interruptions for commer- tively correct to the extent permitted by
cial buildings are presented in the accuracy with which items of cost can
Tables 9 and 10. be forecast.” [21, [131
The essence of the RR method is that
2.2.3 Economic Analysis of Reliability for each alternative plan being con-
in Electrical Systems. There are several sidered, the Minimum Revenue Require-
acceptable methods for accomplishing ments (MRR) is determined. This means
a n economic analysis of the reliability that we find out how much product we
in electric systems. The examples of must sell to achieve minimum accept-
reliability analysis included in this able earnings on the investment
chapter and Chapter 7 utilize the Reve-
involved plus all expenses associated
nue Requirements (RR) method. The with that investment. These MRRs for
application of this method as it applied alternative plans may be compared
to the analyses of the reliability in directly. The plan having the lowest
Industrial Plant Electrical Systems was MRR is the economic choice.
presented in Reference part 6 of [21. MRR is made up of and equal to (1)
Applicable excerpts from this reference variable operating expenses, (2) min-
are included herein.
imum acceptable earnings, (3) deprecia-
2.2.3.1 The Revenue Requirements tion, (4) income taxes, and ( 5 ) fixed
(RR) Method. Although there are many operating expenses. These MRRs may
ways in use to compare alternatives, be separated into two main parts, one
some of these have defects and proportional and the other not propor-

Table 7
Average Cost of Power Interruptions for Industrial Plants*

All P l a n t s $1.89/kW + $2.68/kWh


Plants > 1000 kW $1.05/kW + $0.94/kWh
Max Demand
Plants < 1000 kW $4.59/kW + $8.ll/kWh
Max Demand

‘41 plants i n t h e United States and Canada reporting-published i n 1973.

31
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 8
Median Cost of Power Interruptions for Industrial Plants*
All plants $0.69/kW + $0.83/kWh
Plants > 1000 kW Max Demand $0.32/kW + $0.36/kWh
Plants < 1000 kW Max Demand $3.68/kW + $4.42/kWh
'41 plants in t h e United States and Canada reporting-published in 1973.

Table 9
Average Cost of Power Interruptions for Commercial Buildings

All commercial buildings* $7.21/kWh not delivered


Office buildings only $8.86/kWh not delivered

'54 buildings in the United States reporting-published in 1975.

Table 10
Cost of Power Interruptions
as a Function of Duration
for Office Buildings (with Computers)*

Sample
CostPeak kWh
Not Delivered
Power Interruptions Size Maximum Minimum Average

15-min duration 14 $22.22 $1.88 $8.89

1-Hour duration 16 $24.93 $1.88 $8.30

Duration > 1-hour 10 $67.66 $0.16 $9.81

*Published in 1975.
IEEE
PLANNING AND DESIGN Std 493-1980

tional to investment in the alternative. Considering the first way, the


This may be expressed in a n equation: increased expense due to the failure
includes the following:

G=X+CF (Eq 1)
(1) Damaged plant equipment
(2) Spoiled or off-specification product
where
minimum revenue require- (3) Extra maintenance costs
G =
ments (MRR) to achieve min- (4) Costs for repair of the failed com-
imum acceptable earnings ponent
x = nonfixed or variable operat- Considering the second way, plant
ing expenses downtime resulting from failures is
made up of the time required to restart
c = capital investment
the plant, if necessary, plus the time to
F = fixed investment charge fac- (1) effect repairs, if it is a radial sys-
tor tem, or (2) effect a transfer from the
source on which the failure occurred to
a n energized source.
The last term in Eq 1, the product of C During plant downtime, production is
and F includes the items (2), (31, (4), lost. This lost production is not avail-
and (5) listed in the preceding para- able for sale, so revenues are lost. How-
graph. Equation 1 is now discussed. ever, during plant downtime, some
X-Variable Expenses. The effect of expenses may be saved, such as
the failure of a component is to cause expenses for material, labor, power, and
an increase in variable expenses. How fuel costs. Therefore, the value of the
serious this increase is depends to a lost production is the revenues lost,
great extent on the location of the com- because production stopped less the
ponent in the system and on the type of expenses saved. Some of the variable
power distribution system employed. expenses may vary depending on the
The quality of a component as installed duration of plant downtime. For exam-
can have a significant effect on the ple, if plant downtime is only one hour,
number of failures experienced. A poor perhaps no labor costs are saved. But, if
quality component installed with poor plant downtime exceeds eight hours,
workmanship and with poor application labor costs may be saved.
engineering may greatly increase the If we assume that the value/hour of
number of failures that occur as com- variable expenses does not vary with
pared with a high quality component the duration of plant downtime, then
installed with excellent workmanship the value of lost production can be
and sound application engineering. expressed on a per hour basis, and the
When a failure does occur, variable total value of lost production is the
expenses are increased in two ways. In product of plant downtime in hours and
the first way, the increase is the result the value of lost production per hour.
of the failure itself. In the second way, I t should be noted that both the value
the increase is proportional to the dura- of lost production and expenses incurred
tion of the failure. are proportional to the failure rate. The

33
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

total effect on variable expenses, if the The term g, represents revenues lost
value of lost production is a constant on and it is not really a n expense. How-
a per hourly basis, may be expressed in ever, it is a negative revenue, and as
a n equation. such has the same effect on the econom-
ics as a positive expense item. It is con-
X = h[xi + (g,-x,)(r+s)I (Eq 2) venient to treat it as though it were a n
expense.
where A failure rate of 0.1 failure per year
X = variable expenses ($ per year) is equivalent to a mean time between
failures of 10 years. Since we are deal-
A = failures per year or failure ing with probability, this is what we
rate can expect, but in a specific case, we
xi = extra expenses incurred per might have two failures in one 10 year
failure ($ Der failure) period and no failures in another 10
year period. But considering many simi-
gp = lost per hour Of lar cases, we expect to have an average
downtime ($ per hour) of 0.1 failure per year, with each failure
xp = variable expenses saved per costing a n average of $80,000. This
hour of plant downtime ($ gives a n equal average amount per year
per hour) in the above example of $8,000.
The point is that even though the
r = repair or replacement time actual failures cost $80,000 each and
after a failure (or transfer occur once every 10 years, a given
time if not radial system), failure is just as likely to occur in any
hours of the 10 years. The equivalent equal
s = plant startup time after a annual amount of $8,000 per year is the
failure, hours average value of one failure in 10 years.
c-Investment. Each different alterna-
Assume that tive is a n industrial plant power distri-
A = 0.1 failure per year bution system involves different invest-
ments. The system requiring the least
xi = $20,000 per failure, extra investment will usually be some form of
expenses incurred radial system. By varying the type of
g, = $8,000 per hour, revenues lost construction and the quality of the com-
ponents in the system, the investment
xp = $6,000 per hour, expenses in radial systems can vary widely.
saved The best method is to find one total
r = 10 hours per failure investment in each alternative plan.
Another common method is to find the
s = 20 hours per failure incremental investment in all alterna-
Then, variable expenses affected would tives over a base or least expensive
be : plan. The main reason that the total
investment method is preferable, is that
x = (0.1)[$20,000 in comparing alternatives, the invest-
+ ($8,00Cr$6,000)(10 + 2011 ment is multiplied by an F factor which
= $8,000 per year will be explained later. This factor is
IEEE
PLANNING A N D DESIGN Std 493-1980

usually the same for alternative plans R = minimum acceptable earnings


of the sort being considered here, but per $ of C, investment
this is not necessarily the case.
Using the incremental investment f, = probability of success or risk
adjustment factor
may thus introduce a slight error into
the economic comparisons. t = income taxes per $ of C,
F- Investment Charge Factor. This investment
discussion of investment charge factor -
dt = income tax depreciation,
is taken from [21.
levelized per $ of C, invest-
The factor F includes the following
ment = 1 / L , d , = 1L
items which are fixed in relation to the
investment. e = fixed expenses per $ of C,
investment
( 1 ) Minimum acceptable rate of
-
return on investment, allowing for risk r = levelized return on invest-
ment per $ of C, investment
(2) Income taxes -
d = levelized depreciation on
(3) Depreciation
investment per $ of C, invest-
(4) Fixed expenses ment
-
An equation to calculate the F factor is: t = levelized income taxes on
investment per $ of C, invest-
ment

[
Assume
F= +e (Eq 3)
1-t L = 20 years, life of investment
c = 1 year

This may also take the following form: R = 0.15, minimum acceptable
rate of return
F= F + 2 +t +e (Eq 4) f, = 1, risk adjustment factor

where t = 0.5, income tax rate


-
a, = R + d , , amortization factor d, = -=
L
0.05
or leveling factor
e = 0.0825
d, = R / (Sn-
11, sinking fund fac-
tor Then
s, = +
( 1 R)", growth factor or s, = (l+R)' = (1+0.15)' = 1.15
future value factor
SL = ( l + R ) L= (1+0.15)20= 16.37
n = period of years, such as c or L
dL = R / ( S L - l ) = 0.15/(16.37-1)
c = years prior to startup that a n = 0.0098
investment is made
aL = R+d, = +
0.15 0.0098
L = life of investment years = 0.1598

35
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Substituting into Eq 3 to calculate 3. Determine F, the fixed investment


the F factor, we get: charge factor, F from Eq 3.
4. Calculate G = X + CF, the min-
imum revenue requirements G of each
plan. Eq 1.
5. Select as the economic choice the
plan having the lowest value of G.
+ 0.0825 = 0.4 (Eq 5 ) 2.2.3.3 Conclusions. A technique
has been presented for the economic
All the assumed values are believed evaluation of power system reliability.
to be typical for the average electric dis- The method of determining the failure
tribution system, except the value of e rates and repair times of different alter-
= 0.0825. This latter value was arbi- natives is not covered here. Additional
trarily assumed to make R round out to information relative to the RR Method
0.4. The term e covers such items as is included in [131.
insurance, property taxes, and fixed 2.2.4 Examples. Examples of electric
maintenance costs. A typical value is systems with varying degrees of relia-
probably less than 0.0825. bility (availability), together with fixed
It is believed that a typical value for and variable costs are given in Chapter
minimum acceptable return on invest- 7.
ment in many industrial plants is 15
percent, that is, R = 0.15. The company 2.3 Cost of Scheduled Electrical
average rate of return, based on either Preventive Maintenance
past history or anticipated results, is It is always appropriate to consider in
a measure of what R should be. In the economic evaluation of reliability
plants of higher risk than the average, the costs for scheduled electrical
the risk adjustment factor, f , , should preventive maintenance. Sometimes
probably be less than 1. However, com- these costs are large enough to make it
pany management determines what the desirable to analyze them separately
value of R should be. when comparing alternative designs of
The value of F can be calculated from industrial power systems. The Revenue
Eq 3 using a log log slide rule. In 1141, Requirements Method described in 2.2.3
tabular values are given for the factors includes a term called the Investment
S, and a,, for various rates of return Charge Factor, F which is given by Eq 3
and plant lifes. in 2.2.3 and includes e the fixed yearly
2.2.3.2 Steps for Economic Compari- expenses e (as a percentage of the capi-
sons. tal investment) are attributed to
1. Prepare one-line diagrams of alter- scheduled electrical preventive mainte-
native plans and assign failure rates, nance, insurance, property taxes, etc.
repair times, and investment in each Since the yearly average costs for
component, and determine the total scheduled electrical preventive mainte-
investment C, in each plan. nance may not be the same percentage
2. Determine X, the increased vari- of investment for every component
able expense for each plan as the sum of within the industrial power system, a
the value of lost production and the separate more detailed look is often
extra variable expenses incurred. taken a t these costs for each component.

36
IEEE
PLANNING A N D DESIGN Std 493-1980

Scheduled electrical preventive This is then added to the labor


maintenance has two major cost ele- manhours data to get total equivalent
ments; labor effort and spare parts con- manhours per component per year that
sumed. These costs are often expressed includes both the labor cost and the cost
on a n average yearly basis so as to be of spare parts consumed. The use of
usable with the “Revenue Requirements equivalent manhours for cost data
Method” when a n economic evaluation instead of dollars has two advantages:
is made. These data are needed for each
(1) The equivalent manhours data do
different type of component used in the not become obsolete due to inflation
industrial power system and can be
compiled for each component as follows: (2) The equivalent manhours data can
be considered a n international currency
(1)Labor Costs in manhours per com-
The data are not affected by changing
ponent per year
exchange rates between the currencies
(2) Cost of spare parts consumed in
or different countries. This enables the
dollars per component per year
cost data to be compared with studies
(3) Labor rate in dollars per manhour
from other countries.
If, for example, a component is only
No component data are included in
maintained once every three years, then
this book on the cost of scheduled
its maintenance costs should be divided
electrical preventive maintenance. It
by three in order to determine the aver-
would be desirable to have such data for
age yearly maintenance cost. The labor
all of the electrical equipment
rate used probably should only include
categories listed in Table 11 of Chapter
the overhead costs associated with the
3. It would then be possible to consider
storage of spare parts, direct supervision
the cost of scheduled electrical preven-
of the maintenance, and costs for neces-
tive maintenance in design decisions of
sary test equipment. The labor costs in
the industrial power system by adding
dollars per component per year can be
this into the Minimum “Revenue
calculated by multiplying items (1) and
Requirements Method.”
(3) together; the result can then be
added to item (2) to get the total aver-
age yearly costs that are attributable to 2.4 Effect of Scheduled Electrical
scheduled electrical preventive mainte- Preventive Maintenance on Failure
nance. Rate
Data thus collected can become One of the important total operating
obsolete at a later date due to inflation cost decisions made by the management
which can result in changing the labor of a n industrial plant is how much
rate used and also the average yearly money to spend for scheduled electrical
cost of spare parts consumed. But the preventive maintenance. The amount of
data for labor in manhours per com- maintenance performed on a component
ponent per year does not become can affect its failure rate. Very little
obsolete due to inflation. Some quantitative data have been collected
engineers have chosen to use their labor and published on this subject. Yet this
rate to convert their average yearly cost is a n important factor when attempting
data for spare parts consumed into aver- to study the total owning costs of a
age yearly “equivalent manhours” data. complete power system. If maintenance

37
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 11
Summary of All-Industry Equipment Failure Rate and Equipment Outage Duration
Data for 60 Equipment Categories Containing Eight or More Failures
(See Tables 4 t h r o u g h 1 9 i n A p p e n d i x A f o r additional details)

Actual H o u r s o f
Failure Downtime
Rate Per Failure
(failures Median
Equipment per Industry Plant
Equipment Subclass unit-year) Average Average

Transformers Liquid filled - all 0.0041 529.0 219.0


601-15 000 V -all sizes 0.0030 *174.0 49.0
300-750 k V A 0.0037 61.0 10.7
751-2499 k V A 0.0025 217.0 64.0
2500 k V A a n d u p 0.0032 216.0 60.0
Above 1 5 000 V 0.0130 *1076.0 1260.0
Dry t y p e : 0-15 000 V 0.0036 153.0 28.0
Rectifier: Above 6 0 0 V 0.0298 380.0 80.0
Circuit breakers F i x e d t y p e (including m o l d e d case) - all 0.0052 5.8 4 .O
0-600 V -all sizes 0.0044 4.7 4.0
0-600 A 0.0035 2.2 1.o
Above 6 0 0 A 0.0096 9.6 8.0
Above 6 0 0 V 0.0176 10.6 3.8
Metalclad d r a w o u t - all 0.0030 129.0 7.6
0-600 V - all sizes 0.0027 *147.0 4 .O
0-600 A 0.0023 3.2 1.o
Above 6 0 0 A 0.0030 232.0 5.0
Above 6 0 0 V 0.0036 *109.0 168.0
M o t o r starters C o n t a c t t y p e : 0-600 V 0.0139 65.1 24.5
C o n t a c t t y p e : 601-15 000 V 0.0153 284.0 16.0
Motors I n d u c t i o n : 0-600 V 0.0109 *114.0 18.3
I n d u c t i o n : 601-15 000 V 0.0404 *76.0 91.5
S y n c h r o n o u s : 0-600 V 0.0007 35.3 35.3
S y n c h r o n o u s : 601-15 000 V 0.0318 *175.0 153.0
Direct c u r r e n t - all 0.0556 37.5 16.2
Generators S t e a m t u r b i n e driven 0.032 165.0 66.5
Gas turbine driven 0.638 23.1 92.0
Disconnect switches Enclosed 0.0061 3.6 2.8
Switchgear b u s - i n d o o r Insulated: 601-15 000 V** 0.00170 261.0 26.8
and o u t d o o r (Unit = Bare: 0-600 V** 0.00034 550.0 24.0
number o f connected Bare: Above 6 0 0 V** 0.00063 17.3 13.0
circuit breakers o r in-
strument transformer
compartments)
Bus d u c t - i n d o o r a n d All voltages 0.000125 128.0 9.5
outdoor (Unit =
1 circuit f t )
O p e n wire ( U n i t = 0-15 000 V 0.0189 42.5 4.0
1 0 0 0 circuit f t ) Above 1 5 000 V 0.0075 17.5 12.0
Cable -all t y p e s of Above g r o u n d a n d aerial
insulation ( U n i t = 0-600 V 0.00141 457.0 10.5
1 0 0 0 circuit f t ) 601-15 000 V - all 0.01410 *40.4 6.9
In trays above g r o u n d 0.00923 8.9 8.0
In c o n d u i t above g r o u n d 0.04918 140.0 47.5
Aerial cable 0.01437 31.6 5.3
IEEE
PLANNING AND DESIGN Std 493-1980

Table 11 (Continued)

Actual Hours of
Failure Downtime
Rate per Failure- -
(failures Median
Equipment per Industry Plant
Equipment Subclass unit-year) Average Average

Cable -all types of Below ground a n d direct burial


insulation ( U n i t = 0-600 V 0.00388 15.0 24.0
1000 circuit f t ) 601-15 000 V - a l l 0.00617 *95.5 35.0
In d u c t o r c o n d u i t below ground 0.00613 96.8 35.0
Above 1 5 000 V 0.00336 16.0 16.0
Cable (Unit = 601-15 000 V
1000 circuit f t ) Thermoplastic 0.00387 44.5 10.0
Thermosetting 0.00889 168.0 26.0
Paper insulated lead covered 0.00912 48.9 26.8
Other 0.01832 16.1 28.5
Cable joints -all types of 601-15 000 V
insulation I n d u c t o r c o n d u i t below g r o u n d 0.000864 36.1 31.2
Cable joints 601-15 000 V
Thermoplastic 0.000754 15.8 8.0
Paper insulated lead covered 0.001037 31.4 28.0
Cable terminations - all Above ground a n d aerial
types of insulation 0-600 V 0.000127 3.8 4.O
601-15 000 V - a l l 0.000879 198.0 11.1
Aerial cable 0.001848 48.5 11.3
I n trays above ground 0.000333 8.0 9.0
I n d u c t o r conduit below g r o u n d
601-15 000 V 0.000303 25.0 23.4
Cable terminations 601-15 000 V
Thermoplastic 0.004192 10.6 11.5
Thermosetting 0.000307 451.0 11.3
Paper insulated lead covered 0.000781 68.8 29.2
Miscellaneous Inverters 1.254 107.0 185.0
Rectifiers 0.038 39.0 52.2

*See Tables 48 t h r o u g h 56 i n A p p e n d i x B f o r results of a special s t u d y o n E f f e c t o f Failure R e p a i r


M e t h o d a n d Failure R e p a i r U r g e n c y o n t h e A v e r a g e H o u r s D o w n t i m e p e r Failure.
**See Appendix E f o r d a t a f r o m a later survey.
N O T E : T h e following tables in A p p e n d i x A contain reliability d a t a f o r e q u i p m e n t categories t h a t h a d a
small s a m p l e size (4- 7 failures) :
Table 6 Circuit breakers used as m o t o r starters
Table 8 Generators driven b y m o t o r , diesel, o r gas engine
Table 9 Disconnect switches - o p e n
Table 15 Cable joints, 601-15 000 V, above g r o u n d a n d aerial
Table 16 Cable joints, 601-15 000 V, thermosetting
Table 19 Fuses
Table 19 Protective relays
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

effort is reduced the maintenance costs 141 IEEE COMMITTEE REPORT, Relia-
go down. This may increase the failure bility of Electric Utility Supplies to
rate of the components in the power Industrial Plants, Conf Record 1975 Z &
system and raise the costs associated CPS Technical Conference, pp 131-133.
with failures. There is a n optimum
amount of maintenance for minimum [51 GAVER, D. P., MONTMEAT, F. E.,
total owning cost of a complete power and PATTON, A. D. Power System Reli-
system. ability, I -Measures of Reliability and
The subject of Electrical Preventive Methods of Calculation, ZEEE Trans on
Maintenance is discussed in Chapter 5. PA & S, July 1964, pp 727-737.
Some data are shown in Tables 21 and [61 RINGLEE, R. J. and GOODE, S. D.
22 on the effect of the frequency and On Procedures for Reliability Evalua-
quality of scheduled electrical preven- tion of Transmission Systems, Zbid,
tive maintenance. These data have been April 1970, pp 527-537.
used to calculate the effect of mainte-
nance quality on the failure rate of [71 ENDRENYI, J., MAENHAUT, P. C.,
transformers, circuit breakers, and PAYNE, L. C. Reliability Evaluation of
motors shown in Table 23. Unfor- Transmission Systems with Switching
tunately the data do not relate the After Faults- Approximations and a
amount or cost of component mainte- Computer Program, Zbid, pp 196.31875,
nance to the failure rate. Nov/Dec 1973.
The effect of the cost of component
scheduled electrical preventive mainte- 181 BILLINTON, R. and GROVER, M. S.
nance on the failure rate has not been A Sequential Method for Reliability
included in this book. More industry Analysis of Distribution and Transmis-
studies and published data are needed sion Systems, Proceedings 1975 Annual
on this subject. Reliability and Maintainability Sympo-
sium, J a n 1975, pp 460-469.
2.5 References2
[91 CHRISTIAANSE, W. R., Reliability
111 IEEE COMMITTEE REPORT, Calculations including the Effects of
Report on Reliability Survey of Indus- Overloads and Maintenance, IEEE
trial Plants, ZEEE Transactions on Trans on PA & S, July/Aug 1971, pp
Industry Applications, MarchlApril 1974, 1664-1676.
pp 213-235.
1101 AYOUB, A. K., and PATTON, A. D.
121 DICKINSON, W. H. e t al, Funda- A Frequency and Duration Method for
mentals of Reliability Techniques as Generating System Reliability Evalua-
Applied to Industrial Power Systems, tion, IEEE Trans Power App Syst,
Conf Record 1971 ZEEE Z & CPS Techni- Nov/Dec 1976, pp 192S1933.
cal Conference, pp 1&31.
1111 IEEE COMMITTEE REPORT,
131 PATTON, A. D. and AYOUB, A. K. Report on Reliability Survey of Indus-
Reliability Evaluation, Systems Engi- trial Plants, ZEEE Transactions on
neering for Power: Status and Prospects, Industry Applications, JulylAug 1975.
U.S. Energy Research and Development
Administration, publication CONF- References [ l l , 141, [111, and [121 a r e re.
750867, 1975, pp 275-289. printed in Appendixes A, B, C, and D.

40
IEEE
PLANNING AND DESIGN Std 493-1980

[121 PATTON, A. D. et al, Cost of Apparatus and Systems), vol 77, August
Electrical Interruptions in Commercial 1958, pp 60G635.
Buildings, IEEE I & CPS Conference
Record of May 5-8, 1975. [141 DICKINSON, W. H. Economic
Evaluation of Industrial Power Systems
[131 JEYNES, P. H. and VAN Reliability, Trans AZEE (Applications
NEMWEGEN, L. The Criterion of and Industry) Vol 76, Nov 1957, pp
Economic Choice, Trans AIEE (Power 264-272.

41
3. Summary of Equipment Reliability Data

3.1 Introduction These reliability data on each com-


A knowledge of the reliability of ponent of electrical equipment can then
electrical equipment is an important be used to represent historical experi-
consideration in the design of power dis- ence for use in cost-reliability and cost-
tribution systems for industrial plants availability tradeoff studies in the
and commercial buildings. Ideally these design of new power distribution sys-
reliability data should come from field tems.
use of the same type of equipment From 1973 to 1975 the Power Systems
under similar environmental conditions Reliability Subcommittee of the IEEE
and similar stress levels. In addition Industrial Power Systems Department
there should be a sufficient number of conducted and published [ll, [21 sur-
field failures in order to represent a n veys of electrical equipment reliability
adequate sample size. It is believed that in industrial plants. These reliability
eight field failures are the minimum surveys of electrical equipment and
number necessary in order to have a electric utility power supplies were
reasonable change of determining a extensive, and summaries of pertinent
failure rate or a n “average downtime reliability data are given in this
per failure” to within a factor of two. chapter.
The types of reliability data needed on (1)Failure rate and outage duration
each component of electrical equipment time for electrical equipment and elec-
are: tric utility power supplies
(2) Failure characteristic or failure
(1)Failure rate-failures per year
modes of electrical equipment; that is,
(2) Average downtime to repair or
the effect of the failure on the system
replace a piece of equipment after a
(3) Causes and types of failures of
failure-hours (or minutes) per failure
electrical equipment
(3) Information on pertinent factors
than can have an effect on (1) or (2) ‘Numbers in brackets correspond to those in
above. the References at t h e end of this Section.
IEEE
SUMMARY OF EQUIPMENT RELIABILITY DATA Std 493-1980

(4) Failure repair method and failure (1)Partial or complete plant shut-
repair urgency down, or below-standard plant operation
(5) Method of service restoration after (2) Unacceptable performance of
a failure user’s equipment
(6) Loss of motor load versus time of (3) Operation of the electrical protec-
power outage. tive relaying or emergency operation of
the plant electric system
In addition reference is made to sum-
(4) Deenergization of any electric cir-
maries of pertinent reliability data and cuit or equipment
information that are contained in other
chapters. This includes: A failure of an in-plant component
causes a forced outage of the
(7) Maximum length of time an inter-
component,and the component thereby
ruption of electrical service will not stop
is unable to perform its intended func-
plant production. tion until it is repaired or replaced.
(8) Plant restart time after service is
All of the 60 electrical equipment
restored following a failure t h a t caused
categories listed in Table 11 have at
a complete plant shutdown.
least 8 or more failures. This is con-
(9) Cost of power interruptions to
sidered a n adequate sample size in order
industrial plants and commerical build-
to have a reasonable chance of deter-
ings. mining a failure rate within a factor of
(10) Example showing that the two
two. Failure rate and average downtime
power sources in a double-circuit utility per failure data for a n additional seven
supply are not completely independent. categories of equipment are contained
(11)Equipment failure rate multi-
in [11 (Appendix AJ. These additional
pliers versus maintenance quality.
categories of equipment have between 4
(12) Percentage of failures caused by
to 7 failures and might be considered by
inadequate maintenance versus month
some as too small a sample size, they
since maintained include:
All of the reliability data summarized
in the above twelve items are taken (1) Circuit breakers used as motor
from the IEEE surveys of industrial starters
plants [11 [21 and commercial buildings (2) Generators driven by motor,
[31. The detailed reports are given in diesel, or gas engine
Appendixes A, B, C, and D. A later sur- (3) Disconnect switches-open
vey [41 of the reliability of switchgear (4) Cable joints, 601-15,000 V, above
bus is included in Appendix E. ground and aerial
( 5 ) Cable joints, 601-15,000 V, ther-
3.2 Reliability of Electrical Equip- mosetting
ment (6) Fuses
The pertinent failure rate and aver- (7) Protective relays
age downtime per failure information
for the in-plant electrical equipment are The “failure repair method” and the
given in Table 11. I n compiling these “failure repair urgency” have a signifi-
data, a failure was defined as any trou- cant effect on the “average downtime
ble with a power system component that per failure” for some equipment
causes any of the following effects: categories. Special studies have been

43
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

made of this subject for nine equipment for the one case analyzed the actual
categories t h a t are marked with a n failure rate of a double-circuit utility
asterisk (*I in Table 11. These studies supply is more than 200 times larger
are reported in Tables 48 through 56 of than the calculated value for two com-
111 (Appendix B). pletely independent utility power
sources. See Table 36 of Chapter 7 for a
3.3 Reliability of Electric Utility summary table comparing the actual
Power Supplies to Industrial Plants and calculated failure rates of a double-
The “failure rate” and the “average circuit utility power supply.
downtime per failure” of electric utility It is believed t h a t utility supply
supplies to industrial plants are given failure rates vary widely in various
in Table 12. Additional details are locations. One of the significant factors
given in [21 (Appendix D).A total of 87 in this difference is believed to be dif-
plants participated in the IEEE survey ferent exposures to lightning storms.
covering the period from January 1, Thus, average values for the utility sup-
1968 through October 1974. ply failure rate may not be valid to use
The survey results shown in Table 12 a t any one location. Local values should
have distinguished between power be obtained, if possible, from the utility
failures that were terminated by a involved, and these values should be
switching operation versus repair or used in reliability and availability stu-
replacement of equipment. The latter dies.
have a much longer outage duration An earlier IEEE reliability survey of
time. Some of the conclusions t h a t can electric utility power supplies to indus-
be drawn from these IEEE data are: trial plants was published in 1973 and
(1)The failure rate for single-circuit is reported in Table 3 of [11 (Appendix
supplies is about six times t h a t of mul- A). The earlier survey had a smaller
tiple circuit supplies which operate with data base and is not believed to be as
all circuit breakers closed; and the aver- accurate nor as up to date as the one
age duration time of each outage is summarized in Table 12. The earlier
about 2.5 times as long survey of electric utility power supplies
(2) Failure rates for multiple-circuit had lower failure rates.
supplies which operate with either a
3.4 Failure Characteristic of Electri-
manual or an automatic throwover
cal Equipment
scheme are comparable to those for
The failure characteristic or failure
single-circuit supplies, but throwover
modes of electrical equipment are
schemes have a smaller average failure
important. They identify the effect of
duration than single-circuit supplies
the failure on the system and are
(3) Failure rates are highest for util-
needed in system reliability studies.
ity supply circuits operated a t distribu-
Tables 13, 14, and 15 give the failure
tion voltages and lowest for circuits
characteristic of transformers, circuit
operated at transmission voltages
breakers, and 11 other categories of
I t is important to note t h a t the data electrical equipment.
in Table 12 show that the two power There are some “failure modes” of cir-
sources of a double-circuit utility supply cuit breakers t h a t require backup pro-
are not completely independent. This is tective equipment to operate; for exam-
analyzed in a n example in 7.1.15, where ple, “failed to trip” or “failed to inter-

44
IEEE
SUMMARY OF EQUIPMENT RELIABILITY DATA Std 493-1980

Table 12
IEEE Survey of Reliability of Electric Utility Supplies to Industrial Plants [21
(See Tables 11,111, IV, V in A p p e n d i x D f o r additional details)

Single Circuit Utility Supplies


Failures per Average D u r a t i o n
Unit-Year** ( m i n u t e s p e r failure**)
Voltage level AS hR h rS R
' r
V<15 kV 0.905 2.715 3.621 3.5 165 125
1 5 k V < V 6 3 5 kV - 1.657 1.657 - 57 57
v>35 kV 0.527 0.843 1.370 1.5 59 37
All 0.556 1.400 1.956 2.3 110 79

Multiple Circuit Utility Supplies


All Voltage Levels
Failure per Average D u r a t i o n
Unit-Year** ( m i n u t e s per failure* *)
Switching s c h e m e hS AR A 'S 1 r
All breakers closed 0.255 0.057 0.312 8.5 130 31
Manual t h r o w o v e r 0.732 *0.118 0.850 8.1 * 84 19
Automatic throwover 1.025 0.171 1.196 0.6 96 14
All 0.453 0.085 0.538 5.2 110 22

Multiple Circuit Utility Supplies


All Switching S c h e m e s
Failures per Average D u r a t i o n
Unit-Year* * ( m i n u t e s p e r failure**)
Voltage level AS hR h rS R' r
V<15 kV 0.640 0.148 0.788 4.7 149 32
15 k V < V < 3 5 k V 0.500 *0.064 0.564 4.0 *115 17
v > 3 5 kV 0.357 0.067 0.424 6.1 184 34

Multiple Circuit Utility Supplies


All Circuit Breakers Closed
Failures per Average D u r a t i o n
Unit-Year* * ( m i n u t e s per failure**)
Voltage level AS AR h 'S rR r
V<15 k V 0.175 *0.088 0.263 0.7 *335 112
1 5 kV<V<35 k V 0.342 *0.019 0.361 7.0 *120 13
v>35 kV 0.250 0.061 0.311 11.o 203 49

*Small sample size - less t h a n 8 failures.


**Failure rates A a n d average d u r a t i o n s r subscripted S a n d R are, respectively, rates a n d d u r a t i o n s of
failures t e r m i n a t e d b y switching a n d b y repair o r replacement. Unsubscripted rates a n d d u r a t i o n s are
overall values.

45
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 13 rupt.” Both of these failure modes


Failure Characteristic of Transformers would require that a circuit breaker
further up the line be opened, and this
% Failure Characteristic opening would result in a larger part of
the power distribution system being
92 A u t o m a t i c removal b y protective
equipment disconnected. Thus the data on failure
1 Partial failure reducing capacity modes of circuit breakers shown in
7 Manual removal Table 14 are important in system relia-
bility studies.
The data in Table 15 show that a sig-
nificant percentage of the failures of

Table 14
Failure Modes of Circuit Breakers
(Percentage of Total Failures in Each Failure Mode)

All Metalclad Drawout *Fixed Type


Circuit 6 0 1 - 1 5 000 0-600 V 0-600 V
Breakers All V All Sizes All Sizes All
% % % % % % Failure Characteristic

5 5 2 7 8 6 Failed to close when i t should


9 12 21 0 0 2 Failed while o p e n i n g
42 58 49 71 5 4 Opened when i t should n o t
7 6 4 9 5 4 Damaged while successfully
opening
2 1 0 0 0 4 Damaged while closing
32 16 24 10 77 73 Failed while in service ( n o t
while o p e n i n g or closing)
1 0 0 0 0 2 Failed during testing o r
maintenance
1 2 0 3 0 0 Damage discovered during
testing o r m a i n t e n a n c e
1 0 0 0 5 5 Other

100% 100% 100% 100% 100% 100% Total percentage

165 117 53 59 39 48 N u m b e r of failures in t o t a l


percentage
8 7 0 7 1 1 N u m b e r n o t reported

173 124 53 66 40 49 Total failures

*Includes molded case.


IEEE
SUMMARY OF EQUIPMENT RELIABILITY DATA Std 493-1980

motor starters, motors, and disconnect


switches are discovered during testing
or maintenance.

3.5 Causes and Types of Failures of


Electrical Equipment
Data are given in Tables 16 and 17
on :
(1) Failures, damaged part
(2) Failure type
CJ
rl
(Do
(3) Suspected failure responsibility
(4) Failure initiating cause
0 0 0
(5) Failure contributing cause
The data in Table 17 indicate that N m r l
indequate maintenance is suspected as
responsible for a significant percentage
of the failures for several categories of rl ( D m
CJ
electrical equipment.
0 1 0 0
3.6 Equipment Failure Rate Multi-
pliers Versus Maintenance Quality
The relationship between mainte-
nance practice and equipment failure is 0 0 0

discussed in 5.3.
Equipment failure rate multipliers
versus maintenance quality are given in
Table 23 of Chapter 5 for transformers, 0 0 0
circuit breakers, and motors. These mul-
tipliers were determined in a special
study part 6 of 111; (Appendix B). The
failure rate of motors is very sensitive W ( D r l
to the quality of maintenance. rl

The percentage of failures due to


inadequate maintenance versus the
months since maintained is given in
0 (Do
Table 22 of Chapter 5 for circuit break- rlrl

ers, motors, open wire, transformers,


and all electrical equipment classes
0 0 0
combined. A high percentage of equip- m
ment failures are blamed on inadequate
maintenance if there has been no
maintenance for more than two years CD O N
m CJ
prior to the failure.

47
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

2
$28
* m o *
w
m o rill rl

ig * o r l w o o * m m

gs * m o m 0 0 0 0 0
r l r l w
m n

* o m 0 0 0 o m 0
Q,

* o r l * o Q , o m rl
rl m

q g t - o o m t - - 0
rl
rl

E
3n * om o m c n
N
m r l m 0

* m o o o w N m N
rl rl rl

%
. EI

I- -
IEEE
SUMMARY OF EQUIPMENT RELIABILITY DATA Std 493-1980

3.7 Failure Repair Method and duration, most plants lose motor load.
Failure Repair Urgency However, for power outages between 1
The “failure repair method” and the and 10 cycle duration, only about half
“failure repair urgency” have a signifi- a s many plants lose the motor load.
cant effect on the “average downtime Test results on the effect of fast bus
per failure.” Table 18 shows the transfers are reported in [ 5 ] . This
percentages of these two parameters for includes 4 kV induction and synchronous
thirteen classes of electrical equipment. motors with the following types of
A special study on this subject is loads: (1)forced draft fan, (2) circulat-
reported in Tables 48 through 56 of [11 ing water pump, (3) boiler feed booster
(Appendix B) for nine categories of pump, (4) condensate pump, (5) gas
electrical equipment (marked with a n * recirculation fan. A list of prior papers
in Table 11 of this chapter). on the effect of fast bus transfer on
The IEEE data on “method of electri- motors is also contained in [ 51 .
cal service restoration to plant” are
shown in Table 19. A percentage break-
down of the total shows:
3.9 Critical Service Loss Duration
Replacement of failed component Time
with spare 22% What is the maximum length of time
Repair of failed component 22% t h a t an interrupti00 of electrical service
Other 22% will not stop plant production? The
Utility service restored 12% median value for all plants is 10.0
Secondary selection -manual 11% seconds. See Table 4 in Chapter 2 for a
Primary selection -manual 7% summary of the IEEE survey of indus-
Primary selection-automatic 2% trial plants.
Secondary selection-automatic 2% What is the maximum length of time
Network protector operation- before a n interruption to electrical serv-
automatic 0+% ice is considered critical in commerical
The most common methods of service buildings? The median value of all com-
restoration are replacement of failed merical buildings is between 5 and 30
component with a spare or repair of minutes. See Table 5 in Chapter 2 for a
failed component. Only 22 percent of summary of the IEEE survey of com-
the time is primary selection or secon- mercial buildings.
dary selection used. This would indicate
that most power distribution systems in
3.10 Plant Restart Time
the IEEE survey were radial.
What is the plant restart time after
3.8 Loss of Motor Load Versus Time service is restored following a failure
of Power Outage t h a t has caused a complete plant shut-
A special study has been reported in down? The median value for all plants
Table 47 of [11 (Appendix B) on loss of is 4.0 hours. See Table 6 in Chapter 2
motor load versus time of power outage. for a summary of the IEEE survey of
For power outages longer than 10 cycle industrial plants.

49
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

rl * r- d rl

0 0 W
rl
Q,
m
hl
hl
0 0 W *
I+
hl
rl

0 0 0 0 W 0 m N m rl
m rl hl rl

W
rl
0 W *
rl
0
rl
m * W W
m (9
hl

0 0 hl Q, 0 hl m rl rl (9
m hl m hl

W 0 W m W 0 m 0 hl 0
hl rl rl m

Q, 0 * r-
rl
N
hl
0 hl
hl
r-
rl
Q,
m

m m 0 m 0 0 0 m m
0
* rl m

Q,
01
0 W * m
I+ *
0 rl 0 00 *

m m co
Q,
rl
0 0 Q,
rl
0 W
* 0
rl

m
r(
0 Q, rl r-
rl
* 0 rl m
m W

co 0 rl 0 co m 0 0 oa rl
r l m I+

m
hl
0 * m m
hl
W m 4 (9
m
m
rl

oa
m
0 hl m rl
rl
Q, hl * 0
m m
hl
IEEE
Std 493-1980
SUMMARY OF EQUIPMENT RELIABILITY DATA

>Nrl
m h l
* 0 9 N hl 0 0 00-

0 0 0 0 0 0 0 0 0 0
3 0 0 rl rl
* m

>ria
N
*
N
0 r- N 0 0 0 0 0 0
rl

2rlm r- 0 0
I+
*
rl
m 0 0 oorl
rl
N

3 0 0 m m 0 0 0 0 0 0
mhl * 0 0

0 0 m Q, 0 0 o o m
3m00 m N rl
A N

0 0 0 0 0 0 0 0 0 0 ooul
m r l cc

o * m t- hl 0 0 0 0 0 m o c
hl d
ri

omm Q, m m 0 0 m o oolr
d
hl

o w 0
hlm
* 0
hl
m 0 0 o m o o m

ori00 00 W 0 m rl o * oor-
W

om00 m m rl hl rl r l r l oom
m
r l r i rl

orlm r- 0 ri rl hl o r i oom
N
rlrl rl

51
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

0 0 0 0
r l r
0.1
(
0 0 *
0.1
w
rl
0 0 0 0 0 0

o m o m 0.1 o o 0-a 0.1 0 0 0 0 0


r l 0 . 1 0.1

@ l o o * 00 0.1 rl 0 m o o o m r l
rl m rl

o o o c o rl m o m 0 r l o 0 0.10.1
0.1 m

* w o o 0 t-
rl
0 0 0
m
rl
rl
0 0 0 ( D o

g o o 0 0 0 m 0 0 Lo 0 0 0 Loo
r l 0 . 1
4 0 . 1 rl

g o l o o o m 0 0 0 0 0 0 0 0 0
9
rl 0.1 0.1

g ( m m r l 0 * 0 0 m 0 0 0 0 O D
0.1

o w 0 0 (0 m 0 0.1 m w 0 0 0 0
rl m

l o F i o t - 0
rl
0 0.1 *
m
0.1 0 Lo
rl
rl o m

0 0 0 0 0 0 0 0 0 m r l
0 0
* 0.1

m
rl
o o 0 w 0 0 *
0.1
w o o o m m
IEEE
Std 493-1980
SUMMARY OF EQUIPMENT RELIABILITY DATA

hi d hi vi d
Q,
Q,

*m (D rl
m
(0
rl
0

hl hl 0
m 0
hl hl
rl

m 0 m (D 0
m hl

Q, rl (0 0 Q,
m hl rl

m 0 m m 0
m rl

C m W 0
Q,
hl m

In u3 0
m C
hl

C 0 0 0
0 m
r-

C hl 0 0
(0
rl m

hl
0.1
C *
r-
hl 0

r-
(0
C *m 0 0

C hl In C
*
Q,
hl

m C m
* * C
m

53
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

P
Y

5a
al
M E
0
P
t! P
2
d 5E
Y Y
0
Ui6 l2 E

t-hl o m 0 W
h l r l rl 0 hl
d

* o 0 0 0 m
hl 0 hl
rl

* m o o 0 r l w 0 hl
d hl *
0.163
d 0
rl
hl
rl

m * h l r l o m
rl
d
m
W
*
r l h l 0
0
rl
0
rl

0 0 0 0 0 m I n 0 0 0 0
hl d m m 0 hl
rl

m m o o m 0 0 o m 0 0
hl rl h l r l hl 0 hl
rl

m o r - 0 0 r - 0 o m 0 hl
m rl rl 0 rl
d

0 0 0 0 0 m r - 0 0 0 a,
t- hl 0 W
d

o o m o o o * m o 0 m
c.l m h l r l rl 0 d
rl

m o * o o oa, O N 0 m
rl m h l hl 0 rl
rl m

0 0 0 0 0 hlo o m 0 m
r l r l t- 0 W
rl

w r l w w o r l m * a , 0 0
r l m hl 0 W
rl rl

m o m m o m a , o m 0 m
hl N m 0 t-
rl

r l w r l r l o ILYW r l r l 0 rl
m 0 r-
rl d

t - h l T I h l O
+ hlhl N h l 0 *
d hlhl r l h l 0 0
rl hl
rl
IEEE
SUMMARY OF EQUIPMENT RELIABILITY DATA Std 493-1980

3.11 Cost of Power Interruptions to Table 20


Industrial Plants and Commercial Failure Rate Improvement Factor of
Buildings
Y
Electrical Equipment in Industrial
Plants DW& 11 Year Interval
The cost of power interruptions to
Between 1962 AIEE Survey and
industrial plants is summarized in
1973 IEEE Survey
Tables 7 and 8 of Chapter 2.
The cost of power interruptions to Failure Rate Ratio
commercial buildings is summarized in AIEE (1962)
Tables 9 and 10 of Chapter 2. The effect Equipment Category IEEE (1973)
of computer outages on the costs is
Generators
shown in these tables. Steam turbine driven 16.0
Gas turbine driven** 13.0
Cable
3.12 Reliability Improvement of Nonleaded in underground
conduit 9.7
Electrical Equipment in Industrial Nonleaded, aerial 5.8
Plants Between 1962 and 1973 Lead covered in underground
conduit 3.4
The failure rates of electrical equip- Nonleaded in above-ground
ment in industrial plants have improved conduit 1.6
considerably during the eleven-year Cable joints and terminations
interval between the 1962 AIEE relia- Non-leaded 5.3
Leaded 2.0
bility survey [61 and the 1973 IEEE reli-
ability survey [ll. Table 20 shows how Motors, 50 hp and larger***
Synchronous 8.4
much the failure rates have improved Induction 7.1
for several equipment categories. These Circuit breakers
data are calculated from a 1974 report Metalclad drawout,
[71. In 1962 circuit breakers had failure 0-600 V 6.0
rates that were 2.5 to 6.0 times higher Metalclad drawout,
Above 6 0 0 V 2.9
than in 1973. The largest improvements Fixed 2.4-15 kV 2.5
in equipment failure rates have
Disconnect switches
occurred on generators, cables, motors, Open, above 600 V 3.4
and circuit breakers. The authors dis- Enclosed, above 6 0 0 V 1.6
cussed some of the reasons for the Open wire 3.4
failure rate improvements during the
Transformers
eleven-year interval. It would appear Below 1 5 kV,
that manufacturers, application 0-500 kVA**** 2.0
engineering, installation engineering, Below 1 5 kV,
above 500 kVA 2.0
and maintenance personnel have all Above 15 kV 1.6
contributed to the overall reliability
Motor starters, contactor type
improvement. 0-600 V 1.3
The authors also make a comparison Above 6 0 0 V 1.3
the “actual downtime per failure” for
all equipment categories shown in the *Unit = 1000 circuit ft.
table. In general, the “actual downtime **Middle East pipeline data only for 1962.
per failure” was larger in 1973 than in ***250 hp and larger for 1962.
1962. ****300-750 kVA for 1973.

55
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

3.13 Other Sources of Reliability circuit breaker per year and the cost of
Data spare parts consumed per circuit
The reliability data from industrial breaker per year.
plants which are summarized in this ANSI/IEEE Std 500 1977 1171, is a
chapter are based upon References [ l l reliability data manual for use in the
[21 and [31 which were published during design of nuclear power generating sta-
1973-1975. Reference [SI is a n earlier tions. The equipment failure rates cover
reliability survey of industrial plants such equipment as annunciator
which had been published in 1962. modules, batteries and chargers,
Many sources of reliability data on blowers, circuit breakers, switches,
similar types of electrical equipment relays, motors and generators, heaters,
exist in the electric utility industry. transformers, valve operators and actua-
The Edison Electric Institute (EEI) has tors, instruments, controls, sensors,
collected and published reliability data cables, raceways, cable joints, and ter-
on power transformers, power circuit minations. No information is included
breakers, metal-clad switchgear, motors, on equipment outage duration times.
excitation systems, generators, and Future revisions to ANSIIIEEE Std
prime mover generation equipment 500-1977 will include mechanical com-
[SI - [141. Most EEI reliability activities ponent data.
do not collect outage duration time The Edison Electric Institute also
data; only Reference [41 on prime mover sponsors the Nuclear Plant Reliability
generation equipment contains such Data System (NPRDS) which collects
data. failure data on electrical components in
Failure rate data and outage duration the safety systems of nuclear power
time data of power transformers, power plants. Outage duration time data are
circuit breakers and buses are given in collected on each failure. It is expected
References [51 and [SI. These data have t h a t NRPDS will become a source of
come from electric utility power sys- reliability data for future revisions to
tems. ANSI/IEEE Std 500-1977.
Very little published data are avail-
3.14 References2
able on the failure modes of power cir-
[11 IEEE COMMITTEE REPORT,
cuit breakers and on the probability of a
Report on Reliability Survey of Indus-
circuit breaker not operating when
trial Plants, Parts 1-6 ZEEE Transac-
called upon to do so. An extensive
tions on Industry Application,
worldwide reliability survey of the
March/April, July/August, September/
major failure modes of power circuit
October 1974, pp 213-252, 45G476, 681.
breakers above 63 kV on utility power
systems has been made by CIGRE 13-06 [21 IEEE COMMITTEE REPORT, Relia-
Working Group [71. Failure rate data bility of Electric Utility Supplies to
and failure per operation data have Industrial Plants, IEEE -1CPS Techni-
been determined for each of the major cal Conference, Toronto, Canada, May
failure modes. Outage duration time 5-8, 1975, pp 131-133 in 75-CH0947-
data have also been collected. In addi- 1-1A.
tion data have been collected on the
costs of scheduled preventive mainte- References 121 a n d [31 a r e reprinted in Ap-
nance; this includes the manhours per pendixes A, B, C, and D.

56
IEEE
SUMMARY OF EQUIPMENT RELIABILITY DATA Std 493-1980

[31 IEEE COMMITTEE REPORT, Cost [lo1 Report on Metalclad Switchgear


of Electrical Interruptions in Commer- Troubles, 1975, EEZ Publication No
cial Buildings, IEEE-ICPS Technical 76-82, Dec 1976.
Conference, Toronto, Canada, May 5-8,
1975, pp 124-129 in 75-CH0947-1-1A. [111 Report on Motor Troubles, 1975,
EEI Publication No 76- 79, Dec 1976.
[41 See Appendix E-IEEE COMMIT-
TEE REPORT, Report of Switchgear [121 Report on Excitation System Trou-
Bus Reliability Survey of Industrial bles, 1975, EEI Publication No 76-78,
Plants, IEEE Transactions on Industry Dec 1976.
Applications, MarIApr 1979, pp [131 Report on Generator Troubles,
141-147). 1975, EEI Publication No 76-77, Dec
[51 AVERILL, E. L. Fast Transfer Test 1976.
of Power Station Auxiliaries, IEEE [141 Report on Equipment Availability
Transactions on Power Apparatus and for Ten Year Period 1965-1974, EEZ
Systems, Vol PAS-96, pp 1004-1009, Publication No 75-50 (Prime Mover Gen-
May/June 1977. eration Equipment). These data are now
[61 DICKINSON, W. H. Report of Relia- collected and published by National
bility of Electrical Equipment in Indus- Electric Reliability Council.
trial Plants, AIEE Transactions, P a r t 11, 1151 PATTON, A. D. Determination and
pp 13Z5151,July 1962. Analysis of Data for Reliability Studies,
[71 McWILLIAMS, D. W., PATTON, A. ZEEE Transactions of Power Apparatus
D., HEISING, C. R. Reliability of Electr- and Systems, Vol PAS-87 J a n 1968.
ical Equipment in Industrial Plants- [I61 MALLARD, S. A. and THOMAS, V.
Comparison of Results from 1959 Sur- C. A Method for Calculating Transmis-
vey and 1971 Survey, IEEE-ICPS sion System Reliability, Vol PAS-87, Mar
Technical Conference, Denver, J u n 2-6, 1968.
1974, pp 10&112 in 74CH0855-71A.
[SI Report of Power Transformer Trou- [I71 Will be published in Electra.
bles, 1975, EEI Publication No 76-80,
Dec 1976. [181 ANSI/IEEE Std 50&1977, IEEE
Guide to the Collection and Presenta-
[91 Report on Power Circuit Breaker tion of Electrical, Electronic, and Sens-
Troubles, 1975, EEI Publication No ing Component Reliability Data for
76-81, Dec 1976. Nuclear Power Generating Stations.

57
4. Evaluating and Improving
Reliability of an Existing Plant

4.1 Introduction be made per revenue dollar. However,


The 1974 survey of electrical equip- most utilities are willing to discuss the
ment reliability in Industrial Plants ill1 various supply systems that are avail-
and subsequent investigations showed able to their customers. Many times, a n
the utility supply as being the largest option is available (sometimes with
single component affecting the reliabil- financial sharing between the user and
ity of a n industrial plant. (See Table 3 the utility) that will meet the exact
in Appendix A and Table 12 in Chapter reliability needs of a n industrial plant.
3.) The industrial user may or may not A thorough and properly integrated
be in a position to improve the utility investigation of the entire electric sys-
supply reliability and, as a result, must tem (plant and supply) will pinpoint the
also focus his attention on critical areas components or sub systems having
within his own plant. A logical approach unacceptable reliability. Some impor-
to the analysis of options available in tant general inquiries are listed below.
the industrial plant (in terms of both Many of these questions apply to both
utility supply and plant distribution) the utility and the plant distribution
will lead to the most reliability improve- systems.
ment for the least cost. In many
instances, reliability improvements can (1)How is the system supposed to
be obtained without any cost by making operate?
the proper inquiries. (2) What is the physical condition of
Most industrial users simply “hook the electrical system?
up” to the utility system and do not
fully recognize that their requirements (3) What will happen if faults occur
can have a n impact on how the utility a t different points?
supplies them. A utility is somewhat
bound by the system available a t the ‘Numbers in brackets correspond to those in
plant site and the investment that can t h e References a t the end of this Section.

58
IEEE
EVALUATING AND IMPROVING PLANT RELIABILITY Std 493-1980

(4) What is the probability of a commonly caused by improper settings


failure and its duration? in protective devices, circuit breaker
contacts that were welded shut, or
( 5 ) What is the critical duration of a
relays that were not set (or did not
power interruption that will cause sig- react) properly. This chapter shows the
nificant financial loss? (That is, will a
plant engineer how to minimize down-
one-minute interruption cost production time by analyzing his system.
dollars or merely be a n inconvenience?)
(6) Is there any fire or health hazard 4.2 Utility Supply Availability
that will be precipitated by an electrical Loss of incoming power will cause a n
fault or a power loss? interruption to critical areas unless
alternate power sources are available.
(7) Is any equipment vulnerable to
Therefore, the reliability of the incam-
voltage dips or surges? ing power is of paramount importance
The answers to these and similar to the plant engineer. I t can be stated
questions if properly asked can and will t h a t different plants and even circuits
result in savings to the industrial user within a plant vary in their response to
if they produce action. loss of power. In some cases, production
A question at this point should be- will not be significantly affected by a
How do I get started? However, another 10-minute power interruption. In other
question could be-Why bother? The cases, a 10-millisecond interruption will
answer to the former question is cause significant loss. The plant
covered in this chapter, and the answer engineer should assess his plant’s vul-
to the latter question is based on the nerability and convey his requirements
following analogy. When preparing for a to the local utility (as well as his own
long trip, a motorist will make sure that management). See Section 2.2 of
his car is in good working condition Chapter 2 for information on economic
before he leaves. He will check the loss versus unavailability of incoming
brakes, engine, transmission, tires, power.
exhaust system, etc., to see that they The local utility should be able to
are in good condition and make the supply a listing of the number, type and
required repairs. For the motorist duration of power interruptions over the
knows that “on the road” breakdowns preceding 3 to 5 year period. The utility
and failures are expensive, time con- should also be able to predict the future
suming, and can be hazardous. In a n average performance based on the his-
industrial plant, a n unplanned electrical torical data and planned construction
failure will consume valuable produc- projects. In addition, the utility may be
tion time as well as dollars and may able to supply the “feeder” performance
cause injury to personnel. Circuit of other circuits near the facility under
breakers, relays, meters, transformers, investigation. A second alternative
wireways, etc, need periodic checks and would be to obtain a diagram of the
preventive maintenance (see Chapter 5) utility feed and evaluate its availability
to improve the likelihood of trouble-free using Chapter 2 methods. As a last
performance. Some plants have been resort, the average numbers in this book
shut down completely by events such as will provide a good base (Table 12 of
a ballast failure. These “shutdowns” are Chapter 3).

59
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

The utility’s history of interruptions sion. A list of questions include:


can be compared with recorded plant
dollar loss in verifying the process vul-
(1) How long will the plant be
without power if:
nerability. By assigning a dollar loss to
(a) The main transformer fails
each interruption it will be possible to
(b) The feed to the main trans-
determine a relationship between the
former fails
duration of a power loss and a monetary
loss for a particular industrial plant. (c) The pole supporting the plant
feed is struck by a vehicle and downed
When the actual outage cost is higher
(d) The utility main line fuse or
or lower than would be predicted, the
protector interrupts
cause of the deviation should be deter-
(e) The utility main feed breaker
mined (that is, a 15 minute power loss
opens for a fault
a t a shift change will be less costly than
(f) The utility substation trans-
one during peak production). With a
former fails
refined cost formula in hand, the cost of
available options versus projected losses (g) The utility substation feeds are
interrupted
can be evaluated.
Occasionally, a plant will experience (2) What kind of response time can be
problems a t times other than during a expected from the utility for loss of
recorded outage. These problems may be power:
caused by voltage dips (or-more
rarely -voltage spikes) which are diffi-
(a) During a lightning storm
(b) During a low trouble period
cult to trace. With problems such as
these, it is necessary to begin recording (That is, “normal” conditions.)
(c) During a snow or ice storm
the exact date and time of these
occurrences and ask the utility to (d) During a heat storm (That is,
long periods of high temperatures.)
search for faults or other system
disturbances at (or near) the specific (3) What should be done when the
times that they have been recorded. It plant experiences a n interruption
would be wise to convey the fault times
(a) Who should be called? A name
to the utility reasonably soon after the
and number should be made available to
fault (that is, call them the following
all responsible personnel. Alternates
day). It must be emphasized t h a t unless
and their numbers should be included
these problems are significant in terms
also.
of dollars lost, safety or frequency (that
(b) What information should be
is, every other day), it is not reasonable
given to those called?
to pursue the cause of voltage dips since
(c) How should plant people be
they are a natural phenomenon in the
trained to respond?
expansive system operated by a utility.
(d) Can plant personnel restore
Frequent dips can be caused by large
power by switching utility lines and
motor starts, welder inrush or intermit-
who should be contacted to obtain per-
tent faults in the plant’s distribution
mission to switch?
system (or even by a neighbor’s system).
I t is also reasonable to cover “what (4) Are there any better performing
i f ’ questions with the utility and to feeders near the plant and what is the
weigh their answers in any supply deci- cost of extending them to the plant?

60
IEEE
EVALUATING AND IMPROVING PLANT RELIABILITY Std 493-1980

(That is, is a spare feeder available and existence of a one-line diagram is essen-
what is the cost to make it available?) tial for any plant electrical engineer,
(a) Is this additional feed from the manager or operator. It is the “road-
same station or from another station? map” to any part of the electric system.
(b) What is the probability (fre- I n fact, a one-line diagram should be
quency and duration) of both the main prepared even if the ensuing analysis is
and the spare feeds being interrupted not done.
simultaneously? The one-line diagram should begin at
(c) What is the reliability improve- the incoming power supply. Standard
ment obtained from the additional (or IEEE symbols should be used in
alternate) feed? representing electrical components (see
(5) Will the utility protective equip- ANSI/IEEE Std 315-1975 Graphic Sym-
ment coordinate with the plant’s service bols for Electrical and Electronics
circuit breaker? If not, what can be Diagrams). It is usually impractical to
done to coordinate these series protec- show all circuits in a plant on a single
tive devices? schematic; so the initial one-line
(6) What is the available short circuit diagram should show only major com-
current, and are there plans to change ponents, circuits, and panels. More
the system so as to effect the short cir- detailed analysis may be required in
cuit current? critical areas (described later) and addi-
tional one-line diagrams should be
All of the above questions may not
prepared for these areas as required.
apply to all plants, but should be
Since a n analysis is being made from
matched with specific plant require-
the one-line diagram, the type, size and
ments.
rating of each device as well as its una-
There is a n important fact to consider
vailability should be shown on the
when a multiple ended feed is being
diagram. The diagram should include at
considered. While service is maintained
least the following information:
for a loss of one of the feeds, a voltage
depression will be seen until the fault is (1)Incoming lines (voltage, size-
cleared by proper relay action. There- capacity and rating)
fore, the plant will see a voltage dip for
(2) Generators (in plant)
any faults on all incoming feeds. If the
plant is affected with equal severity by (3) Incoming main fuses, potheads,
either a voltage dip or a short-duration cutouts, switches, main and tie breakers
(several seconds) interruption, a multi-
(4) Power transformers (rating, wind-
ple ended supply (with secondary tie)
ing connection and grounding means)
may actually worsen plant reliability.
This is just one example of the need to (5) Feeder breakers and fused
carefully evaluate the current supply switches
situation in conjunction with the net
(6) Relays (function, use and type)
improvement of various proposals.
(7) Potential transformers (size, type
4.3 Where to Begin-The Plant One-
and ratio)
Line Diagram
The “blue print” for electrical (8)Current transformers (size, type
analysis is the “one line diagram.” The and ratio)
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

(9) Control transformers advantageous to include the incoming


supply and main feeder circuit breakers
All main cable and wire runs with
(at least) and even major equipment
their associated isolating switches
(very large motors or groups requiring
and potheads. (Size and length of
the entire capacity of a main feeder
run).
position) on one diagram. The load end
All substations including integral of the feeders can be detailed on one or
relays and main panels. Exact nature more subsequent drawings. After com-
of load in each feeder and on each pletion of the one-line diagrams, a
substation. comprehensive analysis can begin. How-
The one-line diagram may show ever, the general inspection covered in
planned, as well as actual, feeder circuit 4.4 can, and should, be made concurrent
breaker and substation loads (actual with the preparation of a plant one-line
measurements should be taken). In diagram.
most industrial plants, load is added (or The one-line diagram is a picture of
deleted) in small increments, and the an ever changing electric system. The
net effect is not always seen until some efforts in preparing the diagram and
part of the system becomes overloaded analyzing the system should, therefore,
(or underloaded). Many times, circuits be augmented by a means to capture
are added without appropriate modifica- new pictures of the system (or of pro-
tion of the standard settings on the posed systems) as changes are made (or
associated upstream circuit breakers. In proposed). Therefore, a procedure should
addition, original designs may not have be formalized to ensure that all propo-
included special attention to the critical sals undergo reliability scrutiny (as well
areas of production. With these as one-line diagram update), and that
thoughts in mind, the following infor- their effect on the total system is
mation should be added to the one-line analyzed before the proposal is
diagram: approved. This process not only main-
tains the integrity, but it minimizes
(1) The original system should be
expense by more effective utilization of
identified. The exact nature of the new
existing electrical facilities.
loads and their approximate locations
should be noted. 4.4 Plant Reliability Analysis
(2) Critical areas of the system should An inspection analysis of the physical
be highlighted. condition of a plant’s distribution sys-
(3) The component reliability num- tem can be utilized (hopefully on a con-
bers from Chapter 3 should be inserted tinual basis) to improve plant reliabil-
so that the reliability performance of ity. The following inspection requires
the plant can be analyzed on an “if little, if any, capital investment while
new” basis. (It is preferable to use providing a favorable increase in relia-
numbers indigenous to a particular bility:
plant whenever this information is
(1) Equipment should be periodically
available.)
checked for proper condition, and pro-
The above information may be too grams should be-initiated for preventive
voluminous for clear representation on maintenance procedures as required.
a single drawing. It may, therefore, be (See Chapter 5 for further information.)

62
IEEE
EVALUATING AND IMPROVIUG PLANT RELIABILITY Std 493-1980

(a) Oil in transformers and circuit (b) Open-wire circuits should be


breakers should be periodically checked checked for insulator and surge arrester
for mineral, carbon, and water content failure and contamination.
as well as level and temperature. (c) The system’s key locations (of
(b) Molded case circuit breakers open area distribution centers and lines)
should be exercised periodically (that is, should be checked for foreign growth
operated ‘‘on” to “off’ to “on”). such as trees, weeds, shrubs, etc, as well
(c) Terminals should be tightened. as for general accessibility. The distrib-
Each terminal should be inspected for ution centers should be free from
discoloration (overheating) which is storage of trash, flammables, or even
generally caused by either a bad connec- general plant inventory.
tion or equipment overload. Cabinets, (d) Permanent and portable wiring
etc., should be checked for excessive should be checked for fraying or other
warmth. Remember that circuit break- loss of insulating value.
ers and fuses interrupt as a result of (e) In general, the system should be
heat in the overload mode. checked for any obvious situations
(d) Surge arresters should be where accidents could precipitate an
checked for their readiness to operate. interruption.
(2) Distribution centers should be ( 5 ) The electrical supply room(s)
checked to see that spare fuses are should be thoroughly
- . checked.

available. Spare circuit breakers may


(a) The relay and control power
also be necessary for odd sizes or special
fuses should be intact (not blown).
applications.
(b) Indicating lights should all be
(3) Switches, disconnect switches, bus
operable and clearly visible.
work, grounds should be checked for
(c) All targets should be reset so
corrosion, and unintentional entry of
t h a t none show a tripping. Counters (if
water or corrosive foreign material. It
any) should be checked and the count
may be wise to operate suspected
(number) should be recorded.
switches to see that their mechanisms
(d) The control power, batteries,
are free, so that faults can be properly
emergency lighting and emergency gen-
isolated and switches safely refused.
eration should be tested and checked to
(4) The mechanical part of the electri-
see that they are operational. In many
cal system should be checked.
cases, plants have been unable to
(a) The conduit, duct, cable tray, transfer to their spare circuit or start
and busway systems should be well sup- their standby generator because of dead
ported mechanically, and the grounding batteries.
system should be electrically continu-
ous. Employees can be shocked or (6) Switches, conduits, busways and
injured if a circuit faults “to ground” duct systems should be checked for
overheating. This could be caused by
without a solid continuous return path
overloaded equipment, severely unbal-
to the source interrupter. Supports such
anced loads or poor connections.
as wood poles should be checked for
excessive rusting or rotting which 4.5 Circuit Analysis and Action
would significantly reduce their The first subsequent investigation,
mechanical strength. following completion of the plant one-

63
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

line diagram is the analysis of the sys- refused critical circuit reliability (or
tem to pinpoint design problems. Key increased vulnerability) ?
critical or vulnerable areas, and overdu-
tied or improperly protected equipment Obviously, overloaded equipment
can be located by the following pro- should be replaced or load transferred so
cedure: that the equipment can be operated well
within its rating. The major projection
(1) Assign faults to various points in points-outside the critical areas-
the system and note their effect on the should be capable of keeping the system
system. For example, assume t h a t the intact by clearing faults and allowing
cable supply to the air conditioning the critical process to continue. The
compressor failed. How long could probability of jeopardizing the critical
operations continue? Is any production circuits by extraneous electric faults
cooling involved? Are any computer should be minimized, either by physi-
rooms cooled by this system? What cally isolating the critical circuits or by
would happen if a short circuit (or judicial use and proper maintenance of
ground fault) occurred on the secondary protective devices to electrically sever
terminals of a unit substation? Con- and isolate faults from critical circuits.
sideration should be given to relay With isolation criteria secure, the
action (including back-up protection), investigation should move to the critical
service restoration procedures, etc, in circuits themselves to see that proper
this “what if’ analysis. This review backup equipment is available and that
could be called a failure mode and restoration procedures are adequate. For
effects analysis. example, a conveyer system with large
(2) Calculate feeder loads to verify rollers may have one motor for each
that all equipment is operating within roller, or several hundred motors. The
its rating (do not forget current failure rate is 0.0109 per unit year for
transformers and other auxiliary equip- the motors, or 2 motor failures can be
ment). Graphic or demand ammeters (as expected annually for a plant with 200
required) should be used to gather up- motors. The typical downtime is 65
to-date information. Fault duties hours (but could be less for this specific
should also be considered. (see Chapter example). In this case, there should be a
5 IEEE Std 141-1976, Recommended means of separating the motor from the
Practice for Electric Power Distribution systems and allowing the conveyer sys-
for Industrial Plants. tem to continue operation (possibly
(3) Perform a relay coordination allowing the roller to idle until the end
analysis (See IEEE Std 242-1975 of a shift), and several spare motors
Recommended Practice for Protection should be available to minimize down-
and Coordination of Industrial and Com- time.
mercial Power Systems or Chapter 4 of Most plants have a sufficient number
IEEE Standard 141-1976). of motors to result in several failures
per year. The large variety usually pre-
(a) Are the relays and fuses prop- cludes the maintenance of a spare motor
erly set or rated for the current load stock (although their availability can be
levels? checked with local distributors). Highly
(b) Is there any new load that has critical nonstandard equipment may

64
IEEE
EVALUATING A N D IMPROVING PLANT RELIABILITY Std 493-1980

require spares. However, each com- power supply or transient suppressor


ponent of the electric system should be equipment on computer circuits where
viewed in its relationship to the critical the controlled process is critical.
process and downtime. (Relay or fuse Testing facilities should have a
coordination again plays a n important, backup power supply where interrup-
role here.) tions could abort long-term testing (that
The worth of carrying spare parts is, tests that span large periods of time).
should be carefully weighed when long It is important to note that only suffi-
process interruptions could result from cient power need be supplied to operate
a single component failure. the test itself.
Another area of importance is the
4.6 O t h e r Vulnerable Areas lighting required for safe operation of
In many plants, the major process is the machines. A failure in a particular
controlled by a small component. This lighting circuit may reduce the area
component may be a rectifier system, a lighting to a level below that which is
computer, or a retrofitted magnetic or necessary to maintain a safe watch over
punched tape system. The continuity of production. Two means of overcoming
the electric feed to this controller is this vulnerability are (1) emergency
just as important to the process as the task lighting and (2) sufficient lighting
main machine itself. By proper applica- such that a single circuit outage does
tion of power sources within the device not reduce lighting to a n unacceptable
(usually large banks of capacitors) or level. Another important lighting con-
external uninterruptible power sources, sideration is the fact that some metal
the control can cause the equipment to halide lights (HID) require as long as
go into a “safe-hold” position if the 15 minutes to restart after being
power source is interrupted. This con- extinguished. Since even severe voltage
tinuity (availability) is important to dips can extinguish this type of lighting
note when thousands of dollars worth of (a dip that may go virtually unnoticed
products are being machined in one by production equipment), supplemen-
operation (such as in the aircraft indus- tary lighting is necessary when the
try). The accuracy and efficacy of a metal halide light is a primary source of
computer or a computer based process is illumination. Other new high output
directly related to the “quality” of its lamps will restart in 1 to 6 minutes, but
environment. This quality is determined this too can cause production problems.
by more than just the continuity of the Air, oil, and water systems are fre-
electrical supply. Voltage dips, line quently important auxiliary inputs upon
noise, ineffective grounding, extraneous which production depends. A compressor
electrical and magnetic fields, tempera- outage can, for example, cause signifi-
ture changes, and even excessively high cant production loss. While failures in
humidity can adversely affect the accu- these systems are usually mechanical in
racy of a computer (or to a lesser nature, electrical failures are not
extent, a microprocessor). To minimize uncommon. Pumps are often integral
the probability of errors, the computer parts of the cooling system in large
should be properly shielded and transformers or even in rectifier cir-
grounded. It may even be beneficial to cuits, and loss of coolant circulation
install a continuous uninterruptible could either shut down the equipment

65
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

or significantly reduce production out- determine the harmonic content in the


put. Therefore, pumps should be well plant’s distribution system. The
maintained (mechanically and electri- widespread use of solid-state switching
cally) when they comprise a significant devices has caused a n increase in har-
part of the system, and spare parts may monic content in the plant power, but it
be a wise investment. Ventilation can has been unofficially reported that such
also be critical to cooling, and ventilator devices must approach 50 percent of the
fans are often neglected-until they plant load before significantly detrimen-
fail. Hence, periodic maintenance and/or tal effects occur. However, the engineer
spare ventilator motors may be a good must look a t harmonic content in con-
investment . junction with other criteria to deter-
Some plants rely on a single cable to mine whether there is cause for a signi-
supply their entire electrical require- ficant loss of life in his equipment.
ments, and many plants rely on single Filter circuits are generally used to
cables for major blocks of load. In these remove harmful harmonics, and their
cases, i t may be prudent to take several nature is beyond the scope of this publi-
precautionary steps. One possible step cation. Fluorescent lighting also pro-
would be the periodic testing of cables duces harmonics, but these harmonics
[21. Another measure would be the use are “blocked’ by the use of delta-wye
of spare cables or the storage of a single transformers.
“portable cable” with permanently made
ends (and provisions for installing the 4.7 Conclusion
portable cable at the various cable ter- The plant engineer should analyze his
minations in the plant distribution sys- system electrically and physically and
tem). Lastly, advance (documented) inquire about the city’s system. In this
arrangements could be made with a analysis, the engineer should:
local contractor or the local utility for
use of their portable cables (and/or serv- (1) See that faults are properly iso-
vices) on a n emergency basis. lated and that critical loads are not
Premature equipment failure can vulnerable to interruption or delayed
result from electric potential that is repair
either too high, too low, excessively har- (2) Analyze the critical areas and
monic laden, or unbalanced (and also a evaluate the need for special restoration
combination of any or all of these). equipment, spare parts or procedures
Voltage tolerances are fairly well estab- (3) Based on probability and economic
lished by NEMA and ANSI. However, in analysis, make capital or preventive
[31 a means is provided to evaluate a maintenance investments as indicated
situation where more than one area by the analysis
deviates from rating. It must be noted (4) Make carefully documented con-
that some situations are offsetting such tingency (catastrophy) plans
as a high voltage (less than 10 percent (5) Check the quality of the power
high) and unbalanced voltage. supply from the utility and throughout
It is important to record and log volt- the plant to determine if the equipment
age levels (of all three phases) at vari- is vulnerable to premature failure
ous strategic points on a periodic basis (6) Develop preventive maintenance,
(that is, annually) and to occasionally checking and logging procedures to

66
IEEE
EVALUATING A N D IMPROVING PLANT RELIABILITY Std 493-1980

ensure continuous optimum reliability tions on Zndustry Applications, vol IA- 13,
performance of the plant MayIJune 1977.
[31 LINDERS, J. R. Effects of Power
Supply Variations on AC Motor Charac-
4.8 References2
teristics, ZEEE Transactions on Zndustry
[l] IEEE COMMITTEE REPORT.
Applications, vol IA-8, JulyIAug 1972, pp
Report on Reliability Survey of Indus-
383-400.
trial Plants, Parts 1-6, ZEEE Transac-
[41 ANSIIIEEE Std 315-1975, Graphic
tions on Zndustry Applications, vol IA-10,
Symbols for Electrical and Electronics
MarIApr, JulyIAug, SeptIOct 1974, pp
Diagrams.
213-252, 456-476,681.
[51 IEEE Std 141-1976, Recommended
[21 LEE, R. New Developments in
Practice for Electric Power Distribution
Cable System Testing, ZEEE Transac-
for Industrial Plants.
[61 IEEE Std 242-1975, Recommended
2Reference [11 is reprinted in Appendixes A Practice for Protection and Coordination
and B. of Industrial and Commercial Buildings.

t:

67
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

5. Electrical Preventive Maintenance

5.1 Introduction cleaning, drying, monitoring, adjusting,


The objective of this chapter is to call corrective modification, and minor
to your attention the “why” of electrical repair of electrical equipment to mini-
preventive maintenance and the role it mize or forestall future equipment
can play in the reliability of distribu- operating problems or failures; which,
tion systems for industrial plants and depending on equipment type, may
commercial buildings. Details of “when” require exercising or proof testing.
and “how” can be obtained from other Electrical equipment is a general
sources [11- [91.l term including materials, fittings,
Of the many factors involved in relia- devices, appliances, fixtures, apparatus,
bility, electrical preventive maintenance machines, etc, used as a part of, or in
usually receives meager emphasis in the connection with, a n electric installation.
design phase and operation of electric
distribution systems when in fact it can 5.3 Relationship of Maintenance
be a key factor to high reliability. Large Practice and Equipment Failure
expenditures for electric systems are The Reliability Subcommittee of
made to provide the desired reliability; IEEE Industrial and Commercial Power
however, failure to provide timely and Systems Committee published the
high-quality preventive maintenance results of a survey which included the
leads to system or component malfunc- effect of maintenance quality on the
tion or failure and prevents obtaining reliability of electrical equipment in
the intended design goal. industrial plants [91. Each participant
in the survey was asked to give his
5.2 Definitions opinion of the maintenance quality in
Electrical preventive maintenance is
his plant. A major portion of the
a system of planned inspection, testing,
electrical equipment population covered
~
in the survey had a maintenance qual-
‘Numbers in brackets correspond to those in ity t h a t was classed as “excellent” or
the References a t the end of this Section. “fair.” It is interesting to note t h a t

68
IEEE
ELECTRICAL P R E V E N T I V E MAINTENANCE Std 493-1980

Table 21
Number of Failures Versus Maintenance Quality
for All Equipment Classes Combined

Number of Failures
Percent of Failures
Maintenance All Inadequate Due t o Inadequate
Quality Causes Maintenance Maintenance
~ ~~

Excellent 311 36 11.6%


Fair 853 154 18.1%
Poor 61 22 32.8%
None 238 28 11.8%

Total 1469 240 16.4%

Table 22
Percentage of Failure Caused
from Inadequate Maintenance Versus Month Since Maintained

All Electrical
Failure, (months Equipment Circuit Open Trans-
since maintained) Classes Combined Breakers Motors Wire formers

Less than 1 2 months ago 7.4% *12.5% 8.8% *O *2.9%


12-24 months ago 11.2% 19.2% 8.8% *22.2% *2.6%
More than 24 months ago 36.7% 17.8% 44.4% 38.2% 36.4%

Total 16.4% 20.8% 15.8% 30.6% 11.1%

*Small sample size; less than 7 failures caused by inadequate maintenance.

maintenance quality had a significant motors, open wire, transformers and all
effect on the percentage of all failures equipment classes combined. The per-
blamed on “inadequate maintenance.” cent of failures blamed on inadequate
As shown in Table 21 of the 1469 maintenance shows a close correlation
failures reported from all causes, inade- with “failure, months since main-
quate maintenance was blamed for 240, tained.”
or 16.4 percent of all the failures. From the IEEE data obtained, it was
The IEEE data also showed that possible to calculate “failure rate multi-
“months since maintained” is an impor- pliers” for transformers, circuit break-
tant parameter when analyzing failure ers and motors based upon the “mainte-
data of electrical equipment. Table 22 nance quality.” These “failure rate mul-
shows data of failures caused by inade- tipliers” are shown in Table 23 and can
quate maintenance for circuit breakers, be used to adjust the equipment failure

69
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 23 locking system would be much more


Equipment Failure Rate satisfactory.
Multipliers Versus Maintenance Quality ( 2 ) Space heater installation in
switchgear or an electric motor is a
Maintenance Trans- Circuit vital necessity in high humidity areas.
Quality formers Breakers Motors This reduces condensation on critical
Excellent 0.95 0.91 0.89 insulation components. Installation of
ammeters in the heater circuit is a n
Fair 1.05 1.06 1.07
added tool for operating or maintenance
Poor 1.51 1.28 1.97 personnel to monitor their operation.
All 1 .o 1.0 1.0 (3) Motor insulation temperatures can
be monitored by use of resistance tem-
Perfect perature detectors which provide a n
4 maintenance 0.89 0.79 0.84
alarm indication at a selected tempera-
ture depending on the insulation class.
rates shown in Chapter 3. “Perfect” Such monitoring indicates that the
maintenance quality has zero failures motor is dirty and/or air passages are
caused by inadequate maintenance. plugged.
The distribution system configuration
5.4 Design for Electrical Preventive and features should be such t h a t
Maintenance maintenance work is permitted without
Electrical preventive maintenance load interruption or with only minimal
should be a prime consideration for any loss of availability. Often, equipment
new electrical equipment installation. preventive maintenance is not done or
Quality, installation, configuration, and is deferred because load interruption is
application are fundamental prereq- required to a critical load or to a portion
uisites in attaining a satisfactory of the distribution system. This may
preventive maintenance program. A sys- require the installation of alternate
tem t h a t is not adequately engineered, electrical equipment and circuits to per-
designed, and constructed will not pro- mit routine or emergency maintenance
vide reliable service, regardless of how on one circuit while the other one sup-
good or how much preventive mainte- plies the critical load t h a t cannot be
nance is accomplished. shutdown.
One of the first requirements in Electrical equipment which is improp-
establishing a satisfactory and effective erly applied will not give reliable serv-
preventive maintenance program is to ice regardless of how good or how much
have good-quality electrical equipment preventive maintenance is accom-
which is properly installed. Examples of plished. The most reasonably accepted
this are as follows: measure is to make a corrective modifi-
cation.
(1) Large exterior bolted covers on
switchgear or large motor terminal com-
partments are not conducive to routine 5.5 Electrical Equipment Preventive
electrical preventive maintenance in- Maintenance
spections, cleaning, and testing. Hinged Electrical equipment deterioration is
and gasketed doors with a three point normal. Unchecked, the deterioration

70
IEEE
ELECTRICAL PREVENTIVE MAINTENANCE Std 493-1980

can progress and cause malfunction or ment operations such as arcing and
an electrical failure. Electrical equip- burning. Checking the mechanical
ment preventive maintenance pro- operation of devices and manually or
cedures should be developed to accom- electrically operating any device that
plish four basic functions, that is, keep seldom operates should be standard
it clean, dry, sealed tight, and minimize practice.
the friction. Water, dust, high or low Procedures and practices should be
ambient temperature, high humidity, initiated to substantiate that electrical
vibration, component quality, and count- equipment is kept clean, dry, sealed
less other conditions can affect proper tight, and with minimal friction by
operation of electrical equipment. visual inspection, exercising, and proof
Without an effective electrical preven- testing. Electrical preventive mainte-
tive maintenance program the risk of a nance should be accomplished on a regu-
serious electrical failure increases. larly scheduled basis as determined by
A common cause of electrical failure inspection experience and analysis of
is dust and dirt accumulation and the any failures that occur.
presence of moisture. This can be in the An electrical preventive maintenance
form of lint, chemical dust, day-to-day program certainly will not eliminate all
accumulation of oil mist and dirt parti- failures, but it will minimize their
cles, etc. These deposits on the insula- occurrence. Some of the key elements in
tion, combined with oil and moisture, establishing a program are as follows:
become conductors and are responsible (1) Establish a n “Equipment Service
for tracking and flashovers. Deposits of Library” consisting of bulletins, manu-
dirt can cause excessive heating and als, schematics, parts lists, failure
wear, and decrease apparatus life. analysis reports, etc. The bulletins and
Electrical apparatus should be operated manuals are normally provided by the
in a dry atmosphere for best results; electrical equipment manufacturer.
but this is often impossible, so precau- Often they are not taken very seriously
tions should be established to minimize after equipment installation and are
entrance of moisture. Moisture conden- lost, misplaced, or discarded, but this
sation in electrical apparatus can cause documentation is vital to develop
copper or aluminum oxidation and con- electrical preventive maintenance pro-
nection failure. cedures and to aid in training.
Loose connections are another cause (2) In addition to the above documen-
of electrical failures. Electrical connec- tation, each in-service failure should be
tions should be kept tight and dry. thoroughly investigated and the cause
Creep or cold flow is a major cause of determined and documented. Generally,
joint failure. Mounting hardware and it will be found that timely and ade-
other bolted parts should be checked quate electrical preventive maintenance
during routine electrical equipment ser. could have prevented the failure. If
vicing. correctable by electrical preventive
Friction can affect the freedom of maintenance the corrective action
movement of electrical devices and can should be included on the work list. If
result in serious failure or difficulty. the failure was caused by a weak com-
Dirt on moving parts can cause slug- ponent, then all like equipment should
gishness and improper electrical equip- be modified as soon as possible.

71
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

“Failure analysis” plays a major part in 5.6 References


an electrical preventive maintenance
program. [ l ] ANSI/NFPA 70-1978, National
(3) Provide the training necessary to Electrical (hde2 * 3
accomplish the program t h a t has been
t21 HUBERT, C. I. Preventive Mainte-
established. The techniques utilized in
nance of Electrical Equipment,
performance of a n electrical preventive
McGraw-Hill Book Co.
maintenance program are extremely

ment requires better than average skills


[51 SMEATON, R. W. Motor Application
and special training. Properly trained
and Maintenance Handbook. McGraw
and adequately equipped maintenance
Hill Book Co, New York, NY 1969.
personnel must have a very thorough
knowledge of the equipment operation. [6] Factory Mutual Systems Trans-
It must be able to make a thorough former Bulletin 14-8, October 1976.
inspection and also accomplish repairs. Public Information Division, 1 1 5 1 Bos-
For example, special training in the use ton-Providence Turnpike, Norwood,
of the dc high-potential dielectric tests MA
or megger tests as well as the interpre-
tation of the results may be required. [71 MILLER, H. N. DC Hypot Testing of
(4) A good record system should be Cables, Transformers and Rotating
developed which will show the repairs Machinery, Manual P-16086. Associ-
required by equipment over a long ated Research Inc., Chicago, IL
period of time. On each regular inspec-
[SI CURDTS, E. B. Insulation Testing by
tion, variations from normal conditions
D-C Methods, Technical Publication
be noted‘ The frequency and 22T1-1971 James G. Biddle Co, Plym-
magnitude of the work should then be outh Meeting, 2.
increased or decreased according to an
analysis of the data. Avoid performing [91 IEEE COMMITTEE REPORT.
too much maintenance work as this can Report on Reliability Survey of Indus-
contribute to failures. The records trial Plants, P a r t 6, IEEE Transactions
should reflect availability of spare on Industry Applications, ~ 0 1IA-10,
parts, service attitude of equipment JulylAugust and SeptemberIOctober
manufacturers, major equipment 1974, pp 45&476, 681.4
failures to date and time required for
repairs, etc. These records are not only
useful in planning and scheduling
*American National Standards Institute, 1430
electrical preventive maintenance work, Broadway, New York, NY 1o018.
but are useful in evaluating equipment ’National Fire Protection Association, 470
performance for future purchases. Atlantic Avenue, Boston, MA 02210.
keference [ 9 ] is reprinted in Appendix B.

72
IEEE
ELECTRICAL PREVENTIVE MAINTENANCE Std 493-1980

[lo] ANSZ/ZEEE C57.106-1977, IEEE [131 ANSZ/ZEEE Std 95-1977, IEEE


Guide for Acceptance and Maintenance Recommended Practice for Insulation
of Insulating Oil in Equipment Testing of Large AC Rotating Machin-
ery with High Direct Voltage
std 43-1974' IEEE [14] ZEEE Std 450-1980,IEEE Recorn-
Recommended Practice for Testing
mended Practice for Maintenance, Test-
Insulation Resistance of Rotating
ing, and Replacement of Large Lead
Machinery
Storage Batteries for Generating Sta-
tions and Substations
[121 ANSZ/ZEEE Std 56-1977, IEEE
Guide for Insulation Manitenance of [151 ZEEE Std 62-1978,IEEE Guide for
Large AC Rotating Machinery (10 000 Field Testing Power Apparatus Insula-
kVA and Larger) tion

73
6. Emergency and Standby Power

6.1 Introduction supplied power must be clearly under-


When a reliability analysis has been stood. Reliability is a n indication of how
completed, the rate at which power many power failures can be expected
failures occur and the expected duration over a certain period of time, while
of those power failures can be predicted availability is a n indication of total
a t most points of utilization equipment. downtime due to lack of power over a
This knowledge can be used to deter- certain period. Both reliability and
mine whether there is a need to availability requirements for control
increase the reliability or availability of power for a boiler would certainly be
delivered power supplied to particular greater than those for a room air condi-
utilization points. Emergency or tioner.
standby power can readily be used to Many power-consuming operations
improve both reliability and availability require a high degree of power-supply
of delivered power. A cost-reliability reliability with little concern for avail-
tradeoff decision must be made to ability. A power failure during the vul-
improve reliability or availability of canizing cycle of a rubber manufactur-
power only to those areas which can ing process will cause loss of steam and
justify the cost for such improvement. errors in the timekemperature control
Various types of emergency or standby for proper curing. This results in the
systems are ideally suited to providing product being scrapped. The difference
large improvements to relatively small in loss between a power failure of one-
sections of a power system. minute duration and one of 30-minute
duration is minimal. Thus a power sys-
6.2 Reliability and Availability tem that experiences two power failures
An evaluation of each piece of utiliza- of 30 minutes each is more desirable
tion equipment must be made to deter- than a system t h a t experiences six
mine actual needs. The difference power failures of one minute each, even
between reliability and availability of though the downtime is 10 times
IEEE
EMERGENCY AND STANDBY POWER Std 493-1980

greater in the first case. Other power devices have a failure rate of their own
utilizing equipment demands a high and, thus, actually reduce the reliability
degree of power supply availability with of delivered power. When the primary
little concern for reliability. A power power source is being utilized, a failure
failure to a process which stamps out of transfer device may cause loss of
metal parts will cause little loss due to power which would not have occurred if
the power failure itself; but there will the off-line system had not been
be a loss directly related to the length installed. The selection of a n off-line
of the power failure. Thus, a power sys- system for the metal stamping process
tem that experiences six power failures is a proper application. The off-line sys-
of one minute each is more suitable tem can reduce downtime, resulting in
than one that experiences two power higher availability.
failures of 30 minutes each, even A study must be undertaken to deter-
though the first case has a failure rate mine the systems capable of performing
three times higher and, thus, a lower the desired function. Systems are avail-
reliability. able to provide reliable power to over-
come the problems encountered due to
6.3 System Selection power failures ranging from mil-
The type of emergency or standby liseconds to many hours. More than one
power system to use depends on what type of system may be suitable for a
the system is expected to accomplish. particular application. Selection of the
Can the equipment or process tolerate a proper system will then depend on first
power failure of one millisecond, 10 cost, operating and owning cost such as
seconds, or of one minute? For how long maintenance and fuel requirements,
a period of time does the emergency or system reliability, output power quality,
standby power system have to perform expansion capacity, and environmental
its intended function? For hours, considerations.
minutes, or seconds?
An off-line system is one that is dor- 6.4 Descriptions and Applications of
mant until called upon to operate, such Available Systems
as a diesel generator which is started up 6.4.1 General. The following informa-
when a power failure occurs. An on-line tion contains data on some commonly
system is one that is operating at all used systems. While power sources
times, such as a n inverter supplied by such as solar and chemical may become
dc power via the primary power source viable in the future, they are not in
through a battery charger. The above common use and will not be discussed
system utilizes batteries on float charge here.
to supply the inverter if a power failure 6.4.2 Engine Driven Generators. These
strikes the primary power source. units are available in sizes from 1 kW
The selection of a n off-line engine- to several thousand kW. Fuels com-
driven generator for the rubber monly used are diesel, gasoline, and
manufacturing process mentioned above natural or liquefied petroleum (LP) gas.
would be a misapplication. The off-line If kept warm they will dependably come
system can improve the availability of on line in 8 to 15 seconds. Except for
delivered power, but cannot improve the small units, installed costs range from
reliability. The transfer device or $250 to $400 per kW. Diesel units are
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

generally heavier duty, have less costly since their physical size and weight per
fuel, and fire danger is lower than for kilowatt are less than for enginedriven
gasoline units. Gasoline-driven units units. Turbine driven generators are al-
range up to 100 kW and have a lower most exclusively applied as off-line
initial cost than diesel sets. Natural and systems.
LP gas engines provide quick starting 6.4.4 Mechanical Stored Systems. This
after long shutdown periods because of type of system is comprised of a rotat-
the inherently fresh fuel. One of the ing flywheel which converts its rotating
drawbacks may be the lack of assurance kinetic energy into electric power. It is
of fuel supplies when the system is generally applied as a n on-line system.
needed. Engine-driven generators are Depending on frequency requirements
generally applied as off-line units for of the load, a typical mechanical stored
reducing downtime or in combination energy system can ride through a power
with a mechanical stored energy system failure for up to two seconds. Thus, its
or a small uninterruptible power supply main use is as a buffer to mechanically
to improve both reliability and avail- filter out transients. See Fig 5. A supply
ability of delivered power. time of 15 seconds can be attained by
6.4.3 Turbine-Driven Generators.. Two using a n eddy current clutch and driv-
types of turbines can be used for prime ing the flywheel at a higher speed than
movers, steam or gas. Since steam is the generator it operates. This type of
generally not available when a power system may allow a n engine driven
failure has occurred, only the gas prime prime mover to come up to speed, either
mover will be discussed. Installed costs to drive a separate generator or to
for medium-sized units range from $200 maintain the speed of the flywheel and
to $400 per kW. its associated generator. See Fig 6.
Gas turbines can utilize various Such systems have a history of mainte-
grades of oil as well as natural and pro- nance problems. There are several other
pane gas. Sizes generally range from hybrid systems which utilize dc drive
100 kW to several thousand kW. Gas motors, batteries, engines, and turbines.
turbine generators can be placed on line System costs range from $200 to $1000
in 20 seconds for smaller units up to per kW.
several minutes for larger units. They 6.4.5 ZnvertedBattery Systems. A sim-
can more easily be rooftop mounted ple off-line inverter system is shown in

Fig 5
Simple Inertia Driven
“Ride Through” System

FLYWHEEL

INPUT
POWER
--*--I]---.@--
MOTOR
hr

ALTERNATOR
Bur FOEURT EP DU T
AC
POWER

76
IEEE
EMERGENCY AND STANDBY POWER
Std 493-1980

FLYWHEEL EDDY CURRENT CLUTCH

AC I N P U T
POWER
-- MOTOR
n /

ALTERNATOR
CRITICAL LOAD
AC P O W E R

CONTROL

Fig 6
Constant Frequency Inertia System

,
q-}r:rTh
DC CONTACTOR

AC
POW
I NEPRU T RECTIFIER INVERTER ~ TRANSFER DEVICE

CRITICAL L O A 0
BATTERY /--
AC P O W E R
s Y N c HRONIz IN
SIGNAL
GA
I

Fig 7
Short Interruption Static
Inverter System

STATIC UNINTERRUPTIBLE
POWER INVERTER AC O U T P U T P O W E R

--
-
BATTERY

Fig 8
Non-Redundant Uninterruptible
Power Supply

77
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Fig 7. The system is not a n uninterrup- power can be connected directly to the
tible power supply. The transfer time load.
for a mechanical transfer will cause a Figure 9 shows a redundant uninter-
power interruption of 60 to 190 mil- ruptible power supply with static
liseconds. A static transfer switch is switches to clear a faulted inverter. The
more costly, but will result in a much batteries for this system are required to
shorter interruption. The contactor supply power only until the diesel gen-
closes upon loss of primary power and is erators can be placed on line. The sys-
in the circuit to prevent continual tem in Figure 9 is much more reliable
energization of the static inverter than that shown in Figure 8, but is
whose efficiency is approximately 70 more expensive. Depending on amount
percent and, thus, wastes energy while of redundancy, auxiliary equipment, and
energized. required battery size, the cost per kW
Figure 8 shows the most widely used ranges from $1000 to $3000. Installa-
system for supplying uninterruptible tion requirements can be impressive for
power. The load is basically free of the battery. A battery sized to provide
power interruptions, transient distur- power for a 250 kW inverter for one
bances, and voltage and frequency vari- hour will weigh approximately 25 tons.
ations. Installed costs range from $200 6.4.6 Mechanical Uninterruptible Pow-
to $800 depending on system configura- er Supplies. Figure 10 shows a typical
tion and battery size. A failure of the rotating uninterruptible power supply.
inverter will cause a loss of power until The ac motor drives the dc generator
the inverter is repaired or until prime which in turn supplies power for the dc

Fig 9
Redundant Uninterruptible
Power Supply

-
No1
- RECTIFIER -- No1

INVERTER 4 &;$:
No I
-
A C INPUT----
POWER
No 2
RECTIFIER
--
- No 3
RLCTlFlER
NO 3
IEEE
EMERGENCY AND STANDBY POWER Std 493-1980

AC I N P U T
POWER
-
--*--@~@--e
MOTOR
DC GENERATOR

- OC
-
-
MOTOR
ALT E R NATOR
UONUITNPTUETR RPOWER
UPT'BLE

BATTERY

Fig 10
Rotating Uninterruptible
Power Supply

motor which drives the ac generator. 6.5 Selection and Application Data.
The battery will provide power for the The figures and system descriptions
dc motor upon loss of primary power. presented here are only a few of the
The ac generator provides uninterrupti- many types of system and hybrid sys-
ble power to the load. The lack of mov- tems available. For comprehensive selec-
ing parts in the static inverters and rec- tion and application data, reference is
tifiers has proven to be a strong selling made to IEEE Std 446-1980, Recom-
point over the mechanical uninterrupti- mended Practice for Emergency and
ble power supplies. Standby Power Systems.

79
7. Examples of Reliability
Analysis and Cost Evaluation

7.1 Examples of Reliability and design of the power distribution system.


Availability Analysis of Common 7.1.2 Introduction. An industrial
Low-Voltage Industrial Power Distri- power distribution system may receive
bution Systems power at 13.8 kV from a n electric util-
ity and then distribute the power
7.1.1 Quantitative Reliability and throughout the plant for use a t the
Availability Predictions. A description is various locations. One of the questions
given of how to make quantitative relia- often raised during the design of the
bility and availability predictions for power distribution system is whether
proposed new configurations of indus- there is a way of making a quantitative
trial power distribution systems. Six comparison of the failure rate and the
examples are worked out, including a forced hours downtime per year of a
simple radial system, a primary- secondary-selective system with a
selective system, and a secondary- primary-selective system and a simple
selective system. A brief tabulation is radial system. This comparison could be
also given of pertinent reliability data used in cost-reliability and cost-
needed in order to make the reliability availability tradeoff decisions in the
and availability predictions. The simple design of the power distribution system.
radial system analyzed had a n average The estimated cost of power outages at
number of forced hours of downtime per the various plant locations could be fac-
year that was 19 times larger than a tored into the decision as to which type
secondary-selective system; the failure of power distribution system to use. The
rate was six times larger. The impor- decisions could be based upon “total
tance of two separate power supply owning cost over the useful life of the
sources from the electric utility has equipment” rather than “first cost.”
been identified and analyzed. This Six examples of common low-voltage
approach could be used to assist in industrial power distribution systems
cost-reliability tradeoff decisions in the are analyzed in this section:

80
IEEE
RELIABILITY ANALYSIS A N D COST EVALUATION Std 493-1980

(1)Example 1-Simple radial of incoming power”; for example, “volt-


age drops below 70 percent.”
(2) Example 2-Primary selective to
One of the main benefits of a reliabil-
13.8 kV utility supply
ity and availability analysis is t h a t a
(3) Example 3-Primary selective to disciplined look is taken at the alterna-
load side of 13.8 kV circuit breaker tive choices in the design of the power
distribution system. By using published
(4) Example 4-Primary selective to
reliability data collected by a technical
Primary of transformer
society from industrial plants, the best
(5) Example 5-Secondary selective possible attempt is made to use histori-
cal experience to aid in the design of
(6) Example 6-Simple radial with
the new system.
spares
7.1.3 Definition of Terminology. The
Only forced outages of the electrical definition of terms is given in Section
equipment are considered in the six 2.1.3. The units t h a t are being used for
examples. It is assumed t h a t scheduled “failure rate” and “average downtime
maintenance will be performed at times per failure” are:
when 480 V power output is not needed. A =Failure rate (failures per year)
The frequency of scheduled outages and
the average duration can be estimated, r = average downtime per failure
and, if necessary, these can be added to (hours per failure) = Average time to
the forced outages given in the six repair or replace a piece of equipment
examples. after a failure. In some cases this is
When making a reliability study, it is the time to switch to a n alternate cir-
necessary to define what is a failure of cuit when one is available.
the 480 volt power. Some of the failure 7.1.4 Procedure for Reliability and
definitions for 480 volt power t h a t are Availability Analysis. The “minimal
often used are as follows: cut-set” method for system reliability
evaluation is described in Sections 2.1.6,
(1)Complete loss of incoming power
2.1.8, and 2.1.9. The quantitative relia-
for more than 1 cycle
bility indexes t h a t are used in the six
(2) Complete loss of incoming power
examples are the failure rate and the
for more than 10 cycles
forced hours downtime per year. These
(3) Complete loss of incoming power
are calculated a t the 480 volt point of
for more than 5 seconds
use in each example. The failure rate A
(4) Complete loss of incoming power
is a measure of unreliability. The pro-
for more than 2 minutes
duct Ar,(failure rate X average down-
Definition (3) will be used in the six time per failure) is equal to the forced
examples given. This definition of hours downtime per year and can be
failure can have a n effect in determin- considered a measure of forced unavail-
ing the necessary speed of automatic ability since a scale factor of 8760 con-
throwover equipment t h a t is used in verts one quantity into the other. The
primary-selective or secondary-selective average downtime per failure r could be
systems. In some cases when making called restorability.
reliability studies, it might be necessary The necessary formulas for calculat-
to further define what is “complete loss ing the reliability indexes of the
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

minimal cut-set approach are given in


Table 1. A sample using these formulas
is shown in Fig 11 for two components
f s = A1 +A2 in series and two components in paral-
lel. In these samples the scheduled
outages are assumed to be zero and the
units for A and r are, respectively,
failures per year and hours downtime
A lrl= A 2r2 per failure. The formulas in both Table
rs = 1 and Fig 11 assume the following:
A1 +*,
(1) The component failure rate is con-
(a) stant with age
(2) The outage time after a failure
has a n exponential distribution. (Proba-
bility of outage time exceeding T is
(3) Each failure event is independent
of any other failure event.
(4) The component “up” times are
A 3 A4(r3 + r4) much larger than “down” times:
fp = 8760
Airi Airi
A r (A 4r4) 1- ->>-
8760 8760
fpr* =
8760
The reliability data to be used for the
r3r4 electrical equipment and the electric
rp = ____
utility supply are given in 7.1.5.
r3 + r4
7.1.5 Reliability Data from 1973-1975
(b) IEEE Surveys. In order to make a relia-
Nomenclature: bility and availability analysis of a
power distribution system, it is neces-
f = frequency of failures
sary to have data on the reliability of
A = failures per year
each component of electrical equipment
r = average hours of downtime
used in the system. Ideally these relia-
per failure
bility data should come from field use of
s = series the same type of equipment under simi-
p = parallel
lar environmental conditions and simi-
Fig 11 lar stress levels. In addition, there
Formulas for Reliability Calculations should be a sufficient number of field
(a) Reparable Components in Series failures in order to represent a n ade-
(both must work for success) quate sample size. It is believed t h a t
eight field failures are the minimum
(b) Reparable Components in Paral- number necessary in order to have a
lel (one or both must work for suc- reasonable chance of determining a
cess) failure rate to within a factor of 2. The

82
IEEE
RELIABILITY ANALYSIS AND COST EVALUATION Std 493-1980

Table 24
Reliability Data from IEEE Reliability S u r v e y of Industrial Plants 111
(See Table 11)

r, A -r, Data
Hours of Forced Source
A, Downtime Hours of i n IEEE
Failures Per Downtime Survey Ill,
Equipment Category per Year Failure per Year Table No.

Protective relays 0.0002 5.0 0.0010 19

Metalclad drawout circuit breakers


e600 V 0.0027 4.0 0.0108 5,50
Above 600 V 0.0036 83.1* 0.2992 5,51
Above 600 V 0.0036 2.1" 0.0076 5,51

Power cables (1000circuit ft)


e600 V,above ground 0.00141 10.5 0.0148 13
601-15000 V,conduit below ground 0.00613 26.5* 0.1624 13,56
601-15000 V,conduit below ground 0.00613 19.0** 0.1165 13,56

Cable terminations
e600 V,above ground 0.0001 3.8 0.0004 17
601-15 000 V,conduit below ground 0.0003 25.0 0.0075 17
Disconnect switches enclosed 0.0061 3.6 0.0220 9

Transformers
601-15 000 V 0.0030 342.0' 1.0260 4,48
601-15 000 V 0.0030 130.0*' 0.3900 4,48

Switchgear bus-bare
e600 V (connected to 7 breakers) 0.0024 24.0 0.0576 10
e600 V (connected to 5 breakers) 0.0017 24.0 0.0408 10

Switchgear bus-insulated
601-15 000 V (connected to 1 breaker) 0.0034 26.8 0.0911 10
601-15 000 V (connected to 2 breakers) 0.0068 26.8 0.1822 10

*Repair failed unit.


**Replace with spare.

types of reliability data needed on each cost-availability tradeoff studies in the


component of electrical equipment are: design of new power distribution sys-
tems.
(1) Failure rate, failures per year
During 1973-1975 the Power Systems
(2) Average downtime to repair or
Reliability Subcommittee of the Indus-
replace a piece of equipment after a
trial and Commercial Power Systems
failure, hours per failure
Committee conducted and published [11
These reliability data on each com- [21 surveys of electrical equipment relia-
ponent of electrical equipment can then bility in industrial plants. See Appen-
be used to represent historical experi- dices A, B, and D for the data. See
ence for use in cost-reliability and Chapter 3 for a summary of the data.

83
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 25
Failure Modes of Circuit Breakers
Percentage of Total Failures in Each Failure Mode
(See Table 14)

Percent of
Total Failures
(All Voltages) Failure Characteristic

Backup protective equipment required


9 Failed while opening
Other circuit breaker failures
I Damaged while successfully opening
32 Failed while in service (not while opening or closing)
5 Failed to close when i t should
2 Damaged while closing
42 Opened when i t shouldn’t
1 Failed during testing or maintenance
1 Damage discovered during testing or maintenance
1 Other

100 Total Percentage

Table 26
IEEE Survey of Reliability of Electric Utility Power Supplies to Industrial Plants
(See Table 12)

r,
Hours of A ‘r,
A, Downtime Forced Hours
Number of Circuits Failures Per of Downtime
(All Voltages) per Year Failure per Year
~~

Single circuit 1.956 1.32 2.582


Double circuit
Loss of both circuits* 0.312 0.52 0.1622
Calculated value for loss
of Source 1 (while Source 2
is OK) 1.644 0.15‘ 0.2466

*Data for double circuits had all circuit breakers closed.


**Manual switchover time of 9 min to source 2.

84
IEEE
RELIABILITY ANALYSIS A N D COST EVALUATION Std 493-1980

These reliability surveys of electrical The failure rate and average down-
equipment and electric utility power time per failure data for the electric
supplies were extensive. The pertinent utility power supplies are given in Table
failure rate and average downtime per 26. This includes both single circuit and
failure information for the electrical double-circuit reliability data. The two
equipment are given in Table 24. In power sources in a double-circuit utility
compiling these data, a failure was supply are not completely independent,
defined as any trouble with a power sys- and the reliability and availability
tem component t h a t causes any of the analysis must take this into considera-
following effects: tion. This subject is discussed further in
7.1.15.
(1)Partial or complete plant shut-
7.1.6 Example 1 -Reliability and
down, or below-standard plant operation Availability Analysis of a Simple Radial
(2)Unacceptable performance of
System.
user’s equipment Description of Simple Radial System.
(3)Operation of the electrical protec- A simple radial system is shown in Fig
tive relaying or emergency operation of
12. Power is received at 13.8 kV from
the plant electric system the electric utility. It then goes through
(4)Deenergization of any electric cir-
a 13.8 kV circuit breaker inside the
cuit or equipment
industrial plant, 600 feet of cable in
A failure of a n in-plant component underground conduit, a n enclosed
causes a forced outage of the com- disconnect switch, to a transformer t h a t
ponent, and the component thereby is reduces the voltage to 480 volts, then
unable to perform its intended function through a 480 volt main circuit breaker,
until it is repaired or replaced. a second 480 volt circuit breaker, 300
In addition to the reliability data for feet of cable in above ground conduit, to
electrical equipment shown in Table 24, the point where the power is used in the
there are some “failure modes” of cir- industrial plant.
cuit breakers that require backup pro- Results-Simple Radial System. The
tective equipment to operate; for exam- results from the reliability and avail-
ple, “failed to trip” or “failed to inter- ability calculations are given in Table
rupt.” Both of these failure modes 27. The failure rate and the forced
would require t h a t a circuit breaker hours downtime per year are calculated
farther up the line be opened, and this at the 480 volt point of use.
would result in a larger part of the The relative ranking of how each
power distribution system being discon- component contributes to the failure
nected. Reliability data on the “failure rate is of considerable interest. This is
modes of circuit breakers” are shown in tabulated in Table 28.
Table 25. These data are used for the The relative ranking of how each
480 volt circuit breakers in all six component contributes to the forced
examples discussed in this section. I t hours downtime per year is also of con-
will be assumed that the “flashed over siderable interest. This is given in Table
while open” failure mode for circuit 29.
breakers and disconnect switches has a It might be expected t h a t the power
failure rate of zero. distribution system would be shut down
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

once every two years for scheduled


1 1 3 . 8 LV maintenance for a period of 24 hours.
These shutdowns would be in addition

0Y to the outage data given in Tables 27,


28, and 29.
Concluswns-Simple Radial System.
The electric utility supply is the largest
------
1 Utility
Plant

500 MVA
-- contributor to both the failure rate and
the forced hours downtime per year at
the 480 volt point of use. A significant
improvement can be made in both the
failure rate and the forced hours down-
time per year by having two sources of
600 Feet power a t 13.8 kV from the electric util-
Cable
Cable
ity. The improvements that can be
obtained are shown in Examples 2, 3
and 4 using “Primary-Selective” and in
Example 5 using “Secondary-Selective.”
13 8001480 V
The transformer is the second largest
contributor to forced hours downtime
per year. The transformer has a very
low failure rate, but the long outage
time of 342 hours after a failure results
in a large forced hours downtime per
year. The 13.8 kV circuit breaker is the
third largest contributor to forced hours
downtime per year, and the fourth larg-
est are the 13.8 kV cables and termina-
tions. This is a result of the average
outage time after a failure of 83.1 hours
for the 13.8 kV circuit breaker and 26.5
hours for the 13.8 kV cable.

I
The long outage time after a failure
Cable
for the transformer, 13.8 kV circuit
Feet
breaker, and the 13.8 kV cable are all
480 V based upon “repair failed unit.” These
outage times after a failure can be
Fig 12 reduced significantly if the “replace
Simple Radial System with spare” times shown in Table 24 are
Example 1 used instead of “repair failed unit.” This
is done in Example 6, using a simple
radial system with Spares.

7.1.7 Example 2-Reliability and


Availability Analysis of Primary-Selective
to 13.8 kV Utility Supply.

86
IEEE
RELIABILITY ANALYSIS AND COST EVALUATION Std 493-1980

Table 27
Simple Radial System
Reliability and Availability of Power at 480 V-Example 1

A*r,
A, Forced Hours
Failures of Downtime
Component per Year per Year

13.8 kV power source from electric utility 1.956 2.582


Protective relays (3) 0.0006 0.0030
13.8 kV metalclad circuit breaker 0.0036 0.2992’
Switchgear bus-insulated (connected to 1 breaker) 0.0034 0.0911
Cable (13.8 kV) ; 900 ft, conduit below ground 0.0055 0.1458‘
Cable terminations (6) a t 13.8 kV 0.0018 0.0450
Disconnect switch (enclosed) 0.0061 0.0220
Transformer 0.0030 1.0260*
480 V metalclad circuit breaker 0.0027 0.0108
Switchgear bus-bare (connected to 7 breakers) 0.0024 0.0576
480 V metalclad circuit breaker 0.0027 0.0108
480 V metalclad circuit breakers (5)
(failed while opening) 0.0012 0.0048
Cable (480 V); 300 f t conduit above ground 0.0004 0.0044
Cable terminations (2) a t 480 V 0.0002 0.0008
Total a t 480 V output 1.9896 4.3033

*Data for hours of downtime per failure a r e based upon repair failed unit.

Description - Primary-Selective to Results- Primary-Selective to 13.8


13.8 kV Utility Supply. The primary- k V Utility Supply.
selective to 13.8 kV utility supply is Example 2a-If the time to switch to
shown in Fig 13. It is a simple radial a second utility power source takes 9
system with the addition of a second minutes after a failure of the first
13.8 kV power source from the electric source, then there would be a power
utility; the second power source is nor- supply failure of 9 minutes duration.
mally disconnected. In the event t h a t Using the data from Table 26, for
there is a failure in the first 13.8 kV double-circuit utility supplies, this
utility power source, then the second would occur 1.644 times per year (1.956
13.8 kV utility power source is switched - 0.312). This in addition to losing both

on to replace the failed power source. power sources simultaneously 0.312


Assume t h a t the two utility power times per year for a n average outage
sources are synchronized. Example 2a- time of 0.52 hours. If these utility sup-
Assume a 9-minute “manual switchover ply data are added together and substi-
time” to utility power source No 2 after tuted into Table 27 on the Simple
a failure of source No 1. Example 2b- Radial System, it would result in reduc-
Assume an “automatic switchover time” ing the forced hours downtime per year
of less than 5 seconds after a failure is at the 480 volt point of use from 4.3033
assumed. (loss of 480 volt power for to 2.1291. The failure rate would stay
less than 5 seconds is not counted as a the same a t 1.9896 failures per year.
failure.) These results are given in Table 30.

87
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

1 3 . 8 kV

NC NO

Souice No1 Source No 2

Uti l i t y
--

300

Cable Coble

1 3 800/480 V

Fig 13
Primary Selective to 13.8 kV
Utility Supply
Example 2

88
IEEE
RELIABILITY ANALYSIS AND COST EVALUATION Std 493-1980

Table 28 Table 29
Simple Radial System Simple Radial System Relative
Relative Ranking of Failure Rates Ranking of Forced Hours of Downtime
per Year
A, A.r,
Failures
per Year Forced Hours
~

of Downtime
1. Electric utility 1.956
per Year
2. 13.8 kV cable and terminations 0.0073
1. Electric utility 2.582
3. Disconnect switch 0.0061
2. Transformer 1.0260*
4. 13.8 kV circuit breaker 0.0036
3. 13.8 kV circuit breaker 0.2992'
5. Switchgear bus-insulated 0.0034
4. 13.8 kV cable and terminations 0.1908'
6. Transformer 0.0030
5. Switchgear bus-insulated 0.0911
7. 480 V circuit breaker 0.0027
6. Switchgear bus-bare 0.0576
8. 480 V circuit breaker (main) 0.0027
7 . Disconnect switch 0.0220
9. Switchgear bus-bare 0.0024
8. 480 V circuit breaker 0.0108
10. 480 V circuit breakers (5) (failed 0.0012
while opening) 9. 480 V circuit breaker (main) 0.0108

11. 480 V cable and terminations 0.0006 10. 480 V cable and terminations 0.0052

12. Protective relays (3) 0.0006 11. 480 V circuit breakers (5) 0.0048
(failed while opening)
Total 1.9896
12. Protective relays (3) 0.0030

Total 4.3033
Example 2b-If the time to switch to
a second utility power source takes less
than 5 seconds after a failure of the *Data for hours of downtime per failure are based
first source, then there would be no upon repair failed unit.
failure of the electric utility power sup-
ply. The only time a failure of the util- 1.8835 hours per year a t the 480 volt
ity power source would occur is when point of use; the failure rate would be
both sources fail simultaneously. It will reduced from 1.9896 to 0.3456 failures
be assumed that the data shown in per year. These results are also given in
Table 26 are applicable for loss of both Table 30.
power supply circuits simultaneously. Conclusion-Primary-Selective to the
This is 0.312 failures per year with a n 13.8 kV Utility Supply. The use of
average outage time of 0.52 hours. If primary-selective to the 13.8 kV utility
these values of utility supply data are supply with 9-minute manual switch-
substituted into Table 27, it would over time reduces the forced hours
result in reducing the forced hours downtime per year at the 480 volt point
downtime per year from 4.3033 to of use by about 50 percent, but the
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 30 rate and the forced hours downtime per


Simple Radial System and Primary- year at the 480 volt point of use?
Selective System to 13.8 kV Utility Example 3a-Assume 9-minute manual
Supply Reliability and Availability switchover time. Example 3b-Assume
Comparison of Power at 480 V Point automatic switchover can be accom-
of Use plished in less than 5 seconds after a
failure (loss of 480 volt power for less
A 'r, than 5 seconds is not counted as a
h, Forced Hours failure).
Failures Downtime
Distribution System per Year per Year Results-Primary-Selective to Load
Side of 13.8 kV Circuit Breaker. The
Example 1 results from the reliability and avail-
Simple radial system 1.9896 4.3033
ability calculations are given in Table
Example 2 a
31.
Primary-selective system 1.9896 2.1291 Conclusions -Primary-Selective to
to 13.8 kV utility supply Load Stde of 13.8 kV Circuit Breaker.
(with 9 min switchover
after a supply failure) The forced hours downtime per year a t
the 480 volt point of use in Example 3
Example 2b (Primary-Selective to Load Side of 13.8
Primary-selective system 0.3456 1.8835 kV Circuit Breaker) is about 10 percent
to 13.8 kV utility supply
(with switchover in less lower than in Example 2 (Primary-
than 5 s after Selective to 13.8 kV Utility Supply).
supply failure) The failure rate is about the same.
7.1.9 Example 4-Primary-Selective to
*Loss of 480 V power for less than 5 s is not Primary of Transformer.
counted as a failure.
Description of Primary-Selective to
Primary of Transformer. Fig 15 shows a
failure rate is the same as for a simple one-line diagram of the power distribu-
radial system. tion system for primary-selective to pri-
The use of automatic throwover mary of transformer. What are the
equipment that could sense a failure of failure rate and the forced hours down-
one 13.8 kV utility supply and switch- time per year at the 480 volt point of
over to the second supply in less than 5 use? Assume 1 hour switchover time.
seconds would give a 6 : l improvement Results- Primary-Selective to Pri-
in the failure rate at the 480 volt point mary of Transformer. The results from
of use (a loss of 480 volt power for less the reliability and availability calcula-
than 5 seconds is not counted as a tions are given in Table 32.
failure). Conclusions-Primary-Selective to
7.1.8 Example 3-Primary-Selective to Primary of Transformer. The forced
Load Side of 13.8 kV Circuit Breaker. hours downtime per year at the 480 volt
Description of Primary-Selective To point of use in Example 4 (Primary-
Load Side of 13.8 kV Circuit Breaker. Selective to Primary of Transformer) is
Figure 14 shows a one-line diagram of about 32 percent lower than for the
the power distribution system for Simple Radial System in Example 1.
primary-selective to load side of 13.8 kV The failure rate is the same in Exam-
circuit breaker. What are the failure ples 4 and 1.

90
IEEE
RELIABILITY ANALYSIS AND COST EVALUATION Std 493-1980

d
Y
13.8 LV

NC

aNo
Source N o 2

500 MVA

300
Feet
1
Y1
/
Coble Point 600 F e e t
E Coble

J13 8001480 V

I
480 V
Cable

Fig 14
Primary Selective.to Load
Side of 13.8 kV Circuit Breaker
Example 3

91
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 31
Primary-Selective System to Load Side of 13.8 kV Circuit Breaker
Reliability and Availability Comparison of Power at 480 V Point of Use

Example 3a Example 3b
(9 min switchover (switchover in less
time) than 5 seconds")

A'r, A 'r,
A, Forced Hours A, Forced Hours of
Failures of Downtime Failures Downtime
Component per Year per Year per Year per Year

13.8 kV power source (loss of only source 1) 1.644


Protective relays (3) 0.0006
13.8 kV metalclad circuit breaker 0.0036

Total through 13.8 kV circuit breaker with 9 min 1.6482 0.2472


switchover after a failure of source 1 (and
source 2 is OK)

Loss of both 13.8 kV power sources simultaneously 0.312 0.1622 0.312 0.1622

Switchgear bus-insulated (connected to 2 breakers) 0.0068 0.1822 0.0068 0.1822

Total to point E 1.9670 0.5916 0.3188 0.3444

Cable (13.8kV); 900 ft, conduit below ground 0.0055 0.1458' 0.0055 0.1458'
Cable terminations (6)a t 13.8 kV 0.0018 0.0450 0.0018 0.0450
Disconnect switch (enclosed) 0.0061 0.0220 0.0061 0.0220
Transformer 0.0030 1.0260* 0.0030 1.0260'
480 V metalclad circuit breaker 0.0027 0.0108 0.0027 0.0108
Switchgear bus-bare (connected to 7 breakers) 0.0024 0.0576 0.0024 0.0576
480 V metalclad circuit breaker 0.0027 0.0108 0.0027 0.0108
480 V metalclad circuit breakers (5)(failed
while opening) 0.0012 0.0048 0.0012 0.0048
Cable (480V); 300 ft, conduit above ground 0.0004 0.0044 0.0004 0.0044
Cable terminations (2)a t 480 V 0.0002 0.0008 0.0002 0.0008

Total a t 480 V output 1.9930 1.9196 .3448 1.6724

*Data for hours of downtime per failure are based upon repair failed unit.
**Loss of 480 V power for less t h a n 5 s is not counted a s a failure.

92
IEEE
RELIABILITY ANALYSIS AND COST EVALUATION Std 493-1980

d1 3 . 8 LV

NC

Source No1

-AT I utility

- -A-
Y
Source Nd

-
A A
500 MVA O N C
ONC

Point F
\(
m 1 3 800/480 V

480 V

Fig 15
Primary Selective to Primary
of Transformer
Example 4
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 32
Primary-Selective System to Primary of Transformer
Reliability and Availability Comparison of Power
at 480 V Point of Use

Example 4
(switchover time 1 h)
h.r,
A, Forced Hours
Failures of Downtime
Component per Year per Year

13.8 kV power source from electric utility (loss of source 1) 1.644


Protective relays (3) 0.0006
13.8 kV metalclad circuit breaker 0.0036
Switchgear bus-insulated (connected to 1 breaker) 0.0034
Cable (13.8 kV); 900 ft, conduit below ground 0.0055
Cable terminations (6) a t 13.8 kV 0.0018
Disconnect switch (enclosed) 0.0061
Total through disconnect switch with 1 h switchover
after a failure of source 1 (and source 2 is OK) 1.6650 1.6650

Loss of both 13.8 kV power sources simultaneously 0.312 0.1622


Total to point F 1.9770 1.8272

Transformer 0.0030 1.0260'


480 V metalclad circuit breaker 0.0027 0.0108
Switchgear bus-bare (connected to 7 breakers) 0.0024 0.0576
480 V metalclad circuit breaker 0.0027 0.0108
480 V metalclad circuit breakers ( 5 ) (failed while opening) 0.0012 0.0048
Cable (480 V); 300 f t conduit above ground 0.0004 0.0044
Cable terminations (2) a t 480 V 0.0002 0.0008

Total at 480 V output 1.9896 2.9424

* Data for hours of downtime per failure a r e based upon repair failed unit.

7.1.10 Example 5-Secondary Selective power for less than 5 seconds is not
System. counted as a failure).
Description of Secondary-Selective Results-Secondary-Selective System.
System. Fig 16 shows a one-line The results from the reliability and
diagram of the power distribution sys- availability calculations are given in
tem for a secondary-selective system. Table 33.
What are the failure rate and forced Conclusions-Secondary-Selective
hours of downtime per year at the 480 System. The Simple Radial System in
volt point of use? Example 5a-Assume Example 1 had a n average forced hours
%minute manual switchover time. downtime per year that was 19 times.
Example 5b- Assume automatic switch- larger than the Secondary-Selective Sys-
over can be accomplished in less than 5 tem in Example 5b with automatic
seconds after a failure (loss of 480 volt throwover in less than 5 seconds. The

94
IEEE
RELIABILITY ANALYSIS AND COST EVALUATION Std 493-1980

1 1 3 . 8 kV 1 13.8 LV

8 NC

Source No1 Source No2


Utility
---

500 MVA
0 NC

7
C:eoaeob+l eOf - ' C a b l eF e e t

-t
600 Feet
Cable
300

Feet

d l 3 800/480 V

T- /t\
)N C . , .N C
G. v NO

I
480 V
Cable

Fig 16
Secondary-Selective System
Example 5
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Table 33
Secondary-Selective System
Reliability and Availability Comparison of Power
at 480 V Point of Use

Example 5a Example 5b
(9 min. switchover (switchover in less
time) t h a n 5 SI*)

A.r, A 'r,
A, Forced Hours A, Forced Hours of
Failures of Downtime Failures Downtime
Component per Year per Year per Year per Year

13.8 kV power source (loss of only source 1) 1.644


Protective relays (3) 0.0006
13.8 kV metalclad circuit breaker 0.0036
Switchgear bus-insulated (connected to 1 breaker) 0.0034
Cable (13.8 kV); 900 ft, conduit below ground 0.0055
Cable terminations (6) a t 13.8 kV 0.0018
Disconnect Switch (enclosed) 0.0061
Transformer . 0.0030
480 V metalclad circuit breaker 0.0027

Total through 480 V main circuit breaker with


9 min switchover after a failure of
source 1 (and source 2 is OK) 1.6707 0.2506

Total through 480 V main circuit breaker with


switchover in less than 5 s after a failure of
source 1 (and source 2 is OK) 0 0

Loss of both power sources simultaneously 0.312 0.1622 0.312 0.1622

Total to point G 1.9827 0.4128 0.312 0.1622

Switchgear bus-bare (connected to 5 breakers) 0.0017 0.0408 0.0017 0.0408

480 V metalclad circuit breaker 0.0027 0.0108 0.0027 0.0108


480 V metalclad circuit breakers (2)
(failed while opening) 0.0005 0.0020 0.0005 0.0020
Cable (480 V); 300 ft, conduit above ground 0.0004 0.0044 0.0004 0.0044
Cable terminations (2) a t 480 V 0.0002 0.0008 0.0002 0.0008

Total a t 480 V output 1.9882 0.4716 0.3175 0.2210

*Data for hours downtime per failure a r e based upon repair failed unit.
**Loss of 480 V power for less t h a n 5 s is not counted as a failure.

96
IEEE
RELIABILITY ANALYSIS AND COST EVALUATION Std 493-1980

failure rate of the Simple Radial System downtime per year a t the 480 volt point
was six times larger than the of use.
Secondary-Selective System in Example These data do not include outages for
5b with automatic throwover in less scheduled maintenance of the electrical
than 5 seconds. equipment. It is assumed that scheduled
7.1.11 Example 6-Simple Radial Sys- maintenance will be performed a t times
tem with Spares. when 480 volt power output is not
Description of Simple Radial System needed. If this is not possible, then
with Spares. Fig 12 shows a one-line outages for scheduled maintenance
diagram of the power distribution sys- would have to be added to the numbers
tem for a simple radial system. What shown in Table 35. This would affect a
are the failure rate and forced hours of Simple Radial System much more than
downtime per year of the 480 volt point a Secondary-Selective System because of
of use if all of the following spare parts redundancy of electrical equipment in
are available and can be installed as a the latter.
replacement in these average times? 7.1.13 Discussion-Cost of Power
Outages. The forced hours of downtime
(1) 13.8 kV circuit breaker (inside per year is a measure of forced unavail-
plant only) -2.1 h
ability and is equal to the product of
(2) 900 f t of cable (13.8 kV) - 19 h (failures per year) x (average hours)
downtime per failure. The average
(3) 1000 kVA transformer-130 h
downtime per failure could be called
The above three “replace with spare” restorability and is a very important
times were obtained from Table 24 and parameter when the forced hours of
are the actual values obtained from the downtime per year are determined. The
IEEE Reliability Survey of Industrial cost of power outages in a n industrial
Plants 111. The times are much lower plant is usually dependent upon both
than the “repair failed unit” times that the failure rate and the restorability of
were used in Examples 1 through 5. the power system. In addition, the cost
Results-Simple Radial System with of power outages is also dependent on
Spares. The results of the reliability the “plant restart time” after power has
and availability calculations are given been restored [51. The “plant restart
in Table 34. They are compared with time” would have to be added to the
those of the Simple Radial System in “average downtime per failure” r, in
Example 1 using average outage times Table 35 when cost versus reliability
based upon “repair failed unit.” and availability studies are made in the
Conclusions-Simple Radial System design of the power distribution system.
with Spares. The Simple Radial System The IEEE survey of industrial plants
with Spares in Example 6 had a forced [11 found t h a t the average “plant res-
hours downtime per year t h a t was 22 tart time” after a failure t h a t caused
percent lower than the Simple Radial complete plant shutdown was 17.4
System in Example 1. hours. The median value was 4.0 hours.
7.1.12 Overall Results from Six Exam- 7.1.14 Discussion-Definition of Power
ples. The results for the six examples Failure. A failure of 480 volt power was
are compared in Table 35 which shows defined in this guide as a complete loss
the failure rates and the forced hours of incoming power for more than 5
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

mwm *
**o *m
888 2
0 0 0

** ** *
1 9 *
" 2 0
m
3

m*m w
300 m
0 0 0 m
999 9
3
0 0 0

* *
o m ~ m o o o m w m w*m
* m
Nmm3mmmwOt-O **o m
o o m m * * o m 3 m 3 0 0 0 0
999
99"9?999999
N 0 0 0 0 0 0 - 4 0 0 0 0 0 0 2

* I
- 4 m *
6 W cj
m m *
m

N * N w
-400 m
0 0 0 m
999 9
3
0 0 0

h
L

2 h

E 5 E
S G
x 2
.-Y 2 M

2
Y

g
>
0
m
e
42

+
m
Y

ir

98
IEEE
RELIABILITY ANALYSIS A N D COST EVALUATION Std 493-1980

c
2
Q,
W
3
P-
d

E0,
B
i;
x
t
m
h
2

4* (
Q
0
,
0
m e4
'E
rn
m
9
a
9
W

3 3
9
3

0
3
N
E?
0

m
c-
3

W N m
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

seconds. This is consistent with the Table 36


results obtained from the IEEE survey Comparison of Actual and Calculated
of industrial plants [ l l , which found a Reliability and Availability of
median value of 10 seconds for the Double-Circuit Utility Power Supply
“maximum length of power failure that (Failure Defined as Loss of Both
will not stop plant production.” Power Sources)
7.1.15 Discussion -Electric Utility
Power Supply. Previous reliability stud- A‘r,
ies [SI[71[SI have drawn conclusions A, Forced Hours
Failures of Downtime
similar to those made in this section. per Year per Year
All of these previous studies have iden-
tified the importance of two separate Actual single-circuit
utility power supply
power supply sources from the electric from IEEE survey[21 1.956’ 2.582’
utility. The Power System Reliability
Subcommittee made a special effort to Actual double-circuit
utility power supply
collect reliability data on double-circuit from IEEE survey[2l 0.312’ 0.1622’
utility power supplies in the recent
IEEE survey [21. These data are sum- Calculated-two utility
power sources a t
marized in Table 26 and were used in 13.8 kV t h a t a r e
Examples 2 through 5. The two power completely indepen- 0.0012” 0.0008”
sources in a double-circuit utility supply dent
are not completely independent, and the
reliability and availability analysis *Taken from Table 26.
**Calculated using single-circuit utility power
must take this into consideration. The supply d a t a and the formula for parallel reli-
importance of this point is shown in ability shown in Fig 11.
Table 36 where a reliability and avail- locations. One significant factor in this
ability comparison is made between the difference is believed to be different
actual double-circuit utility power sup- exposures to lightning storms. Thus,
ply and the calculated value from two average values for the utility supply
completely independent utility power failure rate may not be valid for any
sources. The actual double-circuit utility one location. Local values should be
power supply has a failure rate more obtained, if possible, from the utility
than 200 times larger than two com- involved, and these values should be
pletely independent utility power used in reliability and availability stud-
sources. The actual double-circuit utility ies.
power supply data came from the IEEE No examples are included here on the
survey 121 and are based upon 77 reliability and availability improvement
outages in 246 unit-years of service at that could be obtained by using local
45 plants with “all circuit breakers generation rather than purchased power
closed.” This is a broad composite from from a n electric utility. However, it is
many industrial plants in different of interest to note the very high relia-
parts of the country. bility of location generation equipment
I t is believed that utility supply found in the IEEE “Reliability Survey
failure rates vary widely in various of Industrial Plants.”[ll
‘Numbers in brackets correspond to those in 7.1.16 Other Discussion. The reliabil-
the References a t the end of this Section. ity and availability analysis in the six

100
IEEE
RELIABILITY ANALYSIS A N D COST EVALUATION Std 493-1980

examples was done for 480 volt low- ity of industrial power systems would
voltage power distribution systems. It have a n accuracy similar to that
is believed that 600-volt systems would obtained by the Air Force with elec-
have similar reliability and availability. tronic systems.
One of the assumptions made in the Some of the errors introduced when
reliability and availability analysis is making reliability and availability pre-
that the failure rate of the electrical dictions using published industry
equipment remains constant with age. failure rates for the electrical equip-
It is believed that this assumption does ment are:
not introduce significant errors in the
conclusions. However, it is suspected (1)All details that could contribute to
that the failure rate of cables may unreliability are not included in the
change somewhat with age. In addition, study.
data collected by the Edison Electric (2)Some of the contributions from
Institute on failures of power trans- human error may not be properly
formers above 2500 kVA show that the included.
failure rate is higher during the first (3)Equipment failure rates can be
few years of service. The reliability data influenced by the adequacy of the
collected in the IEEE survey [11 did not preventive maintenance program
attempt to determine how the failure [11,[111. Contamination from the
rate varied with age for any electrical environment can also have a n influence
equipment studied. on equipment failure rates.
A logical question asked very often is, (4) Correct conclusions can be made
how accurate are reliability and avail- from statistical analysis on the average.
ability predictions? It is believed that But some plants will never experience
the predicted failure rates and forced these average problems that are
outage hours per year are a t best only designed for. For example, several
accurate to within a factor of 2 to what plants will never have a transformer
might be achieved in the field. How- failure.
ever, the relative reliability and avail-
ability comparison of the alternative I n spite of these limitations, it is
power distribution systems studied believed that reliability and availability
should be more accurate than 2:l. analyses can be very useful in cost-
The Rome Air Development Center of reliability and cost-availability tradeoff
the United States Air Force has had studies during the design phase of the
considerable experience comparing the power distribution system.
predicted reliability of Electronic Sys- 7.1.17 Spot Network. A spot network
tems with the actual reliability results would have a calculated reliability and
achieved in the field. These results [91 availability approximately the same as
show that there is approximately a 12 the automatic throwover secondary-
percent chance that the field failure selective system[71,[81. In addition it
rate will be more than 2:l worse than would have the benefit of no momentary
the reliability prediction made using a outage in the event of a failure of any
reliability handbook for electronic of the 13.8 kV cables or equipment since
equipment such as [lo]. It might be bus voltage is not lost on a spot net-
expected that the prediction of reliabil- work.

101
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

7.1.18 Protective Devices other than be used in the analysis of four exam-
Drawout Circuit Breakers. The six exam- ples.
ples in this chapter used drawout cir- The four example systems included
cuit breakers as protective devices. are :
Other types of protective devices are Example 1-Simple Radial System-
also available for use on power systems. Single 13.8 kV Utility Supply.
The examples in this chapter attempted
to show how to make reliability and Example 2b-Primary-Selective to
availability calculations. No attempt 13.8 kV Utility Supply (Dual)-
was made to study the effect on reliabil- Switchover Time Less than Five
ity and availability of different types of Seconds.
protective devices nor to draw conclu- Example 4-Primary-Selective to Pri-
sions that any particular type of protec- mary of Transformer- 13.8 kV Utility
tive device was more cost effective than Supply (Dual)-Manual Switchover in
another. One Hour
Example 5b-Secondary-Selective
7.2 Cost Data Applied to Examples of
with Switchover Time Less than Five
Reliability and Availability Analysis of
Seconds.
Common Low-Voltage Industrial Power
Distribution Systems” Table 35 lists the expected failures
7.2.1 Cost Evaluation of Reliability per year and the average downtime per
and Availability Predictions“ Cost year for each of the examples. These
evaluations are made of the reliability data will be used to show which of the
and availability predictions of four examples has the Minimum Revenue
power distribution system examples Requirement (MRR) making allowances
from Chapter 7.1. The “Revenue for:
Requirements Method” described in Sec- (1)Plant Startup Time
tion 2.2.3.1 is utilized in order to deter-
mine the most cost-effective system. (2) Revenues Lost
7.2.2 Description of Cost Evaluation (3) Variable Expenses Saved
Problem. Management insists that the
engineer utilize an economic evaluation (4) Variable Expenses Incurred
in any capital improvement program. (5) Investment
The elements to be included and a
method of mathematically equating the (6) Fixed Investment Charges
cost impact to be expected from electri- One of the benefits of such a rigidly
cal interruptions and downtimes against structured analysis is that the presenta-
the cost of a new system were presented tion is made in a sequential manner
in Chapter 2.2. It was pointed out that utilizing cost/failure data prepared with
there are several acceptable ways of the assistance of management. With
accomplishing the detailed economic this arrangement the results of the
analysis for evaluation of systems with evaluation are less likely to be ques-
varying degrees of reliability. One of tioned than if a less sophisticated
those considered acceptable, the Reve- method were used.
nue Requirements (RR) Method was 7.2.3 Procedures for Cost Analyses.
presented in detail, and this method will Utilizing the single-line diagrams for

102
IEEE
RELIABILITY ANALYSIS A N D COST EVALUATION Std 493-1980

the four examples a component quantity incurred per failure, Xi


take-off of each system was made, and a 0.4 per year-fixed investment charge
present-day installed unit costs assigned factor, F
for each component. In the case of dual
13.8 kV Utility Company’s Supply, the These values are shown in Table 38
basic cost of the second supply was after (21, (41, (51, (81, and (13) respec-
estimated on the basis of a hypothetical tively.
case, assuming that a one-time cost only 7.2.6 Results and Conclusions. The
would be incurred. The extension of the minimum revenue requirements for
costs results in the overall installed cost each of the four examples are shown in
for each of the four examples. A sum- item (15) a t the bottom of Table 38.
mary of the installed costs is presented Some of the conclusions that can be
in Table 37. The total installed costs for made are tabulated below:
each example are listed again after item Example 1 -Simple Radial System.
(12) in Table 38. This system requires the least initial
The Revenue Requirements Method is investment-$61,700-but its minimum
used to calculate the total cost in dol- revenue requirements of $112,877 per
lars per year of both the “installed cost” year is second highest of the four exam-
and the “cost of unreliability” for the ples analyzed.
four examples. The methods for making Example 2b-Primary-Selective to
these calculations are tabulated in 13.8 kV Utility Supply (Dual) with
Table 38. The reliability data and the Switchover Time Less than Five Seconds.
assumed cost values used are described This system requires a n initial invest-
in the next two sections. ment of $141,700 or 2.3 times that of
7.2.4 Reliability Data for Examples. the simple radial system; however, the
Table.35 can be used to determine the minimum revenue requirement is
failures per year, A , and the “average $74,495 per year, which is the least of
hours downtime per failure,” r, for each the four examples.
of the examples. The value of “r” is Based on the data presented, Example
determined from dividing “A .r” by “A .” 2b would be selected since it has the
The values of “r” and “A” for the four least minimum revenue requirement.
examples are shown after (1) and (10) Example 4-Primary-Selective to Pri-
respectively in Table 38. mary of Transformer, 13.8 kV Utility
7.2.5 Assumed Cost Values. The fol- Supply (DualbManual Switchover Time
lowing common cost factors were of One Hour. This system shows next to
assumed in 1976 for use in all four of highest initial cost of $171,900 and the
the examples: highest minimum revenue requirement
of $154,250 per year. A major contribu-
10 hours/failure- plant startup time
tor to the high MRR is the fact that
after a failure, s
while a dual system has been provided
$8,00O/hr -revenues lost per hour of the utility supplies one hour manual
plant downtime, g , switchover requirement increases the
failure rate and downtime to account
$6,00O/hr -variable expenses saved
for its high MRR. If a n automatic
per hour of plant downtime, X,
switchover were utilized, the example
$20,00O/failure -variable expenses would be competitive with Example 2b.

103
IEEE
Std 493-198G RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Y
3 0 0

P
s
e
0
0
0
0
0
0
0
0
w
0
0
0
0
0
0
0
m
N
0
0
0
Q,
0
Q,
0
In
0
m
Y
m
0 d f d m
4 0
N
3 0
04
+
r3 ee

W
;
a
x
.-Y
Y m
4
N 0
0
N
N m 3 0
0
m
m
B
3

Y
m 0 0 0 0 0

s 0
0
0
0
0
d
0
0 0
In 0
0
0
Q,
0
Q,

d
m
e
m
*
0
m
0
* d
4
(D N (D 3
m
4
r-
3

a
E
r3 (i,

x
W
x
.-
Y
Y m
N 0
0
0
0
3 3 0
m
0
N 0
9
cp
4
3 m
N

Y
0 0 0 0 0 0

n
N
s
e
0
0
0
0
0
N
0
N
r- 0
0
0
0
(D
0
In
04
0
0
(D
r-
0
3
c-
0
3
Y
id m (9
f
m
e
a ee 0
N

j h
*
*
.e
3 0
W G m 3 0 3 3
0
4 0
(D m
3
cp
Y
0 0 0 0 0 0
s 0
0
N 0 0
0 0
In 0
0 r-
0
0
0
p1

-
3
m
3
m
*
r3
0
0.1

ee
p1 0
N
(0 N (0 3
(D
3
(D

;
a

W
x
.-
Y
Y 3 0 4 3 3 0
0 0
m
3
cp
(0

04 0 0 0 0 0
0 3
0 c.l
0 0 0 0
In
0
.a
- 4 2

p: 0 0
04 m (D N
3u N N
(i
,
Y Y
b7

c
s n
m
I
4 4 .-*
I 1
2
2 *
0

u E
x n
2 2 b< 36 .-bV z
.-
s .-
* * g .r: g .r: .-%
e
.e

0
c(
$
m
za
0
i!
.- $E $2
$2
c c0
a fie
23 -4
*
$
4 aa
W

ui
V
.-0
.-
'E cp: cp: -39
08
0 *4 n
2
$ ?42 52 ;i' g +mI
+ Y

*h
.-
.-
e 5 .$
OS d k s 8
0
Y

3 3 (0 4 s
s' m

104
IEEE
RELIABILITY ANALYSIS AND COST EVALUATION Std 493-1980

Table 38
Sample Reliability Economics Problem*

Example 1 Example 2b Example 4 Example 5b


Primary
Simple Selective Primary
Radial System to 13.8kV Selective**** Secondary
Single 13.8kV Utility Primary of Selective
Utility Supply Supply**** Transformer System***

(1)r = component repair time or


transfer time to restore
service, whichever is
less, hours per failure 2.16 5.45 1.48 0.69

(2)s** = plant startup time, hours 10 10 10 10


per failure

(3)r + s [items (1) + (2)l 12.16 15.45 11.48 10.69

(4)gp** = revenues lost per hour of


plant downtime, $/h $8 000 $8 000 $8 000 $8 000

(5)xp** = variable expenses saved,


$/h $6 000 $6 000 $6 000 $6 000

(6) gp-xp [items (4) (5)1, ~

value of lost production, $/hr $2 000 $2 000 $2 000 $2 000

(7)( g p - x p ) ( r + s) = [items (6) x (3)1,


$/failure $24 320 $30 900 $22 960 $21 380

(8) x L** = variable expenses incurred


per failure, $/failure $20 000 $20 000 $20 000 $20 000

(9)Items (7) + (8) $44 320 $50 900 $42 960 $41 380

(10)A = failure r a t e per year 1.99 0.35 1.99 0.32

(11) Items (9)x (10)= X , $/year $88 197 $17 815 $85 490 $13 241

(12)C * * = investment, $ $61 700 $141 700 $171 900 $200 900

(13)F** = fixed investment charge


factor, per year 0.4 0.4 0.4 0.4

(14)CF = fixed investment charges,


$/year $24 680 $56 680 $68 760 $80 360

(15)G = X + C F , [items (11) + (1411,


minimum revenue
requirement, $/year $112 877 $74 495 $154 250 $93 601

Economic choice Example 2b

*All cost estimates were made in 1976.


**Assumed values in this sample problem.
***Switchover time less than 5 s.
****Manual switchover time 1 h.

105
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

Example 5b-Secondary-Selective Power Systems Technical Conference, Los


System with Switchover Time Less than Angeles, May 10-13, 1976.
Five Seconds. This system requires the
highest initial investment -$200,900- [SI DICKINSON, W. H., GANNON, P.
and produces the next to the least E., HEISING, C. R., PATTON, A. D.,
minimum revenue requirements of and McWILLIAMS, D. W. Fundamen-
$93,601 per year. tals of Reliability Techniques as Applied
to Industrial Power Systems, Conf Rec
7.3 References 1971 IEEE Ind. Comm. Power Syst Tech
Conf 71C18-IGA, pp 10-31.
111 IEEE COMMITTEE REPORT.
Report on Reliability Survey of Indus- [71 HEISING, C. R. Reliability and
trial Plants. ZEEE Transactions on Availability Comparison of Common
Industry Applications, MarIApr, Jul/Aug, Low-Voltage Industrial Power Distribu-
Sept/Oct 1974, pp 213-252, 456-476, tion Systems. IEEE Trans Ind Gen
681. Appl, Vol IGA-6, pp 416-424, Sept/Oct
1970.
[21 IEEE COMMITTEE REPORT. Reli-
ability of Electric Utility Supplies to [81 HEISING, C. R., and DUNKI-
Industrial Plants. ZEEE Technical Con- JACOBS, J. R. Application of Reliabil-
ference, 75-CH0947-1-1A, pp 131-133. ity Concepts to Industrial Power Sys-
tems. Conf Rec 1972 IEEE Industry
L3l GARVER, D. P., MONTMEAT, F. E. Applications Society Seventh Annual
and PATTON, A. D. Power System Reli- Meeting, 72CHO-685-8-1A, pp 287-296.
ability I -Measures of Reliability and
[91 FEDUCCIA, A. J., and KLION, J.
Methods of Calculation. ZEEE Transac-
How Accurate Are Reliability Pre-
tions on Power Apparatus and Systems,
dictions. Rome Air Development Center,
July 1964, pp 727-737.
1968 Annual Symposium on Reliability,
[41 PATTON, A. D. Fundamentals of IEEE Catalog Number 68C33-R, pp
Power System Reliability Evaluation, 280-287.
ZEEE Industrial & Commercial Power
[lo1 Reliability Stress and Failure Rate
Systems Technical Conference, Los
Data for Electronic Equipment, MIL-
Angeles, May 10-13, 1976.
HDBK-217A, Department of Defense, 1
[51 GANNON, P. E. Cost of Interrup- December, 1965.
tions; Economic Evaluation of Reliabil-
[111 WELLS, S. J. Electrical Preventive
ity IEEE Industrial and Commercial
Maintenance. IEEE Industrial and Com-
mercial Power Systems Technical
2References 111 and [21 are reprinted in Ap- Conference, Los Angeles, May 10-13,
pendixes A, B, and D. 1976.

106
8. Basic Concepts of Reliability Analysis
by Probability Methods

8.1 Introduction system. A group of components con-


This chapter provides theoretical nected or associated in a fixed confi-
background for reliability analysis used guration to perform a specified function
in other chapters, Chapter 2 in particu- of distributing power.
lar. Some basic concepts of probability
failure. The termination of the ability
theory are discussed as these are essen-
of an item to perform a required func-
tial to the understanding and develop-
tion. (See 2.1.3 for a more detailed
ment of quantitative reliability analysis
definition applicable to industrial and
methods. Definitions of terms commonly
commercial power distribution systems.)
used in system reliability analysis are
also included. The three methods dis- mean time between failure (MTBF).
cussed are, the cut set approach, the The mean exposure time between con-
state space method and the network secutive failures of a component. It can
reduction technique. be estimated by dividing the exposure
Definitions. Some commonly used time by the number of failures in that
terms in system reliability analysis are period, provided that a sufficient
defined here. These terms are used in number of failures have occurred in
the wider context of system reliability t h a t period.
activities. Additional definitions more failure rate. The mean number of
specifically related to power distribution failures per unit exposure time of a
systems are given in 2.1.3. component.
mean time to repair (MTTR). The
component. A piece of equipment, a mean time to repair a failed component.
line or circuit, or a section of a line or I t can be estimated by dividing the sum-
circuit, or a group of items which is mation of repair times by the number o€
viewed as a n entity for purposes of reli- repairs, and it is, therefore, practically
ability evaluation. the average repair time.
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

8.2 Basic Probability Theory times, the probability of the system


This section discusses some of the being in failed state a t time t is,
basic concepts of probability theory. An
appreciation of these ideas is essential P f ( t ) = N f/ N (Eq 1)
to the understanding and development N+=
of reliability analysis methods. 8.2.4 Combinatorial Properties' of Event
8.2.1 Sample Space. Sample space is Probabilities. Certain combinatorial
the set of all possible outcomes of a properties of event probabilities are use-
phenomenon. For example, consider a ful in reliability analysis are discussed
system of three distribution links. in this section.
Assuming that each link exists either in a. Addition rule of probabilities
the operating or up state or failed or Two events A , and A z are mutually
down state, the sample space is exclusive if they cannot occur together.
S = ( l U , 2U, 3U), (lD, 2U, 3U), ( l U , For events A l and A , that are not
2D, 3U), (1U 2U, 3D), (lD, 2D, 3U), mutually exclusive, t h a t is, which can
(lD, 2U, 3D), ( l U , 2D, 3D), (lD, 2D, 3D) happen together,

Here zXJ, ZDdenote that the component i P(A1 U A + P ( A , ) + P ( A J (Eq 2)


is up or down, respectively. The possi-
ble outcomes of a system are also called -P(A1 nA , )
system states and the set of all possible
system states is called system state where
space.
8.2.2 Event. Now in the example of 3 PCA, U A z ) = Probability of A I
distribution links, the descriptions (lD, or A z , or both
2D, 3U), OD, 2U, 3D), ( l U , 2D, 3D),
P(A1 Az) = Probability of A , and A z
(lD, 2D, 3D) define an event t h a t two
happening together.
or three lines are in the failed state.
Assuming that a minimum of two lines
When A l and A z are mutually
are needed for successful system opera-
exclusive, they cannot happen together,
tion, this set of states also defines the
system failure. The event A is, there-
n
that is, P ( A , Az)=O, and therefore
fore, a set of system states and the (Eq 2) reduces to:
event A is said to have occurred if the
system is in a state t h a t is a member of P(Al + P(Az) (Eq 3)
set A .
8.2.3 Probability. A simple and useful b. Multiplication rule of probabilities
way of looking a t the probability of a n If the probability of occurrence of
occurrence of the event in a large event A , is affected by the occurrence
number of observations. of A z , then A , and A 2 are not indepen-
Consider, for example, t h a t a system dent. The conditional probability of
is energized a t time t=O and the state event A , , given t h a t event A 2 has
of the system is noted at time t. This is already occurred, is denoted by
said to be one observation. Now if this P ( A l I A z ) and:
process is repeated N times and the sys-
tem is observed in the failed state N f P ( A 1 n A z ) = P ( A z ) = P ( A 1 1 A 2 ) (Eq4)

108
~

IEEE
RELIABILITY ANALYSIS BY PROBABILITY METHODS Std 493-1980

This is also used to calculate the condi- following properties:


tional probability:
(1) Px(x) = 0 unless x is one of the
values xo, xl, xz, . . .
(2) 0 6 Px (Xi) 6 1
When, however, events A , and A z are
independent, t h a t is, the occurrence of
A does not affect the occurrence of A ,:
Another useful function is the proba-
bility distribution function or cumula-
tive distribution function. It is defined
Complementation.
by :
A , is used to denote the complement
of event A , . The complement A , is the Fx (XI = PtXGx)
set of states t h a t are not members of
A , . For example, if A , denotes states = Px (xi), X ~ G X (Eq 9)
indicating system failure, then the
states -not representing system failure The probability density function fx(x)
[or simply f ( x ) l for a continuous ran-
make A , .
dom variable is so defined that:
b
P(a 6 X6 b) =$ f ( y ) dy
a
(Eq 10)
8.2.5 Random Variable. A random
variable can be defined as a quantity If, for example, X denotes the time to
t h a t assumes values in accordance with failure, Eq 10 gives the probability
probabilistic laws. A discrete random that the failure will occur in the inter-
variable assumes discrete values val (a, b ) . The corresponding proba-
whereas a random variable assuming bility distribution function for a con-
values from a continuous interval is tinuous random variable is:
termed continuous random variable. For
example, the state of a system is a
discrete random variable and the time
between two successive failures is a
continuous random variable.
= $"f (y)dy
--m
(Eq 11)

8.2.6 Probability Distribution Function. The function f(x) has certain specific
Probability distribution function properties [111 including the following:
describes the variability of a random
variable. For a discrete random variable
X, assuming values xi, the probability
density function is defined by:
8.2.7 Expectation. The probabilistic
behavior of a random varaiable is com-
pletely defined by the probability den-
sity function. It is often, however, desir-
The probability density function for a
discrete random variable is also called 'Numbers in brackets correspond to those in
probability mass function and has the the References at the end of this Section.

109
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

able to have a single value characteriz- between failures is d = l / A , where A


ing the random variable. One such denotes the failure rate of the com-
value is the expectation. It is defined ponent. It should be noted that the
bv: failure rate for exponential distribution
and only exponential distribution is con-
E (X) = c x i P x ( x i ) for discrete stant.
i
random variable
m 8.3 Reliability Measures. The term
= $ -Di)
x f (x)dx for continuous reliability is generally used to indicate
random variable the ability of a system to continue to
perform its intended function. Several
The expectation of X i s also called the measures of reliability are described in
mean value of X and has a special rela- the literature and some of the meaning-
tionship to the average value of X in ful indexes for repairable systems, expe-
that if random variable X is observed cially power distribution systems, are
many times and the arithmetic average described in this section.
of X calculated, it will approach the 1. Unavailability. Unavailability is
mean value as the number of observa- the steady state probability that a com-
tions increases. ponent or system is out of service due to
8.2.8 Exponential Distribution. There failures or scheduled outages. If only
are several special probability distribu- the failed state is considered, this term
tion functions [ll, but the one of partic- is called forced unavailability.
ular interest in reliability analysis is 2 . Availability. Availability is the
the exponential distribution, having the steady state probability that a com-
probability density function: ponent or system is in service, satisfac-
torily performing its intended funtion.
f (x)=Aexp ( - A x ) (Eq 13) Numerically availability is the comple-
ment of unavailability, that is:
where A is a positive constant. The
mean value of random variable X with Availability = 1 - unavailability
exponential distribution is 3. Frequency of system failure. This
index can be defined as the mean
number of system failures per unit
time.
4. Expected failure duration. This
=1/X (Eq 14)
index can be defined as the expected or
long-term average duration of a single
Also the probability distribution failure event.

F(x) = $xhe-Aydy 8.4 Reliability Evaluation Methods


n Numerical values for reliability meas-
= 1- e-Ax
ures can be obtained either by analyti-
(Eq 15) cal methods or through digital simula-
tion. Only the analytical techniques are
If the time between failures obeys the discussed here and discussion on simula-
exponential distribution, the mean time tion approach can be found in [ll. The
IEEE
RELIABILITY ANALYSIS BY PROBABILITY METHODS Std 493-1980

three methods described in this chapter


are the state-space approach, network
reduction and cut-set methods. The
state space approach is very general but
becomes cumbersome for relatively
large systems. The network-reduction
procedure is applicable when the system
consists of series and parallel subsys-
tems. The cut-set approach is becoming
increasingly popular in the reliability
analysis of transmission and distribu-
tion networks and has been primarily
used in this book. The state space and
network methods are discussed in this
chapter for reference and for potential
benefit to the users of this guide.
8.4.1 Minimal Cut Set Approach. The
cut set approach can be applied to sys-
tems with simple as well as complex
configurations and is a very suitable
technique for the reliability analysis of
where cln e,, for example, denotes
the failure of components of both the
power distribution systems. A cut set is minimal cut-sets 1 and 2 and therefore
a set of components whose failure alone
P(C1 means the probability of
will cause system failure and a minimal
failure of all the components contained
cut set has no proper subset of com-
in C1and C,, that is:
ponents whose failure alone will cause
system failure. The components of a
minimal cut set are in parallel since all
of them must fail to cause system
failure and various minimal cut sets are
in series as any one minimal cut set can
probability of component i
cause system failure.
A simple approach for the identifica- being in the failed state
tion of minimal cut sets is described in ri / ( d , + Ti)
Chapter 2 but more formal algorithms
hi/(Ai + p i )
are also available in literature [ll.
Once the minimal cut sets have been MTBF of component i
obtained, the reliability measures can failure rate of component i
be obtained by the application of suit-
able formulae 111, [21. Assuming com- 1/ di
ponent independence and denoting the MTTR of component i
probability of failu? of components in
cut set C, by P ( C , ) , the probability repair rate of component i
(unavailability) and the frequency of
1/ri
system failure for m minimal cut-sets
are given by: product

111
IEEE
Std 493-1980 RELIABLE INDUSTRIAL A N D COMMERCIAL POWER SYSTEMS

The frequency of failure is given by : rn rn

f f = P ( C 1 )w 1 + P(C2) w2
= c
i=l
fcq rcs/c
i= 1
fCSi
(Eq 20)

+ . . . + P(Crn,W, where

-[P(E, n E,) w1,2 d f = system mean failure duration

+ P ( C , n E,) w1,3 rCsi= mean duration of cut set event i

+ . . . + P(E, n Cj) W, jl, i#j The application of Eqs 19 and 20 to


power distribution systems is discussed
in Chapter 2. The components in a
minimal cut-set behave like a parallel
system, and f c s i (assuming n com-
ponents in Ci 1 can be computed as fol-
lows:

and
The mean failure duration is given by :

d f= Pf Iff
For example, for a cut-set having three
When the mean time between the components 1, 2, and 3:
failure of components is much larger
than the mean time to repair or in A1 A 2 A 3 (Pl + P2 + P3)
other words, the component availabili- f c s i = (A1 + p1) (A2 + p 2 ) (A3 + pug)
ties approach unity, Eqs 16 and 17 can
be approximated [31 by simpler equa- =Al A, A, (rl r 2 + r 2 r3 + r 3 rl),
tions:
assuming A i <<P
rn rn
Pf= P(C2) = Z P c s , (Eq 18) and
2=1 i= 1

and rl r2 r3

rn rcs, = r1 r 2 + r2 r 3 + r 3 r1
f f = 2 P ( E i , Wl
2=1
= CfCS;
i= 1
(Eq 19)
8.4.2 State Space Approach. The
state-space method is a very general
where Pcsiand f C s i are the probability
approach and can be used when the
and frequency of cut-set event i. Also, components are independent as well as
d f = Pf I f f for systems involving dependent failure
and repair modes. The different steps of
= IC
CPCSL fCSL
this approach are illustrated using a
r=l i=l
IEEE
RELIABILITY ANALYSIS B Y PROBABILITY METHODS Std 493-1980

simple example of a component in series simultaneous equations needs to be


with two parallel components, as shown solved to obtain state probabilities [ll.
in Fig 17. Only the independent case is discussed
1. Enumerate the possible system states. here and for this, say the probability of
Assuming each component can exist being in state 2 can be determined by:
either in the operating state (U) or in
the failed state (D) and that the com- (Eq 23)
ponents are independent, there are where
eight possible system states. These
states are numbered 1 through 8 in Fig piu = probability of component i being
18 and the description of the component UP
states is indicated in each system state. di,(di + ri)
2. Determine interstate transition rates.
The transition rate from si (that is, /J-i/(Ai + pi)
state i) to sj is the mean rate of the sys- and
tem passing from si to s j . For example,
in Fig 18 the system can transit from s1 Pjd = probability of component i being
to s2 by the failure of component 1 and in failed state
the repair of component 1 will put the = r i / ( d i+ r i )
system back into sl.Therefore, the tran-
sition rate from s1 to s2 is A , and the = hi& +pi)
transition rate from s2 is s1 is p,. 4. Determine reliability measures. The
3. Determine state probabilities. When states constituting the failure or suc-
the components can be assumed cess or any other event of interest are
independent, state probabilities can be identified. For the system shown in Fig
found by the product rule as indicated 17, if the links 2 and 3 are fully redun-
in Equation 6. When, however, statisti- dant, system failure can occur if either
cal dependence is involved, a set of component 1 fails or component 2 and 3

Fig 1 7
One Component in a Series with
Two Components in Parallel

SOURCE

--=---I __O LOAD


IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

ID 2 U 3U IU 2D 3 U lU 2U 3D
Is.

SUCCESS

FA1L U R E

Fig 18
State Transition Diagram for the
System Shown in Fig 17

fail or if all the components fail. The Applying to our example,


state space S as shown in Fig 18 is
Pf=P , + P , + P , + P , + P ,
S = {1,2,3,4,5,6,7,8)
where Pi can be found by the product
The subset A representing failure can rule as in Eq 23.
be identified as: The frequency of system failure, that
A = (2, 5, 6, 7, 8) is, the frequency of encountering subset
A can be computed by the following
and the subset representing the success relationship:
states is
S-A = (1, 3, 4)
Unavailability or the probability of the
system being in the failed state is now
given by: where A i j transition rate from state i
=
to state j .
P f = XPG (Eq 24) Applying Eq 25 to the system of Fig
LEA 17:

where i EA indicates t h a t summation is


over all states contained in subset A.
IEEE
RELIABILITY ANALYSIS BY PROBABILITY METHODS Std 493-1980

/ IU 2 u 3u I,

I LU 2D 3 U I
SZ
F2
SYSTEM S U C C E S S
----
1, SYSTEM FAILURE
i
I D 2D 3U I U 2 D 3D

.s5

Fig 19
State Transition Diagram for the
System Shown in Fig 17 when
Components are not Independent

The mean failure duration can be 0.4.3 Network Reduction. The net-
obtained from P f and f f using: work reduction procedure is useful for
systems consisting of series and parallel
d f= p fI ff (Eq 26) subsystems. The method consists in suc-
cessively reducing the series and paral-
lel structures by equivalent components.
In the preceding analysis, it has been The knowledge of series and parallel
assumed that the failure of a component reduction formulas is essential for the
does not alter the probability of failure application of this technique.
of the remaining components. If, how- 0.4.4 Series system. The components
ever, it is assumed t h a t after the system are said to be in series when the failure
failure, no further component failure of any one component causes system
will take place, the state transition failure. It should be noted that the com-
diagram of Fig 18 will be modified as ponents do not have to be physically in
shown in Fig 19. Now once component 1 series, it is the effect of failure t h a t is
fails or components 2 and 3 fail, no important. Two types of series systems
further failure is possible. The probabil- are discussed.
ities in this case cannot be calculated by a. Independent components. For the
simple multiplication. It can be com- series system of independent com-
puted by solving a set of linear equa- ponents, the failure and repair rate of
tions [ l l . Once the state probabilities the equivalent component are given by:
n
have been calculated, the remaining A,= hi
procedure is the same. (Eq 27)
i= 1
IEEE
Std 493-1980 RELIABLE INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

and I t can be seen from Eqs 29 and 30 t h a t


p , = A, /(n(1+
n

i= 1
A i l p i ) -1) (Eq 28)
for component MTBF much larger than
MTTR, the r s for the dependent and the
independent cases are practically equal.
where A, and p , are the equivalent 8.4.5 Parallel system. Two com-
failure and repair rates of the series sys- ponents are considered in parallel when
tem and either can ensure system success. The
n
equivalent failure and repair rates of a
denotes product of values 1 through parallel system of two components are
i=l given by:
n.

Assuming t h a t A i is much smaller A1 (rl + r2) (Eq 31)


than p i (which, in other words, means
t h a t MTBF is much larger than MTTR),
1 + A rl + A, r2
the quantities involving products of h i and
can be neglected and Eq 28 reduces to:
pp=p.1 +F2 (Eq 32)

If A 1 r l and A 2 r 2 are much smaller than


1, then Eq 31 can be written as:
b. Components involving dependence.
When it is assumed t h a t after the sys-
tem failure no more components will
fail, the equivalent failure and repair 8.6 References
parameters are: [11 SINGH, C. and BILLINTON, R. Sys-
tem Reliability Modelling and Evaluation,
London, Hutchinson Educational, 1977.
A,= c Ai
n

i= 1 [21 SHOOMAN, L.M. Probabilistic Relia-


bility: A n Engineering Approach, New
and York, McGraw-Hill, 1968.
n [31 SINGH, C. On the Behaviour of
r,= Cri A ~ / A , (Eq 30) Failure Frequency Bounds, IEEE Trans
i= 1
Reliability, vol R-26, Apr 1977, pp 6 S 6 6 .
Appendix A
Report on Reliability Survey of Industrial Plants

Part 1
Reliability of Electrical Equipment

Part 2
Cost of Power Outages, Plant Restart Time,
Critical Service Loss Duration Time, and
Type of Loads Lost Versus Time of Power Outages

Part 3
Causes and Types of Failures of Electrical
Equipment, The Methods of Repair, and the Urgency of Repair

BY
Reliability Subcommittee
Industry & Commercial Power Systems Committee
IEEE Industry Applications Society

W. H. Dickinson, Chairman
P. E. Gannon D. W. McWilliams
M. D. Harris R. W. Parisian
C. R. Heising A. D. Patton
W. J. Pearce

Industrial and Comercial Power Systems Technical Conference


Institute of Electrical and Electronics Engineers, Inc
Atlanta, Georgia
May 13-16,1973

Published by
IEEE Transactions on Industry Applications
MarIApr 1974

117
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

Report on Reliability Survey of Industrial


Plants, Part I: Reliability of Electrical
Equipment
IEEE COMMITTEE REPORl

Absrrocr-An IEEE sponsored survey of electrical equipment reliabil- 6) repair urgency information;
ity in industrial plants was completed during 1972. The results are 7) causes and types of failures:
reported from this survey which included a total of 1982 equipment 8) maintenance data and policies,
failures that were reported by 30 companies covering 68 plants in nine
industries in the United States and Canada. ‘It is not practical to publish all the results contained in the
survey in a single paper. They will be presented in six sep-
INTRODUCTION arate parts. The first three parts are published at this time

A KNOWLEDGE of the reliability o f electrical ‘quipinent


is an Important consideration i n t h e design power
distribution systems for industrial plants. It is possible t o make
part 1: ~ ~ l , ~ bof i~l i ~l ~ ~~ ~ ~ ~ ~ i ~~ ~
Part 2 : Cost of Power Outages, Plant Restart Time, Critical
Service Loss Duration Time, and Type of Loads
l i ~ ~

quantitative reliability comparisons between alternative designs Lost Versus Time of Power Outages [ I 1) ;
of new systems and then use this information in cost-reliahil- Part 3 , Causes and Types of Failures, Methods of Repair,
ity tradeoff studies t o determine which type of power distrihu- and Urgency of Repair [ I21 .
tion systems to use [ 1 ] - [ 1 0 ] . The cost of power outages at
the various plant locations can he factored into the decision as A major part of the data in these three papers are presented
to which type of power distribution system to use. These in summary form. It is expected that the additional three
decisions can then he based upon t o t a l owning over papers will be presented at a later date and will contain further,
useful life of the equipment rather than first cost. in-depth information where questions have been raised to point
O u t the need for data.
In 1969 a Reliability Working Group was formed under the
Industrial Plants Power Systems Subcommittee, Industrial and
Cominercial Power Systems Committee. In 1972 the activity SURVEYFORM
was changed to a Reliability Subcommittee under the same The survey form is shown in Appendix A . Three types of
Committee. One of the major activities of the Reliability cards were used for reporting the information.
Working Group and the Reliability Subcommittee has been to Card type 1 asks for data on plant identification and other
conduct a survey of equipment reliability in industrial plants. general plant information.
This survey was conducted during the latter half of 1971 and Card type 2 asks for data on a specific equipment class, in-
the early part of 1972 and attempted to update a similar sur- cluding the total number of installed units, on their failure
vey [ 1 I ] which had been conducted eleven years ago. The experience, on maintenance practices, and on estimated repair
results from the present survey contain data o n failure rate and times of failed equipment.
average downtime per failure for 74 equipment categories. The Card type 3 asks for data on each individual failure reported
Reliability Subcommittee also felt that additional information on a card type 2 .
was needed in the present survey beyond what was collected It was necessary to provide definitions for “failure” and
twelve years ago. Some of the additional information is the “repair time.”
following: A failure is defined as any trouble with a power system com-
ponent that causes any of the following to occur:
1) cost o f power outages of industrial plants;
2 ) plant restart time; I ) partial or complete plant shutdown, or below-standard
3) critical service loss duration time; plant operation;
4) type of loads lost versus time of power outages; 2 ) unacceptable performance of user’s equipment;
5) repair or replacement time data; 3) operation of the electrical protective relaying or emer-
gency operation of the plant electrical system;
Paper TOD-73-158, approved by the Industrial and Commercial Pouer 4) de-energization of any electric circuit or equipment.
Systems Committee of the IEEE Industry Applicatlons Society for
presentation at the 1973 Industrial and Commercial Power Systems A failure on a public system may the
Technical Conference, Atlanta, Ca., May 13-16. Manuscript released
for publication November 5, 1973. user to have either I ) a power interruption or loss of service. or
2 ) a deviation from normal voltage or trequency of sufficient
, ~ ~ ~ ~ ~ ~ ~ ~ d ~ ~ ~ ~ ~ ~ ~ : Y c ~ ~ ~ ~ ~ ~ a f : , e e f ~ h ~ ~ ~ ~ , ~
P. E. Gannon, id.D. Harris. C. K . Heisinp, D. \v. !dcwilliams, R . w. Pan- magnitude or duration to disrupt plant production. A failure
sian, A. D. Patton, and W . J . Pearce. on an in-plant component causes a forced outage of the compo-
118
IEEE-IAS TRANSACTIONS MAR/APR 1974

nent, and the component thereby is unable t o perform its A typical value often chosen for the confidence interval IS
intended function until it is repaired or replaced. 0.90. Once values for hL_and XU are found, one can say that
Repair time of a failed component or duration of a failure is 1,whose best estimate is A, lies between X L and Xu with 1007
the clock hours from the time of the occurrence of the failure percent confidence. Clearly the narrower the izterval between
t o the time when the component is restored to service, either A, and X u , the greater one’s confidence that X is a good esti-
by repair of the component or by substitution with a spare mate of X, the true failure rate. Expressions for X L and Xu are
component. It is not the time required to restore service t o a given as follows [ 171 :
load by putting alternate circuits into operation. It includes
time for diagnosing the trouble, locating the failed component,
waiting for parts, repairing or replacing, testing, and restoring
the component t o service.

RESPONSETO SURVEY
A total of 30 companies responded to the survey question- where x 2 p , nis the p percentage point of a chi-squared distribu-
naire, reporfing data on 68 plants from nine industries in the tion with n degrees of freedom. xzp. n is tabled in statistical
United States and Canada as shown in Table I . There was a handbooks.
total of 1982 equipment failures reported i,n the survey; this By substituting the value of T from (1) into (4) and (5) we get
included more than 620 000 unit-years of experience. Many of
the plants reported data covering more than one year of
experience.
Most of the data were reported to the IEEE Reliability Sub-
committee during late 1971 and early 1972. Unfortunately, a (7)
downturn in the business cycle during thjs period of time
caused many companies to reduce their work force and The deviation of the lower confidence level f r o m a in percent
because of this fewer were able to participate in the survey than of% is
had been originally hoped
%devL = 100 ( 1 - %)
SURVEY DATAPREPARATION \ AI

ofthe returned survey forms were reviewed, Similarly, the deviation of the upper confidence level from ‘i
An attempt was made to clarify any discrepancies that were in percent O f % is
detected. usable data were punched onto IBM cards for use in
data processing. %devu = 100 (?- 1) . (9)

STATISTICAL O F EQUIPMENT
ANALYSIS FAILURES Equations (6)-(9) were used to develop Fig. 1 . These curves
Two equipment parameters are of prime importance in avoid the need of looking up xZp,n.Here hL and X u are
making system reliability studies. These parameters are 1) fail- plotted in terms of percent deviation from X as a function of
ure rate and 2) average outage duration or repair time. The the observed number of failures.
best estimate for the failure rate of a particular type of e q u i p The best estimate for the average outage duration or repair
ment is the number of failures actually observed, divided by time for a particular type of equipment is simply the average
the total exposure time in unit-years, that is, of the observed outage durations. Confidence limit expressions
for average outage durations are also available if the distribu-
A -
f
tional nature of outage durations is known [17].However,
T
such expressions are not given here primarily because the
where average outage durations given in this paper are intended as a
rough guide only. Equipment outage durations are believed to
1 best estimate of failure rate in failures per unit-year
be more a function of the nature of a power system’s operator
X true failure rate
f number of failures observed than an inherent function of the equipment itself. Hence,
T . total exposure time in unit-years. average outage durations for equipment used in reliability
studies should be values believed most reasonable for the
Statements regarding the accuracy of failure rate estimates can particular system being studied.
be made through the use of confidence limits [IO], [ 141 -[ 17). The data from the survey contained information on the
Failure rate confidence limits are upper and lower values of failure and repair characteristics of 217 categories of equip-
failure rate such that the following equations hold: ment. However, the number of observed failures for many
equipment categories was too small t o allow adequately accu-
rate estimates of failure rates to be made. The Reliability Sub-
committee felt that a minimum of eight to tenobserved failures
was required for “good” accuracy when estimating equipment
(3)
failure rates (see Fig. 1). Therefore, whenever possible and
where reasonable from an engineering point of view, equipment cate-
gories having less than ten observed failures were combined
A, lower confidence limit of failure rate with other categories so as to bring the number of observed
XU upper confidence limit of failure rate failures in the combined category up to a minimum of ten. In
7 confidence interval (or confidence level). some cases an equipment category with a large number of

119
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

+180

4160

+120

+loo

+@I

Deviation
i n Percent + 60
of Best
Estimate
o f Failure + 40
Rate

+ 20

- 20

- 40

- 60

-100
1 2 5 10 20 50 100 200
Number of Observed F a i l u r e s

TABLE 1 - RESPONSE TO SURVEY QUESTIONNAIRE

Nurrber Number
of of
Type o f I n d u s t r y Companies Plants

A l l Industry - USA & Canada.. ... 30* ....... 68


Auto ............................ 0 ....... 0
Cement .......................... 0 ....... 0
Chemical ........................ 8 ....... 21
Metal.... ....................... 3 ....... 3
Mining. .......................... 0 ....... 0
Petroleum ....................... 5 ....... 8
P u l p and Paper .................. 1 ....... 1
...............
Rubber & P l a s t i c s 3 ....... 3
Textile ........................ 1 ....... 3
.....
O t h e r L i g h t Manufacturing.. 4 ....... 17
Other Heavy Manufacturing.. ..... 1 ....... 2
Other ........................... 9 ....... 10
Foreign ......................... 1 ....... 1
*Some companies i n c l u d e more than one i n d u s t r y

120
IEEE-IAS TRANSACTIONS MAR/APR 1974

observed failures was further subdivided. In most cases the circuit electric utility power supplies. In addition, there was
equipment size attribute was eliminated by combining cate- some confusion on the outage time after a failure of a single
gories that were identical except for equipment size. These circuit of a double- or triple-circuit utility power supply. See
steps reduced the original 217 equipment categories to the 74 the separate discussion elsewhere in this paper on these points.
categories published in this paper. A total of 66 equipment These are the only known major problems of misinterpretation
categories have eight or more observed failures each; the other of survey questions.
eight categories have between four and seven observed failures I t is suspected that the failure rate estimates may be biased
each. on the high side due to the tendency of companies to report
only on equipment that has actually experienced failures. In
SURVEYRESULTSOF EQUIPMENT
FAILURES other words, some companies may have omitted submitting
Table 2 gives a summary of the “All Industry” equipment unit-years of experience data ori equipment that had no
failure rate and equipment outage duration data for the 6 6 failures. This factor may be partially balanced out by the be-
equipment categories that contain eight or more failures. The lief that the companies that participated in the survey may be
“actual hours downtime per failure” is based upon the actual the ones that have the best maintenance programs and keep the
outage data of the failed equipment; the “industry average” best records and thus may have lower failure rates than the
uses all equipment failures, and the “median plant average” average.
uses all plants that reported actual outage time data on e q u i p It is expected that a future paper will contain a comparison
ment failures. of the equipment reliability from this survey with the results
The 1962 survey [ 1 I ] contained equipment outage duration from the previous survey [ I l l that was published in 1962. A
data on failures that have been challenged for two reasons. preliminary comparison has been made and shows the following
1) Repairing a failed component may take much longer than overall conclusion for 1973 versus 1962.
replacing with a spare (for example, a large power transformer). 1) The 1973 equipment failure rates are about 0.6 times the
2) The urgency for repair is a significant factor in the outage 1962 failure rates.
time (low priority repairs may take days or weeks). 2) The 1973 average downtime per failure is about 1.6 times
In order to help correct these deficiencies, two additional the 1962 average downtime per failure.
columns on “repair” and “replace with spare” were included 3 ) The product of failure rate times average downtime per
in the survey and contain average estimated clock hours to fix failure is almost the same in 1973 as 1962.
failure during a 24-hour work day. These estimates are averaged Both of these parameters are within a factor of two; and this
over all the plants participating in the survey, even where there is often the best accuracy that can be expected from reliability
were no actual failures. These results are reported in Table 2 data.
and are not included in the more detailed Tables 3-19. How accurate are the failure rates shown in Tables 2-19?
Tables 3-19 give more detailed data on equipment failure Fig. 1 shows the upper and lower confidence limits of the
rate and actual hours of equipment downtime per failure for failure rate versus the number of failures observed. It can be
74 equipment categories; this includes the 6 6 equipment cate- seen that ten failures has upper and lower confidence limits of
gories in Table 2 plus the eight equipment categories containing +70 percent and -46 percent for a 90 percent confidence
from four to seven failures. The additional detail includes interval. It is possible to determine the upper and lower confi-
dence limits for the failure rate data shown in Tables 3-19.
1) sample size in unit years;
2) number of failures; EXAMPLEO F CONFIDENCE
LIMITCALCULATION
3) number of plants reporting data; The use of Fig. I to determine confidence limits will be
4) additional data on actual hours of downtime per failure; illustrated with an example. Suppose that it is desired to
5) data for various industry groups where there were ten or compute confidence limits on the failure rate of liquid-filled
more failures in that industry. transformers with voltage above IS kV in the chemical in-
The data on average estimated clock hours to fix failure dustry. _The desired confidence interval is 9 0 percent. From
during 24-hour work day have been omitted from Tables 3-19. Table 4 , X = 0.01 19 failures per unit-year, and the number of
The reliability data in Tables 1 4 , 1 6 , and 18 on cables, joints, observed failures is 19. Entering Fig. 1 with 19 observed fail-
and terminations represent a different look at the same data ures and using the 90 percent confidence interval curves yields
that are contained in Tables 13, 15,and 17. Oneset of tables
looks at the type of insulation and the other set of tables looks
at the application of the cable. X, = % - 0.34%
= 0.01 19 - 0.0041 = 0.0078 failures per unit-yea1
A N D DISCUSSION
GENERALCOMMENTS
A survey that collects data from many plants often contains
X u = % t 0.46%
errors. Some of the errors are due to a misinterpretation of = 0.01 19 + 0.0055 = 0.0174 failures per unit-year.
the question by the respondent, and in other cases they can be
caused by omission.
Many of the respondents apparently misinterpreted the There is a 90 percent chance that the true failure rate lies
question on “number of installed units” for double- or triple- between 0.0078 and 0.0174 failures per unit-year.
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

*OhrnOorn
9'749Y ... h
9 999'9'9999.
ew-amhe-mw
Y9
e w
'0 N-
N Q :

m w m m h o
. . . . . . . .?
mUJCOmCO0
Nhw7-hmg
. . . . . ............
w h N W W N c

--~oo-Nm e-hwwm
LD- NNO-m
c
Lo~NQIOQIhp?
-Ne
LDw
~g
WCO
-- N- N

%Z
- 7

99
00

.. .. .. .. .. . .. .. .. .. .. .. .. .. .......... ... ...


:. :. : .: .: $ ~

..r
.. .. .. .. .. .. .. ..
.. .. ... ... ... ... ... ...
-u.:... :... :... :... :... :... :... :... :...
7
.. ..
.. .. . . ..al
- . .. .. .. .. .. .. .. .. ..
. . . . . I -
.a. . . . . .
.V)

.. .. --.>aL . e ..- .. .. ... ... ... ...


. N . . .........
a . . . . . . . . . .-
..C
V I,

:. : y o :o .v, ..- . .. . .. .. w.V ). . . . . . . .. .. ..


mvI . . .
v) .>
- 0

.. ...- 6 .
.C,

.- . . .. . a . . ..
.v) VI

.< .. .. .. .--
uu . m Val
.C,C,

.. , .. .. .. ..>>
N e
. . . ..- . . .
. . N . . -0

. . . - . .. ..
v
.. ..L3uc . V I
. V U .C, oo .C
a m . . .-VI. 3%
.. ..-.- ..r
L a . . . . . u Lo

.. ..ua 3I na>l Lv ... 0-


0
w 1

.. c , a- v
-
0%-
.#-%CU . I .E$%
.VI.
I
. V I .
;g$
.C.. a L m . - -
.r 7 C,
7
v vI g m - 0 3
c u
1 -
oCvI, k r n G o 0w
. yI- 3 4 . m o > m- m o > .^...
:.- L'S*"e
.u g s o
- 0 0
>owon>owo
L O 0 an
ala
0
. a l a l o 3 V I
. - - C , c V I
w
now
Ih- w
o o
O I 0 a-w
ew-uuw s w
0 0
I 0 al
b%
- b -\

. m n a m o n z v n > v u
QC,
.e a 4 E J u I O U 0 - IO4 0 m m
..C 0 o m n
-v,n
c
l o
.r
4+0 < QC,
e c
U
0 V
0
4 U E

....
... ...
VI
._
al

.. ..
.. ..
VI
.. ..
.. ..
..
... ...
In

ul
C,I

m
u
I
n

L
0

0
I

122
IEEE-IAS TRANSACTIONS MAR/APR 1974

O h o h m
----
r.io;oajrr; ..
zN ez
?
$1
?Y1
W N
9
ID
9 , l b .?9
mommw
mW--N
7
???
www
NNN
I

- 0- N
b W-w
V lh -w- -hmm w
mm
azG: C O h
-0
-bmm=r
0-06-
mwwm
0000
.........
C

m
CIIl m
p W
0 -00
000 99 00000 0000 ~

9'9 ? 999 00 00000 0000


00 0 000
.. .. .. .. .. .. : . .. .. .. ..
.. ... ... ... . ... . ... .. .. .. .. .. .. .. .. .. .. .. v. ..
.. ... .. ... ... .. .. . . . . . .
.. .. .. ... ... ... ... ... ... .. =o ..
. E .
. ... ... ... . .. .. .. .. .. ..
... ...
.. ... .. .. . .. . .. .. a ..
. L .
.. .? ...
.v)

..
. ..
... ...
- ...
.L)
.VI
.C,
.> .
. O . ..
I n . -
C , . .
..
-0
.C

.. ...
7
0 .
..
.
.
.

.. ..
w
I
.. .
> . e

.. ..
E
.r
E
c, c .
0
0
9 :::
.
.
.
. ..
In cn- .In
u % & ->
- e o
.c,
v L al
'rS
--VI-
w0
N
n .- -
1
>O
0
0
0
alw oow w0
o
w E wo
m
-I w
nL .-
.r
r .-
V I 0
W W
> 8%
=f
I-

- -:?!e
U
II
-nL
al $09 m
EI-
v)
.... - w
I O
wv)
uIC
V r Yn
U
E
W r m m
n
- a m 04:

... ... .. ..
.. ..
..
..-.
-C,
E .
0 .
.r
*c,
-
... ... -. m w
.Lww - w
aLL
.. .. ...-a
.+I
E
VI *
.. ..
.. .. . L
. U
.-.-v
.. .. In
w
r
.. .. c,
* o
.. .. c
z
-0
:9
VI
v)

U
U
.-
al 11
Q

r
0
c, .r c,
L
s-3. 0
E 3 .C

s -
0 W
E
VI
w-
E D
n n
0

123
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

r
T
I
.< .. .. .. .. .. .. .. .. .. .. ..
4I
.. .. .. .. .. .. .. ... . ... .. .. . . . .
.
c .. .v
. . ..
V
E
.u
.. .. .. ..
....
- 0 .
E .
...
. .u
c ::e :
L
0
U :E 3 .
:.-: : .: vou, .: : :el
L
:. :9
. o .
: g ..-> :. :%!
<
v :
:. :.-a C
v0
. .. vo
.. ..v
t
. W

... .. ma .a. .. ..ma


rn .u
. m
c, .A
.al . ._I
.-I
. .v
.r
V I . V I - .
3::TJ: l n 3
c,U c,
-
1"
W
c,
. w
-. -E: 7 .

ou,J
F .
: Z
0 V
0 ovc,
we- m
o u mc,
=-.- K m
w.-srn
+I.-- c,- c, .- C
o

-
0 - 3 VI+ 3
oVIc,3 * O 0
0 L o m e VI
o m e v ) o m v )
%=22 : O
. c'
0- r
n- %L2& e '

LI 1,
V
m m au
-
-I Ea Ew kn &= I
0
I a n I a w n
m
0)'I
L .r
c,+

r x m w cu'
>
-EE2S 7 - -I-"
0
-+I-"
W
0 -K0 1W
0
W ID
0

... ... ..
. 7
3 .
.

.h
.. V).
s -
I .
.c,
. W
-aJ
.L .- L C .

...-a
.c, .. 0 .
V I .

. a *
a .
u
.L
.. v : 2 :
.r
.. C
C
.
.

-0
-0 : 4 :. .: .:
.-
:a!. :. c , .v) v)
c,
. 11 ..
- C
.r=
o
K
. F = =
0
I .c, . 7 3

124
IEEE-IAS TRANSACTIONS MAR/APR 1974

*
O m O O O O
0 0 000
999
Lo
h
??F
G O G dN
N-N
dd www rn be0

www hh-
. .
LnyLn
- 7 -
m
I
n
--0
...
N N O

L n N m
***
v - 7
m
e -!e c "9, c c c
0
999
0 - 000

m w m m h o
*
ww-
. . . . . . 2?2
mwwLnOO0
-LnOO-N
. . 7 - 7
8
W
YY?
000

~ h N L n W o I mmm L n mm
. . ss?:
*mNmLnr * * W
..
7

...
-
wrnrqye- N
rqY*
000000 000 0 N N m

:. :. :.: .: ..-
E .. .. .. .. .. ..
.- .. .. ...
:. :. - L : :e .- . .- L.
. . < a . c ..-
.a 4 L
. ? !
- 7

-* >
4w
:. :. , A : .e
O " 0 . I O

:. :.zx: e .-TI ..r 0)


... u wu
:+I0

.. .. Lucu, .e :. 2L c%,
.3c .VI .r
. 3 J T

... ... .v -3. rwL u3


LC,
..r
. .r .C

.. . w 0.7 .- C n S L .u 3
.a,
.
.-
W l
. - h c V
..,-.,-.-e-.
. e a- u .a 3 .r
.. n-h.r 7 VI
v)U
.. uL eL .m.--
.3
3 4
5
-In
.LI;;;
.e u .+
.. L ue~
. m W E
u0
- u
..-Le : L 'S .r

--
'c
..U o mE - ~ . o m 3:
. O ) W O 3 v )
O
:as
-- . o m
.
. W c
O,
E
mN

- -:!?z
,--c, E In e 7

.. c 3 4 1 1 1 .n
. m = a m o
:
3

-
- m n
4
.r 0
,-n
c
4
7

4
--00

4
c c

...... .. .. .. .. ... ..
... ... ... ... ... ... .. ... ... ... .
......
.. .. .. .. .. .. ... . . .. ... ...
.. . . . . . . .. .. .. ... ...
... .. .. .. .. ..
... ... ... ... ... m
- G W
.
...... .r
E
0
)
' I
7

ee .r

7
7 z = = = z w x= I
4:
c
V n e
w

000
NNN -
0 mmw
**e

ww- Lo Lnm*
G dd *
www W Cd&& -7

h h W m NN-
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

wl.i
h0
-e
7

. . . . . -.e.
LDO

-
wwmme
we O h
he
m o
L D N

..
LDLD
ee

. .9
m e - h w w m
. . . . . m. N. m. o.m. m. e.
L Dh
N - w -N
- hNL 0D-8m
- mLD7hN
m w e 8X

wm
m 0
0 e
99
00000 00
.. .. .. .. .. .. .. ..
... ... ... ... ... ...
.. .. .. .. .. .. ..
. . .. .. ..
w . . .
U V ) . . . . . . . V ) .
a
LI A.- :.: .: .: :. :. . ...? .. . .. .. w . N . .
. V )
.N

b .. .
.r

.- ... .- .?
l n . . . V ) .Ln .ln
.
. V )
.....c, .c,
5 .-
. -Q .. .. .. . u o
7 . . .V)-

: . - 5
.7

:e
. O

a - 1
I- F

-V0
4 I
F
C 1 0
U u
a w o
b
-0
-0
.r
LLLD
7
.
V I
.C 7
3 0
Urn
.r
J

.. .. .. .. .. .. .. .. ... .. .. .. .. ..
... ...
.. .. .. .. .. .. .. .. ..... ... ... ...
.. .. .. .. .. .. .. .. . .... ..
> .. .. .. .. .. .. .. .. .. .. .. .. .. $ *
U
V) .. .. .. .. .. .. .. ..
.. .. .. .. .. .. .. .. w
u
........
7
E
I 0
LI
w
U
a

-0
c-

-m
Ne
5
"
1

om
IEEE-IAS TRANSACTIONS MAR/APR 1974

999..
---ww
. .9
7 - 7 Plnln
-h
E r
99".
ddN

..........
mmmOlnmNNN-
ooom-oooo-
...
mmm
000

m
&$ r.i
NN

ommas
Nmm
-0-00
hWOO
N N m
000
99999 999
00000 000

- ... ... ... ... ... ... ... ... ... -- .. .. ..


e .. . .
... ... ...
.. .. ..
........ . .. ... ...
m
.. .. ..
U
C
LI
1
- ..... ..... ..... ..... ..... ..... ..... ..... ..
fi

01
-...
w . . .
.. .. ..
.. .. ..
I.
v)
m .. .. .. .. .. .. .. .. .. V I . . .
m . . .
...
C
L: U
vl . .. .. .. .. .. .. .. U
...
. . .

. . .. ...
n . . .
-E;;; .-.-
- 0 0 ) .
-u.- . . .-
t 0 ) N . . . v l .
0)
a m . .
TI w
- .w
VI .

c
C
- m . . . - r 4 . . N e.-
- N *
:e m .
1 ,
c C .
c,-,
0'4 :
u 5 ' .
AS E
L

C -le
+ u
- 0
>c
m c
I-ou
u o I
-wc

.. .. .. .. .. .. .. .. . ... ... ... ...


.. ...... .. ... ... ... .. .. .. ..
.. ... ... . ... ... ...
.. .. .. .. .. .. .. ..
...
.. .. .. . . ..
... ....
.. . .. .. .. .. .. .. .. 7
m
..-
W

-.. .. .. .. .. .. .. .. ..
7

X
c,= =
-= = = = = = z I
c"
a

OOmm
NN-

0 m m
m m e
4%?
2m-r

LnmNhh PYmN
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

m
. .w. m
. . mm.o.m. m.- . m. . h
-ON
hb
*
7 -
m
N
m
m
h
3
s
N-
-m-
m m a
m,
uz N
& <
m e
7 -
U
In
N

"?W ? m mm
. . . . . g$
m m
..O N
..
* W N
N-
W
7
m
h
-
*
0
b
- m-
W mm-
mm
m-
- 7
mm
m-
7-
0
7
N

m m mm
799 ..
-
??W
m ~ * 6.i m
?'9 ..
- -
m
h 0 m W b
m
*
b
c
W m mm
m N
00
N m
h
lo

... m
. . . m.m.
m m
LnbN
W N
W
00
m
N
m
h
-
0
*
b -
*W
7h
.?
m m h
mhm
7
N W
NUl
..
m

- --
m m
c)N
..
W m
mm
h
0
N

L
*
000
. . .
W
0
N

?
0
0
*
h
N

0
-
N
0,

0
m e
-
0b
??
00
0
h W W
0-v)

000
Nm
mm
o
99
u
h m
o
Ou
99
m
W m
cum
N

99
O
W
N
h

?
00 0 0 00 0

... ... ... .. .. ... ... ...


.. . . .. ...
.. ... ... .. .
.. .. ..
.. .. ..
.. .. .. .. .. .. .. ..
.. .. .. c,
VI c,
v) .. .. .. .. .. .. .. ... .. ... ...
.. .. .. ... ...
7

...
7

... ... ...


0 0
.
... . . .. .... .... .... .. .. ..
0
c,
VI
7
0
. ... .. .. .. .. ..
..
-- ...
-B
0
0
. 9
.. m m .
I 0
0
W
c
c
I
.c,
-VI
.-
.. O
> . > u.. .-
.c,
. V I .
.c
. O ..>
o
.-
.>
.c,
.VI .c,
.VI

. O
.-
.c,
.v)

. O
- 5
v)
c,

0 I 0
W
.^
W
.. a..l
0

al
W

n
2 I-2
I- Iz
-
c, C, +
m m m
E,
c c, c,
c c
u
0 u
0
....... .. .. .. .. ..
... ... ... ... ... ... ... ... ... ... ... ... ...
u

.. .. .. .. ........... .. .. .. .. ..
.. .. .. .. .. ... ... ... . ... ... ... ... ... ... ... .. .. .. .. .. ..
.. .. .. .. .. .. .. .. .. .. .. .. .....
... ... ... ... i .. .. .. . .. .. -. . . . . .
.. .. .. ..
. . . . .-E
7
m
c
m
-B ... ..a . . U

C, c,
u
c E
W L
W

- -
U
m
7
a

*W
9
m
h
0
N
W
W
N
W- N

h c N mN N

128

.
IEEE-IAS TRANSACTIONS MAR/APR 1974

0 a o w
.. m 1

m g& Nb c
z
-
c)
P N
v)

z; m ,
a N- W
N !
9m
... W N c

-
-Ln- N
90: 9
NU3 W
t
,
9: a
00 c

.m. c

o m
.'9 a
n
Oh
In-
L n
i C

2
cum- b m Ln a
mmW -Io h U
00 m
0
9'99 C
000 m -W
N n 99 9
00 0 C
88
00
c
C
C
... ...
. . . , ... ... .. .. c,
v)

... ...
0
!
.. ..
I .. .. .. .. E
, ... ... +"
.. .. -
.In
.c, v)
c
I .c I r

i ... ... . O
In>
U
-0
0
W
C

C
i >W
0 0 ..I

.Q U U
! .U

e z
*a
OI
.V
-
E
W
U

u
U

O W
L
e
+ ... ... .. .. .. ..
.. .. .. ... ... ... ... ... ...
... ... ... .. .. .. .. .. ..
.. .. .. ..... ..... ... ... ... ...
... ... ... - .. .. .. ..
...
...
-. . a . . I .

=; 2! 7
-=
4
i: I

0-
m
-
W

n mo
D 0
0,

?-?
UUl
- N.
ct

v)

'3 I--

--
U NLn
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

;ai
r 0

VI
?9 h
*N
c

?9 9
*
-0

..
nu,
U- h
Y W
W
0
L

N
E$ 3
0
??
3 0 0

... ...
.. ..
.-
.c,
.VI

. O
S’ F
c,
v)

-
000 0
>0
.
25 0

-w 9
n r u,
- 0 c

AS 0
I

... ...
... ...
.. ..
.. ....
..
2
v
‘c
.. ..
.. .. a
. . ..-
-
C
c
-=
F

4 u
c

cn-
01- 0
c

W
aDW
V I 0 N
01
N
77
In.-

LI
111

O h m
c

130
IEEE-IAS TRANSACTIONS MAR/APR 1974

.. 20
zlnm
z *E

h W
"9': 99
bhb mm
N N La-4
NU7

9N.99'u.
N O W Q O
9 9 9 '9'9
N W N NN
hh
hh
..

....
o m w o
mlnww
YaD.7 99
lnhh
97
-mm- m e o m
m -NmN

- o m a h
e7N-m --
on 0 1m
N 0
-b0101e
0-06-
99999
w0
0
99
w
33
- 00000

.. .. .. .. .. .. .-
0000

.
000 00 0 0

... ... ... - v ... ...


z
E
I- .. .. ... .. . .. .. ac .. .. .. .. .L .E
.. ..
2 .. .. .. .. .. .. ." . . O .
. L .
. . . ."
.3
. O
..
.. .. .. .. . . .
v)
L
n
r
. . :';;; : : B
.'C1 : : :z :g
LL+
o a
v)U
W
n+
I>
- :.
J S
2:
v
C
w c
m
JC

40-
I
m.
-1
-
WI-
m .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ... ... .. .. .. .. .. .. ..
4
I-
.. .. .. .. .. .. .. .. .. ... ... ... ... .. .. .. .. .. .. .. .. ..
.. .. .. .. .. .. .. .. .. .......
.. .. .. .. .. .. .. .. .. ... ... ... ... .. ..
.. .. ... ... ... ... ... ... ...
.. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. ..
.. .. .. .. .. .. .. .. .. .. .. .. .. 5
.........
... ... ... ... ... ... ... ... ... . .
- - - P

........... 0
L n
U
n
r = = z =

-= = = = =: = I
al
U

*-W
b-N ea
00
NN
SP
NN N
c-

ul
LI

131
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

w<;dai
'9 U
h r
hOOCVl0
-m-, U
0

h r
'm
9 N.?9
mm
ON
N
h
N C
U
:
9?'49
-
N h N C O
h

h
O

U
r 9
7

u;r;om
h m
--9 c
I
*
,
--
# -
7
N C
-9
h

mm*h v)C
7

mohm mr co
h

y z
mOhN
0-NN 0.-
9 c
o c
0
0
9
0

I .... ... .u
.. .. ... U
E
.T 0
: :el : :I
:. :. Of :. :s W

. . .. - c
.... .-a
1

.a .
.U
. ."
.C

-T
-
3
0

m
0

.. . .- o .. :._
. a .
.
.-I
. a C,
.r
a
*
::;&$: : ul U
gC,"--. .. -e.s?
C, m+ VIE
- . - ~ m en -
G0O
tnwa > L
0 2 $ 2 :. o w c
ontn-
C,"
0
0
ln- 0 o u
OC,
K- oE wE nk sd -3 w c
: 1 r n
- a
-0
,-
Izs m * le
-+*no -+P 7 -
0
D W
0 0
W

.. .. .. .. .. .. .. .. .. .. .. ..
... ... ... ... ... .. .. .. .. ..
..... ... ... ... ...
..
..... ... ... ... ... ... .. ..
.. .. .. .. .. .. .. \;=;n,
i
C .. .. .. ~ ... ...
..... .. ..
.. ..
4 '
-
u . . .
E . . .
M
.. .. ..
. . . - m

.. .. ..
w
.-uE n
e, =
C,
n
W V

-mwm

N01
001
'? r'!
N-

S I

NN

132
IEEE-IAS TRANSACTIONS MAR/APR 1974

000
mW
'dcd
N

999
me-
-
...
O D *

-zm
LnN-

I :. :. :. :I
. .'CI
iI . . . . . - .-
: :e n .
...
..
: :9 . . . . .a .
.....E:
.....-. ...
.. .. v
- ...
..
. O

. .u.I 7 .

.. -. w
* .A :
. .w
.'CI
m 1
.r .
.
V I .
c, u mc'
-.r c m
cI'nu.
c .r
LV).
wc'
u-0 -w
.
O c , . r c OVc)
,
V)W a 5 -a 5 0
W c ' V )
0- w s 0- 'CIgv
o nv)- o n 50-
3 %
- w a n
X.s m
SP
InL
- w
Zd.2
a-1 L
w
I -I-
1 - c
-ccp.
W
0 O
W ow
n

::I...
U
. . . . . . .. .. .. .. .. .. .. .. .. .. .. .. .. ..
:. :. :.: .
.. .. .. .. ...
.. .. .. .. .. .. .. .. .. .. .. .. .. ..
.. .. .. .. .. .. .. .. .. .. .. .. .. ..
2 *. : ".
. . . . . ... . I
... ... ... ... ... ... ... ... ... ... ... ... ... ...
+I
.. ... h
.. .. .. .. .. .. .. .. : : : f "
-
c

.. .. .. .. .. .. .. .. m
V ) . . . .

.. .. .. .. m. .
a . . . .
.. .. .. .. .. .. .. .. -u= = -o = =
' C I . . . . w
E a
m
I
.. .. .. .. .?
u
s ........
W

-z = = = =
.... E E
W
V
c
- = = = = = = =
U
E
W
0
L
c
W
n
,

133
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

.. . . .
...... ...
2
U

5 ..
I-
.. .... ..
C
. .... ..
... .. . ..
.. .. .. ...
n
C

L n . . .
.
U

5
z
a0
I-
Y

0
C
q:
....
l o

... ... ... ...


Q
.....
+ :. :. :. . .:
.. .. .. .. ..
-
a I- C,

.. .. .. .. .
....
-
u)
a
I,
.. .. .. .. u
c .... m
.. .. .. .. -u
0

I-
.. .. .. .. . . e E .
-=
c I = 7
- = = =
C
c
U 4 V

134
IEEE-IAS TRANSACTIONS MAR/APR 1974

APPENdIX A (P. 1 o f 7 )
USER INSTRUCTIONS FOR I E E E SURVEY FORM ON
RELIABILITY OF ELECTRIC EQUIPMENT I N INDUSTRIAL PLANTS

(SPONSORED BY THE RELIABILITY WORKING GROUP,


INDUSTRIAL PLANTS POWER SYSTEMS SUBCOMMITTEE,
INDUSTRIAL AND COMMERCIAL POWER SYSTEMS COMMITTEE1

'URPOSE T h i s s u r v e y i s i n t e n d e d t o c o l l e c t d a t a on f a i l u r e s t h a t o c c u r i n i n - p l a n t e l e c t r i c
? q u i p m e n t and i n p u b l i c u t i l i t y e l e c t r i c power s u p p l i e s t h a t a f f e c t o p e r a t i o n s i n i n d u s t r i a l p l a n t s .
.le hope t h a t t h e s e d a t a w i l l d e t e r m i n e n o t o n l y a c c u r a t e f a i l u r e r a t e s and r e p a i r times on m a j o r
: l a s s e s o f e q u i p m e n t . b u t w i l l a l s o g i v e a n i n s i g h t i n t o t h e c a u s e s o f t h e s e f a i l u r e s i n s u c h a way
t h a t r e m e d i a l r e c o m m e n d a t i o n s may b e f o r m u l a t e d t o r e d u c e f a i l u r e s and t o i m p r o v e p l a n t p e r f o r m a n c e .

UILING INSTRUCTIONS Mail a l l f i l l e d - o u t forms t o t h e f o l l o w i n g a d d r e s s .

IEEE-IGA R e l i a b i l i t y Working Group


C a r e o f A s s i s t a n t P r o f e s s o r A D P a t t o n , Dept o f E l e c t r i c a l E n g i n e e r i n g
Texas ALM U n i v e r s i t y
C o l l e g e S t a t i o n , Texas 7 7 0 4 3

IATA PROCESSING T h e s e f o r m s w i l l b e g i v e n a c o n f i d e n t i a l company c o d e , a n d w i l l t h e n b e key


x n c h e d on c a r d s f o r p r o c e s s i n g by a d i g i t a l c o m p u t e r a l o n g w i t h d a t a c o l l e c t e d from o t h e r s . The
zomputer w i l l p r e p a r e a s u i t a b l e r e p o r t on f a i l u r e r a t e s , d u r a t i o n s , and c a u s e s of f a i l u r e .

kIDDITIONAL INFORMATION The r e v e r s e s i d e o f t h e S u r v e y Form a s k s f o r a d d i t i o n a l i n f o r m a t i o n . The


f o l l o w i n g i n f o r m a t i o n should be f i l l e d i n o n t h e r e v e r s e s i d e o f t h e f i r s t p a g e of d a t a f o r e a c h
p l a n t : company name, p l a n t name, t y p e and l o c a t i o n , t h e name, a d d r e s s , and phone number o f t h e
individual submitting the d a t a and/or the i n d i v i d u a l t o whom q u e s t i o n s a b o u t t h e d a t a may b e
directed.

I n a d d i t i o n , s p a c e i s p r o v i d e d f o r r e m a r k s or c l a r i f y i n g comments o n t h e d a t a b e i n g r e p o r t e d . These
comments s h o u l d b e f i l l e d i n o n a l l d a t a s h e e t s , i f n e e d e d t o c l a r i f y d a t a .

DEFINITIONS

A component 1s a p i e c e of e q u i p m e n t , a l i n e or c i r c u i t , or a s e c t i o n o f a l i n e o r c i r c u i t , Or a
g r o u p o f i t e m s w h i c h i s viewed a s a n e n t i t y .

A system i a a g r o u p o f components c o n n e c t e d or a s s o c i a t e d i n a f i x e d c o n f i g u r a t i o n t o p e r f o r m a
s p e c i f i e d f u n c t i o n of g e n e r a t i n g , t r a n s m i t t i n g , or d i s t r i b u t i n g power.

A failure is d e f i n e d a s any t r o u b l e w i t h a power s y s t e m component t h a t c a u s e s any o f t h e fOllOWin9


t o occur.

(1) P a r t i a l or c o m p l e t e p l a n t s h u t d o w n , or b e l o w - s t a n d a r d p l a n t o p e r a t i o n
(2) Unacceptable performance o f u s e r ' s equipment
(3) O p e r a t i o n of t h e e l e c t r i c a l p r o t e c t i v e r e l a y i n g o r emergency o p e r a t i o n o f t h e p l a n t
e l e c t r i c a l system
(4) D e e n e r g i z a t i o n o f any e l e c t r i c c i r c u i t o r e q u i p m e n t

A f a i l u r e on a p u b l i c u t i l i t y s u p p l y s y s t e m may c a u s e t h e u s e r t o h a v e e i t h e r (1) a power


i n t e r r u p t i o n o r loas o f s e r v i c e , or ( 2 ) a d e v i a t i o n f r o m n o r m a l v o l t a g e o r f r e q u e n c y o f s u f f i c i e n t
m a g n i t u d e or d u r a t i o n t o d i s r u p t p l a n t p r o d u c t i o n .

A f a i l u r e on an i n - p l a n t component c a u s e s a f o r c e d o u t a g e o f t h e c o m p o n e n t , a n d t h e component
thereby is unable t o perform i t s intended f u n c t i o n u n t i l i t is r e p a i r e d o r r e p l a c e d .

R e p a i r t i m e o f a f a i l e d component o r d u r a t i o n o f a f a i l u r e i s t h e c l o c k h o u r s f r o m t h e t i m e o f t h e
O c c u r r e n c e o f t h e f a i l u r e t o t h e t i m e when t h e component is r e s t o r e d t o s e r v i c e e i t h e r b r e p a i r
o f t h e component or by m u b s t i t u t i o n w i t h a s p a r e component. I t i s n o t t h e t i m e ' r e q u i r e d $0 r e s t o r e
a e r v i c e t o a l o a d by p u t t i n g a l t e r n a t e c i r c u i t s i n t o o p e i a t i o n .

I b i n c l u d e s t i m e f o r d i a g n o s i n g t h e t r o u b l e , l o c a t i n g t h e f a i l e d component, w a i t i n g f o r p a r t s .
r e p a i r i n g or r e p l a c i n g , t e s t i n g , and r e s t o r i n g t h e component t o s e r v i c e .

R e v i s i o n 3-4-71

135
A P P E N D I X A R E P O R T ON RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

2
USER INSTRUCTIONS FOR I E E E SURVEY FORM ON
RELIABILITY OF ELECTRIC EQUIPMENT I N INDUSTRIAL PLANTS
(SPONSORED BY THE RELIABILITY WORKING GROUP,
INDUSTRIAL PLANTS POWER SYSTEMS SUBCOMMITTEE,
INDUSTRIAL AND COMMERCIAL POWER SYSTEMS COMMITTEE)

GENERAL INSTRUCTIONS

THE SURVEY FOtU4 The I E E E S u r v e y Form 1' 1-70 i s a n i n p u t d a t a f o r m f o r a c o m p u t e r p r o g r a m . The


d a t a on t h e s e f o r m s w i l l b e key punched o n t o c o m p u t e r c a r d s a n d a n a l y z e d by t h e c o m p u t e r p r o g r a m .

CODED DATA The S u r v e y Form a s k s f o r c o d e d a n d u n c o d e d d a t a . I t is necessary t o r e f e r t o the


instructions i n filling in either. The f o l l o w i n g s h o w s t h e columns o n e a c h c a r d t y p e t h a t r e q u i r e s
f i l l i n g i n a code.

CARD TYPE COLUMNS R E Q U I R I N G CODES

1 1-10, 36
2 11-18. 33-36
3 25, 29, 30-53, 57, 58

I t may h a p p e n t h a t none o f t h e c o d e s shown f i t t h e p a r t i c u l a r c a s e b e i n g r e p o r t e d . For s u c h c a s e s ,


t h e " o t h e r " c o d e s h o u l d be u s e d , by f i l l i n g a " 9 " o r a " 9 9 " i n t h e s p a c e p r o v i d e d . " O t h e r " means
not otherwise c l a s s i f i e d . I f t h i s i s d o n e , e x p l a i n on r e v e r s e s i d e o f p a g e , r e f e r r i n g t o c a r d t y p e
and column number.

EQUIPMENTC U S S A group o f codes i s used t o s p e c i f y a n equipment c l a s s . An e q u i p m e n t c l a s s


c o n s i s t s o f a main c o d e , two s u b - c l a s s c o d e s , a v o l t a g e c o d e a n d a s i z e c o d e . These a r e e x p l a i n e d
i n the instructions. F o r t h e e x a m p l e shown o n t h e f i l l e d - o u t f o r m , t h i s c o d e i s a s f o l l o w s .

CODE DESCRIPTION

Main 20 = t r a n s f o r m e r
Sub 1 4 = parer
sub 2
Voltage
Size
2 -
34 = l i q u i d f i l l e d
601-15,000 v o l t s primary
3 = 300-750 kVA

The above c o d e d e q u i p m e n t c l a s s c o v e r s a l l l i q u i d - f i l l e d power t r a n s f o r m e r s , w i t h a p r i m a r y v o l t a g e


o f 6 0 1 - 1 5 . 0 0 0 v o l t s a n d r a t e d 300-750 kVA. Any t r a n s f o r m e r i n t h e p l a n t t h a t d o e s n o t f i t t h i s
e x a m p l e i s a d i f f e r e n t c l a s s i f i c a t i o n and r e q u i r e s a d i f f e r e n t c o d i n g . Thus, a 5000 kVA power
t r a n s f o r m e r r l i q u i d f i l l e d . 13.8 kV p r i m a r y v o l t a g e would be c o d e d 20-4-34-2-5.

CARD-TYPES The S u r v e y Form a s k s f o r t h r e e t y p e s o f i n f o r m a t i o n u n d e r t h e h e a d i n g s CARD-TYPE 1,


CARD-TYPE 2 , a n d CARD-TYPE 3 .

I n g e n e r a l , CARD-TYPE 1 a s k s f o r d a t a o n p l a n t i d e n t i f i c a t i o n and o t h e r g e n e r a l p l a n t i n f o r m a t i o n .

CARD-TYPE 2 a s k s f o r d a t a on a s p e c i f i c e q u i p m e n t c l a s s , i n c l u d i n g t h e t o t a l number o f i n s t a l l e d
u n i t s , o n t h e i r f a i l u r e e x p e r i e n c e , o n m a i n t e n a n c e p r a c t i c e s , and o n e s t i m a t e d r e p a i r times of
f a i l e d equipment. The t o t a l i n s t a l l e d u n i t s a n d t h e i r f a i l u r e e x p e r i e n c e i s t h e most e s s e n t i a l
d a t a asked f o r .

CARDS-TYPE 3 ask. f o r d a t a o n e a c h i n d i v i d u a l f a i l u r e r e p o r t e d o n a CARD-TYPE 2 .

A t y p i c a l p l a n t m i g h t h a v e a s many a s , s a y 30 d i f f e r e n t e q u i p m e n t c l a s s e s . T h e s e 30 e q u i p m e n t
c l a s s e s might h a v e , f o r exarrple 10 d i f f e r e n t f a i l u r e s . To r e p o r t t h i s i n f o r m a t i o n r e q u i r e s 30
p a g e s o f t h e S u r v e y Form, o n e f o r e a c h d i f f e r e n t e q u i p m e n t c l a s s . CARD-TYPE 1 i s f i l l e d i n
c o m p l e t e l y o n t h e f i r s t p a g e a n d p a r t l y t h e r e a f t e r . CARD-TYPE 2 i s f i l l e d i n o n e a c h p a g e .
CARDS-TYPE 3 a r e f i l l e d i n 1 0 times, o n c e f o r e a c h f a i l u r e , i f a n y .

CARD-TYPE 1 CARD-TYPE 1 i s u s e d t o i d e n t i f y t h e r e p o r t i n g company and p l a n t o f t h a t company a n d t i


give general information about t h a t plant. The f i r s t 10 columns o n t h i s c a r d a r e t o b e r e p e a t e d by
t h e key p u n c h e r o n t o CARD-TYPE 2 a n d CARDS-TYPE 3 f o r i d e n t i f i c a t i o n p u r p o s e s .

Only o n e CARD-TYPE 1 i s u s e d by t h e c o m p u t e r p r o g r a m . However, we a s k t h a t o n e a c h p a g e o f t h e IEEl


S u r v e y Form t h a t t h e f i r s t 7 columns b e f i l l e d - i n i n c a s e t h e f i l l e d - o u t s u r v e y f o r m s become
separated.

F i l l i n I t e m s 1-8 o n r e v e r s e s i d e o f f i r s t p a g e o f d a t a f o r e a c h p l a n t .

ALL CARD TYPES F i l l i n CARD-TYPE, column number, a n d r e m a r k s o r comments o n r e v e r s e a i d e , i f a n y ,


on a l l d a t a c a r d s .

136
IEEE-IAS T R A N S A C T I O N S M A R / A P R 1974

WD
APPENDIX A (P. 2 o f
3
USER INSTRUCTIONS FOR I E E E SURVEY FORM ON
RELIABILITY OF ELECTRIC EQUIPMENT I N INDUSTRIAL PLANTS
(SPONSORED BY THE RELIABILITY W J R K I N G GROUP,
INDUSTRIAL PLANTS POWER SYSTEMS SUBCOMMITTEE,
INDUSTRIAL AND CCUMERCIAL POWER SYSTEt4S COMMITTEE

CARD-TYPE 2 The s e c o n d o r CARD-TYPE 2 i s u s e d t o r e p o r t on e a c h d i f f e r e n t e q u i p m e n t c l a s s i n t h e


plant. A t y p i c a l p l a n t m i g h t h a v e a o n e t y p e o f u t i l i t y s u p p l y , and s e v e r a l d i f f e r e n t c l a s s e s e a c h
o f t r a n s f o r m e r s , c i r c u i t b r e a k e r s , c a b l e s , e t c . T h e s e d i f f e r e n t c l a s s e s a r e shown i n Columns 11-19.
T h e s e Columns 11-18 a r e t o b e r e p e a t e d by t h e key p u n c h e r o n a l l CARDS-TYPE 3. T h e r e w i l l be a s
many CARDS-TYPE 2 a s t h e r e a r e d i f f e r e n t e q u i p m e n t c l a s s e s .

Each CARD-TYPE 2 i s u s e d t o r e p o r t (1) t h e t o t a l number i n s t a l l e d o f o n e e q u i p m e n t c l a s s and t h e


t o t a l number of f a i l u r e * e x p e r i e n c e d ( i f any1 o f t h a t e q u i p m e n t c l a s s .

I n a d d i t i o n , e a c h CARD-TYPE 2 i s u s e d t o r e p o r t o n m a i n t e n a n c e p r a c t i c e s and e s t i m a t e d r e p a i r t i m e s .
T h e s e a r e y o u r b e a t e a t i m a t e o f r e p a i r times. T h e s e e s t i m a t e d t i m e s w i l l be u s e d i f a c t u a l r e p a i r
tims a r e n o t known, o r i f a c t u a l r e p a i r times a r e much d i f f e r e n t from t h e a v e r a q e f o r some s p e c i a l
r e a s o n which is u n l i k e l y t o r e c u r . W e p r e f e r t o use a c t u a l d a t a i f a v a i l a b l e .

These d a t a a r e t o be l e f t b l a n k f o r f a i l u r e s on t h e u t i l i t y power s u p p l y , s i n c e t h i s i n f o r m a t i o n
1. n o t n o r m a l l y a v a i l a b l e .

CARD-TYPE 3 The t h i r d or CARD-TYPE 3 i s u s e d t o r e p o r t o n a c t u a l d a t a f o r e a c h f a i l u r e r e p o r t e d


o n a c o r r e s p o n d i n g CARD-TYPE 2. T h u s , a s s o c i a t e d w i t h e a c h CARD-TYPE 2 i s a s e t o f CARDS-TYPE 3.
The number o f CARDS-TYPE 3 will be t h e same a s t h e number o f f a i l u r e s (column 3 1 ) r e p o r t e d on CARDS-
TYPE 2 , f o r e x a m p l e , i f a CARD-TYPE 2 h a s a 3 i n Column 3 1 , t h e n 3 CARDS-TYPE 3 s h o u l d b e f i l l e d i n .

Each CARD-TYPE 3 r e p o r t r s p e c i f i c i n f o r m a t i o n on o n e f a i l u r e , s u c h a s f a i l u r e d u r a t i o n , u r g e n c y o f
r e p a i r , c a u s e o f f a i l u r e , l o a d s a f f e c t e d by t h e f a i l u r e , and e f f e c t o f f a i l u r e o n p l a n t o p e r a t i o n s .

RIGHT-ADJUSTMENT OF DATA I n f i l l i n g i n d a t a , numbers s h o u l d be r i g h t - a d j u s t e d , t h a t i s , t h e y must


e n d i n t h e r i g h t - h a n d column o f t h e a s s i g n e d f i e l d . T h i s means t h a t i f , f o r e x a m p l e , t h e s u r v e y f o r
p r o v i d e s 3 columns t o i n a e r t d a t a b u t a t w o - d i g i t number i s t o b e i n s e r t e d i n t h e s p a c e a v a i l a b l e ,
t h e n t h e number s h o u l d b e f i l l e d i n t o t h e two r i g h t - h a n d c o l u m n s .

SAMPLE FILLED-OUT FORM Refer t o t h e a t t a c h e d sample f i l l e d - o u t form. T h i s g i v e s an example o f a


r e p o r t o n o n e c l a s s o f t r a n s f o r m e r s w i t h two f a i l u r e s .
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

ShHPL E
7)DATE 3 - 4- 7/ IEEE SURVEY FORM 11-1-70 PAGES PAGE

I RELIABILITY OF ELECTRIC LOUIPMENT IN INDUSTRIAL PLANTS


i
I CARD - TYPE 1
(REFER TO SURVEY FORM INSTRUCTIONS)
(NOTE - * REFERS TO CODED DATA)

CARDS - TYPE 3

138
IEEE-IAS TRANSACTIONS MAR/AF'R 1974

UID APPENDIX A ( P . 3 of 7)
5
USER INSTRUCTIONS FOR CARD-TYPE 1
(REFER Po SURVEY FORM IWSTRUCTIOW
CARD - TYPE 1 -
(NOTE * REFERS TO CODED DATA1

NAME CODE DESCRIPTION

Company Code F i l l i n on a l l p a g e s a t h r e e - l e t t e r a b b r e v i a t i o n of company name f o r


i d e n t i f i c a t i o n of d a t a .

P l a n t No F i l l i n on a l l p a g e s a s e q u e n c e number s t a r t i n g w i t h "1" f o r P l a n t 1,
" 2 " f o r P l a n t 2 , e t c . f o r i d e n t i f i c a t i o n o f d a t a . A p l a n t may c o n s i s t
o f o n e o r more u n i t s a t t h e same s i t e .
Plant v p e F i l l i n on a l l p a g e s t h e p l a n t t y p e

1 Auto I n d u s t r y
2 Cement I n d u s t r y
3 Chemical I n d u s t r y
4 Metal I n d u s t r y
5 Mininq I n d u s t r y
6 Petroleum I n d u s t r y
7 P u l p and P a p e r I n d u s t r y
8 Rubber and P l a s t i c s I n d u s t r y
9 Textile Industry
10 Other Light Manufacturing
11 O t h e r Heavy M a n u f a c t u r i n g
99 Other

Plant Location 1 USA and Canada


2 Foreign

Plant Climate Average of d a i l y maximums f o r h o t t e s t month:


(For e n t i r e Temperature R e l a t i v e Humidity ( R H ) ( m e a s u r e d a t noon t o 2 PM S1
plant s i t e)
1 Hot l>9OF) High ( > 5 5 RH)
2 Hot 0 9 O F ) Moderate I 50-55 R H )
3 Hot W O F ) LOW ( 4 5 0 RH)
4 M o d e r a t e I80-9OF) High (>55 RH)
5 M o d e r a t e (80-90F) Moderate I 50-55 R H )
6 M o d e r a t e (80-9OF) LOW k50 RH)
7 Low ((80 F ) High l>55 RH)
8 Low IWOF) Moderate 150-55 R H )
9 Low K 8 0 F ) LOW (e50 R H )

P l a n t Atmosphere 1 Clean t o s l i g h t l y p o l l u t e d a i r
(For e n t i r e 2 With s a l t s p r a y a n d c o r r o s i v e c h e m i c a l s
plant site) 3 With s a l t s p r a y a n d d u s t o r s a n d
4 With s a l t s p r a y o n l y
5 With c o r r o s i v e c h e m i c a l s and d u s t o r s a n d
6 With c o r r o s i v e c h e m i c a l s o n l y
7 With d u s t o r s a n d o n l y
8 With c o n d u c t i v e d u s t
9 Other

Plant Operating
Schedulc
Hours p e r d a y G i v e h o u r s p e r n o r m a l w o r k i n g day t h a t p l a n t o p e r a t e s

Days p e r week G i v e d a y s p e r n o r m a l w o r k i n g week t h a t p l a n t o p e r a t e s

Estimated Plant
Outage C o s t , D o l l a r s

Per Failure E x t r a expense i n c u r r e d because o f a f a i l u r e only ( n o t i n c l u d i n g p l a n t


d o w n t i m e ) , s u c h a s for damaged e q u i p m e n t , s p o i l e d p r o d u c t , e x t r a
maintenance, o r e x t r a r e p a i r c o s t s
EB
APPENDIX A R E P O R T O N RELIABILITY S U R V E Y O F I N D U S T R I A L P L A N T S

6
USER INSTRUCTIONS FOR CARD-TYPE 1

(REFER TO WRVEY FORM IWITRUCTIONS)


CAR0 - T Y P E 1
-
(MOTE * REFERS TO CODE0 DATA)

OL
MN NAME CODE DESCRIPTION

20 P e r h o u r downtime Value o f l o s t p r o d u c t i o n i n d o l l a r s p e r h o u r of p l a n t d w n t i m e o n l y .
T h i s is t h e e s t i m a t e d r e v e n u e s (sales p r i c e ) of p r o d u c t n o t made, l e s a
e x p e n s e s s a v e d i n labor, m a t e r i a l , u t i l i t i e s , etc. If t h i s v a r i e s
w i t h t h e d u r a t i o n o f t h e p l a n t d w n t i m e , u s e an a v e r a g e v a l u e p e r h o u r

25 P l a n t maximum demand G i v e t h e maximum e l e c t r i c powar demand when t h e p l a n t i s o p e r a t i n g a t


a t design capacity, i t s r a t e d or d e s i g n c a p a c i t y i n k i l o w a t t s .
kW

31 Plant r e s t a r t time, G i v e t h e time r e q u i r e d t o g e t t h e p l a n t back i n t o o p e r a t i o n a f t e r


hours s e r v i c e is r e s t o r e d f o l l o w i n g a f a i l u r e t h a t h a s c a u s e d a c o m p l e t e
p l a n t shutdown, h o u r s .
Critical service loss
durat i o n

33 No o f u n i t s G i v a t h e maximum tifra i n u n i t s d e f i n e d i n C o l 36 o f l o s s o f s e r v i c e
t o t h e p l a n t which w i l l n o t c a u s e a complete p l a n t 8 h u t d w n . h Y
power i n t e r r u p t i o n of l o n g e r d u r a t i o n w i l l c a u s e a p l a n t shutdown.
I n o t h e r w o r d s , g i v e maximum l e n y t h o f power f a i l u r e t h a t w i l l n o t
stop plant production. T h i s time i s t y p i c a l l y i n the r a n g e Of
cycles t o minutes.

36 Units S e l e c t c o d e f o r a p p r o p r i a t e time u n i t t h a t w i l l g i v e a c c u r a t e r e s u l t s .
Days
HOUIS
Minutes
Seconds
Cycles

140
IEEE-IAS T R A N S A C T I O N S M A R / A P R 1974

7
USER INSTRUCTIONS FOR CARD-TYPE 2
CARD - TYPI ?

CODE DESCRIPTION

S e l e c t a p p r o p r i a t e c o d e f o r Column 11-18
1 Main C l a s s 10 U t i l i t y power s u p p l i e s t o p l a n t
20 Transformers
30 C i r c u i t Breakers
40 Cable (Excluding j o i n t s and t e r m i n a t i o n s )
41 Cable J o i n t s
42 Cable Terminations
43 C a b l e Duct o r Busway
44 Open Wire
45 Busduct
46 S w i t c h g e a r Bua - i n s u l a t e d
47 S w i t c h g e a r Bus - b a r e
50 notors
60 Generators
70 notor Starters
eo Diaconnect Switches
90 Mincellaneous
99 qther

3 Sub C l a s s 1 For 1 0 - U t i l i t Y PWeK S u p p l i e s (A r e d u n d a n t s u p p l y w i l l c a r r y t h e p l a n t


l o a d , i f t h e n o r m a l c i r c u i t i s o u t of s e r v i c e )
1 S i n g l e C i r c u i t (NO r e d u n d a n t s u p p l y )
2 Double C i r c u i t (One r e d u n d a n t s u p p l y )
3 T h r e e o r more c i r c u i t s ( t w o o r more r e d u n d a n t s u p p l i e s )

For 20 - Transformers

4 Pcwer
5 Other

For 3 0 - C i r c u i t Breakers

6 Metal C l a d , drawout
7 F i x e d Type ( i n c l u d e s molded c a s e t y p e )

F o r 40-17 C a b l e o r Bus

9 Cable i n Trays - abovearound


10 Cable i n Conduit -aboveground
11 A e r i a l Cable
12 Direct B u r i e d C a b l e
13 Cable i n n u c t o r Conduit -belarground
14 Bua o r B u s d u c t - i n d o o r
15 BU. o r B u a d u c t - o u t d o o r

F o r 50 - Motors
16 Induction, ac
17 Synchronous, a c
le Direct-current
F o r 60 - Generators
19 Steam T u r b i n e D r i v e n
20 Can T u r b i n e D r i v e n
21 Diesel o r Can E n g i n e D r i v e n
22 Motor-driven
F o r 70 - Motor S t a r t e r s
C o n t a c t o r Twe
23
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

nD
e
USER INSTRUCTIONS FOR CARD-TYPE 2

CARD - TYPE 2

OL
IMN NN4E CODE DESCRIPTION

3 sub class 1 (Cant) For 80 - Disconnect Switches

25 Open
26 Enclosed

For 90 - Miscellaneeus

27 Fuses
28 Protective relays
29 Batteries
30 Inverters
31 Rectifiers
99 Other

.5 sub Class 2 For 10- Uti li ty Supplies


When service is lost because of a loss of one circuit Of a
redundant supply service is restored

1 Automatically
2 By remote control
3 Manually

For 2 0 - Transformers

34 Liquid Filled
35 Dry Type
38 Rectifier

For 4 0 - 5 1 Cable
Type of Insulation
40 Thermoplastic (PVC)
41 Thermoplastic (Polyethylene)
42 Thermosetting ( S B R (Buna S ) Rubber)
43 Thermosetting (Buty1 Rubber )
44 Thermosetting (Oil Based Rubber)
45 Thermosetting (Cross-Linked Polyethylene)
46 Thermosetting (Silicone Rubber)
41 Thermosetting (Ethylene Propylene)
48 Thermosetting (Chlorosulphated Propylene)
49 Paper-Insulated Lead Covered
50 Varnished Cambric Insulated-Lead Covered
51 Mineral-Insulated
99 Other (Applies to Col 13-15, all classea, if not o t h e w l s e classified)

17 volt Class 1 0-600 volt (Note: For transformers this i s p r h a K y volta9.e)


2 601-15.000 volt
3 Above 15,000 volt

142
IEEE-IAS TRANSACTIONS MAR/AF'R 1974

Lo APPENDIX A (P. 5 o f 7)
9
USER INSTRUCTION FOR CARD-TYPE 2
CARD-TYPE 2

3L
YN NAME CODE DESCRIPTION

8 Size Class F o r Main C l a s s 10 - U t i l i t y Supplies


For Main C l a s s 30 - C i r c u i t Breakers
F o r Main C l a s s 80 - D i s c Switches
For Main C l a s s 90 - M i s c e l l a n e o u s , Fuses

1 100-600 m p e r e s
2 Above 600 amperes

F O ~Main C l a s s 20 - T r a n s f o r m e r s
3 300-750 kVA
4 751-2499 kVA
5 2500-up kVA
F o r Main C l a s s 40-45 - Cable, etc
6 Above No 1 A W ;
F o r Main C l a s s 50 - M o t o r s
FOK Main C l a s s 7 0 - Motor S t a r t e r s
7 50-1500 h o r s e p o w e r
8 Above 1500 h o r s e p o w e r
For Main C l a s s 60 - Generators
9 500-up kW
P e r i o d c o v e r e d by G i v e month and y e a r ( n u m e r a l s ) f o r p e r i o d f o r w h i c h f a i l u r e d a t a i s
t h i s report available
9 From: Mo S t a r t i n g Month ( T r y t o i n c l u d e d a t a from d a t e of i n s t a l l a t i o n )
1 Fromi Y r S t a r t i n g Year
3 To: N o E n d i n g Month (Try t o i n c l u d e d a t a t o d a t e o f t h i s r e p o r t )
5 To: Y r Ending Year
7 No o f i n s t a l l e d G i v e t o t a l number o f u n i t s i n s t a l l e d . For c a b l e or open w i r e , g i v e
units l e n g t h o f c l r c u i t or r u n i n N f t . For cable d u c t or busduct, g i v e
c i r c u i t length i n feet. For s w i t c h g e a r b u s , g i v e t h e number o f
c o n n e c t e d c i r c u i t b r e a k e r s or i n s t r u m e n t t r a n s f o r m e r c o m p a r t m e n t s .
For u t i l i t y power s u p p l i e s , g i v e t h e number o f s e p a r a t e s u p p l i e s .
11 NO o f F a i l u r e s G~~~ t o t a l number o f f a i l u r e s t h a t o c c u r r e d d u r i n g P e r i o d o f r e p o r t .
I f more t h a n 10 u s e a d d i t i o n a l p a g e .
S e l e c t codes f p L w
13 Average Ace 1 Less t h a n 1 y e a r o
2 1-10 y e a r s o l d
3 More t h a n 1 0 y e a r s o l d

Maintenance Give n o r m a l c y c l e f o r p r e v e n t i v e m a i n t e n a n c e - (even i f a f a i l u r e has


34 Normal C y c l e . MO 1 L e s s t h a n 1 2 months not occurred)
2 1 2 - 2 4 months
3 * o r e t h a n 2 4 months
4 NO p r e v e n t i v e m a i n t e n a n c e

36 Mai n t e n a n c e Q u a l 1t y your e s t i m a t e of q u a l i t y of p r e v e n t i v e maintenance iS -


1 E x c e l l e n t (by own f o r c e s )
2 F a i r ( b y own f o r c e s )
3 Poor. i n a d e q u a t e (by own f o r c e s )
1 None
5 E x c e l l e n t (by c o n t r a c t e d f o r c e s )
6 Fair (by c o n t r a c t e d f o r c e s )
7 Poor i n a d e q u a t e (by c o n t r a c t e d f o r c e s )
APPENDIX A R E P O R T ON RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

~~ ~

10
USER INSTRUCTIONS FOR CARD-TYPE 2
CARD - TYPE 1

OL
MN NAME CODE DESCRIPTION

Estimated clock hours R e p a i r t i m e ( s e e d e f i n i t i o n s ) F i l l i n t h e c l o c k time f o r d i a g n o s i n g


t h e t r o u b l e , l o c a t i n g t h e f a i l e d component, w a i t i n g f o r p a r t s
r e p a i r i n g o r r e p l a c i n g , t e s t i n g a n d r e s t o r i n g t h e component t o
s e r v i c e . T h i s i s y o u r estimate o f t h e a v e r a g e r e p a i r t i m e . Please
n o t e t h a t a c t u a l r e p a i r times a r e r e q u e s t e d i n CARD-TYPE 3, Col 2 6 .
E x p l a i n on r e v e r s e s i d e how work i s done i f by o t h e r t h a n own f o r c e s .

7,epair f a i l e d component With r e p a i r o f f a i l e d e q u i p m e n t

24-hr p e r day On r o u n d - t h e - c l o c k emergency b a s i s


8-hr p e r day On b a s i s o f r e p a i r d u r i n g normal work day

With r e p l a c e m e n t o f f a i l e d e q u i p m e n t w i t h a s p a r e by removal o f
f a i l e d e q u i p m e n t and s u b s t i t u t i o n o f s p a r e e q u i p m e n t

Repair w i t h s p a r e
24-hr p e r day On r o u n d - t h e - c l o c k emergency b a s i s
8-hr p e r day On b a s i s o f r e p a i r d u r i n g n o r m a l work day

144
IEEE-IAS T R A N S A C T I O N S M A R / A P R 1974

APPENDIX A (P. 6 of 7)

OL
M NNU CODE DESCRIPTION

9 F a i l u r e No F i l l i n o n e c a r d ( l i n e ) f o r e a c h f a i l u r e . The l a s t f a i l u r e number i n
Co1 1 9 i h o u l d c o r r e i p o n d w i t h t h e t o t a l f a i l u r e s r e p o r t e d i n C o l 3 1 o f
CARD-TYPE 2 . I f t h a t number waa " 0 " t h e n n o TYPE 3 c a r d s s h o u l d b e
t i l l e d in.

F a i l u r e Date
1 no F i l l i n month f a i l u r e o c c u r e d ( n u m e r a l )
13 Yr F i l l i n y e a r f a i l u r e occurred (numeral)

15 ~ a i l u r iF o r e w a r n i n q For p u b l i c u t i l i t y power i n t e r r u p t i o n o n l y
1 I t no f o r e w a r n i n g waa g i v e n
2 I f f o r e w a r n i n g waa g i v e n
F o r o t h e r t y p e a of f a i l u r e , l e a v e b l a n k

F a i l u r e Duration F i l l i n d u r a t i o n o f f a i l u r e from i t s i n i t i a t i o n u n t i l (1) s e r v i c e is


r e a t o r a d t o n o r m a l , i f a power i n t e r r u p t i o n , or ( 2 ) t h e a f f e c t e d
component or i t a r e p l a c e m e n t o n c e a g a i n becomes a v a i l a b l e t o p e r f o m
it. i n t e n d e d f u n c t i o n .

!6 No o f U n i t a F i l l i n t h e nwnber o f time u n i t s s e l e c t e d i n C o l 2 9 .

!9 Unit. S e l i c t c o d e f o r a p p r o p r i a t e time u n i t t h a t w i l l g i v e a c c u r a t e r e s u l t s .
For moat c a s e a a e l e c t h o u r s as u n i t .
1 Days
2 Houri
3 ninutei
4 Second.
5 Cycle.
S e l e c t c o d e f o r C o l 30-44 (Leave b l a n k f o r u t i l i t f a i l u r e s )
IO F a i l u r e Repafr 1 Repair o f f a i l e d component in p l a c e or s e n t o u t f%r r e p a i r
Method 2 R e p a i r by r e p l a c e m i n t o f f a i l e d component w i t h s p a r e
I2 F a i l u r e Repair 1 Requiring round-the-clock a11 o u t e f f o r t s
Urgency 2 R e q u i r i n g r e p a i r work o n l y d u r i n g r e g u l a r v o r k d a y , p e r h a p s w i t h some
overtinu.
3 R e q u i r i n g r i p a i r work on a n o n - p r i o r i t y b a s i a .

I4 F a i l u r e , month. F a i l e d canponent l a a t had p r e v e n t i v e maintenance -


aince maintained 1 Leaa t h a n 1 2 month. a g o
2 12-24 montha a g o
3 Over 24 montha a g o
4 NO p r e v e n t i v e maintenance

I6 F a i l u r e , Dunaged 1 Inaulation - winding


Part 2 Ineulation - buahinq
3 Inaulation -other
4
5
Uechanical
Uechanical
--beuingr
other moving p a r t s
6 Uichanical -other
7
8
9
Other e l e c t r i c a l
Other e l e c t r i c a l
Tap c h a n g e r -- --
auxiliary device
protective device
no l o a d t y p e
10 Tap c h a n g e r load type
99 Other

145
A P P E N D I X A R E P O R T ON RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

OL
MN NAME CODE DESCRIPTION

0 F a i l u r e Type 1 F l a s h o v e r or a r c i n g i n v o l v i n g gTOUr.3
2 ~ 1 o1t h e r f l a s h o v e r or a r c i n g
3 Other e l e c t r i c a l d e f e c t
4 Mechanical d e f e c t
99 Other

Your b e s t estimate of s u s p e c t e d r e s p o n s i b i l i t y

0 Failure 1 M a n u f a c t u r e r - d e f e c t i v e Component
Responsibility 2 Transportation t o S i t e - defective handling
3 Application Engineering - improper a p p l i c a t i o n
1 I n a d e q u a t e i n s t a l l a t i o n and t e s t i n g p r i o r t o s t a r t u p
5 Inadequate maintenance
6 Inadequate operating procedures
7 O u t s i d e agency - p e r s o n n e l
0 O u t s i d e agency - o t h e r
99 Other
#2 Failure
I n i t i a t i n g Cause I n s u l a t i o n breakdown c a u s e d b y
1 T r a n s i e n t o v e r v o l t a g e d i s t u r b a n c e ( l i g h t n i n g , mwitching s u r g e s ,
a r c i n g ground f a u l t i n ungrounded s y s t e m )
2 Overvoltage
3 Overheating
4 O t h e r i n s u l a t i o n breakdown
21 M e c h a n i c a l b r e a k i n g , c r a c k i n g , l o o s e n i n g , a b r a d i n g , or d e f o r m i n g
o f s t a t i c or s t r u c t u r a l p a r t 8
22 M e c h a n i c a l b u r n o u t , f r i c t i o n , or s e i z i n g of moving p a r t s
23 M e c h a n i c a l l y c a u s e d damage f r o m f o r e i g n s o u r c e ( d i g g i n g , v e h i c u l a r
accident, e t c )
41 S h o r t i n g by t o o l a or m e t a l o b j e c t s
42 S h o r t i n g by b i r d s , s n a k e s , r c d e n t a , e t c
51 Loss o f c o n t r o l p o u e r
52 M a l f u n c t i o n of p r o t e c t i v e r e l a y c o n t r o l d e v i c e . or a u x i l i a r y b e v i c *
61 Low v o l t a g e
62 Lou f r e q u e n c y
99 Other

I4 Failure 1 P e r s i s t e n t overloading
C o n t r i b u t i n g Cause 2 Above-normal t e m p e r a t u r e s
3 Belou-normal t e m p e r a t u r e
4 E x p o s u r e t o a g r e s s i v e c h e m i c a l . or .OlVOnts
5 E x p o s u r e t o a b n o r m a l m o i s t u r e or w a t e r
6 E x p o s u r e t o n o n - e l e c t r i c a l f i r e or b u r n i n g
0 O b s t r u c t i o n o f v e n t i l a t i o n by f o r e i g n o b j e c t or m a t e r i a l
9 Normal d e t e r i o r a t i o n from a g e
10 S e v e r e w i n d , r a i n , anow, s l e e t , or o t h e r w e a t h e r c o n d i t i o n s
11 P r o t e c t i v e r e l a y i m p r o p e r l y .et
12 LOSS or d e f i c i e n c y o f l u b r i c a n t
13 LOUS or d e f i c i e n c y o f o i l or c o o l i n g medium
14 M i s o p e r a t i o n or t e s t i n g error
15 Expo8ure t o d u s t or o t h e r c o n t a m i n e n t s
99 Other

146
IEEE-IAS TRANSACTIONS MAR/AF'R 1974

WHD APPENDIX A (P. 7 of 7)


13
USER INSTRUCTIONS FOR CARD-TYPE 3
CARDS - TYPE 3

:oL
IMN NAME CODE DESCRIPTION

16 Failure Utility Power S u p p l i e s ( S e l e c t code)


Characteris t i c 1 Failure o f s i n g l e c i r c u i t (No r e d u n d a n t s u p p l y )
2 Failure o f one c i r c u i t of a d o u b l e - c i r c u i t r e d u n d a n t s u p p l y
3 Failure of both c i r c u i t s of a double-circuit redundant supply
4 Failure o f a l l c i r c u i t s o f a t h r e e or more c i r c u i t r e d u n d a n t s u p p l y
5 Partial f a i l u r e o f a t h r e e or more c i r c u i t r e d u n d a n t s u p p l y

T r a n s f o r m e r s ( S e l e c t code)
6 A u t o m a t i c r e m o v a l by p r o t e c t i v e e q u i p m e n t
7 P a r t i a l f a i l u r e reducing capacity
8 Manual r e m o v a l
C i r c u i t Breakers ( S e l e c t code)
9 F a i l e d t o c l o s e when i t s h o u l d
10 F a i l e d w h i l e opening
11 Opened when i t s h o u l d n ' t
12 Damaged w h i l e s u c c e s s f u l l y o p e n i n g
13 Damaged w h i l e c l o s i n g
14 F a i l e d w h i l e o p e r a t i n g ( n o t w h i l e o p e n i n g or c l o s i n g )

G e n e r a l ( S e l e c t code for any o t h e r c l a s s )


15 Failed (this applies to a l l classes)
16 F a i l e d d u r i n g t e s t i n g or m a i n t e n a n c e
17 Damage d i s c o v e r e d d u r i n g t e s t i n g or m a i n t e n a n c e
20 Partial failure
99 Other

Loads L o s t What l o a d s were l o s t b e c a u s e of f a i l u r e ( l = y e s , O=no, 9= n o t known)


e v e n t h o u g h power is r e s t o r e d p r o m p t l y

18 Compu te1 One or more c o m p u t e r s or s o l l d - s t a t e control devlces operated


incorrectly

19 Motor One or more m o t o r s ( c o n t a c t o r d r o p o u t )

50 Lighting Lighting load

51 Solenoid One or more s o l e n o i d - o p e r a t e d d e v i c e s d r o p p e d o u t , s u c h as a s o l e n o i d .


operated fuel valve
52 Other L o s t o t h e r l o a d s , d e s c r i b e i n remarks

ja Percent Production 0 None


LOS t 1 0-30 p e r c e n t
2 Above 30 p e r c e n t

147
APPENDIX A R E P O R T ON RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

14
USER INSTRUCTIONS FOR CARD-TYPE 3

URDS - TYPE 3
L CAILUIE

:oL
JMN NAME CODE DESCRIPTION

54 NO of U n i t s F i l l i n number of t i m e u n i t s s e l e c t e d i n Col 5 1

57 Units S e l e c t c o d e for a p p r o p r i a t e t i m e u n i t t h a t w i l l g i v e a c c u r a t e
results. F o r m o s t cases s e l e c t h o u r s a s u n i t .
1 Days
2 Hours
3 Minutes
4 Seconds
5 Cycles

58 Service restored G i v e method of r e s t o r i n g s e r v i c e t o p l a n t


1 Primary s e l e c t i o n -manual
2 Primary s e l e c t i o n - a u t o m a t i c
3 S e c o n d a r y s e l e c t i o n -manual
4 Secondary s e l e c t i o n - a u t o m a t i c
5 Network p r o t e c t o r o p e r a t i o n - a u t o m a t i c
6 R e p a i r of f a i l e d c o m p o n e n e t
7 R e p l a c e m e n t of f a i l e d component w i t h s p a r e
8 Utility restored service
9 Other - e x p l a i n i n remarks

148
JBEE-IAS TRANSACTIONS MAR/APR 1974

DIsc ussI ON circuit and a double or triple circuit. This is evidently due to
the predominance of the throwover mode of operation of mul-
Motors tiple-circuit supplies. However, the actual downtime per failure
The data in Tables 7 and 2 show that synchronous motors, is about three to nine times higher for a single circuit than for a
0-600 V, have a failure rate approximately 1 5 times lower double or triple circuit; the downtime depends on whether
than induction motors, 0-600 V. It is believed that the failure manual switchover or automatic switchover is used on a mul-
0.0007 per year for synchronous motors, 0-600 V, is much too tiple-circuit system.
low and is in error. It is believed that synchronous and induc- I t appears that many respondents misinterpreted the “num-
tion motors, 0-600 V, should have failure rates that are nearly ber of installed units” for double- or triplecircuit electric
the same. utility power supplies. What was desired was the number of
separate and independent points of supply, but this was often
Generators interpreted to be the number of circuits in the utility supply
The data in Tables 8 and 2 show that steam turbine driven system. Thus the tendency was to report two installed units
generators have a failure rate almost 20 times lower than gas for double-circuit supplies. I t is believed that this error was
turbine driven generators. It is believed that the failure rate of made in almost every case. Therefore, the Reliabiliry Sub-
0.032 per year for steam turbine driven generators is too low; committee changed the number of installed units for multiple-
the failure rate should probably be several times higher than circuit utility supplies to 1 except in those cases where other
this value. The gas turbine data in Table 8 show that one plant evidence indicated the presence o f more than one point of
in the petroleum industry had 54 failures in 5.5 unit-years; supply. The sample size shown in Tables 3 and 2 reflects this
this compares with 3 failures in 83.9 unit-years for the other change for double- or triple-circuit electric utility power sup-
three plants that submitted data in the survey. It is believed plies. Thus a double- or triple-circuit supply for one year is
that the overall failure rate of 0.638 per year for gas turbines is counted as one unit-year.
too high. I t also appears that a few respondents incorrectly interpreted
failure duration on card type 3 for multiple-circuit electric
Open Wire utility supplies. What was desired was the period of time
A clear definition was not given for “open wire” on the during which service was interrupted. However, in a few cases
survey form (see Appendix A). I t is believed that all of the it appears that what was given was the time to repair one cir-
respondents interpreted “open wire” to mean “bare or weather- cuit of a multiple-circuit supply even though the supply
proof conductors supported on insulators.” interruption time is limited to the time required to throw over
to the alternate supply circuit. The Reliabilip Subcommittee
Cable changed the failure duration to the value given for plant out-
The data in Tables 13 and 2 show that cable above ground age duration in those cases in which such at1 error was
and aerial has a failure rate for 0-600 V that is ten times lower believed to exist. However, i t is suspected that not dl of these
than 601-15 000 V. I t is believed that the failure rate of errors were corrected. The effect of this change was t o reduce
0.00141 per unit-year for 0-600 V above ground and aerial is the actual hours of downtime per failure for multiple-circuit
too low. supplies. The majority of the multiple-circuit supply failures
There is a wide variation in the fallure rate for cable, 601- are due to loss of the normal feed, and the duration of the fail-
15 000 V, based upon the application (in trays above ground. ure is limited to the time to switch to the alternate feed. The
in conduit above ground, aerial cable, in duct or conduit below average outage duration in Tables 3 and 2 is shorter for auto-
ground). This variation covers a range of 8 to 1. I t is believed matic switching than for manual switching, as one would expect.
that the failure rate of 0.04918 per year is too high for cable. There were 25 recorded cases of simultaneous failure of all
601-15 000 V , in conduit above ground. circuits in a double- or triple-circuit supply. This gives a
There is a wide variation in the cable failure rate shown in failure rate of 0.1 19 failure per year for loss of all circuits at
Table 14 (and Table 2) for the different types of insulation one time. Further details on this are given in Part 3 [ 1 3 ] .
(601-15 000 V, all applications). These failure rates vary over Thus a multiple-circuit electric utility power supply has a
a range of 5 to I . The very low failure rate data for thermo- failure rate (loss of all circuits at one time) that is only about
plastic insulation and the high failure rate data for other five times lower than the failure rate (0.537 failures per year)
insulation came primarily from the chemical industry. for a single-circuit supply and about six times lower than the
all-inclusive failure rate of 0.643 failure per year. The ratio
Switchgear Bus between all-inclusive failure rate and the failure rate for loss of
The failure rate in Table 10 (and Table 2 ) shows that insu- all circuits at one time is not as large as one might suspect.
lated bus, 601-15 OOOV, has a failure rate about three times Some of the reasons for this are the following.
higher than bare bus, above 600 V. It is believed that this is 1) Some portion of utility supply failures are due to failure
the opposite of what it should be. The datasubmitted by the of the bulk power system which feeds all the supply circuits.
chemical industry has caused this distortion; they had a very 2) At least some cases of loss of all circuits at one time occur
high failure rate for insulated bus (601 -1 5 000 V) and a low when a forced outage of one circuit overlaps a scheduled or
failure rate for bare bus (above 600 V). maintenance outage of the other circuit (typical utility industry
data indicate that this type of overlapping outage is often more
probable than overlapping forced outages).
Electric Utility Power Supplies 3) The all-inclusive failure rate is, in effect, an average out-
The data for electric utility power supplies are shown in age rate reflecting the performance of some throwover schemes
Tables 3 and 2 . The failure rate is about the same for a single and some normally closed breaker schemes. Thus, since throw-

149
APPENDIX A R E P O R T O N RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

over schemes are expected to have higher outage rates than two points just reflect the facts of life.
normally closed breaker schemes, it follows that the computed A comparison of the all-inclusive failure rate (0.643 failures
all-inclusive outage rate is probably somewhat lower than the per year) with the failure rate for loss of all circuits at one time
outage rate which would be computed for throwover schemes (0.119 failures per year) gives a rough idea of the degree of
only. (Unfortunately we cannot compute the throwover supply failure rate improvement possible by going from a
scheme outage rate since we do not know which of the reported throwover scheme to a scheme using normally closed circuit
utility supplies are throwover schemes.) breakers.
Only point 3) reflects on the accuracy of the data; the other

REFERENCES
[ 11 W. H. Dickinson, P. E. Gannon, C. R. Heising, A. D. Patton, and
D. W. McWilliams, “Fundamentals of reliability techniques as
applied t o industrial power systems,” in Con5 Rec. 2972 IEEE
Ind. C o m m . Power Syst. Tech. Con5 71C18-IGA, pp. 10-31.
[ 21 C. R. Heising, “Reliability and availability comparison of common
low-voltage industrial power distribution systems,” IEEE Trans.
Ind. Gen. Appl., vol. IGA6, pp.416-424, Sept./Oct. 1970.
[3] W. H. Dickinson, “Economic evaluation of industrial power sys-
tem reliability,” AIEE Trans. (Appl. l n d . ) , vol. 76, pp. 264-271,
Nov. 1957.
[ 4 ] W. H. Dickinson, “Evaluation of alternative power distribution
systems for refinery process units,” AIEE Trans. (Power Appl.
S y s t . ) , vol. 79, Apr. 1960.
[ 5 ] W. H. Dickinson, “Economic justification of petroleum industry
automation and other alternatives by the revenue requirements
method,” IEEE Trans. Ind. Gen. Appl., vol. IGA-1, pp. 39-50,
Jan./Feb. 1965.
[6] D. P. Garver, F. E. Montmeat, and A. D. Patton, “Power systems
reliability I-Measures of reliability and methods of calculation,”
IEEE Trans. Power Appl S y s . , vol. 83, pp. 727-737, July 1964.
[7] F. E. Montmeat, A. D. Patton, J. Zemkoski, and D. J. Cummin,
“Power system reliability 11-Applications and a computer pro-
gram,” ibid., vol. PAS-84, pp. 6 3 6 4 4 3 , July 1965.
[8] Z. G. Todd, “A probability method for transmission and distribu-
tion outage calculations,”IEEE Trans. Power App. S y s t . , vol. 83,
pp. 695-701, July 1964.
[9] C. F. DeSieno, and L. L. Stine, “A probability method for deter-
mining the reliability of electric power systems,” IEEE Trans.
PowerApp. Syst., vol. 83, pp. 174-181, Feb. 1964.
[ 101 “ G e n e d principles for reliability analysis of nuclear power gener-
ating station protection systems,” IEEE Publ. 352, ANSI N41.4,
1972.
[ l l ] W. H. Dickinson, “Report on reliability of electric equipment in
industrial plants,”AIEE Trans. (Appl. Ind.), vol. 81, pp. 132-151,
July 1962.
[12] IEEE Committee Report, “Report on reliability survey of indus-
trial plants, Part 11: Cost of power outages, plant restart time,
critical service loss duration time, and type of loads lost versus
time of power outages,” this issue, pp. 236-241.
[13] IEEE Committee Report, “Report on reliability survey of indus-
trial plants; Part 111: Causes and types of failures of electrical
equipment, methods of repair, and urgency of repair,” this issue,
pp. 242-249.
[ 141 N. H. Roberts, Mathematical Methods in Reliability Engineering.
New York: McGraw-Hill, 1964.
[15] I. Bazovsky, Reliability Theory and Practice. Englewood cliffs,
N.J.: Prentice-Hall, 1961.
[ 161 D. K. Lloyd and M. Lipow, Reliability: Management, Methods,
and Mathematics. Englewood Cliffs, N.J.: Prentice-Hall, 1962.
[ 171 A. D. Patton, “Determination and analysis of data for reliability
studies,”IEEE Trans. Power App. Syst., vol. PAS-87, pp. 84-100,
Jan. 1968.

150
IEEE-IAS T R A N S A C T I O N S M A R / A P R 1974

Report on Reliability Survey of Industrial


Plants, Part 11: Cost of Power Outages,
Plant Restart Time, Critical Service Loss
Duration Time, and Type of Loads Lost
Versus Time of Power Outages

IEEE COMMITTEE REPORT

Abstract-An IEEE sponsored reliability survey of industrial plants includes computer, motor, lighting, and solenoid loads,
was completed during 1972. This survey included the cost of power
outages, plant restart time, aiticai service loss duration time, and type
and gives plant outage duration times resulting from
of loads lost versus power outage duration time. Survey resultsreflect these failures).
data from 30 companies covering 68 plants in nine industries in the
United States and Canada. This information is useful in the design of Paper TOD-73-158, approved by the Industrial and Commercial Power
industrial power distribution systems. Systems Committee of the IEEE Industry Applications Society for
mesentation at the 1973 Industrial and Commercial Power Svstems
Technical Conference, Atlanta, Ga.. May 13-16. Manuscript rdleased
for publication November 5 , 1973.
INTRODUCTION Members of the Reliability Subcommittee of the IEEE Industrial and
Commercial Power Systems Committee are W. H.Dickinson. Chairman,

K NOWLEDGE of the cost of power outages and of


plant restart time is important information for use in
the design of industrial power distribution systems. In addi-
P. E. Gannon, M. D. Harris, C. R. Heising, D. W. McWilliams. R. W.
Parision, A . D. Patton, and W. J. Peace.

SURVEY
FORM
tion it is also desirable to know the critical service loss dura-
tion time and the type of loads lost versus the time of power The survey form used is shown in Appendix A of Part 1
outage. [ I 1. The information on the cost of power outages came
During 1972 the Reliability Subcommittee of the IEEE from card type 1, columns 13, 20, and 25. Card type 1 also
Industrial and Commercial Power Systems Committee com- contained plant restart time (column 31) and critical service
pleted a reliability survey of industrial plants. This is the
loss duration (columns 33 and 36).
second part, which reports results from the survey. Included The data on type of loads lost came from card type 3,
in this paper are the following results: columns 48, 49, 50, 51, and 52. The data on time of power
outage came from columns 26 and 29 of card type 3; these
1) cost of power outages to industrial plants in the United data are actually the outage duration time after a failure of
States and Canada (dollars per kilowatt interrupted plus the electric utility power supply or a failure of electrical
dollars per kilowatthour of undelivered energy); equipment in the power distribution system.
2) plant restart time after a failure that has caused complete
plant shutdown; RESPONSETO S U R V E Y
3 ) critical service loss duration time, that is, the maximum A total of 30 companies responded to the survey question-
length of power failure that will not stop plant naire reporting data on 68 plants from nine industries in the
production; United States and Canada. Every response did not supply all
4) type of loads lost versus the time of power outage (this the information requested on every question. Tables 22-29
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

give data on how many plants provided answers to the Of the 41 plants that reported outage cost data in the survey,
various questions 31 had a maximum demand greater than 1000 kW and 10 had
a maximum demand less than 1000 kW. Cost data for plants
STATISTICAL
ANALYSIS with maximum demands less than 1000 kW are not considered
The results were compiled for the United States and Canada. particularly reliable due to the small number of such plants
Data from one foreign plant are also included separately. represented in the data.
There is a wide spread in the cost of power outages. Con-
SURVEYRESULTS sequently few plants with high outage costs can have a
Cost of Power Outages significant effect on the overall average cost. In such cases
the median cost of power outages may be more representative
Each plant was asked to report data on the cost of power
than the average cost. The median cost is such that half of the
outages as follows:
1) Dollars per failure, Le., extra expense incurred because plants have a cost greater than this value and half have less.
of a failure only (not including plant downtime) such as for Table 21 shows the median power outage costs. Additional
d e t d s on the cost of power outages are given in Tables 22-27.
damaged equipment, spoiled product, extra maintenance, or
These additional details include: 1) number of plants reporting
extra repair costs.
the outage cost per failure and the outage cost per hour of
2) Dollars per hour of downtime, i.e., value of lost produc-
downtime, 2) minimum plant cost, 3) maximum plant cost,
tion in dollars per hour of plant downtime only. This is the
estimated revenues (sales price) of product not made, less 4) costs for various industries.
Tables 22, 24, and 26 give the cost of outage per failure per
expenses saved in labor, material, utilities, etc. If this varies
with the duration of the plant downtime, an average value per kilowatt maximum demand. Tables 23, 25, and 27 give the
hour was to be given. cost of a sustained outage per hour down per kilowatt maxi-
mum demand.
3) Maximum electric power demand when the plant is
operating at its rated or design capacity in kilowatts.
l h s made it possible to calculate an estimate of the cost of Plant Restart Time
power outages in terms of the dollars per kilowatts inter- Each plant was asked to report data on the time required to
rupted plus the dollars per kilowatthours of undelivered get the plant back into operation after service is restored
energy. The average cost of power outages from the survey following a failure that has caused a complete plant shutdown.
is given in Table 20. A total of 43 plants reported these data. The average plant

A l l Plants $1.89 p e r kW + $2.68 p e r kWh

P l a n t s ) 1000 kW $1.05 p e r kW + $0.94 p e r kWh


Max. Demand

1
~ ~~~

~ P l a n t s l O O OkW $4.59 p e r kW + $8.11 p e r kWh 1


Max. Demand I
TABLE 21 - MEDIAN COST OF POWER OUTAGES FOR
INDUSTRIAL PLANTS I N THE UNITED STATES
OF AMERICA AND CANADA
A l l plants $0.69 p e r kW + $0.83 p e r kiJh

Max. Demand

152
IEEE-IAS TRANSACTIONS MAR/APR 1974

restart time was 17 h. The median was 4 h. Additional de- times after an equipment failure affected the loads lost. The
tails are given in Table 28. average plant outage duration resulting from these failures is
Critical Service Loss Duration Time also given in Table 30.

One of the most commonly asked questions is, What is a


DISCUSSIONOF RESULTS
power failure? In particular, How long can power be lost
without causing a complete plant shutdown? Each plant was Cost of Power Outages (Tables 20-27)
asked t o report data giving the maximum length of power 1) There is a wide spread in the cost of power outages (per
failure that will not stop plant production. This time is kilowatt and per kilowatthour) of industrial plants. Even
typically in the range of cycles to minutes and is called within a given industry,such as chemical, there is a wide spread
“critical service loss duration time.” in the cost of power outages (per kilowatt and per kilowatt-
A total of 55 plants reported data on critical service loss hour) for different plants.
duration time. The median value was 10 s, that is, half of the 2 ) Plants with a maximum demand of less than 1000 kW
plants were greater than this value and half were less. Addi- have a much higher cost of power outages (Der kilowatt and
tional details are given in Table 29. per kilowatthour) than plants with a maximum demand of
greater than 1000 kW. This indicates that small industrial
Loads Lost Versus Time of Power Outage plants have a hgher cost of power outages (per kilowatt and
Each plant was asked, What loads were lost because of fail- per kilowatthour) than large industrial plants. It is suspected
ure even though power was restored promptly? Five types of that this may be because the small industrial plants have more
loads were included in the survey: employees per kilowatt (and per kilowatthour). It is also pos-
1) computer: one or more computers or solid-state control sible that high-consumption industries tend to have a lot of
electrochemical or heating processes, and these tend t o have
devices operated incorrectly;
low outage costs; for example, heat not supplied now can be
2 ) motor: one or more motors (contactor dropout);
supplied later, providing the outage is not too long.
3) lighting; lighting load;
3) It is suggested that the “all-industry’’ data for the 41 and
4) solenoid: one or more solenoid-operated devlces dropped
42 plants should be compiled t o show 25 percent and 75 per-
out, such as a solenoid-operated fuel valve;
cent in addition to the minimum median and maximum val-
5 ) other: lost other loads, to be described in remarks.
ues already tabulated (Tables 22 and 23).
A very short outage duration time after an equipment failure 4) It is suggested that future surveys also include the cost of
(including electric utility power supply) might not result in a power outages (per kilowatt and per kilowatthour) of com-
loss of load. Table 30 shows how short power outage duration mercial buildings.

153
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

J
zz

a:*
'
I
a:
W v )
aI-
z
s5i
o n
W-l
we
U
s
. . . .I . . . .1 . . . . . tz
v . . . . . . . . . . . . .
0

. . . . . . . . .mm.,
c . . . . . . . . .%=e.. 4
"m .: ... ... ... ... ... ... ... ...-L L .. .. n
.r

a . . . . . . . . . w e . .
. 3 3 . . I
......
2 : :. .: ... ... ....--v . m m .. ..
. v u . .
.V) O
N
.'c 'c
3
.. .. .. .. .. .. I * . a m . .
. .
. m
. 3 3 . .
. % = I C . .
. . . . . . a - .TI: .. ..
2 : : : : :1 % - -
c, . .. .. .. . . a v :. oZ m? .: . :
= . .
. m .
I - . S o $ ..- ...me.
. .
.aJc a J - 1 I
Y . e..-- c o
c . w v .ml-mL-
0
L L
aJ.VL.r
€ f o ~ I n n w a J a ~ a ~ w
- e 2 w w c e - n x z c s ~
- 3 w c aJ33aJwwwo
44""~zaa~k-ooo~

154
IEEE-IAS TRANSACTIONS MARlAPR 1974

al
D
m mco ~ m o o h hm
5 o
7
. I !
h-
. . I ........
.-mmoNm8m e
U7 I I . . .
mm
mv)
c f h w u m m m ~ ~
I N q Y N W m W C .....
W
5
4: I I---
0 r?W
1 -m-NOhOm
I
-m
I
mhmcfomhh
I
m
. I t
m-
. . I ........
mmhmwwmr>
I
-m
. . I
U
. .7 . .- . m. . .
O ~ N N ~ ~ C
N
I
I I I I
N Nco h m o o o h c f m u m
m I I N -
. . . . . . . . . .
I O m U l O r - W m W I -m I N
c f h W d U r n O h
. . . . . . . . . .
O ~ N L O ~ ~ O
N
I I---
- 0

I I
I cu I
N
0 I I NCD o m W h m h m m
I
m
0
a r I
0
I
o
. . . . . . . . . .
0 - O ~ N O O C D N ~
~~

0
0 I t o m
?y I dhCOUmmmh
........
0 0 N N m m h 0

I I
7

I I
I I I I

5
u
.. .. .. .. .. .. .. .. .. .. .. .. ..
.. .. .. .. .. .. .. .. .. m. m. .. . .
m
I I
.. .. .. .. .. .. .. .. .. .. .. . .
c . . . . . . . . . = E . .
5
. . . . . . . . ..- .- . .
v
m .. .. .. .. .. .. .. .. .. m= g= l .. ..
. .. ... ... ... ... ... ... .
c
. . . . . . . . ..C.C . .
... ... ... ... ... ... ... ... .. >L L> ... ...
5 m
3 . . L L . . v
=s..
4
......
. . .uc,..
.VI . " U . .
da
...... .++I
. v u . .
.VI
5 : : :. .: .: :. :.: :22 : : 5 : : : : : :.: : 2 2 : :
2 . . . . . . .u
.. .. .. .. .. .
3 . . _ _ .U
. . T 3 . .
. V I . = = . .
~
. > = I . .
I
. . . * . - w - .- = m m . .
. L 5
=:.
2:::::::,"":,,.:

155
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

m
m
I I 7* I 1

I I I
I I I
I
fE
-I
0 h N O m 00

- m
W
9
0
, 1 1 .
d
1 I I I , ? ?
-
-0
.C I 1 - 1 1 99, I
X N h
I I - r-3
z N

I I I

I
2
W
v)
m
. I l l
h
\D
U
*

I
I
I I I l

I
I
I
-0
..
-0
-m
m
ET
.I-

; I 1
m
m
7
*

I
: I

-
0 h O h m
I n 1 1 1 - 1

U
I 111mw
.. I l m l I
Worn
I l w m l
.. I
7 m

I I I I
I
0 0 0 0 - 0 0 0 0 0 N h O C
I I I
c

I I
.. .. .. .. .. .. .. .. .. .. .. .. .. I .. .. .. .I. .. .. .. .. ..
v . . . . . . . . . . . . .
m m . . . .
m . . . . . . . . . o m . . v . . . .
.. .. .. .. . o m . .
......
m . . . . . . . . ..- .- . .
E T . . . . = E T . m . . . .
. . . . ..? . .
.. .. .. .. .. .. .. .. . iL . .. C
m
. . . .

. . . . .. ... ... ... . w e . .


. . . .
. C
~~ -
C
c
. .

e . . . ..
v . . . .
. . . . . . . . .. v+ eu .. ,. . 1 = . . L L . .

3 .: .: .: .: .: .I
. 3 3 . .
08
......
: : : :.. .. . . m m .. . .
.v)
. v u . .
....
. a m .
..
.lJ
..r .Y-+
I

3
x . . . . . . .e
.V)
.lJ
.r .Y- Y-

, .. .. .. .. .. .
3 . .
. ) = I . .
. E T = . .
. . . . . .all- .. = E .. ..
.V)
. a m . .
. L 4
L-. .... 2 : : : : -. .no-
e . . . . . .nu I g 2 I I
. m
.- .
V ) . . . . . m a . .

.r L L L
-.-- -
3 .
- 0 .. m .
K .+lJ 0
*aJC
, m L-
aJAI . C
.m

- E aJQ .-
-C.r+- K O L L.r
eaJaJ0)a
X T T C L -e
0 E m L n X S LaJ
aJ o, aJ
aJeee0 3 aJJ= aJ
I-OOOL -=cuvvE:

156
IEEE-IAS TRANSACTIONS MAR/APR 1974

v
. v .
w e
.- . - .
u l u l
aJ
u u v u u
w w w
- 7
v u
ulvl

aJ m'r a J h a J h W . h >
ul E ulvulvmcuu
m
0 I
d
I
..
N O
-In
I ooooo'Eoo
:ddddmdLn
7 7 -Nm-bN-
I I
1 - I

I I
I I
I
I I
m00m,0m7mmh7rn-
e - I 1
l I LDoOONO--'
I n N

1 1
..............
. .. .. .. .. .. .. .. .. .. .. .. .. ..
m
.. .. .. .. .. .. .. .. .. m. m. .. .. .. .. .. .. .. .. .. .. .....
... ... ... ... ...
73
m
c .. .. .. .. .. .. .. .. ....-=L.-eL ... ... .. .. .. .. .. .. .. ... .
-
5
.. .. .. .. .. .. .. .. m .. .. .. . .
...... ... ... . mm
. 3 3 . . U
m
. .. .. .. .. .. ... *..
.
6 . . .*c,..
. ... cL cL
. ..
. v u .
<
m . . . . . .
. 5 m .
.++
E
5
V
.. ..
.C .r

. 3 3
.. .. .. .. .. ..
z . . . . . .
.. -*e
. v u
I
. . .. .. .. .. 4:
m
x
. m 5
.+4-
L'. . . . . .
.. U
m
I . .

u . . . . . .
.
. c
..r . 3 3

157
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

For Equipment For Equipment For Equipment


F a i l u r e s 1 Cycle F a i l u r e s Between F a i l u r e s 10
o r less i n 1 and 10 Cycles Cycles o r More
D u r a t j on i n Duration i n Duration
Type o f Not Not Not
Load Yes No Known Yes No Known Yes No Known

Compu te r 0% 0% 0% 4% 96% 0% 9% 91% 0%


Motor 0% 0% 0% 33% 67% 0% 67% 33% 0%
Lighting ’ 0% 0% 0% 22% 78% 0% 38% 61% 2%
Solenoid 0% 0% 0% 22% 74% 4% 25% 66% 9%
Other 0% 0% 0% 7% 15% 78% 25% 62% 13%

Average
Plant 0.0 Hours 1.39 Hours 22.6 Hours
Outage
Duration

Only non-zero data was used i n computing t h e average p l a n t outage d u r a t i o n

5) Additional information on the cost of power outages in had computer loads t o give such a low value. In fact, many
Sweden, Norway, and the United States is contained in [2]. plants must not have had motor loads or solenoid loads either.
The important parameter to look at is the change in these
Plant Restart Time (Table 28) percentages from 0 to the maximum value as the length of
The textile, petroleum, and chemical industries have a much power outage time is increased.
longer plant restart time than the other industries included in 2) It is suggested that loss of load data be compiled for the
the survey. following additional categories of outage duration time:

&tical Service Loss Duration (Table 29) a) IO to 15 cycles,


b) IS+ to 30 cycles,
1) There is a wide spread in critical service loss duration
c) 0.5 + to 2.0 s,
time for the 55 plants in the survey.
d) 2.0+ to 4.0 s,
2) It is suggested that the data from the 55 plants should be
e) greater than 4.0 s.
compiled t o show several percentiles (IO, 25, 75, and 90 per-
cent) in addition t o the median value already tabulated. The average plant outage duration should also be determined
for these categories.
Loads Lost Versus Time of Power Outage (Table 30)
1) An outage between 1 t o I O cycles resulted in 33 percent
REFERENCES
of the plants losing motor loads and 22 percent losing a sole-
noid and only 4 percent losing a computer load. An outage [’] IEEE Committee Report, “Report on reliability survey of mdus.
trial plants; Part I: Reliability of electrical equipment,” this issue,
greater than 10 cycles resulted in 67 percent of the plants los- pp. 213-235.
ing motor loads and 25 percent losing a solenoid and only 9 1’1 R. B. Shipley, A. D. Patton, and I. S. Denison “Power reliability
cost vs worth,” IEEE Trans Power App. Syst., vol. PAS-91, pp.
percent losing a computer load; many plants must not have 2204-2212, SeptJOct. 1972.

158
IEEE-IAS TRANSACTIONS MAR/APR 1974

Report on Reliability Survey of Industrial


Plants, Part 111: Causes and Types of
Failures of Electrical Equipment, the
Methods of Repair, and the Urgency
of Repair
IEEE COMMITTEE REPORT

Absrrocf-An IEEE sponsored reliability survey of industrial plants The failure repair urgency also has a significant effect on the
was completed during 1972. This included the causes and types of aveiage downtime per failure and thus is an important factor in
failures of electrical equipment, the methods of repair, and the urgency reliability and availability calculations.
of repair. The results are reported from the survey of 30 companies
covering 68 plants in nine industries in the United States and Canada. A preventive maintenance program can have an effect on the
This information is useful in the design of industrial power distribution failure rate of electrical equipment. Thus a knowledge of
systems. whether or not maintenance has been performed recently prior
to the failure is a significant factor in helping to determine
INTRODUCTION whether or not the maintenance program is adequate.

A KNOWLEDGE of the causes and types of failures of


electrical equipment is useful in the design of industrial
power distribution systems. In addition it is also useful to
The damaged part from a failure is of interest. In addition, a
knowledge is also desirable of the type of failure, initiating
cause, contributing cause, and suspected responsibility. This
know the failure repair method, whether or not the repair was information is useful for correcting deficiencies in electrical
urgent, and how long it had been since the previous mainte- equipment and electrical systems.
nance had been performed. During 1972 the Reliability Sub- The failure characteristic can be defined as the effect that
committee of the IEEE Industrial and Commercial Power the failure has on the electrical system. Thus this information
Systems Committee completed a reliability survey of industrial is very important.
plants. This is the third paper reporting results from the survey.
Included in this paper are the results for 14 main classes of S U R V E YFORM
electrical equipment on The survey form used is shown in Appendix A of Part 1
[ I ] . All of the information reported on m this paper came
1) failure repair method;
from card type 3 , columns 3 0 - 4 6 . The definitions of failure
2 ) failure repair urgency; and repair rime are given in Part 1 [ 11 .
3) failure, months since maintained;
4 ) failure, damaged part; RESPONSETO SURVEY
5) failure type;
A total of 30 companies responded to the survey question-
6 ) suspected failure responsibility;
naire, reporting data on 68 plants from nine industries in the
7) failure initiating cause;
United States and Canada. Every failure report on card type 3
8 ) failure contributing cause;
did not have filled in all the information called for in columns
9) failure characteristic.
3 0 - 4 6 . Tables 31 and 32 give the data for each main equip-
The failure repair method includes either the repair of the ment classon how many failures had the information called for
failed component or the replacement of the failed component in columns 3 0 - 4 6 . Each main equipment class contains 18 or
with a spare. This can have a significant effect on the average more failures; this is believed to be an adequate statistical
downtime per failure, and thus is an important factor in re- sample size.
liability and availability calculations.
STATISTICAL
ANALYSIS
Paper TOD-73-158,approved by the Industrial and Commerclal The results were compiled for 14 main equipment classes.
Power Systems Committee of the IEEE Industry Applications Society
for presentation at the 1973 Industrial and Commercial Power Systems The number of failures were tabulated for each category of
Technical Conference, Atlanta, Ga., May 13-16. Manuscript released each column ( 3 0 - 4 6 , card type 3). This was then divided by
for publication November 5,1973.
Members of the Reliability Subcommittee of the IEEE Industrial and the total failures in each column so as to give the percentage
Commercial Power Systems Committee are W. H. Dickmson, Chair- for each category for each column (for each main equipment
man, P. E. Cannon, M. D.Harris, C. R. Heising, D.W. McWilliams,R. W.
Parisian, A. D. Patton, and W. I. Pearce. class).

159
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

SURVEY RESULTS protective relay control device initiated the failure with 4 0
The results are tabulated for the 14 main equipment classes percent of the respondents reporting that normal deterioration
in Tables 3 3 - 4 1 . Each table represents one column (of 3 0 - 4 6 , from age was a contributing cause. Over half of the respondents
card type 3). felt that improper application was primarily responsible for the
failure. In the cases reported 36 percent had been discovered
SUMMARY OF CONCLUSIONS during testingar maintenance, and 2 0 percent were only partial
Transformers failures. Lack of preventive maintenance was not a big problem.
Those starters that had been maintained less than 12 months
In the cases reported, there were approximately an equal
prior t o the failure accounted for 67 percent of the cases
number of incidences of repairing the failed transformer and
reported.
replacing it with a spare. The repair urgency slightly favored a
round-theclock repair over the regular workday schedule.
Motors
Inadequate preventive maintenance did not seem t o have much
influence on the reported failures since no preventive mainte- Of the reported motor failures, about three quarters were re-
nance was reported on only 5 percent of the failures; 11 percent paired versus about one fourth being replaced by a spare.
of the failures were blamed on inadequate maintenance. About three quarters were repaired on a regular workday
Damaged insulation both in the windings and bushings ac- basis. The types of failures varied from flashovers to electrical
counted for the majority of the transformer damage, with the defects, to mechanical defects, with winding insulation and
majority of failures being flashovers involving ground. 24 bearings sustaining the majority of the damage. Insulation
percent of the reported cases considered normal deterioration breakdown, overheating, and mechanical seizing were blamed
from age as the contributing cause of the failure, yet 39 per- as the primary initiating causes with normal deterioration from
cent reported that they felt the manufacturer was primarily re- age, loss or deficiency of lubricant, exposure to abnormal
sponsible. Transient overvoltages, from lightning or switching moisture, and exposure to aggressive chemicals ranking high on
surges, and other insulation breakdown account for 41 percent the list of contributing causes. 30 percent of the failures were
of the reported failures. In 90 percent of the reported cases discovered during testing or maintenance, which probably
the transformers were removed from the system by automatic resulted in less actual damage in those cases. lnadequate
protective devices; only 7 percent had manual removal. maintenance, improper application, and defective equipment
were listed as having primary responsibility. However, over
Circuit Breakers half of the respondents could not assign responsibility into one
of the survey classes. The motors that had been maintained be-
About the same number of circuit breakers were repaired in tween 12 and 24 months prior to the failure accounted for
place as were replaced by spares. The relative importance of 57 percent of the reported cases with less than 12 months and
circuit breakers was indicated by 73 percent of the survey re- more than 24 months accounting for 22 percent and 19 per-
spondents making repairs on a round-the-clock basis. The bulk cent, respectively. No preventive maintenance accounted for
of the reported failures involved flashovers to ground with only 2 percent, yet this does not correlate well with inadequate
damage primarily to the protective device components and the
maintenance being listed as having primary responsibility in
device insulation. Transient overvoltages, insulation break-
17 percent of the reported cases.
downs, and protective device malfunctions were considered a
major initiating cause with normal deterioration from age and Generators
misoperation or testing errors considered as contributing causes.
Of the reported generator failures 8 4 percent were repaired
However, 33 percent of the respondents could not classify the
in place. About the same number were repaired on a round-
initiating cause into any of the survey classes, and 55 percent
theclock basis as were repaired on a regular work-day basis.
could not classify the contributing cause into any of the survey
69 percent of the respondents reported damage other than the
classes. In addition, 3 6 percent of the suspected causes of
survey classes with electrical auxiliaries, winding insulation, and
failure were blamed on “other.” 4 2 percent of the reported
moving parts sustaining some damage. Mechanical breaking,
failures involved circuit breakers opening when they should not;
transient overvoltages, and about half unclassified items were
it is possible that several of these fadures were external t o the
considered the primary initiating causes with normal deteriora-
circuit breaker and of unknown cause and were blamed on the
tion from age and persistent overloading considered contribut-
circuit breaker. 32 percent of the reported failures involved
ing causes. Responsibility was spread between inadequate
circuit breakers that failed during a loadcarrying condition.
maintenance and defective components with about half of the
23 percent of the failures were blamed on the manufacturer
respondents unable to place primary responsibility into any of
and another 23 percent on inadequate maintenance, but 36
the survey classes. Infrequent or no preventive maintenance
percent were blamed on “other.” Inadequate preventive
were not involved in any of the reported cases, a point that
maintenance (PM) could be a factor of same significance since
does not correlate with the fact that some of the respondents
no PM was reported on 16 percent of the failures.
felt inadequate maintenance was the primary responsibility.
Motor Starters Disconnect Switches
Of the reported motor starter failures, about two thirds were Of the reported disconnect switch failures. 70 percent were
repaired by replacing the starter with a spare and two thirds repaired by replacement with a spare, with work in 80 percent
were repaired on a round-theclock basis. About half of the of the cases being performed on a regular work-day schedule.
cases reported indicate that the damage was other than the Electrical defects, mechanical defects, and flashovers t o ground
classes listed in the survey, primarily resulting from flashovers resulted in damage to mechanical components and insulation.
or electrical defects. 6 4 percent felt that a malfunction of a Some form of mechanical breaking or contact from foreign

160
I E E E - I A S T R A N S A C T I O N S MAR/APR 1974

TABLE 31 - NUMBER OF FAILURES FOR ELECTRIC UTILITY


POWER SUPPLIES THAT CONTAINED THE
INFORMATION CALLED FOR I N COLUMNS 30-46,
-
CARD TYPE 3

r Number
f
Col u r n Title
F a i 1ure Repair Method.. ...........
F a i l u r e Repair Urgency ............
F a i l u r e , Months Since Maintained..
F a i l u r e , Damaged P a r t.............
38 F a i l u r e Type ......................
40 Suspected F a i l u r e R e s p o n s i b i l i t y . ,
42 ........
F a i l u r e I n i t i a t i n g Cause.. 53
44 ......
F a i l u r e C o n t r i b u t i n g Cause..
46 Failure Characteristic.. .......... 145

TABLE 32 - NUMBER OF FAILURES FOR EACH MAIN EQUIPMENT


CLASS THAT CONTAINED THE INFORMATION CALLED
FOR I N COLUMNS 30-46, CARD-TYPE 3

Main
Equi pment
Class Maxi mum M i n i mum &
Trans formers 101 97 100
C i r c u i t Breakers 176 161 171
Motor S t a r t e r s 88 88 88
Motors 561 (col .36) 493(co1.40) 517
Generators 83( c o l .36) 31(all other) 37
Disconnect Switches 101 100 101
Swgr. Bus-Insulated 20 20 20
Swgr. Bus-Bare 24 20 23
Bus Duct 20 18 20
Open Wire 109 104 108
Cable 223 21 1 21 8
Cable J o i n t s 45 44 45
Cable Terminations 51 47 50
A P P E N D I X A R E P O R T ON RELIABILITY S U R V E Y OF INDUSTRIAL P L A N T S

sources accounted for about half of the initiating causes, with percent) and inadequate maintenance (35 percent) were held re-
exposure to dust and contaminants and a large number of un- sponsible for the failures.
classified items considered contributing causes. Inadequate Bus Duct
operating procedures, inadequate maintenance, and defective
Of the reported bus duct failures, 65 percent were repaired in
components were considered primarily responsible, which
place with the majority of them being repaired on a round-the-
seems t o correlate with over 66 percent of the reported cases
clock basis. 90 percent of the respondents reported some form
not having any preventive maintenance and 21 percent not
of damaged insulation resulting from a flashover to ground.
having any preventive maintenance 24 months prior to the
Mechanical failure, insulation breakdown, and overheating were
failure.
blamed as initiating factors, with normal deterioration due to
Switchgear Bus, Bare age being listed as a contributing factor in half of the cases.
Responsibility for the reported failures varied from defective
Of the reported uninsulated switchgear bus failures, about
components (26 percent), improper application ( 1 6 percent),
two thirds were repaired in place, with a little more than half
to inadequate maintenance (16 percent).
of them being repaired on a round-theclock basis. 79 percent
of the respondents report some form of insulation damage all Open Wire
resulting from flashovers either to ground (79 percent) or be- Of the reported open-wire failures, 70 percent were repaired
tween phases (21 percent). Mechanical failure, Shorting by in place with a little over half involving a round the clock ef-
metal objects, and insulation breakdown were the predominant fort. About half of the failures involved flashovers either to
initiating causes with exposure t o abnormal moisture, exposure ground or between phases and about 25 percent involved other
to dust, exposure to aggressive chemicals, and normal deteriora- electrical defects. In the reported failures, transient overvolt-
tion due to age listed as contributing causes. Interestingly, ages, overheating, or shorting by metal objects were con-
15 percent of the respondents listed misoperation or testing er- sidered the most significant initiating causes, with severe
rors as a contributing cause. 39 percent felt that an outside weather and exposure to aggressive chemicals being the pre-
agency was responsible for the failure, while 22 percent blamed dominant contributing causes. 81 percent of the respondents
inadequate maintenance. indicated that no preventive maintenance had been performed
in over two years, which supports the fact that over a third of
Switchgear Bus, Insulated
them blamed inadequate maintenance as being responsible.
Of the reported insulated switchgear bus failures, essentially
all were repaired in place with over two thirds of the repairs Cables
being completed on a round-theclock basis. 90 percent of the The relative importance of primary cable was again indicated
respondents reported insulation damage resulting primarily by about two thirds of the reported cases making repairs on a
from flashovers to ground and between phases. Insulation round-theclock basis. There were a few more reported cases
breakdown was considered t o have initiated the failure in about where repairs to cables were made by complete replacement
half of the cases, with exposure t o contaminants, moisture, rather than by in-place repairs. About three quarters of the
severe weather, and normal deterioration from age being con- failures involved flashovers to ground, resulting in insulation
sidered as contributing factors. Improper application (45 damage.

162
IEEE-IAS TRANSACTIONS MAR/APR 1974

2
0
m

SNOIlVNIW831

SlNIOP
31av3
I-
% 2 0
1
W N
mcu
N
N
0

ww Io 0
W N

38IM N3d0 mw 0
*(u

i3no
sna 82 *
38va ---
w o w 0
-Sna 8V33H31IMS
a 3ivins N I +-
*
*m

o m *
- Sfla 8V33H31IMS m O1 h(u
0

S3H31IMS 00 0 0
N W
133 "03s Ia
S801VU3N33 e-*
W N 0 0

I SUOlOW m e N 0
N h

S8318VlS we- 0 0
UOlOW W m

I m N
h N
m 0

1 S83WUOdSNVUl
-m
me-
e- 0

I S3IlddnS 83MOd
AlIlIln 31813313
-01
m
0 0
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

I
.u I I 2

--ij
o c u m o o 6 o o o o

=
-cu w 0 0 -10 0 0 0 0 0 0

m
01

0 el0 0- -Ii- 7d
00
co
0-
,l
o o e mlm 0 0
4
mmoloc
cue-cu

--4 4
m o l n o o o o o o o

0 co 0 00 010 00

- Sfla
aiiwinsN1
8V33H31IMS
o m mI o c
-om
0m o I0 0 0 mlo
01
00
4
133NN03SIa
,
,,i
,,
h 0 OIcu
I
PI e 01-0 0
-1 4
NPIQIcuC
cum-I
P I P I W O C
w--1

I S3IlddllS 8 3 M O d
AlIlIlfl 3 1 8 1 3 3 1 3
*
ecoculmc
mmcu

m e
I

164
IEEE-IAS T R A N S A C T I O N S M A R / A P R 1974

S N O I l V N IWtl31
31av3
n
L SlNIOr
-~
Vi-PIrnb
318V3 I -
3tlIM N3d0 b
0"
0rnIul N
-

3
000~00
h0

m .
J
.. -
4 3tlV8 m-0100
hN
+
- S n 8 tlV39H31IMS
.-
a3ivinsNI rnrn000
- Sn9 tlV33H31IMS . _
S3H31IMS rnbhbl-
133NN03SIa -
m0mNul
Stl O l V t l 3N33
. -
stlolow . _
C0bNl-W

Stl31tl V I S born-0
11 O l O W
.-
Stl3XV3119
I In3tl I 3 . -
Stl3WtlOj S N V t l l

165
APPENDIX A R E P O R T ON RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

I I
ooco m ~ o o o 3 e
SNOIlWNIWd31 - m N 7

3iaw3
SlNIOr 0 0 0 0
L n
CQOLnINLc
- n

-
38wa
S f l f l 8W35H31IMS
W m o d
-
h NON'hrn
N NI-

I
I
S 3 I l d d f l S U3MOd coo0 0 O W h N a 3
r-mm
I

166
IEEE-IAS TRANSACTIONS MAR/APR 1974

.-$ r u
m m
S C
.r .C
c N

>
C
c
+a
4
c
Q
r
+
.r
t-

a
r
In:
+

-
SNOIlWNIW83I
31av: -
SlNIOl 0 0 0 0 002
31aw:
-
319v: 0 - m e 0 N O 0 0 0 0 0
- N NN 7

3811
N3dl
1 10
N
0 -Nm h 0 0
7
e m 0 0
-
-1
0 0 -

13n1 1 0 ooom 0 0 m o o 0 0001


sn: m N e

38V'
- Sfla MV33H31IM
-
a3ivinsN Ln 0000
m-
0 0 0 0 0 0 oom
CI)
-Sn9 UV33H31IM
S3H31IM
133NN03SI
S8OlVM3N3
stlo10
Stl3lMVl
8010
S83IV3M
lIIl3tlI
Stl3WtlOdSNVM
S 3 I l d d n S 83MO
AlIlIlll 3181337
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

W
m
-I

;
I
.-
SNOIlWNIWt131
319w3 -
SlNIOP
319w3
.-
319w3
3tlIM"
-
N3d0

------A-
-----%E/ -
- Sn9
---GiKq
-Sn9
tlV33H31IMS

tlW33H31IMS
- oLno'ou,oo

I
?
00
NN
000000
I
d

COm-lOdOO u,o o o o o g ~
I I
o a o l o ~ m oN m a o O O O N
St101Vtl3N33 . - 7 m 1 -
stl O l O W V)-OlhOON ZN Om-lOmW
-
. _ 7
~~

stl31tl V I S ooo/oooo 00 0NOlW-m


tlO1OW e u,
.- I

st13xv3tla I
e-oNmOO b- N-0 mu,
iIn3tiI3. _ u,

SI3WtlOJSNVtll
S 3 I l d d n S tl3MOd
. -
- I
m O O O ~ O O
I
za o o o m m e
j d

"""p""
( y ~ 0 0 N 0 0
AlIlIlII 3Itl13313 , 1

168
IEEE-IAS TRANSACTIONS MAR/APR 1974

V
I
W
c -1
LO
c1
m
p:
W
3
I-

9 SNOIlYNIWN31 bp 2 cu o o o N O 0
V 3iav3
W
CL
3
SlNIOP bp o o o o o 000
-I
U
LL

I
3 i a n
3 i w
jtlIM
= -
h h 0 0 o *oo

bp 0 0 0 0 0 000
*
7
N3d0
W
-I
m 13na bp 0 0 0 0 CI 000

z-. sna 7

3yva bp w 0 0 w 0 ooc
-Sn8 tlW39H31IMS

I -sns 1v39H311MSi i
a3ivinsNI bp ~ l n 0 0 0 000

I SIlOlOWl "I O O O O O
000

Stl3lNVlS " 0 0 0 0 0 000


tl0lOW
stl31v3tla
iIn3tlI3
bp 0 - - 0 0 000

169
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

>
C
a
4-
(F
c

a
F
n
I-

SNOIlVNIW1131
31av3
> 1
""2
W
100

SlNIOr 000000 We0 00


31av3 I QI

3iav3 000'000 In" ern-

311 I N I
000000 ON- Worn
N3dO I W N

i3na
sna -
omoooo
I
m
W m o Lno

I
3YVB 000000 --o 00
-Sna UV39H311MS h-
I
a 3 i v i n s N I 000000 m o o 00
- sna ~ V ~ ~ H ~ I I N S I W

S3H31INS 000000 wornw W?


W -
133NN03SIa
SUOlV113N39 0 0 W 0 0 0 goo gs
000000
s1101ow I z-8 00

SU 3 I d V I S
dolow
S113IV3d9 u7cnNLNN 0-? 00
1 1 n311I 3
S113WdOJSNVYl
N
S 3 I l d d f l S 113MOd 1
0-0000 000 00
A l I l I l n 311113313
I
IEEE-IAS TRANSACTIONS MAR/APR 1974

An interesting point is that in over two thirds of the failures initiated by an insulation breakdown, with normal deterioration
there had been no preventive maintenance, yet inadequate due to age, severe weather, and exposure t o abnormal moisture
maintenance was only listed in 10 percent of the cases as being or aggressive chemicals contributing significantly to the prob-
responsible for the failure. 16 percent placed the responsibility lem. 39 percent felt that inadequate installation and testing
with the manufacturer, 14 percent with inadequate installation prior to start-up was primarily responsible, while 22 percent
and testing prior t o start-up, with 38 percent of the cases re- felt that inadequate maintenance should be blamed. This also
porting reasons for the failure in classes other than those listed seems to correspond to the reporting that in 40 percent of the
in the survey. cases no preventive maintenance had been performed in over
The initiating causes varied from transient overvoltage two years.
disturbances to insulation breakdown, to mechanical failures,
with 30 percent reporting normal deterioration from age as a GENERALCONCLUSIONS
contributing cause.
Electrical Equipment
Cable Joints The general picture from Tables 38 and 35 spotlights in-
Of the failures reported, 87 percent were repaired in place, adequate maintenance as a significant factor in the suspected
with just over half being repaired on a round-thezlock basis. responsibility for failures. Yet the owner appears willing to
Almost all of the failures resulted in damaged insulation, pri- work round the clock to fuc failures after they have occurred.
marily from flashovers t o ground, which were initiated by in- Lack of cleaning and lubrication is apparent on disconnect
sulation breakdowns, transient overvoltages, or mechanical switches, buses, open wire, cable, cable joints, cable termina-
failure. tions, and motors.
29 percent of the respondents felt that normal deterioration
from old age contributed to the failure, while 35 percent Electric Utility Power Supplies

-
blamed abnormal moisture or exposure to aggressive chemicals. Many of the results shown in Tables 33-38 are not really
Inadequate installation and testing were considered responsible applicable for electric utility power supplies because the
for 50 percent of the failures. 60 percent of the respondents questions asked are not well suited. The importance of the
reported that no preventive maintenance had been performed, utility supply was indicated by 91 percent of respondents
but only 18 percent blamed the failure on inadequate making repairs on a round-theclock basis. The failures were
maintenance. predominantly flashovers involving ground, caused by lightning
during severe weather or by dig-ins or vehicular accident. Out-
Cable Terminations side agencies, probably the local utility, were predominantly
Of the reported cable termination failures, 60 percent were responsible for the failure with preventive maintenance having
repaired in place with just over half of the repairs being made no apparent effect on the cases reported.
on a round-the-clock basis. The primary damage was insulation The data reported under “failure characteristic” in Table 41
involving either a flashover to ground or other electrical de- are of special significance in the case of double- or triplecircuit
fect. About half of the respondents felt that the failure was electric utility power supplies. In particular, the failure rate can

TABLE 42 - SIMULTANEOUS FAILURE OF ALL CIRCUITS


I N ELECTRIC UTILITY POWER SUPPLIES

U t i l i t y Power Supplies -
Failure Characteristic
a b l e 41 Failures from T a b l e 41

3. F a i l u r e o f both c i r c u i t s
of a d o u b l e - c i r c u i t
redundant supply

4. Failure o f a l l circuits o f
a t h r e e o r more c i r c u i t
redundant supply

T o t a l n u h e r o f simul-
taneous f a i l u r e s o f a l l
c i r c u i t s i n a double o r
more c i r c u i t redundant
supply

171
A P P E N D I X A R E P O R T O N RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

be calculated for the simultaneous failure of all circuits in a Table 36: The damaged part of one percent of failed circuit
double- or triplecircuit electric utility power supply. breakers is a tap changer. The damaged part of three percent
From Table 3 of Part 1 [ I ] the sample size is 210.7 unit- of failed cables is a bearing. Winding insulation is shown as the
years for a double- or triplecircuit electric utility power supply. damaged part in failures of cables, bus ducts, and motor
A double- or triplecircuit supply operating for one year is starters.
counted as one unit-year. It is possible to calculate a failure Table 39: Three percent of the failures in disconnect
rate from these data as follows: switches were initiated by low voltage.

~-
25 - 0.1 19 failures per year for simultaneous failure REFERENCES
210‘7 of all circuits in a double- or triplecircuit [ 11 1EEE Committee Report, “Report on reliability survey of industrial
plants, Part I: Reliability of electrical equipment,” this issue.
electric utility power supply. pp. 213-235.

Some discrepancies were found in the data on the number of


installed units for double- and triplecircuit electric utility
power supplies. See the discussion in Part 1 [ I ] on this point.
Discussion
Discrepancies 1. Krasnodebski, N. M. Thompson, D. H. Cooke, A. W. W. Cameron,
S. Basu, and T. 1. Ravishanker (Ontario Hydro. Toronto, Ont., Canada).
A survey such as this one often obtains some data that ap- 1) Qunlrty of Input Dora The confidence level of data in a survey
pear t o contain errors. Sometimes the results look ridiculous. of this kind cannot be assessed by mathematics only. One key prob-
However, some of the ridiculous looking results may actually lem is the adequacy of records and completeness of data. Some of the
be correct. Some of the errors are believed due t o a mis- apparent discrepancies noted in the paper seem to indicate quite sub-
interpretation of the question by the respondent. stantial omissions in records. Unless the industries involved keep much
better failure records than we have done to date, this is not surprising.
The data in Tables 31-41 have been published without at- The first requirement of a useful reliability program is an adequately
tempting to correct discrepancies or errors. A brief list of complete and accurate system for recording failures and consequences
some possible discrepancies is given. (in outage terms).

TABLE A
GENERATORS

Forced Outages

EEI R e p o r t

Number of
Sample Size Occurrences Outage Hours
(unit-years) per Unit-Year per Occurrence

204 0.142 91.8


4 04 0.839 126.5
705 0.521 54.4
483 0.393 125.6

IEEE Reliability Survey

Number of
Sample Size Occurrences Outage Hours
Type of Drive (unit-years) per Unit-Year per Occurrence

Steam turbines* 7 6 1.8 0.032 165.0


Jet engines
Gas turbines 89.4 0.638 23.1
Diesel engines 59.4 0.067 127.0

* E E I results a r e f o r generators 60-89 Mw.

172
IEEE-IAS T R A N S A C T I O N S M A R / A P R 1974

The requirements for better records, along with the detall involved in sembling and correlating the mountainous volume of data in a simple,
the report forms, indicate that acquuing useful data of this kind is time easy to understand tabulation. I would like to add some discussion
consuming. that I feel would help the value ef these tables and add to the accuracy
It is suggested that, d a choice is necessary, i t might be preferable to of future studies. My two main points are 1) the downtime per failure
have a limited (but statistically adequate) number of plants establish a (111 a single-circuit utility supply is extremely high (possibly by a factor

reliably complete recording and reporting system rather than increase of five), and 2) the equation for the dollars lost per interruption may
the sue of the sample under current record systems. be improved by using other than the kilowatt demand and kilowatt-
2) Survey Results on Equipment Failures The failure rate is given in hour usage as bases.
failures per unit-year. Is year in this context a calendar year or 8760 My company gathers, codes, and analyzes by computer all inter-
hours of plant or equipment operating time? If the failure rate is given ruptions t o our three quarter million customers. The average down-
per calendar year, were adjustments made for plants operating for 4 0 time per customer on our distribution system (which is a single-circuit
hours per week against those operating for up to 168 hours per week? radial supply) has been between 5 1 and 61 min for five of the past
3) Discussion of Equipment. six years. Our service area experienced a catastrophic storm during
Motors: It is suspected that the discrepancy in fadure rates results 1969 which caused the average downtime per customer to jump to 124
from the different application of the two types of motors. Synchronous min. In addition, my company is of the opinion that no plant
motors are usually applied only in engineered situations and are care- should be down for more than 4 h earring major catastrophies). A
fully designed for the application. Large synchronous motors are report is therefore written for each interruption exceeding 4 h in dura-
usually slow speed. Induction motors are mass produced. purchased off tion, and these reports are extremely few in number. Furthermore, 13
the shelf at the lowest cost, and usually operated to take advantage of utilities have polled their reliability statistics for customers fed from the
any service factor. The survey figures are probably correct but cannot distribution system and found the average downtime per interruption
be used for comparison of reliability, leading to a conclusion that for 1971 to be approximately 1% h long. The average downtimes
synchronous motors are more reliable. I t is a comparison of apples and ranged from 0.75 t o 3.2 h.
This information Ahows that the downtime per failure for industrial
oranges.
Switchgeor Bust The paper states that the reported data are the plants is probably outside the predicted tolerance on the IEEE data.
opposite t o what they should be. The reported figures may be correct. This variance may be due to either a major long disturbance affecting
Manufacturers regularly reduce the spacing between buses and the a majority of those industrial plants participating or t o misinterpreta-
spaces between phases and ground when they use insulated bus. As the tion of the information requued.
conductor insulation is usually also reduced by design and occasionally For over five years I have worked with our customers in regard to
by inferior material standards compared to that on insulated cables. and reliability problems. My experience has shown that the plant invest-
workmanship is frequently less than perfect, failures on this type of ment, labor cost, and v J u e of product is a better gauge of the cost per
gear are probably at least as common as those on air-insulated minute down than would be either maximum kilowatthour demand or
equipment. usage. For example, I worked with a manufacturer of magnesium parts
Circuit Breakers. The fadure rate for cucuit breakers appears much for mllitary aircraft (1 will call this plant A ) and another manufacturer
too low. I t must of course be a function of the frequency of opera- of parts for conveyor systems (plant B ) . The dollar loss for A per
tion as well as lapsed time. We did not find a definition of circuit minute down was 100 times greater than that for B. However, plant
breaker fadure, which we believe should differ from cable, transformer, B’s demand is 2500 kW and A’s demand is 500 kW. which is an in-
or other static device fadures. Circuit breaker fadures should be based dication that the kilowatthour consumptions in these particular cases
on fadure to operate satisfactorily either to remain closed or to open are not related at all t o the economical loss due to a power interruption.
or to close when called upon. I t should be clear whether these figures In general I find that the cost of downtime is tied heavdy to one of the
include failures caused by ausiliaries such as instrument transformers. following: 1 ) the number of employees, 2) the cost of the product in
relays, and control switches. Since any calculation of the reliability production (piecework), or 3) the dollar output per hour (high produc-
of a power system would be made unreasonably complex by attempts tion). A combination of these three items would indicate that loss I S
to treat all these devices individually. a figure for cucuit breaker failures tied to the dollars out of the plant per unit of time. Therefore I feel
which includes them is usually required by the designer that future studies should relate downtime t o dollars per minute of
Generators. For the generators in the electrical power industry a plant production. gross plant, etc.
good source of data exists in the EEI “Report on Equipment Avail-
ability for Twelve-Year Period 1960-197 I .” The comparison between
the failure rates and average repau time contained in that report and
J. W. Beard (Union Carbide Corporation, South Charleston, W. Va
the survey discussed are shown in Table 43 EEI data quoted for
steam turbine driven generators are for the sue class 60-89 MW, which
25303): The report format and the manner in which the information
is probably larger than the average sue of a corresponding generator in- is presented is generally quite adequate. Appendix A (Part I ) IS some-
what difficult to read because of the reduced print, but I am not sug-
cluded in the industrial survey.
gesting it be upgraded for this report. Because of the many and various
I t can be seen that the EEI failure rate for steam turbine driven pen-
pieces of data used for the report. i t 1s understandable that the reader
erators based on forced outages is higher by a Factor of 5 than in the
must spend a great deal of time in studying and analyzing the informa-
industrial survey. For gas turbines, fadure rates contained in both
tion in order t o properly apply it. The “readily” understandable factor
reports are of the same order, while the outage duration quoted in the
should perhaps be given niore consideration in defining the criteria for
EEI report is higher. 5 4 failures in 5.5 unit years in the petroleum in-
future surveys
dustry can probably be explained by the start-up troubles
It is my opinion that the most useful types of lnformation presented
In summary. experience in the utility industry seems to explain
are.
results obtained in the industrial survey to a large degree
4 ) Causes of Failure 1 ) failure rate and failure rat? confidence limits;
a ) How important is the age of equipment’! I t is mentioned only 2) failure, damaged part;
a \ a “contributing cause,” second in frequency only to “other.” 3) failure type:
Are there economic replacement times. or does obsolescence usually 4) failure initiating cause;
come f l r S t 7 5 ) failure contributing cause;
b) Should the inference be drawn that reliability of industrial 6) failure characteristics.
equipment. which is reasonably well suited to its lob. depends mainly
on 1) stringent acceptance testing. especially overvoltage testing, I believe it is a good assumption that the raw data submitted for
2 ) adequate cleaning. and 3) proper lubrication of bearings? many of the other types of information represented were of much lesser
5 ) Additional Suggestions f o r Analvsis Consideration should be accuracy than for these. For example, most plants reporting data
given to add the manufacturer of the main class of equipment to pro- for information types such as plant outage cost, critical service loss
vide information on reliability ot.ddferent manufacturers. duration, and loads lost versus time of power outage probably had to
draw on someone’s memory of each failure and then apply the “best
Carl Becker (Cleveland Electric Illuminating Company, Cleveland, Ohio estmate” principle. This factor alone raises the question as to whether
44101): The Reliability Subcommittee did an outstanding job in as- these types of information can ever be constructed to have useful

173
APPENDIX A REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

meaning. Except for near catastrophic fadures, which result in heavy m the investigation of most equipment failures, and IEEE could per-
financial losses, it is doubtful that most plants will spend the money form an important service to industry by developing a socalled “evalua-
to document this type of data. Furthermore, in a practical sense, when tion of possibility of transient overvoltage contribution to equipment
configuring systems and applying electrical equipment. the reliability failures” guide.
requuement must be carefully considered for each producing unit
served inasmuch as there are many variables that enter into the cal-
culation of downtime losses. Stanley Wells (Union Carbide Corporation, Port Lavaca, Tex. 77979):
The following suggestions are offered for consideration in any future The Reliability Subcommittee should be congratulated for performing
surveys. such a comprehensive reliability survey of industrial plants and for pro-
1) Basically concentrate on fiulure rates and failure causes. viding a very thorough report.
2) Simplify and reduce scope of the survey questionnaue forms I would like t o limit my discussion to Part 3 and, in particular, the
(present forms tend to scare users from contributing). preventive maintenance effect on the failure rate. A preventive main-
3) Omit asking for types of information such as cost of outage, repau tenance program can very definitely have a direct effect on the failure
time, plant start-up time, etc rate of electrical equipment. In the modern automated plant of today,
4) Instruct usersnof to report failures of equipment where reasonable production demands and losses associated with downtime mfluence
preventative maintenance is not performed. maintenance schedules. Equipment is often allowed to remain in op-
5 ) Instruct useisnot to report failures of misapplied equipment. eration for periods that exceed desired preventive maintenance time
6) Instruct users not Io include equipment installed prior to Jan- schedules. It is interesting to note that the survey indicates that pre-
uary I , 1968. ventive maintenance can be performed, yet equipment failures occur
7) Instruct users to give “in-service” date (energued) of all equip- within a tune period which is less than 12 months since preventive
ment units, not just on the reported failures. maintenance was performed. Our first attempt at a preventive main-
8) Define “failure” as “damage to equipment sufficiently severe to tenance program met with the same results. The program was reviewed
force an outage by either manual or automatic removal of voltage.” in depth and it was found that it was inadequate and that the preventive
(Keep in mind that failures caused by the conditions in 4 ) and 5 ) are maintenance procedures and time schedules should be reviewed and
not to be reported.) correlated with our failure experience. As experience was gained, the
Part I There seemed t o be a gieat deal of confusion by the respon- equipment preventive maintenance program developed into a very
dents on the information desired for electric power supplies. Thus the useful tool to practically eliminate electrical equipment failure. We
published failure rates may be questionable. I t is my opinion that the won recognized that where preventive maintenance periods were over
questionnaue form for this was too nondescript. Perhaps one way to 24 months or where no preventive maintenance at all was performed,
clearly describe the power supplies on which information IS desued chances of failure were extremely high. This fact is born out in the
would be to include on the form simple single-line diagrams of the more results of this survey. Table 35, “Failure-Months Since Maintained,”
common types of utility services has been rearranged to show that a large reduction in failures may be
I t is my opinion that the lack of response by many companies was
possible if preventive maintenance periods are on a 12- to 18-month
due primarily to poor andlor nonexistent records. A major contribut-
basis (Table B).
ing cause may have been the massive amount of information asked for.
Let’s define preventive maintenance. Preventive maintenance is a
The Reliability Subcommittee’s judgement that a minimum of 8 to 10
system of routine inspections designed to minimize or forestall future
observed failures was requued for “good” accuracy when estimating
equipment operating problems or failures, and which may, depending
equipment fadUrK rates seems reasonable.
upon equipment type, require equipment exercising or proof testing.
The value chosen for the confidence interval ( 0 9 0 ) uas a good
From this definition, the four following items listed under Table 38,
choice. The inclusion of confidence limits curves (Fig. I ) adds mea-
“Suspected Failure Responsibility,” can be considered a definite part
surably to the report.
of a maintenance program:
I generally concur with the Subcommittee’s discussion comments
Theu discussion of yome of the results presented in the tables rein- 1) manufacture, defective components (locate by inspection or test);
forces my feeling that the survey was too broad in scope, and the in- 2) application engineering, unproper application;
1.orrnation submitted by the plants too ambiguous for meaningful 3) inadequate installation and testing prior t o start-up (proof test);
interpretation. 4) inadequate maintenance.
Whde the sample sues would be made mailer, as a general rule 1 feel
that equipment should be grouped by voltage c l a ~ .For example, in It is interesting to note that the survey indicates that these four items
are responsible for a very large percentage of failures. The total for
Table 2 one grouping of cable terminatlons 15 for 601-15 000 V. In
each category is listed below.
this instance it would be especially helpful to know the failure rate on
15-kV cable terminations alone
Part / I As stated in my general comment,. 1 feel that i t is not prac-
tical to generate reasonably accurate informrtion of these types. Percent
The bases for the units used in cost calculations. dollars per kilowatt
plus dollars per kdlowatthour, are somewhat contusing Clarification Transformers 55
of this would be helpful. Circuit breakers 53
In the Subcommittee‘s discus\ion of the cost of power outages, Motor starters I1
item 2), I must disagree w t h their thought that electrochemical or Motors 42
heating processes tend t o have low outage costs because heat not sup- Generators 41
plied now can be supplied later. Disconnect switches 52
In the discussion of loads lost versus time of power outage the ”time” Switchgear bus insulated 95
factor is questionable Most plant\ are not equipped to measure short- Switchgear bus uninsulated 52
duration power outages (cycles or even seconds). Bus duct 63
Parr 111 Many of the information types in this part are very impor- Open wire 41
tant. Some, I feel, are not 1 suggest that the questions on failure Cable 48
repair method, failure repair urgency; failure. months Since mainte- Cable joints 68
nance; and suspected failure responsibility be omitted from future
Cable terminations 79
surveys The remdining types of information may be refined using
knowledge gained from this survey
In the Subcommittee’s Summary of Conclusions they report that
transient overvoltages were a major cause of fadure in equipment such To increase the electrical system reliability, each failure should be
as, for example, transformers and cucuit breakers; but I got the im- very carefully analyzed to determine the failure cause, and corrective
pression that much of this was speculation on the part of those re- action to prevent additional failures should be applied t o all applicable
sponding. The possibility of transient overvoltage should be considered equipment.
IEEE-IAS T R A N S A C T I O N S M A R / A P R 1974

TABLE B
FAILURES

Less than 12 Months or More


12 Months Ago or No
Preventive Preventive
Maintenance Maintenance

Transformers 34 65
Circuit breakers 18 81
Motor starters 67 33
Motors 22 78
Generators 58 42
Disconnect switch 8 92
Switchgear bus insulated 10 90
Switchgear bus uninsulated 35 65
Bus duct 25 75
Open wire 1 98
Cable 11 89
Cable joint 18 82
Cable terminations 12 88

R. E. Kuehn (IEEE Reliability Group): The reliability. maintainability, switchgear bus. My quandary is that if I accept your Judgment in all
and downtime logistics in the power area is very important and should logic. I must question the validity of all the data collected, not just for
lend itself to cost analysis, which is the ultimate Judge of the value of motors. generators, cable, and switchgear bus. A possible procedure
reliability and maintainability programs. A great deal of data have been would have been t o test the hypothesis that a part of the data was
analyzed with all the obvious advantages and disadvantages that aTe significantly different enough from the total grouped data t o justify its
entailed in such a data base. Parts I and 2 present me with a severe rejection as part of the group data.
problem as a reliability professional and manager. In both papers a I would like to recommend analysis of variance or multiple regression
large effort was spent indicating that the survey results do not agree m analyzing the data. I t would appear that a number of possible
with what the engineering judgment says the results should be; for variables exist and their effects are suitable for quantization. n e s e
example, the discussion of Part 1 on motors, generators, cable, and procedures are covered in [ I ] - [ 4 ] .

REFERENCES
(1) R. G . Stokes and F. N. Sehle, “Some life-cycle cost estimates for
electronic equipments,” in Proc. I968 Annu. Symp. on Reliability,
pp. 169-183.
[2] B. L. Retterer, “State of art assessment of reliability and maintain-
ability as applied to ship systems,” in Proc. I969 Annu. Symp. on
Reliability, pp. 133-145.
[3] H. Dagen, “Multiple regression,” in Proc. I972 Annu. Symp. on
Reliability,” pp. 51-58.
[4] “Cost effectiveness evaluation procedures for shipboard electronic
equipment,” ARINC Research Publ. 509-01-2-564 and 541-01-
1-766.

175
APPENDIX A R E P O R T ON RELIABILITY S U R V E Y OF INDUSTRIAL P L A N T S

Tai C. Wong (American Electric Power Service Corporation, New York. the failure rate. The assumption of a constant failure rate with age can
N.Y. 10004): The members of the Reliabllity Subcommittee are to be be justified for most electrical equipment based upon reliability surveys
commended for conducting and analyzing the results of a survey that made by others.
covers so many elements in industrial power systems. Mr. Becker and Mr. Beard have raised questions about the accuracy of
Perhaps the authors want t o clarify why the chi-squared distribu- the cost of power outage data and the attempt t o relate it to kilowatts
tion was used in fitting the data and what kind of statistical testing and kilowatthours. Information was collected but not published on the
technique was employed t o ensure the adequacy of the distribution estimated plant outage costs 1) per failure and 2) per hour of down-
chosen. The authors did compare the results of the recent survey time. The authors consider that the cost of power outages is an im-
against those obtained in 1962. The readers should be warned that portant factor that should be considered in the design of power
this is only an observation based on empirical data and that any in- distribution systems for industrial plants. Since power distribution
ference of a trend in the equipment reliability may not be valid. The systems are designed on the basis of kilowatt capacity and kilowatthour
paper indicates that many of the reported data cover more than one of delivered energy. it was felt that it is necessary to attempt to relate
year of operating experience. Because the first survey was conducted the cost of power outages to these two parameters. The approach used
twelve years ago, it is felt that the number of years that the different by the Reliability Subcommittee is the same as that which has been
equipments were in service should be published (or the data collected used by electric power companies in several European countries. The
during the next survey if they are not yet available) so that the reader survey result of the median cost of 83/ per kilowatthour of unde-
can have a better understanding of the data background when he has to livered energy is In the same range as values obtained from surveys that
draw further conclusions, beyond the tables presented. have been made in Sweden, Norway, France, Italy, and West Germany.
The authors indicated that the purpose of this survey is to make pos- The authors agree that the published data of the cost of power outages
sible the quantitative reliability comparisons between alternative designs are more meaningful if related t o specific types of plants.
of new systems and then use this information in cost-reliability tradeoff The authors acknowledge Mr. Beard’s suggestion that a one-line
studies t o determine which type of power distribution system to use. diagram should be used in the survey of the electric utility supply. A
It appears that the authors focus on making the economic tradeoff new survey of the electric utility supply is being started.and MI. Beard‘s
comparisons based on the available system components a t a given time. suggestion wlll be included. This new survey should clear up the prob-
However, the authors pointed out that the product of failure rate times lem of the questionable accuracy mentioned by MI. Beard. The au-
the average downtime per failure is almost the same in 1973 as in 1962. thors acknowledge Mr. Beard’s comment questioning the accuracy of
Perhaps the equipment manufacturers and the industries can establish the “time” factor in loads lost versus time of power outage in Table 30.
more dialogues, leading to an answer to the following two questions. In answer to several questions raised by MI. Krasnodebski, the au-
1) Should the equipments have a lower failure rate, but when failing, thors make the following comments.
take longer t o repair? or 1) The failure rates are based upon a calendar year of 8760 h,
2) Should the equipments have a higher failure rate. but when failing, not upon an operating time, which could be lessand would thus result
need shorter repair time? in a higher failure rate than reported in the survey.
In a few instances during the survey, the respondents misinterpreted 2) The failures of circuit breakers are meant to include the auxiliaries.
either the question(s) and/or the definition of the terms, thus leading 3) The failure modes of circuit breakers are included in Table 41;
to unreliable or biased results. This is especially true in the area of this includes “fail t o close,” “fail t o open,” etc. However, data were
preventive maintenance. I might suggest that during the next survey not collected on the number of circuit breaker operations.
I ) the definition of all terms that are likely to cause confusion in the 4 ) The Reliability Subcommittee does not consider that it would be
questionnaire be included, 2) a pilot survey be instituted and any neces- appropriate for a technical society such as IEEE to collect and publish
sary modifications be made t o the questionnaire before a full-scale reliability data by name of manufacturer.
survey is launched, or 3) the survey form he sent out without request- 5 ) The authors agree that better record keeping of fadures would
ing data, but instead requesting the respondent’s interpretations of the improve survey results It is expected that future surveys will cover
questions and the terms used. Then the survey form may be redesigned only a few categories of electrical equipment that are considered
and data requested. trouble areas.
6) The authors acknowledge the logic in the very interesting com-
1. 0. Sunderman (Lincoln Electric System, Lincoln, Nebr.). The au- ments made on synchronous motors and switchgear bus and generators.
thors have presented an interesting cross section of costs involved with 7) The steam turbine generators in industrial plants probably have
industrial electric equipment downtime as accumulated by the com- constant operation and thus could be expected to have a much lower
puter. The data are to be utilized by interested parties in the choice
failure rate than 60-89 MW units in utility applications where the
of a reliability design for industrial power distribution systems. The
operation was cyclical.
wide range of costs as split into the two parts over 1000 kW and under
The authors wish to thank Mr. Kuehn for his suggestions in analyzing
1000 kW suggests consideration of other kW brackets at 500, 2500,
the data. These suggestions included 1) test hypothesis that part of
5000, 7500, 10 000 kW, etc. The sufficiency of data will dictate
data can be rejected, and 2) analysis of variance or multiple regression.
breaking points, as the author already questions the cost data below
MI. Becker has raised a point where this approach for analyzing the data
1000 kW.
could possibly be tried. Mi. Becker feels that the survey results are too
In Part 3 the authors have reviewed and presented in excellent tables
high on the downtime per failure of a single-circuit electric utility
the results of electric equipment outage reports and repair. I t must have
been disturbing t o note the numerous “other than categories classified.” supply. This may be true for his system, but perhaps other utilities are
not as good as his company’s system.
Perhaps further reporting on the “other” category comments, if avail-
Mr. Wong has raised a warning about drawing the conclusion that
able, would bring additional results t o light.
equipment reliability has improved since the previous survey con-
IEEE Reliability Subcommittee: The authors wish t o thank those who ducted 11 to 12 years earlier. A separate paper has been prepared on
presented discussions on these three papers. Some of the suggestions this subject and wffl be published in the near future. This paper con-
given can be considered for incorporation into future surveys and they tains the conclusion that the failure rate of electrical equipment has
can also be used in the analysis of the results. shown a definite trend of improvement during the 12-year interval.
Several discussers have raised the question about the effect of “in The authors wish to thank Mr. Wells for his discussion on preventive
service date” or age on the reliability of electrical equipment. Popula- maintenance. A lot more data on preventive maintenance are being
tion data were collected on the average age of equipment in service; processed and will be included in Part 4 . Mr. Wells’ Table B shows
these will be published in Part 4. However, the Reliability Subcom- more failures in the “ I 2 months or more” category than for the “less
mittee did not request these data in the survey questionnaire on equip than 12 months ago” category. The authors would like to point out
ment failures. This subject was considered by the Subcommittee when that the electrical equipment has more unit-years of exposure in the
making up the questionnaire; it was not included because this would “12 months or more” category and thus could be expected to have
have added additional complications to a questionnaire that was al- more failures. Thus it is not possible to conclude that more frequent
ready considered too long. This meant that the assumption was made preventive maintenance will reduce the failure rate. The Reliability
that the failure rate was constant with age. Thus a chi-squared dis- Subcommittee is investigating this subject in further detail and will
tribution is appropriate for use in calculating the confidence limits of publish the results in Part 4.

176
Appendix B

Report on Reliability Survey of Industrial Plants

Part 4
Additional Detailed Tabulation of Some Data
Previously Reported in the First Three Parts

Part 5
Plant Climate, Atmosphere, and Operating
Schedule, the Average Age of Electrical
Equipment, Percent Production Lost, and
the Method of Restoring Electrical Service After a Failure

Part 6
Maintenance Quality of Electrical Equipment

BY
Reliability Subcommittee
Industrial & Commercial Power Systems Committee
IEEE Industry Applications Society

A. D. Patton, Chairman
C. E. Becker C. R. Heising
W. H. Dickinson D. W. McWilliams
P. E. Gannon R. W. Parisian
S. Wells

Industrial and Commercial Power Systems Technical Conference


Institute of Electrical & Electronics Engineers, Inc
Denver, Colorado
June 3-6,1974

Also Published
IEEE Transactions on Industry Applications
Jul/Aug and Sept/Oct 1974
Part 4 pp 456462
Part 5 pp 463466
Part 6 pp 467468,681,469476

Reprinted from pp 113-136


in 74CH0855-71A, the 1974
I&CPS Technical Conference
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

Report on Reliability Survey of Industrial Plants, Part IV:


Additional Detailed Tabulation of Some Data Previously
Reported in the First Three Parts
lEEE C O M M I T T E E R E P O R T

Abstracf-An IEEE sponsored reliability survey of industrial Table 47 lists loss of motor load vvrsus tinw of power
plants was completed during 1972. This survey included 30 com- outage, adding the following length of power outage
panies covering a total of 68 industrial plants in the United States
and Canada. Additional detailed results are reported on some data categorirs:
that were previously reported in the first three parts. This includes 1) 10 to I 5 cyclrs
failure modes of circuit breakers, cost of power outages, critical 2 ) I,?+ to 30 cyrlcs
service loss duration time, loss of motor load versus time of power
outage, and the effect of failure repair method and repair urgency 3) 0.5f t o 2.0 s
on the average downtime per failure of electrical equipment. This 4) 2 +-t o 4.0 s
information is useful in the design of industrial power distribution 5 ) >4.0 s.
systems.
Tables 48 throuyh 56 report t h r effwt r i f failure repair
method and failure repair urgency on the average down-
I K T R O D U C T I O Y S X D RESTJLTS time per failure for the follon.ing equipnwnt cateyoriw:
ERIN(; 197’2 the Reliability Subcommittee of the 1) transfrmnrn -liquid filled
D Industrial and Conlmercial Power Systems Com-
mittee completed a reliability survey of industrial plants.
a ) 601 i.io00 ir
1,) ah,vt. 13 no0 I’
This paper presents P a r t IV of the results from the survey. 2 j rircuit hrrakrra--nit,tal(lad drair o u t
T h e first three parts [1]-[3] were published previously. a ) O--tjOO V
Sonip of t h r d a t a in the first three parts caused questions b) ahove (in0 V
to be raised about t h e possibility of obtaining additional 3) motors
details. These additional details are being reported in this a ) induction, 0 600 I‘
paper a n d include t h e following results. h ) induction, 601-15 OOO V
Tubk 4.3 gives failure modes of circuit, breakers, in- c ) synchronous, 601-15 OOO V
cluding 4 1 rable
a ) ahovr ground and arrial. (io1 1.5 OOO 1’
~

1) metalclad drawout, h) twIo\v ground and dirwt burial, 001-15 OOO V


a) &600V
h ) 60lLl5 OOO V In each of the Tahlrs 43 through 56 reftwnw is made
c) all voltages to the tables in Parts I , 11, and I11 ivhrrt. lirrvior~sr w i l t s
2 ) fixed type (includes molded caso) had beeu rc.portrd.
a ) (r6OOV 1)1SCLISSlOS--I~AI l,tiltlC .\IOI)ES ()E’
b) all voltages. <‘IRCl J IT 13 K E A I< B ItS
Tables 44, 45 give cost of power outages, adding 25 T h e d a t a on failure rnodes of circuit brrakcm given in
and 75 percentile d a t a t o what was previously published. Table 43 s h i m sotne very interesting results.
Table 46 gives Critical service loss duration time (maxi-
m u m length of power failure t h a t nil1 not stop plant Carcuit Hreukers, 0 BOO 1’
production), adding 10, 25, 7 5 , and 90 percentile d a t a t o 71 pvrcent of the failurrbs o f tnetalrlad drawout circuit
what was previously published. breakers ware “opened when it shouldn’t” versus 5 percent
of t h r failurrs for fixed-typt. circuit hrtsakers (inc1udt.s
nioldcd case), 77 percrnt of the failurcs of fixcd-type
Paper TOIb74-33 approved by the Ilrdustrial aid (hinmervinl circuit hrrakrrs (includes niolded case) were “failed while
Power Systems Committee of the IEEE Industry Applications
Society for presentation at the 1974 Industrial and Commercial operating (not while opening nr closing) ,” a n d onlj 10
Power Systems Technird Confereirce, Ilenver, Colo., Jiriie 2 4 . percent of the nietalclild drawout failures includrd this
Manuscript released for publication April 15, 1971.
Members of the Ileliability Suhctmmittee (rf the IEEE Iiid~rstrisl failurc. mode.
and Cominerrid Power Sghtenis Committee are A. 1 1 . Pattnii, Soric. of thc failures rtiportrd for either typ? of circuit
Chairman, C. E. Berker, W. H. I)ickiriaori, P. k;. (;niimui, C . JI
Heking, D. W. RlcWilliains, K.W. Parisian, aitd S. Wells. breaktxr were “failed while opening.” Only 9 percent arid

178
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

7- ~
o c
r n
?
o
c
c
4
c , o

.C
v
c
*
W

.r
.

a o m m
I
O h
h
0 0 v:
s?-

h 0 - m
h
oz o m o m
m
h

N-m* Od 0 0 0 m o
N Lo

A-JrnCUh
d
NN
m
- - - I I

179

- .
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

,? percent. rrsprctivrly, of tlir failurrs w r e “damaged for power outagrs between 1 to 10 cyclrs duration. only
vhile succrssfully opening.” 01113. i to S prrcrnt of the about half as many lose thr motor load. Thus, power
failurrs \wrv “failed to (,losr whr~iit Fhould.” outages of lrss than 10 cyrlrs duration nray often not
It appears that the dominatr failure mode for mrtalclad result in losing t h e motor load.
dra\vout circuit breakers, (t600 V, is “oprned \\-hen it There w r r many power outages of mort’ than 4.0 s
shouldn’t.” It is possihlr that somr of thrsr failurrs were duration, and 35 prrcciit did not lnsr motor load. It is
rxtrrnal to thr brraker arid nf unknown causr and were suspected that many of thrsc did not h a w a motor load.
blamrd on thr hrrakrr. Somc of thrsr may have bern dur Somr may have had a duplicatr frrd and thus did not lose
to impropvr srtting of thr trip rurrrnt. the motor load.
Thr doininatr failurr modis for fiwd-typr circuit, breakrrs
(includrs moldrd caw), 0-600 V. is “failrd whilr oprrating DISCGSSIOS-EI:FECT 01: I ~ A I L U I t EItEI’AIR
(not while opening or closing) _ ” AII<THOD A S D I’AILURE I1EPAIIt
U R G E S C Y O S AVERAGE HOURS
dletalclad Drarroul Circuit Rrmkers. 601-15 000 1. DOWSTIXIE PER 1;AILUltE
;\Ictal dra\+oiit rircuit hrrakrrs. 601-15 000 V, had 21 Data were givrri in Part I on the avrrage hours downtime
prrcrnt of thr failurw classifird as “failrd while opriiing” prr failurr for 74 catrgorirs of rlectrical rquipmrnt. I t is
and 4 prrrrmt classifird as “damagrd ivhilr succcwfully kno\vii that thr downtime after a failure ran be affected
oprning.” Anothcr 24 pcrrcmt of thr failurrs x r r r chssi- to a largv cxtrnt h) thr failure repair mrthod and the
fird as “failrd n-hile oprrating (not tvhilr opc~titrgo r failurr repair urgrncy. The failure repair method includes
rlosing) .” 49 percent of thr failurrs \\-rrv classifird as eithrr rrpair of the failed component or rlse rrplacrment
“oprnrd whrn it shouldn’t;” it is suspcsctrd that some of ir-ith a spare. Somr data were given in Tables 33 and 34 of
thrsc may havr bwn duv t n improprr setting of the- trip Part 111 on thr failurr repair mrthod and thr failurr repair
rurrrrit. urgrncy for wholr classrs of rlrctriral rquipmrnt.
It appear:: that mrtalrlad drawnit circuit hrrakers. .I mow dvtailed study is rrportrd in Tables 48-36 of
601-1.i @MI t‘, havr about half of thrir failurrs as “operird this paper o n the rffrct of the failurr rrpair method and
w h m it shouldn’t” and thr othrr half as “failed \vhile thr failure rrpair urgency on thr average hours downtime
oprrating or while oprning.” prr failurv. This is only reportrd for 9 rlrctrical equipment
catrgorirs, rathrr than thc 74 catcgorirs givrn in Part I.
DISCUSSIOS-LOSS 01: ;\IOTOR LOAD These 9 electrical equipment categories were selected he-
V E R X S TIAIE OF POWER OUTAGE cause an adequatr .sample size rxistrd of the number of
Thr data on loss of niotor load shown in Table 47 failures and hrcause the average downtime per failure
indicate that for powrr outagrs greater than 10 cyclrs was effectrd significantly by the failure repair method
duration most of t h r plants lose the motor load. Howvrr, and/or the failure repair urgency.

180
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

cn
W a) d F

L
9 m In m
In
'9 Q, 7

>
W
?
7
9
7 d
N a)

5E
-f
X
9
ac
0
9
0
7
0
In

h
0
9
z
.r
X
9
0
9
h
N
h
h
In
0
9
h
N

W
0) F
F -r
.r c1 7
h 0
N 0
In
h Hpc
In
In
F
m N Inw N
h U N 7

N 7 cd L
a
W
7

W
N

-0
S L
9 c m N
Q,
W m
N aJ
10 O - u
9
.r
09 83 d
N
=j
m 5 *
N
N
v) W
W 7

bp's
m c 0
h Q, F
h N W 2 (u
7 co
7
9 7
tl 7

a
W

Q, Q,
0 0
N N 0 0 W
0 0
9 9
0
In
9 9 ?

U
c

s N
d
m
N 2 -n 7
d
F
0 z
4
a
i
a C
L

I
I
*
* *
In

W
z z w
-1
5 3
Y

0
-1 0 0 rn 0
m 0 0 0
0 <
I-
J
c,
VI
c,
VI
c c
9 7

-
7
L
a
7
7

< 4

181
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

E E
.C -r
E
M
0 0 m
QI, 0
C a N
a)

E E
4 .I- .r
bel E E
L n ll
h
0
< Ln
9
Ln
C 7

U
U
aJ
VI M M M MW bp M
s W
VI 00-oo_ooo

-9 -
0 In
T
9 0
N
I
v) v)
a W ai
r 7 7
U U
+
bee
m aC
3 3
- m
N 0
L
na 0 a)

a VI
r W
.I- 7
t U
M E
Z8 3
0 I h a )
a
W
9
In m

c
U
W .r
E
2 W
%! N
cc 7

In

W
e.
W
-I
rn I
U
I-
2,"
22
3 5
VE V
--E

-=I
-Lo
U 3

182
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

-
L
4 c,
v)
7
3 3
.r
L
0 3
L .r

p,
cn.- .-L
0
'c
aJ
L
0
-7
L
E+ n c
3,
-r L I n
E 0 I
L a>
3 J 0 c
0 0 c > 7 0
V ? c
> 4 z
W 4
3 P 4

-
V c
z
W o
E m
O 0
W
PI V
Y E
2 0 0
a
PI
Lc,
Y T L
Y
3 PI V Y
0 .r 0 Y I L
aJ
PI
Y
3 3
LIn
3
L
B
W T
c,
0
3

>
B
W e-4 n
4 .r
4 >
PI I
TI
L
.r
V PI nc n z
V w c
3 4
z aJL aJ
w
PI n
w
PI
W
W
PI
LO)
n
L
cn PI
W
53
-J L
0 e,
53
F a 53
Y

i5 CT, cn
3
PI
c(
-I
Y

2
.-L uh
o 4
r
c
L
-r
-r I
PI
E
.r
L
E
-r
L
ax .r v
d U
0 1L
0
3 .I
0 - 1 a
U
-r
a er

P I 3 PwI aA u u
LWL I. D
c
tx
aJ 7
4
c,
N m 0
e m I-
-

-
0
m e I
c u c
L
In
3
0
I
W*
h
0
Y

aJ
0,
N 4
I L
* t %
u s I >
aJ
4
7

-
w
N
m
e
0
I h W e .o
e N

N r n o m
N .o
W
m
-I
c
4

e -
o 0
N N
e
0

183
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

VI
L
c,
c,
ul
L e 3
0
Y- b
.r
'c
aJ
.C
L
0
'c L c
c, L

-
aJ 0
.C a n
c, L 0
a n c
0 I 0
E
0
F c
7 m
7 m
rn Y
m V
Y
u t:
0
7
E
0 0 U Y
I L
u Y 0) 0
I L t
c, 3
al 0
L
r 3 I
c, -0 .r
> UI L m
u .r a a
z
W
E m L
0 0)
a n L
a
PI
3
2 2 cn cn
c
cn cn c .
r
E c L L
.r c c a -VI
L L a *I-

.r .r ul V Uul
U
a
aJ
PI
a .r
UVI
a m
p:n -
m
c,
0
PI
aJ

-
a m
czn

m
c
m
c,
0
I-
m I-
7

- -
I
? e c
ul
L
3 5
0

5"
m * e I I

-
I
0 (u
0;
h 0
e
c
5
W
aJ
cn
m m
L
m L
F j c c
e!
-1
B e I >
W
U
4 iz
-
m
PI u - w VI _I W N 0 , W
e - In
O h m W
In w

-
m - c 7
N
7
In

w
-I
20' 0
(u

2
I-

-1
u d
m m 0 12
(3

z - r D
m
W In
e
- - -

184
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

>
u
z
W
PI
CJ
3
PI
I-4

d
W
p:

w
c1
d

I
. .
- N m
. .
I - N m

h
i m
d N I
F

I- r. UY
m h
I-

E N UY O
e Q )
o 0

N l n
I - h
I-
0
A2 0 PI, z

185
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

0
le
m
c,
L -
m
L
3
0,
3
.r
le aJ L
al
c,
’P
0,.I-
0
.r
L
3 .C
r W
L n
0 I
LaJ
=3>
c
7 0
> - 0 0 E
> v m m
V
z 2 P
W Y
w
Z a u o m
C O E
0
a r o
ar
W 3 -
u Y
3 a r l Lc,
Y T L
n a J 0 .r 0
E 2 5 3 3 3
n
d
w
W
aru
I .,-
L vn
m m
) L
.r
4
C
m w 3 nr n
P I 0 W L 0)
w 3 L LaJ L
ar -1 n
3 > Y o 3 cn cn
c - E
-1
Y V
z
w
2 .EL ‘f 3
.r
L
Y I 2 a .r
3 -0
x a

-
-r .r .r
v)
w a
ar
3 0- alL
U o 0-m
3 CL
ar
al ar3 aa rl mn
Y 4
c,
0
I-
d w
-

v)
L
3
* + I 0
X
d

*
0

aJ
0,


m
c o - ?m + + w
aJ
2 2 * 4

m
r-

d o 0 d
c u m 0 7

-
’ I b
c o r n
N V )

r
186
IEEE-IAS T R A N S A C T I O N S J U L / A U G , S E P T / O C T 1974

FAILURE REPAIR METHOD FAILURE REPAIR METHOD

Rep1ace Replace
, ReDair w i t h Spare Total ReDair w i t h Soare
Average Hours Downtime FAILURE R E P A I R URGENCY
Nunher o f F a i l u r e s per Failure
17 57 74 26.5 19.0 1. R e q u i r i n g round-the-clock a l l out e f f o r t s

2 33 35 77.8 2. R e q u i r i n g r e p a i r work o n l y d u r i n g r e g u l a r
workday, perhaps w i t h some overtime

3 3 6 * * 3. R e q u i r i n g r e p a i r work on a n o n - p r i o r i t y
basis

22 93 115 Average 95.5 Hours Total

In several cases there is a disparity in the downtime Motors


between the “average” and the cases where work is done Most users of synchronous motors, 601-15 OOO V, did
“round the clock.” When making availability calculations, not have a spare. Thus the average downtime per failure
this should be considered when deciding what value to use was 175 h for all failures.
for the downtime after a failure. Induction motors, 601-15 OOO V, had an average down-
time per failure of 35 h for replacement with a spare,
Transformers, Liquid Filled compared to 84 to 88 h for repair. Induction motors, 0-
Transformers, above 15 OOO V, had an average down- 600 V, had an average downtime per failure of 6.6 h for
time per failure of 1842 h when sent out for repair without replacement with a spare while working round the clock.
round-the-clock urgency. This compares with an overall This compares with 123 h for repair and not w-orking
average of 1076 h for all outage times, which included round the clock.
several cases of replacement with a spare. Thus it can be Cables
concluded that repair gives a much longer outage time
than replacement with a spare for transformers, above Cables, above ground and aerial, 601-1.5 OOO V, had an
15 OOO V. average downtime per failure of 9 h for repair when
Transformers, 601-15 OOO V, had an average downtime working round the clock. This compares with 40 h for all
per failure of 342 h when sent out for repair without failures. This shows that it is possible to reduce the down-
round-the-clock urgency. This compares with 130 h for time by working round the clock when fixing cables, above
replacement with a spare while working round the clock. ground and aerial, 601-15 OOO V.
Thus it can be concluded that repair gives a much longer Cables, below ground and direct burial, 601-15 OOO V,
outage time for transformers, 601-15 OOO V, than replace- had an average downtime per failure of 96 h for all failures.
ment with a spare while working round the clock. However, this was only 19 to 27 h when norking round the
clock. This shows that it is possible to reduce the down-
Circuit Breakers, Metalclad Drawout time by working round the clock when fixing cables, below
ground and direct burial, 601-15 OOO V.
Aletalclad drawout circuit breakers, o-600 V, had an
average downtime per failure of 3.3 h to 3.8 h when fixing DISCUSSIOX-COST OF POWER OUTAGES
the failure with round-the-clock efforts. This compares Data are given in Tables 44 and 45 on the cost of power
with an overall average of 147 h for all outage times. Thus outages to industrial plants. This has added 26th and 75th
it can be concluded that 24 percent of the outages of percentile data to what had previously been reported in
metalclad drawout circuit breakers, o-fioo V, had low Part 11. These were added because of the wide spread in
urgency for fixing the failure, and that these 24 percent the cost of power outages to industrial plants.
of the failures resulted in increasing the average downtime
per failure from 3.8 h to 147 h. REFERESCES
hIetalclad drawout circuit breakers above 600 V, had [ I ] W. H. IXckirisnn e1 al., “Report on reliability survey of industrial
plants, part I: Itelishility of electrical equipment ” IEEE Trans.
an average downtime per failure of 109 h for all outages. Ind. . 4 p p / . , vol. IA-IO, pp. 213-235, Mar./Apr. i974.
However, when round-the-clock effort was applied it only [2] W. H. Dirkinson el al., “Report on reliability survey of induytrial
plants, part 11: Coat of power outages, plant restart time, critical
took 83 h for repair and only took 2.1 h for replacement service loss duration time. and type of loads lost versus time of
with a spare. This shows that it is possible to reduce the power outages,” IEEE Trans. Ind. A p p l . , vol. IA-IO, pp. 2 3 6
241, Mar./Apr. 1974.
downtime by having a spare and working round the clock [3] W. H. Dirkinsoil el a/., “Report on reliability survey of industrial
when fixing metalclad drawout circuit breakers, above plants, part 111: CaiLw and types of failures of electrical equip-
ment, the methods of repair, and the urgency of repair,” IEEE
600 v. Trans. Ind. .4ppl., vol. 14-10, pp. 242-252, Mar. /Apr. 1974.
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

Report on Reliability Survey of Industrial Plants, Part V:


Plant Climate, Atmosphere, and Operating Schedule, the Average
A g e of Electrical Equipment, Percent Production Lost, and the
M e t h o d of Restoring Electrical Service after a Failure
IEEE COMMITTEE REPORT

A bslrocl-An IEEE sponsored reliability survey of industrial


plants was completed during 1972. This survey included the plant
climate, atmosphere, and operating schedule, the average age of
electrical equipment, percent production lost, and the method of C o l . 25
Percent Card-Type 3
restoring electrical service after a failure. The results are reported
from the survey of 30 companies covering 68 plants in nine industries If no f o r e w a r n i n g was g i v e n
97% 1.
in the United States and Canada. This information is useful in the
design of industrid power distribution systems. -3% 2. I f forewarning was g i v e n
F o r o t h e r types of f a i l u r e , leave blank

100% Total Percent


IXTRODUCTION AND RESULTS 172 T o t a l I n t e r r u p t i o n s Reported

URISG 1972 the Reliability Subcommittee of the


D Industrial and Commercial Power Systems Com-
mittee completed a reliability survey of industrial plants.
SURVEY FORM

This paper presents Part V of the results from the survey. The surve!. form is shown in Appendix A of Part I [l].
The information reported in this paper camp from 1) card
The first three parts [1]-[3 J were published previously;
some of the data of lesser importance were not published type 3, columns 2.5, .i3, and 58; 2) card type 2, column 33;
a t that time but are presented in this paper. Included in and 3 ) card type 1, columns 9-11 and 13. The definition
Part V are of failure is given in Part I.

RESPOSSE TO SURVEY
Table 57-Failure Forewarning for Public Utility
Power Interruption Only, A total of 30 companies responded to the survey
Table 58-Percent Production Lost, questionnaire, reporting data covering 68 plants in nine
Table S9--1\Iethod of Service Restoration, industries in the United States and Canada. For the
Table 60-Average Age of Electrical Equipment , purpose of reporting results in this paper, Part V, the
Table 61-Plant Climate, number of industries were rcduccd from nine down to fiw
Table 62-Plant Atmosphere, plus an “all other” category. The five industrirs selected
Table 63-Plant Operating Schedule. w r r the ones for which equipment failure rate data were
reported in Tables 3 through 19, Part I. All of the remain-
These data are useful when using the results published in ing industries were combined into an “all other” category
Parts I, 11, 111, IV [4], and VI [SI. This information is in Tables 61-63 on plant rlimatc, plant atmosphere. and
also useful in the design of industrial power distribution plant operating schedule.
systems. The data on average age of electrical equipment
and plant operating schedule provide answers t o some DISCUSSIOS-FOREWARSISG FOR PUBLIC
points raised in the written discussion to Part I. UTILITY POWER ISTERRUPTIOS
Only 3 percent of the time was a failure forewarning
given for a public utility power interruption to the indus-
Paper TOD-74-33, approved by the Industrial and Commercial trial plant. Data from Table 3, Part I, and Table 57,
Power System.. Committee of the IEEE Industry Applications
Society for presentation at the 1974 Industrial and Commercial Part V, indirate that a large pcrcentage of these interrup-
Power Systems Technical Conference, Denver, Cola., June 2 4 . tions w r e on double- or triple-circuit supplies. Forewarn-
Manuscript released for publication April 15, 1974.
Mernhem of
....___._... the
.~..Reliahilitv Subcommittee of the IEEE Industrial
~~ ing can be important to plants xith a single circuit. I t can
and Commercial Power &terns Committee are A. 1). Patton, also be important to plants containing a double circuit
Chairman. C. E. Becker, W. H. IXckinson. P.E. Gannon, C. 11.
Heising, D. W. MeWilliams, R. W. Parisian, and Y. Wells. with manual switchover.

188
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

c,
S
W
V
Q L
EO)
an
V
L O
W O
n
0)
w o >
sm 0
o in
Z 0 4

Of-N

hv)co
*mf-

mcom
mm

0.30-
NIDI-

NInm
IDNI-

OInIn
mm-

000
NIDN

0V)U-i
N h

*mm
SLlOlOWl N h

S831sYIS/a 1101ow
mmco
-h

Nmv)
NID-

S l I l d d n S 1I1MOd
AlIlIln 3 I K w i 3 I ap - N h
*mN

189
A P P E N D I X B R E P O R T O N RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

SNOIlVNIWU31
3iam
SlNIOr
3 i a n
Ll

I I

In000
*
N N -w
31av3 N
I
7

I 1 I
I
:! ,
c t C u - 0
I
-
m
,w -N
e-
, $
w
I
W-

C
I
.
L
C

L
<
C
L
c
L
C I
C
E
i
W
0
I

C
L 4
L
c
t

-
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

- 1 1
I-
v,
I
I
E
I I
I

I3HlO N 0 0 0 m O N - r
N ,
11V

3111x31 -000--0oc NOOO-OOOC

S3IlSVld oooo-NOOC
2
0 0 0 0 - O O N C
ONW I 3 8 8 f l I

W n 3 108 1 3 d mOONO-ONe
a
P I - o o o o o o c

lW13W

lW3IW3H3
', I
-00--0ooc
I

C ~ F . ) O ~ I ~ - O O C
---J-L
- 0 O O O O O N C

N * o o Q ) ~ o o c

-e- mL AO-O- m d N I n r
AIlSflONI P-3 I -

11V

191
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

-
RA1 EDULE
I
1

w
-1
c( T i t l e , Card-Type 1 Column No.
I-
%
W
-
I-

NUMBER OF PLANTS HOURS PER DAY (Col . 11 )


Less than 8
8
-9to15- - __ -
16
17 t o 2 3
24

DAYS PER WEEK ( C o l . 1 3 )

Less than 5
-
6
7

DISCUSSIOS-PERCEST PRODUCTION LOST


Rrplacernent of failed component
The most severe category of failure in an industrial with sparti ?1 percent
plant is where above 30 percent of the production is lost. Repair of failed componrnts 2" percent
Data from Table 38 show that the folhving percent of Other 22 percent
equipment class failures resulted in losing above 30 percent Utility servircl restored 12 percent
of the production. Secondary sclrction-manual 11 prrcrnt
Primary sclrrtion--manual 7 percent
Switchgear bus-bare 50 percent Primary selrction~automatic 2 prrcent
Electric utility power supplies 27 percent Secondary selection-automatic 2 prrcrnt
Switchgear bus-insulated 20 percent Set\\-orkprotector oprratioii-automatic Of percent
Cable terminations 18 percent
Bus duct 1.5 prrcent
Transformers 1.5 percent
Genrrators 15 percrnt
Open wire 13 percent The most common methods of scsrvice restoration arc
Cablr 13 percent replacemc~ntof failrd component xith a spare or repair
Cable joints 9 percent of failed componrnt. Only 22 percrnt of the time is primary
Circuit breakers 8 percrnt selection or secondary srlectiorl usrd; this Jvould indicate
Motors 3 percent that most power distribution systems arc radial.
Motor starters '2 percent

I t can be seen that failures of switchgear bus and electric


utility power supplies often result in losing above 30 DISCC'SSIOS-AVERAGE AGE 01'
percent of the production. ELECTRICAL EQUIPAIEST
DISCUSSIOT-LIETHOD 01' SERVICE llany rrspondents to the rrliability survry of industrial
RESTORATIOS plants submitted data covering a ten-vrar period. Thus it
Thr data on method of rlectrical service rrstoration to is not surprising to see that Table 60 s h o w a large popula-
plant is shown in Table 59. A percrntage breakdonm of the tion that is more than ten years old. The following percent
total show the follo\\-ing results. of installed units are classified as more than ten years old.

192
IEEE-IAS T R A N S A C T I O N S J U L / A U G , S E P T / O C T 1974

Bus duct 92 percent


Open ivirc 92 percent
Generators !IO percent
.\lotors 6.i percent
Cable 64 percent
Cable joints ti3 percent
Cable terminations (iY percent
Transfornicrs .i4 pcrcrnt
Sn-itchgear bus-insulated .i2 prrcmt

llotor starters. disconnwt s\\-itchcs.switchgear hu-hare,


nnd circuit brcdwrs liad over 30 percent of the installed
units one t o tcw >-carsold.
1.i prrwnt of the circuit breakers \vcrr less than one
yvar old. All other equipment classes had lcss than ti per-
cent of the installtsd units less than a yrar old.
1)ISCUSSIOS-l'LAST CLIJIATE
A S D AT.\IOSI'H E RE
Data on plant climate and plant ntniosphcrc :ire given
in Tahles 61 arid (2.43 percent of thr plants w w in a
hot climate. . i 3 percent in a moderato cliniatc, and only
4 percmt in a lo\v climatc. (cold climatc-). 43 prrcmt of
the plants had high relative humidity, 31 pcrcrnt had
modcratc. rrlative tiuniidity, and 3;prrceiit had low rrla-

193
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

Report on Reliability Survey of Industrial Plants, Part VI:


Maintenance Quality of Electrical Equipment
IEEE COMMITTEE REPORT

Abstract-An IEEE sponsored reliability survey of industrial SURVEY l~’OR\l


plants was completed during 1972. This included maintenance
quality, the frequency of schedule maintenance, and the failures Thr survry form is shown in .4pprndix h of Part I [l].
caused by inadequate maintenance. The results are reported from The information rrported in this paper came from 1) card
the survey of 30 companies covering 68 plants in nine industries in type 2 , col. 34 (maintrnance, normal cyclr): 2 ) card
the United States and Canada. This information is useful in the type 2 , 1-01. 36 (maintrnance quality); 3) card typr 3,
design of industrial power distribution systems.
col. 34 (failure. months sincr maintained) ; 4) card t y p r
3, col. 40 (suspected failurc rrsponsibility). Thr drfinition
INTRODUCTIOS of failure is givrn in Part I.
KKOWLEDGE of maintenance quality of rlectrical RESPOSSE TO SURVEY
A equipment in industrial plants is useful information
when planning thr maintenance program of industrial
A total of 30 conipanirs responded to the survry qurs-
tionnairr, reporting data from nine industrirs in thr Unitrd
power distribution systems. I n addition it is usrful to Statrs and Canada. Evrry plant did not rrport all thr
know how this correlates mith the normal .maintenance information rallrd for in card typr 2, columns 34 arid 36.
cycle and the failures blamed on inadequate maintrnance. Every failurr rrport did not h a w filled out all of thv
During 1972 thr Rrliability Subcommittre of the Industrial information callrd for in cmd typr 3 , columns 34 and 40;
and Commrrcial Pov-rr Systrms Committrr completed a a. total of 1460 failures had this infomiation filled i n and
reliability survey of industrial plants. This paper presents arr rrportrd hrrr in Part VI, and 240 of thrsr f d u r r s
Part VI of the results from the survry. The first thrrr parts w r r . hlanird (in inadrquatr maintrnance. Diffrrrncrs in
[1]-[3] were publishrd prrviously. Table 38 from Part I11 thr nunihcr of failurrs and unit-yrars rrportrd hrrr i n
reported that inadrquatr maintenancr was hlanird for Part VI and thosr, prrviously rrportrd in Part I and Part
between 8 to 30 percent of the failurrs of electrical equip- 111 can bc txplainrd from the preceding.
ment. This information has causrd the Reliability Sub-
committee to make a further study of the failurr data; STATISTICAL ATALYSIS
the results from this study are being rrportrd in this paprr. Thf, suhjrrt of statistical analysis of cquipmrnt failurrs
Included in Part VI are the rrsults for 12 main classrs nf is discussrd in Part I [l]. Confidrncc limits for thr failurci
electrical equipment on ratr arc. shmvn in 1;ig. 1 of Part I. The Rciiability Suh-
1 ) equipment population vrrsus a ) maintrnancr quality committrc concludrd that right failures is an adrquatr
and b) normal maintenancr cyclr ; sanipk. sizr for rrporting failurr ratrs in thcs summary in
2 ) failures due to all causes versus a ) failurr, months Tablfs 2 , I’m-t I. In a frw I-asci. failurc ratr data ivcr(8
since maintainrd, and h) maintenance quality; rrpnrtrd in Tahlrs :ithrough 19, I’:trt I, n.hcrr thrrrs ivew
Irss than right failurcss.
3) failures due to inadrquatr niaintenance vrrsus a )
failure, months sincr maintained, and b) maintc- In this paprr sevrral rases arr rrported in T:iMs 67
nancr quality through 7% \vhc.rr the failurr ratr contains lrss than right
failurrs; thrsr cases have brrn marked “small samplr size.”
The “maintenance quality” is an opinion that, \vas
reported by each participant in thr survry. Thc four SlJRVEY RESULTS
classifications used were “excrllent,” “fair,” “poor,” and Itrsults arc’ tabulatrd for 12 main rquipmrnt classes in
“none.” The “normal maintrnancr” cyclr is the frrqurnry Tahlr 64 where thr equipmrnt population is givrn vrrsus
of performing preventive maintenance 1 ) maintenancr quality and 2 ) normal maintenancr cyclv.
Table 65 summarizes t h r percrnt of eaeh rlrctriral
rquipmcmt class population versus the maintenanrcx qual-
Paper TOU-74-33, approved by the Iiidwtrial arid C‘onimereiaI
Power Systems Committee of the IHEE Indiistr? Applirati(ins
ity. Tabk 66 summarizcs thr percent of rach rlrctrical
Society for presentation at t,he IS74 Industrial and Commercial equipmrnt class population vrrsus the normal maintrnancr
Power Systems Technical Conferenre, Ilenver, Colo., Jiirie 245. cyclc..
.Manuscript r e l e a d for pnbliration April 15, 1974.
Members of the Reliability Suhmmmittee oi the IEEE Industrial Ilrsults arr tabulatrd for rach of thr 12 main rquipmrnt
and Commercial Power Systems Committee are A. I ) . Pattoti, classcs in Tablrs 67 through 78, whrre the number < ) f
Chnirmun, C. E. Becker, W. H. I)irkinson, P . E. Gannon, C. I t .
Heising, D. W. MrWilliam?, R. W. Parisian, and S. WelLs. failures is givrn for 1 ) failurrs dur to all causes and 2)‘
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

195
APPENDIX B R E P O R T ON RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

failures due to inadequate maintrnancr, vrrsus 1) failure, fair. Lrss than 5 prrcent of thr population in each equip-
months since maintained, and 2) maintenance quality. ment class (except for motor startrrs) were classifird as
Failure rate calculations are also given in Tables 67 through poor. Four cquipmrnt catrgorirs had betwrcn 24 percent
78; these calculations usrd the population data from to 43 prrcrnt of the population classifird as “nnnr” under
Table 64. maintrnawe quality; this included cablr trrrnination (43
Table 79 summarizes the number of failures for all percc~it),disconncct switches (40 percent), cable (3.5 per-
equipment classes combined versus the maintenance qual- cent), and cable joints (24 percent).
ity. Table 80 summarizes thr nurnbrr of failures for all 1Iaintenanrc quality had a significant rffect nn the
equipment classes combined versus thr months since percent of all failures that were blamed on inadequate
maintained. maintrnancr. In the “poor” category 3.7 percent of all
failurrs w r c blamed on inadequatr maintenance. This
GENERAL CONCLUSIONS-hlAINTENASCE coniparrs with 1s prrrrnt for fair maintenancc and 12
QUALITY percrnt for rxcrllcnt maintrnancr. Thr “none” category
The maintenance quality is an opinion that was reported for maintrnancr quality also had 12 percent of all failures
by each participant in the survey. The major portion of blamed on inadequatc rnaintenancr; hut %‘percent of these
the electrical equipment population in the survey had a failurrs wei-r for rquiprnent classes that do not require
maintenance quality that was classified as excellent or much maintenance (cablr, cable terminations, cable joints,

TAE 65 -PERCENT OF ELECTRICAL EOUIPHENT


PC LATION VERSUS MINTENANCE Q i L I T Y
1 1 Data Tak n T a b l e 64
If - -

M I NTENANCE VI
QUALITY =
VI
-1
Y -1z
W b-
Card-Type 2 0
b- m m-
Col. 36 x
0 U
V u
UoT
- - -
% % %
- - -
Excellent 41 5 20 26
59 58- 53 -30.
0 2 3 1
None 0 40 35 24 43
-
Total 100 E 100 100 00 100
- - __ 100

TABLE 66 - PERCENT OF ELECTRICAL EQUIPMENT


POPULATION VERSUS NORMAL MAINTENANCE CYCLE
(1111 O a i a T a k y f r o i ‘ a y e 64)) ,, -

----
I
MAINTENANCE.

Card-Type 2
tlr!y3:YCLE

Less than 12 Months


12-24 Months __
More t h a n 24 Months
-
1
58 -47 .-E
41
O+
LOO
37
15
1
32
1
100 ,
2

100
3
__ 55
5
IO
O+
100
.-;; 22
0
0
100
13:.-13

100
40.
0
77
10
100
.-
0
42
57
1
100
~-3
5
1
10
Y
2
m
u
4
_.
%
-

29
34

100
-
2

196
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

TABLE 67 - NUMBER OF TRANSFORMER


FAILURES VERSUS MONTHS SINCE MAINTAINED AND MAINTENANCE QUALITY
I I
I I FAILURE, MONTHS SINCE MAINTAINED I I

QUALITY
Card-Type 2
12
Months
Ago
Card-Type 3, Col. 34

I
12 - 24
Months
Ago
More
I
Than 24
Months
Ago
1
NO
Preventive
Maintenance
I
Total
I F a i 1u r e s
per
Uni t - Y e a r
ALL
I
C o l . 36 Number of F a i l u r e s Due t o ALL CAUSES CAUSES

1 Excellent 22
- F a i r - - - 10 __- 26
11
_ _- 16
5
- __ - 1 -
0
__
38
-53 - - - -
Poor 2 1 1 5
None 0 0 0 3 3 .. -
Total 34 38 22 5 99 ,00473

t Numbe; o f F a i l u r e s ' D u e t o INADEQUkTE MAINTENANCE


1 (Card-Type 3 Col. 40) j
INADEQUATE
MAINTENANCE

Excel l e n t
-Fair -
Poor
__- 01
0
__ - 0
0
1 2
6 -
0
__ - 0 -
0
1
__
3
- 7 - .- ,00075.
1
.00027*

,00294;
-

None 0 0 0 0 0 00000
Total 1 1 8 1 11 ,00053

TABLE 68 - NUMBER OF CIRCUIT BREAKER


FAILURES VERSUS MONTHS SINCE MAINTAINED AND MAINTENANCE QUALITY
1 I I I
FAILURE, MONTHS SINCE MAINTAINED
Card-Type 3, Col. 34
Less More No F a i 1u r e s
Than 12 12 -24 Than 24 Preventive per
Months MOnths Months Maintenance Total Unit-Year .
Ago Ago Ago ALL
Nurrber o f F a i . u r e s Due t o ALL CAUSES CAUSES

Small S a m l e S i z e

TABLE 69 - NUMBER OF MOTOR STARTER

r
IMAINTENANCE
QUALITY
Card-Type 2
ILURES VERSUS MONTHS SINCE MAINTAINED AND MAINTENANCE QUALITY

Less
Than 12
Months
Ago
FAILURE. MONTHS SINCE MRINTAINED

12 - 24
Months
A qo
Caid-Type 3 C o l . 34
More
Than 2 4
Months
Ago
no
Preventive
Maintenance Total
F a i 1u r e s
per
Uni t - Y e a r
ALL
COl. 36 Number o f F a i l u r e s Due t o ALL CAUSES CAUSES

Excellent 13 1 4 0 18
Fair - 45 __ - 13 __- 8 __ - 66
- 0 ~- __ ~- ~

Poor 1 1 2 0 4
None 0 0 0 0 0
crotal 59 15 14 - 0 88 ,00741
I N u r i e r o f F a i l u r e s Due t o INADEQUATE MAINTENANCE INADEQUATE
I I (Card-Type 3 C o l . 40) I MAINTENANCE
Excel l e n t 1 0 0 1 ,00035;
Fair
Poor
~ - -0 -
0
- 1 - - 3 - - o - ~ 4
2
__ ,00051 -
.00170*
MQUe 0 0 0 a 0 -
Total 2 1 4 0 7 .00059*

* Small Sarrple S i z e
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

TABLE 7 0 - NUMBER OF MOTOR


FAILURES VERSUS MONTHS SINCE MAINTAINED AND MAINTENANCE QUALITY
-I I -1
I I F4lLURE, MONTHS SINCE MAINTAINED

MAINTENANCE
QUALITY
Less
Than 1 2
Months
1
12 - 24
Months
1
Card-Type 3 C o l . 34
More
Than 24
Months
No1
Preventive
Fai 1ures

Unit-Year
Card-Type 2 Aqo I Ago I Ago I Maintenance Total
C o l . 36 Number o f F a i l u r e s Due t o ALL CAUSES CAUSES

1 Excellent 56 2 80 0
11 I-4;iJ
t
Fair- -5 8 - - 4

, Number of F a i l u r e s Ow t o INADEQUATE MAINTENANCE


(Card-Type 3 C o l . 4 0 ) , I INADEQUATE
MAINTENANCE

Excellent
Fair
Poor
8
-2 - - 25
0
1
_ _ - 41
1
_ _- 2 - -
0 10
70 __ ,00058
.00280
.01390*
-
None 0 0 0 0 0 .DOOOO'
Total 10 26 44 2 82 ---.uuT94

TABLE 7 1 - NUMBER OF GENERATOR


FAILURES VERSUS MONTHS SINCE MAINTAINED AND MINTENANCE QUALITY

S m a l l Sarrple S i z e

TABLE 72 - IIUMBER OF DISCONNECT SWITCH


FAILURES .VERSUS MONTHS SINCE MAINTAINED AN&~AINTEfiAfiCE QUALITY

FAILURE, MONTHS SINCE MAINTAINEO


1
Card-Type 3 C o l . 34

MAINTENANCE
QUALITY
Card-Type 2
C O l . 36
______ i
E x c e l 1e n t
~-
Poor 0 0 16 .O 16
None 0 . 0 0 67 67
Total 8 5 21 67 101 ,00542

Number o f Fa1 l u r e s Due t o INADEQUATE MAINTENANCE 1 INADEQUATE


I (Card-Type 3 C o l . 4 0 ) I MAINTENANCE
Exce 1 1e n t 0 0 1 0 1 ,0001 3'
_Fair - 0 - -4 - - 1 - - 0 ~ -- 5 .00160* -
Poor 0 0 .ooooo*
, None 0 0 0 7 7 ,00095' .
Total 0 4 2 7 13 .00070
* s m a l l Sanple S i z e

198
IEEE-IAS TRANSACTIONS JUL/AUG, SEPT/OCT 1974

TABLE 73 - NUMBER OF SWITCHGEAR BUS-INSULATED


FAILURES VERSUS MONTHS SINCE MAINTAINED AND MAINTENANCE QUALITY
1 7
FAILURE. MONTHS SINCE MAINTAINED
Card-Type 3 C o l . 34

Card-Type 2
CAUSES

- Excel l e n t
F a i r __
Poor
~-
0 --
2 3
-4 -
0
-1
10

0
-
15
- 0 ~- 5
0
0
~ ./ ~ ~

None 0 0- 0 -Op--Lp
Total 2 11 0 20 ,00127
I
Number o f F a i l u r e s Due t o INAOEQUATE MAINTE?IANCE 1 IliAOEQUATE
(Card-Type 3 C o l . 40) I -MAINTENANCE

Excellent 0 0 6 0 6 ,00048'
- Fair __ - 0 - 0 .- 1 ~~ ~ 0 -~ 1 ~ .00059'
Poor 0 0 0 0 0
None 0 0 0 0 0 -9 -
Total 0 0 7 0 7 ,00044'

* S m a l l Sample S i z e
* * U n i t = Number o f Connected C i r c u i t B r e a k e r s o r I n s t r u m e n t T r a n s f o r m e r C o n p a r t m n t s

FAILURE. MONTHS SINCE MAINTAINED


Failures
MA INTENANCE
QUALITY
Card-Type 2 A=- ALL
C o l . 36 CAUSES

Exce 1 1en t 2 1
- Fair -
Poor
__24 __ 0
None __ 0 00
Total 8 __7 _~ 3 .~ ,00044

__ -
Excellent 0 0 0 0
- F a i r __ __
0
1 - --1-
0
- 2
0
- - o-- 40 -- ..OOOlB*
00000' -.
.00000~
Poor
None 0 0 0 1 1 00271 .
Total 1 1 2 1 5 .00009*

S m a l l Sanple S i z e
* * U n i t = Number of Connected C i r c u i t B r e a k e r s o r I n s t r u m e n t T r a n s f o r m r COnpartmentS

TABLE 75 NUMBER OF OPEN WIRE-


FAILURES VERSUS MONTHS SINCE MAINTAINED AND MAINTENANCE QUALITY
- - - - I I7
FAILURE, MONTHS SINCE MAINTAINED
Card-Type 3 C o l . 34

MAINTENANCE
QUALITY
Less
Than 1 2
Months
1
1 2 - 24 I
More
Than 2 4
M;cm;hs
No I
/A P r l v e n t i v e
1I Failures

"Unit-YeK
c A t ; s F Maintenance Total
-
u er k
a i u r e s ue t o LL c USES
7-
CAUSES

Poor

S m a l l Sample S i z e
** U n i t = 1.000 C i r c u i t F e e t

199
APPENDIX B REPORT ON RELIABILITY SURVEY OF INDUSTRIAL PLANTS

TABLE 76 - NUMBER OF CABLE


FAILURES VERSUS MONTHS SINCE MAINTAINED AN0 MAINTENAfiCE QUALITY
I 1

FAILURE, MONTHS SINCE MAINTAINED

F a i 1u r e s

Card-Type 2
C o l . 36

Excel l e n t 6
-Fair -
Poor
__1058 - - 19 - - 1 6
3
2

2
- - 6 -
21

21
__
34
59
26
___ _
None 0 0 2 e5 9l
Total 23 28 22 143 216 ,00755

'I Number o f F a i l u r e s Due t o INADEQUATE MAINTENANCE


I I (Card-Type 3 C o l . 40) 1 I
INADEQUATE
MAINTENANCE
Excellent 0 0 0 0 0 .00000'
Fair 0 - - 2 - - 0 - - 0 - - 2 - - .00012* -
Poor 0 0 6 8 .01290
None 0 0 0 12 12 .00119
Total 0 2 2 18 22 ,00077

TABLE 77 - NUMBER OF CABLE JOINT


FAILURES VERSUS MONTHS SINCE MAINTAINED AND MAINTENANCE QUALITY

FAILURE. MONTHS SINCE MAINTAINED


Card-Type 3 C o l . 34
'

1
More F a i 1u r e s
MAINTENANCE Than 12 12 - 24 Than 2 4 No I per
QUALITY Months Months Months Preventive Uni t-Year
Card-Type 2 Less
. Ago Ago Ago Maintenar,ce Total ALL
COl. 36 Number 01' F a i l u r e s Due t o ALL CAUSES ~ ~
CAUSES
. -.
_

Excellent 2 4 0 0 6
- F a i r __ 6 __ - 5 __ - 1 __ - 5 - - 17 __ ~

Poor 0 0 0
None 0 ~.o_-.-o 15 15 .
Total ..
8 - ~~~
27 45 ,00091

Exce 1 1e n t
- Fair
Poor
None
~

+ I
;-- -f-- -I
1
0
0
0
0
+1
,
-~- I -~:
1
7
1
8
--
.00000'
.00004* -
,00405:
mQ!E
.00016
Total
S m a l l Sample S i z e

TABLE 7 8 - NUMBER OF CABLE TERMINATION


FAILURES VERSU: MONThS SINCE MAINTAINEO AND MAINTENANCE QUALITY

FAILURE, MONTHS SINCE MAINTAINED


Card-Typc 3 C o l . 34
Less F a i 1u r e s
per
Uni t-Year
Card-Type 2 AL ALL
COl. 36

None
Total .00040
I
INADEQUATE
I MAINTENANCE

Excell e n t
Fair ~ ~

Poor 0
NOne
Total 1
-- __ 6 .L
S m a l l Samp:e Size

200
I E E E - I A S T R A N S A C T I O N S JUL/AUG, SEPT/OCT 1974

TABLE 79 -
NUMBER OF FAILURES VERSUS
MAINTENANCE QUALITY FOR ALL EQUIPMENT
CLASSES COMBINED

I MAINTENANCE
I Nunber o f F a i l u r e s
1 PERCENT
o f Failures
QUALITY i n Tables 67 t h r u 78 Due t o
Card-Type 2
Col. 36
ALL
CAUSES 1 INADEQUATE
MAINTENANCE
Inadequate
Maintenance

1 None
Total
1 2 38
1,469
4 I
1
36

5 224
28
240
11.6%
18.1%
32.8%
11.8%
16.4%

TABLE 80 - NUMBER OF FAILURES VERSUS


MONTHS SINCE MAINTAINED FOR ALL
EQUIPMENT CLASSES COMBINED

PERCENT
Number o f F a i l u r e s o f F a i 1 ures
FAILURE, MONTHS i n Tables 67 t h r u 78 Due t o
SINCE MAINTAINED ALL INADEQUATE Inadequate
Card-Type 3, Col. 34 CAUSES MAINTENANCE Maintenance

+ :;;-t
I 1

I Less than 12 Months AQO I 310 I 23


-. I . ..4 %
7
12-24 Months Ago ~

More Than 24 Months Ago - -1703 -


No P r e v e n t i v e Maintenance I 316 44 13.9%
Total I 1,469 2 40 16.4%

and disconnect switches). Thus this 12 percent for “nonr” 3 percrnt of the population for transfornicrv. motors, and
is explainable and is not inconsistent with what could bc grnrrators. This niay possibly arcount for some of thr
expected. listings of “nonr” undrr niaintc~nnncc.clwtlity rrportrd for
As maintrnance quality drcrcases from “excellrnt” to failures of circuit hrrakers.
“fair” to “poor,” the following cquipment classes showcd
an increasing failure rat(, from failurrs blamed on inade- Motors
quate maintrnance: transformers. circuit brrakers, motor .\lotors n i t h a maintenancr quality of “fair” had a
starters, motors, disconnect switches, switchgear bus-- failure ratc dur t o inadcquatc rnaintrnancc that \\-as five
barr, open wirr, cable, and cahlc joints. In sninc of t h r v timrs highrr than motors with exccllcrit maintcnancc
caws the sarnplc sizr is smallw than dcsirahlc (Irss than quality.
eight failures) in order to conclusively prove this general
statpmrnt. Open W21.e
Oprn n-irc \\ ith a maintrnancr quality of “fair” had a
OTHER COSCLUSIOSS failure ratc due to inadequate maintcnanrc that \vas morc
than tcn tinics highrr than open wirr xith cwdlrnt
Circuit Breakers maintenancc quality.
Approxiniatcly 1.i prrrrrit of thc circuit hrrakcr popula-
tion had a maintcnanrr quality classifivd as “nonr.” This D I S C U S S I O S ~ ~ I A I S T E S A S CQCALITY
E
comparrs with lrss than 1 prrcrnt of the population for From Tablr 79 it is possible t o r:ilculatr for 311 rquip-
tranFformcrs, motors, and generators. ment classes conibincd the ratio of thr numhcr of failures
It is of intrrrst to notr that data from Table 60, Part V from inadcquatc maintcnancc to thr numbrr of failurrs
also show that 15 pcrcrnt of the circuit brcaker population from all othrr causra. This ratio vrrsus maintcnancc
was lrss than onr ?car old; this rompares with 1rss than quality is as follows: poor-4.49. fair-0.22, (,xcrllrn-

201
A P P E N D I X B R E P O R T ON RELIABILITY S U R V E Y OF I N D U S T R I A L P L A N T S

0.13. This is a nreasurc of ~ ( J Wniurh improvrmrnt can br


obtained by upgrading the maintenancr quality from
poor to fair to excrllrnt. An rxrcllrnt maintenancr program
has only 13 percrnt more failures added by inadrquate
maintenance, while a poor maintrnance program has 49
percent more failures added by inadequatr maintenance.
I t is apparent from t h r data that excellent maintenance
quality is very important on oprn wirr and on motors.
I t ~vouldalso apprar froni tlir data i n Tal~lr6.i that
essrntially evcryonc in thr survey did cscrllcnt or fair
maintrnancr on transformrrs, grncrators, and switchgrar
bus--bare. Ho\wvcr, on cirruit hrrakrrs 15 prrccnt of the
population had “nonr” and 4 prrccnt had “poor” on
maintenanrc quality. On motor startrrs 10 prrcriit had
“poor” on maintrnancc quality. Thus, it would appcar
that rveryonr did not maintain cirruit 1)rrakrrs and motor
starters as well as trar~sfornic~rs, grnrratiirs. and sivitch-
grw bus bare.
Onr of thc draxvbacks to thr r r s u l t s rrportrd undrr
maintenance quality \vas t h a t t h r r r \v:iq no obji~rtivr
drfinition of “cwdlrnt, fair.” or “pilor.” T h r r r a r c no
stand:trds for niaintrnanrc~(Iuality, and thus this data
must he ronsidrrrd t o hr individual judgmrnt. Hon-cbvrr,
data rrportrd wider “failurr. ~iionthssinw rnaintaiiird”
does not have. this Sam(’ c:r:i\\-t)acl<; this ti:it:i C:UI I)(, con-
sidrrd fartual.

202
Appendix C
Cost of Electrical Interruptions
in Commercial Buildings
75 CHO 947-1-1A
pp 123-129

BY
Power System Reliability Subcommittee
Industrial & Commercial Power Systems Committee
IEEE Industry Applications Society

P. E. Gannon, Coordinating Author


A. D. Patton, Chairman
C. E. Becker C. R. Heising
M. F. Chamow R. T. Kulvicki
W. H. Dickinson D. W. McWilliams
M. D. Harris R. W. Parisian
S. Wells

Industrial and Commercial Power Systems Technical Conference


Institute of Electrical and Electronics Engineers, Inc
Toronto, Canada
May 5 8 , 1 9 7 5

203
APPENDIX C COST O F E L E C T R I C A L I N T E R R U P T I O N S T O COMMERCIAL BUILDINGS

COST OF ELECTRICAL INTERRUPTIONS


I N COMKERCIAL BUILDINGS

bY

Paver Systems R e l i a b i l i t y S u b c o d t t e e Report


P h i l i p E . Cannon, Coordinating AuthorAf

Abstract Survey D a t a P r e p a r a t i o n

An IEEE s p o n s o r e d r e l i a b i l i t y s u r v e y t o d e t e r - A l l o f t h e r e t u r n e d s u r v e y forms were reviewed. Use-


mine t h e c o s t o f e l e c t r i c a l i n t e r r u p t i o n s i n c o m r - a b l e d a t a was punched o n t o computer c a r d s f o r use i n
c i a 1 b u i l d i n g s was completed i n 1974. The s u r v e y d a t a processing.
form w a s a s i m p l i f i e d v e r s i o n o f forms used i n 1972
r e l i a b i l i t y s t u d y o f i n d u s t r i a l p l a n t s . The s u r v e y Survev R e s u l t s -- Cost o f Power Outaces
i n c l u d e d b u i l d i n g t y p e s and l o c a t i o n s , and l e n g t h and
c o s t o f e l e c t r i c a l s e r v i c e i n t e r r u p t i o n s . The s u r v e y Each r e s p o n d e n t v a s asked t o r e p o r t on t h e c o s t of
r e s u l t s r e f l e c t d a t a from 48 companies c o v e r i n g power o u t a g e s as f o l l o w s :
5 5 b u i l d i n g s i n t h e United S t a t e s . This i n f o r m a t i o n
i s u s e f u l i n t h e d e s i g n of e l e c t r i c a l systems f o r 1 D o l l a r s p e r f a i l u r e -- 15-minute d u r a t i o n , one-
commercial b u i l d i n g s . h o u r d u r a t i o n , and g r e a t e r t h a n one-hour dura-
t i o n ; t o t a l v a l u e of l o s t o p e r a t i o n i n c l u d i n g
w a g e s , damages f o r d e l a y s , l o s s o f computer t i m e ,
Introduction and l o s s o f r e t a i l s a l e s minus c o s t of goods n o t
s o l d w a s t o be i n c l u d e d .
Knowledge of t h e c o s t o f power o u t a g e s , b o t h f o r nor-
mal and c r i t i c a l s e r v i c e s , is u s e f u l i n t h e d e s i g n of 2 C r i t i c a l s e r v i c e loss d u r a t i o n time -- l e n g t h of
commercial b u i l d i n g power s y s t e m , a l l o w i n g c o s t - t i m e b e f o r e an i n t e r r u p t i o n c a u s e s a s i g n i f i c a n t
e f f e c t i v e judgements t o be made w i t h r e s p e c t t o t h e loss.
i n s t a l l a t i o n o f a second u t i l i t y company s e r v i c e , an
emergency g e n e r a t o r , o r p o s s i b l y an u n i n t e r r u p t i b l e 3 B u i l d i n g maximum power demand, and u s a g e , a s v e l 1
power s u p p l y . a s a r e a and number o f employees.

During 1974, t h e R e l i a b i l i t y Subcommittee o f t h e R e d a t a made i t p o s s i b l e t o c a l c u l a t e t h e c o s t o f


I n d u s t r i a l and Commercial Power Systems Committee power o u t a g e s i n t e r n o f d o l l a r s p e r k i l l w a t t - h o u r s
completed a s u r v e y of t h e c o s t o f e l e c t r i c a l i n t e r - o f u n d e l i v e r e d energy a t b u i l d i n g peak l o a d .
r u p t i o n s i n commercial b u i l d i n g s i n t h e U n i t e d S t a t e s .
Included i n t h i s paper are the following r e s u l t s : The a v e r a g e c o s t of power o u t a g e s from t h e s u r v e y f o r
t h e b u i l d i n g s surveyed i s g i v e n i n Table 1.
1 Cost of p w e r outages t o c o m e r c i a l b u i l d i n g s
($ p e r KWH o f u n d e l i v e r e d e n e r g y ) .
TABLE 1
2 C o s t o f p w e r o u t a g e s t o commercial b u i l d i n g s
( $ p e r s q u a r e f o o t l h r and $ p e r e m p l o y e e l h r ) . AVERAGE COST OF POWER OUTAGES
FOR BUILDINGS I N THE UNITED STATES
3 C r i t i c a l service l o s s d u r a t i o n time ( l e n g t h o f
t i m e b e f o r e an i n t e r r u p t i o n c a u s e s a s i g n i f -
icant loss). A l l commercial b u i l d i n g s $7.21/Ki\Tl n o t d e l i v e r e d
5 Miscellaneous items r e l a t i v e t o provision of O f f i c e b u i l d i n g s only $8.86 /KWH n o t de 11ve red
a u x i l i a r y g e n e r a t o r s , t y p e s o f e l e c t r i c a l ser-
v i c e , and o t h e r p h y s i c a l d a t a .

Survey Form The a v e r a g e maximm demand was 3,095 KW f o r a l l con-


m e r c i a l b u i l d i n g s r e p o r t i n g o u t a g e c o s t s . The maxi-
The s u r v e y form i s shown i n Appendix A (two p a g e s ) . mum demand f o r t h e o f f i c e b u i l d i n g s was only 3,035 KW.
A simple m u l t i p l e choice or s i n g l e l i n e f i l l - i n
form was u t i l i z e d i n a n a t t e n p t t o reduce t h e t i m A d d i t i o n a l d e t a i l s of t h e c o s t of power o u t a g e s a r e
o f the responders, b u t s t i l l provide p e r t i n e n t d a t a g i v e n i n T a b l e s 2 , 3 , and 4. The t a b l e s p r e s e n t addi-
f o r a meaningful a n a l y s i s . t i o n a l d a t a including:

1 Outage c o s t s f o r “ o f f i c e b u i l d i n g s ” a s a f u n c t i o n
Response t o Survey o f d u r a t i o n of o u t a g e f o r t h r e e time p e r i o d s .

A t o t a l o f 48 companies r e p o r t i n g on 5 5 b u i l d i n g s re- 2 E f f e c t o f computers on o u t a g e c o s t s .


sponded t o t h e s u r v e y w i t h complete d a t a . I n c o m p l e t e
d a t a , o m i t t i n g the c r i t i c a l outage c o s t information 3 R e l a t i o n s h i p o f o u t a g e c o s t s t o : KWH n o t d e l i v -
vas r e c e i v e d on 121 add1 t i o n a l b u i l d i n g s . Unfortu- e r e d , t o c o s t p e r 1 , 0 0 0 s q u a r e f e e t p e r h o u r of
n a t e l y , t h i s d a t a w a s of no v a l u e i n t h e p r e s e n t b u i l d i n g a f f e c t e d , and t o c o s t p e r employee p e r
survey. Valid d a t a w a s submitted almost equally f o r hour affected.
b u i l d i n g s l o c a t e d i n t h e e a s t e r n , c e n t r a l , and western
r e g i o n s o f t h e U.S.A.; w i t h 4 3 p e r c e n t of t h e b u i l d - 1/ O t h e r Embers o f Sub-Committee: A . D . P a t t o n Chair-
i n g s i n downtown a r e a s , 17 p e r c e n t i n urban a r e a s , and man; C . R . H e i s i n g , Vice Chairman; C . E . Becker;
40 p e r c e n t i n s u b u r b a n a r e a s . F o r t y - s i x p e r c e n t o f M.F. Chamow; W.H. D i c k i n s o n ; X . D . H a r r i s ; R.T.
t h e b u i l d i n g s were used 5 days p e r week; 39 p e r c e n t , K u l v i c k i ; D . W . McWilliams; R.U. P a r i s i a n ; S t a n l e y
6 days p e r week; and 15 p e r c e n t , 7 days p e r week. Wells

204
7 5 - C H 0 9 4 7 - 1 - 1 A , I E E E - I & CPS C O N F E R E N C E R E C O R D MAY 1 9 7 5

TABLE 3
TABLE 2
OUTAGE COSTS FOR "OFFICE BUILDINGS"
OUTAGE COSTS FOR "OFFICE BUILDINGS" AS A FUNCTION OF DURATION
AS A FUNCTION OF DURATION (WITHOUT COMPUTERS)
(WITH AND WITHOUT COXPUTERS)
--
Samplm
Sample Size Yaximun .linimum Average
Size E I a x i m u m Minimum Average -
15-Minute Duration

Costlpeak KW hr. Costlpeak KW hr.


not delivered 11 $ 10.7C $ 1.50 $ 5.84
not delivered
Cost/1.000 s q . ft. of Cost/1.000 s q . ft. of
bldg. /hr. 11 107.4 10.54 49.54
bldg.1hr. 28.56 3.00 12.56
Costlemployeelhr. 11
Costlemployeelhr.

1-Hour Duration
Costlpeak KW hr.
not delivered 13 $ 13.3: $ 0.91 $ 5.30
not delivered 29 $ 6.74
Cost/1,000 sq. ft. of Cost/1,000 s q . ft. of
bldg. Ihr. 15 120.0 5.24 49.42
bldg. /hr. 32 53.12 28.5; 1.25 10.64
Costlemployeelhr. 15
-
32 -

$lOO.O( $ 1.97 $ 36.66


not delivered 13 Cost/1,000 s q . ft. of
$ 16.16 320.0( 48.00 156.00
Cost/1,000 s q . ft. of bldg./hr.
bldg.1hr.
Costlemployeelhr.
14
14
68.06 Costlemployeelhr.
- 50.0( 0.00 27.52

TABLE 4

OUTAGE COSTS FOR "OFFICE BUILDINGS"


AS A NNCTION OF DURATION
(WITH COXPUTERS)

Samplm
Size ,laximum Xinimum Average

15-Minute Duration
Costlpeak Kli hr. n o r
not delivered 14 s 22.22 $ 1.88 $ 8.89
Cost/l,000 sq. ft. of
bldg.1hr. 15 250.00 16.57 78.21
Costlemployeelhr. 15 52.00 4.00 18.53

1-Hour Duration
Cost/peak KW hr.
not delivered 16 $ 24.93 $ 1.88 $ 8.30
Cost/1,000 s q . ft. of
bldg.1hr 17 125.00 15.88 54.52

tl
Cost/employee/hr. 17 34.30 4.00 13.62

lration 1 Hour
Costlpeak KW h r .
not delivered
Cost/1,000 s q . ft. of
bldg./hr.
Costlemployeelhr.

205
A P P E N D I X C C O S T OF E L E C T R I C A L I N T E R R U P T I O N S TO COMMERCIAL BUILDINGS

TABLE 5

CRITICAL SERVICE LOSS DURATION TIXE


FOR "ALL BUILDINGS"

1 ? 8 1 3 5 3 3 1 1 2
Cycle Cycles Cycler Stc. Scc. Xln. !:ln. Hour 8 m r .
I.-

Percent of bulldlngs
w i t t i rrirlcJ1 scrvlce loss
32 61 9: 15. 161 It2 642 79: 1OG:
durarlon 1c.r than or equal
10 t h c t i r e lodlcated.

TABLE 6
CRITICAL SERVICE LOSS DURATION TIME
FOR "OFFICE BUILDINGS"

TABLE 7

RELATIONSHIP OF AUXILIARY GENERATORS

Buildings w i t h
computers
Number
~~ I 1
AND SINGLE FEEDER SERVICE TO "ALL BUILDINGS"

Buildings No Auxiliary
w;t~
Auxiliary
Generltion
and Only
Responses Generation Single Feeder

Buildings w l t h -
out computers

TOTAL

Survey R e s u l t s -- C r i t i c a l S e r v i c e Loss
D u r a t i o n Time ably define. The r e s u l t s o f t h e s u r v e y i n d i c a t e t h a t
i n d i v i d u a l r e a u i r e m e n t s f o r e l e c t r i c a l energy
.. a r e such
The amount of t i m e a n e l e c t r i c a l s e r v i c e can be i n t e r - t h a t i t i s p r o b a b l y n o t p o s s i b l e t o e s t a b l i s h a gen-
r u p t e d b e f o r e i t c a u s e s s i g n i f i c a n t l o s s e s 1s a ques- e r a l c r i t i c a l s e r v i c e l o s s d u r a t i o n t i m e . The s u r v e y
t i o n which o u r p r o f e s s i o n h a s n o t been a b l e t o s u i t - r e s u l t s a r e shown i n T a b l e s 5 and 6.

206
75-CH0947-1-1A,IEEE-I & CPS CONFERENCE RECORD MAY 1975

TABLE 8 TABLE 9

TYPE OF ELECTRICAL SERVICE PHYSICAL DATA -- "ALL BUILDINGS"


m "ALL BUILDIEGS"
Sample

Number of f l o o r s

Annual usage -
Megawatt hours

Peak K i l o w a t t demand 52 17,250 95 3.095

TABLE 11

AVERAGE OF PHYSICAL DATA


FUR "ALL BUILDINGS"
TABLE 10
AND FOR "OFFICE BU1LL)lE;CS"
PHYSICAL DATA -- "OFFICE BUILDINGS"
All Office
Item Buildings Buildings
Sampl1
Size laximun inimu .verage
__ -- - Megawatt hours/1,000 sq. f t .
of b u i l d i n g s a r e a l y e a r 35.5
35 1,600 38 371
Megawatt hours/employee/year 20.2
Number o f f l o o r s 35 44 2 13
Peak Kilowatt desand/1.000 sq.
Nmber o f employees 35 7,000 150 1,651 f t . of b u i l d i n g a r e a 11.3

Annual usage - Peak Kilowatt demand/employee 5.0


Uegswatt hours 32 51,046 840 9,444
Employees/l,000 sq. f t . of
Peak K i l o v a t t demand 32 17,000 2 70 3.035 building area 3.9
-- - -

T h i r t y - s i x p e r c e n t of " a l l b u i l d i n g s " r e p o r t i n g c o u l d p a r i s o n i s shovn f o r b u i l d i n g s n o t having computers;


b e without e l e c t r i c a l energy f o r 5 minutes b e f o r e t h e i n t h e s e i n s t a n c e s , 4 1 p e r c e n t of t h e b u i l d i n g s have
l a c k of e n e r g y was c o n s i d e r e d t o be c r i t i c a l , w h i l e a u x i l i a r y g e n e r a t i o n and 22 p e r c e n t a r e s e r v e d by s i n -
6 p e r c e n t c o u l d b e w i t h o u t energy f o r o n l y 2 c y c l e s g l e f e e d e r s from t h e u t i l i t y company.
and 3 p e r c e n t f o r o n l y one c y c l e b e f o r e s i g n i f i c a n t
l o s s e s were i n c u r r e d . T a b l e 8 shows t h e t y p e o f e l e c t r i c a l s e r v i c e t o a l l
buildings reporting. Eighty-seven p e r c e n t o f t h e
F i f t y p e r c e n t of t h e " o f f i c e b u i l d i n g s " r e p o r t i n g b u i l d i n g s w i t h computers have network o r m u l t i p l e
could be without e l e c t r i c a l energy f o r 5 minutes f e e d e r s e r v i c e , w h i l e 53 p e r c e n t of t h e b u i l d i n g s
b e f o r e t h e l a c k of e n e r g y was c o n s i d e r e d t o b e c r i t i - v i t h o u t computers have network o r m u l t i p l e f e e d e r
c a l , w h i l e 10 p e r c e n t could b e w i t h o u t e n e r g y f o r o n l y service.
2 c y c l e s , and 5 p e r c e n t f o r o n l y one c y c l e b e f o r e s i g -
n i f i c a n t l o s s e s Were i n c u r r e d . Survey R e s u l t s -- Demand and Usage Data

P r e c a u t i o n a r y measures t a k e n t o minimize c r i t i c a l out- Each r e s p o n d e n t was a s k e d t o r e p o r t g r o s s f l o o r a r e a ,


a g e s i n b u i l d i n g s where computers a r e i n s t a l l e d a r e number o f f l o o r s , number of employees, and e l e c t r i c a l
i n d i c a t e d i n T a b l e 7 , where 65 p e r c e n t (15 of 23) o f e n e r g y u s a g e and demand. While n o t d i r e c t l y r e l a t e d t o
t h e b u i l d i n g s r e p o r t i n g have a u x i l i a r y g e n e r a t i n g t h e s u b j e c t of t h i s p a p e r , t h e d a t a i s of i n t e r e s t , and
units. Only 4 p e r c e n t (1 of 23) o f t h e b u i l d i n g s re- w i l l p e r h a p s allow t h e r e a d e r t o make a b e t t e r judge-
p o r t i n g have n o a u x i l i a r y g e n e r a t i o n and a r e s e r v e d by ment of t h e v a l i d i t y o f t h e d a t a p r e s e n t e d p r e v i o u s l y .
a s i n g l e f e e d e r from t h e u t i l i t y company. A l i k e com- The d e t a i l s a r e g i v e n i n T a b l e s 9 , 10, and 11.

207
A P P E N D I X C C O S T O F E L E C T R I C A L I N T E R R U P T I O N S T O COMMERCIAL BUILDINGS

I t is b e l i e v e d t h a t t h e employee d a t a f o r t h e " A l l d A comparison o f t h e a v e r a g e c o s t s of o u t a g e s


B u i l d i n g s " c a t e g o r y may n o t be v a l i d , s i n c e i t a p p e a r s f o r commercial buildings4wJ t h t h a t f o r indus-
t h a t n o t a l l employees were r e p o r t e d f o r Some m u l t i - t r i a l p l a n t s (Reference 12 it shown i n T a b l e
function b u i l d i n g s , t h e o f f i c e / r e t a i l category i n 12. The d a t a is i n t e r p r e t e d t o mean t h a t
particular. short-term outages i n i n d u s t r i a l p l a n t s could
b e more c o s t l y t h a n t h o s e i n commercial b u i l d -
C o n c l u s i o n s and D i s c u s s i o n o f R e s u l t s i n g s , w h i l e long-term o u t a g e s a r e more c o s t l y
i n c o m e r c i a l buildings.
1 C o s t o f Power a t a g e s (Tables 1, 2. 3 , and 4 )
e A d d i t i o n a l i n f o r m a t i o n on t h e c o s t of power
a There is a wide s p r e a d i n t h e c o s t of power o u t a g e s i n Sweden, Noway, and t h e United
o u t a g e s (KWH n o t d e l i v e r e d ) i n commercial S t a t e s i s c o n t a i n e d i n R e f e r e n c e 3.
b u i l d i n g s . Even w i t h i n l i k e t y p e s of b u i l d -
i n g s , w i t h O K w i t h o u t computers, t h e r e i s a
g r e a t d i f f e r e n c e i n the c o s t s assigned. 2 C r i t i c a l S e r v i c e Loss D u r a t i o n Time
( T a b l e s 5 and 6 )
b The c o s t p e r Kb'H n o t d e l i v e r e d i n c r e a s e s
g r e a t l y when t h e o u t a g e d u r a t i o n time e x c e e d s a As would b e e x p e c t e d , t h e r e is a wide s p r e a d
one hour. An e x c e p t i o n t o t h i s i s b u i l d i n g s i n t h e c r i t i c a l time o f a power i n t e r r u p t i o n .
w i t h computers. T h i s i s probably due t o t h e wide v a r i a t i o n s of
t y p e of work b e i n g accomplished, t h e t y p e of
I t is p r o b a b l e t h a t f o r o u t a g e s o f l e s s t h a n equipment i n v o l v e d , and t h e g e n e r a l work e n v i -
o n e h o u r , employees may remain p a r t i a l l y pro- ronment. For example, a windowless b u i l d l n g
d u c t i v e and t h e t e m p e r a t u r e of t h e i r e n v i r o n - i n which a s e n s i t i v e computer o p e r a t i o n i s
ment remains t o l e r a b l e . For l o n g e r o u t a g e s , performed would be more r a p i d l y a f f e c t e d t h a n
employees may have t o be f u r l o u g h e d f o r t h e a window-wall b u i l d i n g p e r f o r m i n g normal o f -
remainder of t h e day. f i c e functions.

c The c o s t o f power i n t e r r u p t i o n s f o r b u i l d i n g s b I t is suggested t h a t a f u t u r e survey attempt


w i t h computers v a r i e s from S8.89IKwH a v e r a g e t o d e f i n e t h e r e a s o n s f o r t h e wide v a r i a n c e s
f o r o u t a g e s of 15-minutes d u r a t i o n t o $9.81/
&?If o r o u t a g e s of g r e a t e r t h a n one h o u r . It 3 Demand and Usage Data (Tables 9 , 1 0 , and 11)
is s u s p e c t e d t h a t t h e s m a l l d i f f e r e n t i a l i s
due t o t h e f a c t t h a t a s h o r t d u r a t i o n a s w e l l a Of t h e " a l l building" data reported, the areas
as a l o n g o u t a g e r e n d e r s t h e computer i n o p e r - a v e r a g e d 400,000 s q u a r e f e e t , 12 f l o o r s i n
a b l e , and t h e employees a r e e i t h e r non-produc- h e i g h t , x i t h an a n n u a l usage of almost 12.000
t i v e during t h i s period o r r e p a i r i n g p o s s i b l e megawatt h o u r s , and a demand of 3,095 K!:.
damage c a u s e d by t h e o u t a g e . Minimum and maximum d a t a were n o t a v a i l a b l e .

TABLE 12

COHYARISON OF AVERAGE COSTS OF POWER OUTAGES


IN COHMERCIAL BUILDlNGS AND INDUSTRIAL PLANTS

$8.86/kWH n o t d e l i v e r e d

The d a t a f o r " o f f i c e b u i l d i n g s " i n d i c a t e a v e r - References


a g e v a l u e s w i t h i n 10 p e r c e n t of t h a t f o r " a l l
b u i l d i n g s , " e x c e p t f o r t h e number of employees, 1 A.D. P a t t o n . e t ~ 1 "Report. of R e l i a b i l i t y Survey
which is 16 p e r c e n t g r e a t e r . of I n d u s t r i a l P l a n t s . P a r t 4 - Additional Detail-
ed T a b u l a t i o n of Some Data P r e v i o u s l y Reported in
b The a v e r a g e e l e c t r i c a l u s a g e f o r a l l b u i l d i n g s t h e F i r s t Three P a r t s , ' ' IEEE I L CPS Conference
and f o r o f f i c e b u i l d i n g s only i s n e a r l y e q u a l Record, J u n e 2-6, 1974.
when p l a c e d on a p e r u n i t b a s i s (33.5 KWH/
Sq. F t . ) a s i s t h e peak demand ( 1 1 . 3 W a t t s / 2 W.H. Dickinson. e t e l , "Report of R e l i a b i l i t y
S q . F t . t o 11.5 i:atts/Sq. Ft.). The r e l a t i o n - Survey of I n d u s t r i a l P l a n t s , P a r t 2 - Cost of
s h i p o f usage and demand t o employees does n o t Power Outages, P l a n t R e s t a r t Time, C r i t i c a l Ser-
c o r r e l a t e f o r a l l b u i l d i n g s and o f f i c e b u i l d - v i c e L o s s D u r a t i o n Time, and Type of Loads L o s t
i n g s o n l y . A s mentioned h e r e t o f o r e , t h e va- vs. Time o f Power Outages," IEEE I 6 CPS Confer-
l i d i t y of employee d a t a w i t h r e g a r d t o t h e e n c e Record, Flay 14-16, 1973.
O f f i c e I R e t a i l c a t e g o r y of b u i l d l n g s i s ques-
t i o n a b l e . On t h i s b a s i s , no a t t e m p t t o draw 3 R.B. S h i p l e y , A . D . P a t t o n , J . S . Denison. "Power
c o n c l u s i o n s h a s been made. R e l i a b i l i t y Cost VS. Worth," IEEE T r a n s a c t i o n s on
Power Apparatus and Systems, PAS-91, P. 2204-
2212, September/October 1972.

208
75-CH0947-1-1A, IEEE-I & CPS C O N F E R E N C E R E C O R D MAY 1975

SURVEY FORI1 ON COST OF ELECTRICAL ItlTERRUPTIONS IN CO?tlERCJAL BUILDJNGS


ELCCTnICAL A N 0
ELEClnONlCS
ENGINEERS, INC.

INDUSTRY AND GENERAL APPLICATIONS GROUP


RELIABILITY SUSC0I:FlITTEE OF THE INDUSTRIAL
& COMMERCIAL POWER SYSTEMS COEIMITTEE

P&uhe d&us *eply to:


A. D. Patton
Texas A & H University
Electric Power I n s t i t u t e
College Station. TX 77843
Date

1. COMPANY NAME ( F i l l i n 3 - l e t t e r abbreviation of name)

2. BUILDING NO. ( F i l l i n sequence number 1. 2 , 3 , etc.


f o r building(s) reported on)

3. BUILDING TYPE (Check type which best describes your building):


D Office 0Office/Retail Sales D Office/Retail Sales/Apartment
0 Retail Sales 0 Other (describe)
4. BUILDING LOCATION (Check applicable items):
0 Downtown; [7 Urban; 0 Suburban;
0 USA: Eastern; 0 USA: Central; 0 USA: Western

5. BUILDING DATA - GENERAL


Gross Area, square f e e t
Number o f Floors
Average Usage of Building: HourslOay DayslWeek
Estimted Number of Office Employees ( i f any)
Estlmated A n n u a l Retail Sales ( i f any)
Is Auxiliary o r Emergency Generation Provided: D Yes No

209
A P P E N D I X C C O S T OF E L E C T R I C A L I N T E R R U P T I O N S TO COMMERCIAL BUILDINGS

SURVEY FORM - C O I W R C I A L BUILDINGS IN USA Page 2 o f 2

6. BUILDING ELECTRICAL USAGE DATA


Electrical Energy Usage f o r 12-month Period Kwti

Electrical Maximum Demand f o r t h i s Period Ku


Type of Service: 0 Single Feeder; 0 Network; Multiple Feeders With
Automatic Transfer
D Other (Explain)

7. COST OF A TOTAL IKTERRU~7IOIlOF ELECTRICAL SCRVICE TO YOUR BUILDING


DVRlCGEAKFi$lOO: (best Opinion - I f no interruptions have
occurred, assum hypothetical instances)
a) 15-Minute Duration $ -
b) 1-Hour Duration s
c) -Hours Duration s
Does a , b , o r c include losses from
an "on-line" electronic computer? Yes No

For "Office Buildings" loss shogld include wages of a l l employees affected,


plus any other d i r e c t costs incdrred includin; delays, and damage to equip-
w n t . This would include any losses from an on-line" electronic computer.
For "Retail Sales" cost should include estinated loss of sales minus cost
of goods not sold, plus cost of any damage incurred.

8. LENGTH OF INTERRUPTION OF ELECTRICAL SERVICE


If there a definitive. length of time before
an interruption causes a s i g n i f i c a n t loss? D Yes tl No
If "Yes", what i s mximum time before
s i g n i f i c a n t losses will be incurred? Hours Minutes

210
Appendix D
Reliability of Electric Utility Supplies
t o Industrial Plants
75 CHO 947-1-1A
pp 131-133

BY
Power Systems Reliability Subcommittee
Industrial & Commercial Power Systems Committee
IEEE Industry Applications Society

A. D. Patton, Chairman
C. E. Becker C. R. Heising
M. F. Chamow R. T. Kulvicki
W. H. Dickinson D. W. McWilliams
P. E. Gannon R. W. Parisian
M. D. Harris S. Wells

Industrial and Commercial Power Systems Technical Conference


Institute of Electrical and Electronics Engineers, Inc
Toronto, Canada
May 54,1975

211
A P P E N D I X D RELIABILITY OF E L E C T R I C UTILITY SUPPLIES T O I N D U S T R I A L P L A N T S

RELIABILITY OF ELECTRIC UTILITY


SUPPLIES TO INDUSTRIAL PLANTS

by
Power S y s t e m s R e l i a b i l i t y S u b c o m m i t t e e
I n d u s t r i a l and Commercial Power Systems Committee
A. D. P a t t o n , C o o r d i n a t i n g A u t h o r l l

___
ABSTRACT
Mode o f o p e r a t i o n i f more t h a n o n e S u p p l y
The p a p e r s u m m a r i 7 e s t h e r e s u l t s of a 1 9 7 4 s u r v e y c i r c u i t : a l l c i r c u i t b r e a k e r s normally
of t h e r e l i n h i l i t y of r l c c t r i c u t i l i t y s u p p l i e s t o in- c l o s e d , manual t h r o w - o v e r s c h e m e , or a u t a -
d u s t r i a l plarils. Results include the average ratP5 of m a t i c t h r o w - o v e r scheme
a c c u r r e n r r drld d u r a ~ i o n so f power l n t r r r u p t i o n s a s II V o l t a g e of u t i l i t v c i r c u i t s supplyin. t h e
f u n c t i o n o f t y p r of r l r ~ tt-lc titilit* iupply. l h ~ . it,- plant
format i o n s l i n r i l d h e l p i n d u r t r l a l p l a n t n p e r a t < v . I l l o o b ? Type o f s u p p l y c i r c u i t s : overhead o r
tlir t \ p e - i o f t . I t , , t i i c ~ i t i l i t g\ i i p p l ~ r s h c i t b u i t t ' c ! t c undcrgrounU
thpir pl?nl,. i: 5 k e t r h of t h e e l e c t r i c i i t i l l t y s u p p l y
5\.;,rm
I N-rEcTuLtt.1 i i i v Thc p r r i o d o f t i m e c o v e r e d bv t h e q u r v e v r e -
port. (Respondents werr asked t o l i m i t t h e i r
l i i r c l c l r i L i i t i l i t y s i i p p l y r c l i a b i l l t y survt-'. I ? - - r e s p o n s e t o t h e p e r i o d J a n u a r y 1 , 1968 t o t h e
bCirteti 11"re i i ., t o l l o w u p t o t l i e 1 Y 7 ? S L I I V I , ~ i o i t h e rt- present.)
i i a h i l i t > of c i e i t r i c a l e q u i p m e n t i n i n d u s t r i a l p l d n t s . The number o f i n t e r r u p t i o n s t o t h e p l a n t d u e
1 , 2 .Thi. 1 9 7 2 s u r v e y showed t h a t t i i t e l e c t r i c u t i l l t y t o los5 o f t h e e l e c t r i c u t i l i t v s u p p l y d u r i n g
s u , i p l y I > t h e most f a l l i b l e "component" o f a n I n d u s t r i - t h e t i m e p e r i o d of ( 3 ) .
a l p l a n t system and t h e r e f o r e d e s e r v e s c a r ? i u l c o n s i d - The d u r a t i q n o f e a c h e l e c t r i c u t i l i t y s u p p l y
eration. i n t e r r u p t i o n , an i n d i c a t i o n whether s e r v i c e
w a s r e s t o r e d t o t h e p l a n t by a s w i t c h i n g o p e r -
C e r t a i n of t h e J a t a i n t h e e a r l i e r survey were a t i o n o r by r e p a i r o r r e p l a c e m e n t o i f a i l e d
i l i b j c c t t o p o s s i b l e e r r o r due t o m i s i n t e r p r e t a t i o n o f e q u i p m e n t . a n d , i f known, t h e e q u i p m e n t w h i c h
lrie h u r v e y form. Hence, a p r i m e o b j e c t i v e o f t h e p r e s - failed causing the interrupt1o:l.
e n t s u r v e y was t o i m p r o v e t h e a c c u r a c y o f d a t e a n e l e r -
t r i c u ~ i l i t ys u p p l i e s . A s e c o n d o b j e c t i v e was t o p r o -
\ , d e more d e t a i l e d a n d d e f i n i t i v e d a t a o n r l e r t r i c
i i t i l i t y s u p p l y i n t e r r u p t i o n r a t e s and a v e r a g e d u r a t i n n b Some r e s p o n d e n t s t o t h e s u r v e y l i , t r - d v o l t a g e d i p s
a 5 a f u n c t i o n u f t h e number a f s u p p l y c i r r i i i t h . t h e w h i c h c a u s e d d i s r u p t i o n o f p l a n t p r o d u L t l o n ds w e l l a s
t y p e of s w i t c h i n g scheme, and t h e v o l t a g e o f t h e sup- complete i n t e r r u p t i o n s of e l e c t r i c u t l l l t v s e r v i w .
ply c i r c u i t s . A third objective was t o obtain data O t h e r r e s p o n d e n t i commented on p r o d u c t i o n d i s r u p t i o n s
f r o m a l a r g e r "timber o f p l a n t s t h a n i n t h e 1972 s u r v e ) d u e t o v o l t a g e d i p s w i t h o u t g i v i n g d e t a i l s . However,
t h e r e b y p e r m i t t i n g i n t e r r u p t i o n r a t e s and a v e r a g e d u r a - most r e s p o n d e n t s r e p o r t e d o n l y on c o m p l e t e i n t c r r u p -
t i o n s t o he determined w l t h g r e a t e r p r c L i s i o n . A t o t a l t i o n s o f s e r v i c e and t h i s was t h e i n t e n t o f t h e s u r v e y .
o f 87 p l a n t s p r o v i d e d u s a b l e d a t a , a l m o s t t r i p l e t h r The S u h c o m m i t t e e f e e l s t h a t t h e s e n s i t l v i t v t o v o l t a g e
number o f p l a n t s p r o v i d i n g d a t a o n e l e c . t r i i utility d i p s is a r a t h e r uniqup c h a r a c t e r i s t i c o f each plant
s u p p l i e s i n t h e 1972 s u r v e v . Survey r c s p and p i o r e s s and t h a t a v e r a g e i n t e r r u p t i o n r a t e s i n c l u d -
d u m by i n d u s t r v i s a s f o l l o w s : cempnr = 2 . c h e m i r a l = i n g v o l t a g e d i p s would n o t b e v e r y m e a n i n g f u l . Thtre-
1 4 , m e t a l = 4 , p e t r o l e u m = I O , p u l p and p a p e r = I , rrih- f o r e . a l l v o l t a g e d i p e v e n t s w e r r removed from t h e s u r -
b e r a n d p l a s t i c s = 4 , and o t h e r manufai t i i r i n g = J2. v e y d a t a l e a v i n g o n l y t h o s e i n t e r r u p t i o n s duP t o c i m -
p l e t c 10s.; o f e l e c t r i c u t i l i t y s e r v i c e . H e n r r . t h r
l t s h o u l d b e e m p h a s i z e d t h a t e l e c l r i c u t i l i t y s"p- i n t e r r u p t i o n r a t e ' g i v e n i n t h e summarv t a b l e . r e f l e c t
p l y r e l i a b i l i t y i s a f u n c t i o n o f a numhrr o f f a r t o r = complk,tr l o s s o f e l e c t r i c u t i l ~ t vs e r v i c e o n l y . If a
not d i r e c t l y identified i n the data presented here. p l a n t is s e n s i t i v e t o v o l t a g e d i p s . t h e r a t e o f s u c h
Included i n t h e s e r e l i a b i l i t y - i n f l u e n c i n g fd?tOrS a r r t w n t - m u s t he added t o t h e r e p o r t e d i n t e r r u p t i o n r a t e s
l i n e e x p o s u r e , w e a t h e r and o t h e r e n v i r o n m e n t a l condi- t o o b t a i n t h e t o t a l r a t e of p r o d u c t i o n d l s r u p t i o n due
t i o n s , a n d u t i l i t y o p e r a t i n g and m a i n t e n a n c e p r a c t l r ' e . t o u t i l i t v supplv troublrs.
T h u s , t h e e l e c t r i c u t i l l t y s u p p l y r e l i a h i l i t y d a t a giv-
en i n t h i s p a p e r r e p r e s e n t s average performance and Almost a l l r e - p o n d e n t s i n d i r a t e d t h a t u t i l ~ t s<up-
s h o u l d n o t be used i n p r e f e r e n c e t o q p e c i f i c d a t a wnrn p l y i r c u i t s a r e overhead ratI7er than undcrgrouiid.
this is available. Methods a r e a v a i l a b l e f o r c o m p u t i n g Hence, no e f f o r t w a s made t o s e p a r a t e s u p y l i e s v i t h
t h e r e l i a b i l i t y p e r f o r m a n c e o f a n e l e c t r i c u t i l i t y '.up- overhead d n d underground c i r c u i t s . The < l a t a g i v f n i n
p l y when t h e r e l i a b i l i t y p e r f o r m a n c e p a r m w t c t , o f 8 1 - t h e S U ~ J K t a~ b l e s essentially r e f l e c t s o v e r h e a d S U O -
t i l i t y s y s t e m c o m p o n e n t s a r e known.3 p l v c i r c u i t s due t o t h e preponderance o i s u r h c i r c u i t s
I" t h P s u r v e y r r b p o n s e .
SURVEY QUESTiONNAIKE
P r r l i m i n a r v a n a l y s e s of i i t i l i t y supplv i n t e r r u p -
The s u r v e y q u e s t i o n n a i r e r e q u e s t e d t h c followiny. t i o n r a t e s by i n d u s t r y c a t e g o r y i n d i c a t e d no s i g n i f i -
d a t a f o r each e l e c t r i c u t i l i t y supply. r a n t d i t f e r e n c e s hetween i n d u s t r i e s . Further. there
I . Type o f i n d u s t r y seem- L O h e n o good r e a s o n whv u t i : i t y s u p p l ~ e so f t h e
2 . Type o f e l e c t r i c u t i l i t y s u p p l y .;me t y p e and v o l t a g e s h o u l d d i f f e r h e t w e e n i n d u s t r i e s .
d. NllmhrK o f u t i l i t y c i r c u i t s s u p p l v ~ n g rile r l i f i e f a r e . t h e d.ita p r e s e n t e d i n t h e s u m , ? r y t a b l e s i s
___-_ plant n d t b r o k e n down by t n d u s t r , .
-
11 Members o f :he Power S y s t e m s R e l i e h i l i t s S u b c o m -
mittee are: A . D. P a t t o n , r h a i m d n , C . F. Bedki,r, I h r s u r v e y r e s p o n s e b r o k e n Gown hy n u m b e r of
M. F. Chamow, W . H . D i c k i n s o n , P. E. i;annon, !l. D . Har- i i t t l i t v s u p p l y c i r c u i t s . v o l t a g e of u t i l j r y s u p p l y c i r -
r i s , C . R . t l e i s i n g , R . 1. K u l v i c k i , D . W . ? I c k ' i l l i a m s , c u l t b , a n d mode o f o p e r a t i o n o f m u l t i p l e s u p p l y c i r r u i t
R. W. P a r i s i a n , a n d S . Wells. i i t l l i t y s u p p l i e s is g i v e n i n T a b l e I .

212
75-CH0947-1-1A, IEEE-I & CPS CONFERENCE RECORD MAY 1975

Table I is r e s t o r e d b y : ( a ) some s w i t c h i n g o p e r a t i o n o r se-


quence o t s w i t c h i n g o p e r a t i o n s i n t h e e l e c t r i c u t i l i t y
Number of Responding P l a n t s
s y s t e m , a n d ( b ) r e p a i r o r r e p l a c e m e n t o f components
With E l e c t r i c U t i l i t y Supplies
which f a i l e d i n t h e e l e c t r i c u t i l i t y system. If serv-
of V a r i o u s T y p e s i c e c a n be r e s t o r e d by some a u t o m a t i c o r manual s w i t c h -
i n g a c t i o n i n t h e e l e c t r i c u t i l i t y s y s t e m , w h e t h e r re-
N u m b e r of S u p p l y C i r c u i t s mote o r w i t h i n t h e u t i l i t y s w i t c h g e a r a t t h e p l a n t , i n -
t e r r u p t i o n s a r e u s u a l l y much s h o r t e r t h a n i f r e p a i r o r
1circuit - 20 p l a n t s replacement of f a i l e d components i s r e q u i r e d t o r e s t o r e
2 circuits - 56 p l a n t s s e r v i c e . The r e a s o n f o r p r o v i d i n g d a t a a n b o t h s h o r t -
3 or more circuits - 11 p l a n t s d u r a t i o n s w i t c h i n g - t e r m i n a t e d i n t e r r u p t i o n s and on
l o n g - d u r a t i o n r e p a i r - t e r m i n a t e d i n t e r r u p t i o n s i s be-
Supply C i r c u i t Voltage c a u s e of p o s s i b l e d i f f e r e n c e s i n impact on p l a n t o p e r -
ations.
v o l t a g e 5 15 KV - 22 p l a n t s
I t sh.iuld b e m e n t i o n e d h e r e t h a t i n t e r r u p t i o n
1 5 KV < v o l t a g e 5 35 KV - 17 plants
r a t e s a n d a v e r a g e d u r a t i o n s computed f r o m a small num-
v o l t a g e > 3 5 KV - 48 p l a n t s
b e r o f o b s e r v e d i n t e r r u p t i o n s s h o u l d b e r e g a r d e d as
l e s s a c c u r a t e t h a n t h o s r computed f r o m d l a r g e r s a m p l e
S w i t c h i n g Scheme o f M u l t i p l e C i r c u i t S u p p l i e s of observations. I n p a r t i c u l a r , R e f e r e n c e [ I ] shows
t h a t i n t e r r u p t i o n r a t e s computed f r o m a n o b s e r v e d num-
all breakers closed - 45 p l a n t s b e r of i n t e r r u p t i o n s l e s s t h a n a b o u t 8 o r 1 0 may w e l l
manual throwover - -9 plants he i n e r r o r by p l u s o r minus S O p e r c e n t o r more d u e t o
automatic throwover - 13 plants random v a r i a t i o n s a l o n e .

The d a t a of T a h l e s I 1 t h r o u g l i L' s h o w t h e e x p e c t e d
t rends.
(1) U t i l i i v s u p p l y i n t e r r a p t i o n r a t e s a r e l o w e s t
for m u l t i p l e c i r c u i t s u p p l i e s which o p e r a t e
w i t h a l l c i r c u i t b r e a k e r s closed and h i g h e s t
f o r s i n g l r - c i r c u i t s u p p l i e s . T a b l e s 1 1 and
l a h l e 1 shows t h a t t w o - c i r c u i t s u p p l i e s a r r t h e most I l l show t h a t t h e i n t e r r u p t i o n r a t e f o r s i n -
common among t h e r e s p o n d i n g p l a n t s . A much b m a l l e r g l e - c i r c u i t s u p p l i ? + i s a b o u t s i x tlmrs t l t d t
number o f p l a n t s r e p o r t e d t h r e e o r more s u p p l y c i r - o f m u l t i p l e c i r c u i t s u p p l i e s which o p e r a t e
cuits. A l l m u l t i p l e - c i r c u i t s u p p l i e s a r e combined i n w i t 1 1 d11 c i r c u i t b r e a k e r s c l o b e o . Interrup-
t h p d a t a t a b l e s which f o l l o w b e c a u s e s u c h s u p p l i e s a r e tion rateh f o r multiplr-clrr!!it supplies
r - i p c r ' d t o have s i m i l a r i n t e r r u p t i o n r a t e s a n d b r - whicii o p e r a t e w i t h n t h r o v o v r r schemi, a r e
cause o f t h e r e l a t i v e l y s m a l l sample of s u p p l i e s w i t h comp,!rahli, t v t h o s e f o r i i n q l r - r l r c u i t s u p -
t h r c e o r more c i r c u i t s . Responses have been broken p l i e s . h u t tiirowover schemes h a v e a s m a l l e r
i n t o t h r e e v o l t a g e c a t e g o r i e s corresponding roughly t o averag? i o t e r r u p t i o n d x l r a t l o n t h a n h ~ n g l c -
d i s t r i b u t i o n v o l t a g e s , L u b t r a n s m i s s i o n v o l t a g e s . and c i r c u i t s!lpplirs,
transmission voltages. 'This w a s done b e c a u s e e l e c t r i ( (2) I n t e r r u p t i o n r e t e ? are h l g h e i t f o r utility
u t i l i t y d e s i g n and o p p r a t i n g p r a c t i c e i s r a t h e r d i f - supply c i r c u i t s operated a t distribution
f e r e n t ~t t h e s e t h r e e f u n c t i o n l e v e l s . Hence, i t c a n vo1tag.r.; and l o w e s t f o r r i : c u i t - . u p e r a t e d a t
b e e x p e c t e d t h a t u t i l i t y s u p p l y r e l i a b i l i t y w i l l be a transmiision voltages.
f u n c t i o n o f t h e s y s t e m l e v e l a t which s e r v i c e i s p r o -
vided.

Table I i n d i c a t e s t h a t about two-thirds o f t h e


responding p l a n t s having m u l t i p l r c i r c u i t u t l l i t y sup-
p l i e s operate wlth a l l c i r c u i t breakers closed. That
is, s e r v i c e is s u p p l i e d s i m u l t a n e o u s l y o v e r a l l supply
circuits. S e r v i c e may a l s o he l o s t , however, by f n i l -
u r e s i n t h e p l d n t s u b s t a t i o n o r by a w i d e s p r c c d f a i l u r e
i n t h e s u p p l y i n g u t i l i t y ' s system. P l a n t s linving
throwover schemes o p r r a t r w i t h a s i n g l e c l r i u i t pro-
v i d i n g normal s e r v i i c . Thus, such p l a n t s s u f f e r an
i n t e r r u p t i o n any t i m r t h e normal supplv c i r i u i t f a i l s .
The d u r a t i o n o f i n t e r r u p t i o n t o s u c h p l a n t s 1s U S u d l l y
l i m i t e d t o t h e t i m r r e q u i r e d ro r ~ c l o c i . t h e normal
supplv c i r c u i t o r t o switch t u t h e a l t e r n a t e supply
c i r c u i t i f t h e n o r m a l c i r c u i t i s perrmiinentlv f a u l t e d .

TI,iblr I I i i i m n l r l r i L e s i n t e r r i i p t i o n r a t e nil aver.igc


interruption dnr.itian d?ta tor single-circuil i i t i l i l x
s l i p p l i e s h r o k e n down i,y v o l t a g c l e v e l . 1nti.rruption
r a t e s and a v e r a g e d u r a t i o n s a r v g i v e n 5 e p a r d t e l y f o r
i n t e r r u p t i o n s r e p o r t e d t e r m i n a t i . d by u t i l i t ; s w i t c l i i n g
i > p e r a t i o n i . .ind hr rc'p.iir dr ~ < , p l a < r m t . nof t L i i l e d ran-
p o n e n t s . A l s o g i v c n a r t ' overall i i i l c r r u p t i u n r a t e < i.
and average d u r a t i o n + _

T a b l e s I11 a n d 1 V show i n t e r r u p t i o n r a t e s and


average durations l u r multiplc c i r c u i t u t i l i t y supplies
b r o k e n down by s w i t c h i n g schcmr .md b;, v o l t a g e l e v e l .
l a b l e V shows i n t e r l u p t i o n r a t e s a n d a v e i a g e d u r a t i n n s 2.
f o r m u l t i p l e - c i r c u i t u t i l i t y i o p p l i e s which o p e r a t e
w i t : , a l i c i r c u i t b r e a k e r s rlosvd b r o k e , , down by v o l r -
age levels. S i m i l a r bir.skdowna hy v u l t n g l , f u r t h r o w
o v e r s w i t c h i n g schemes w e r e n o t p o s s i b l e d u e t o l a c k of
an adequate d a t a hase.
3. R . H i l l i n t o n , R . . I . K i n g l e e , a n d A . 1 . Wood, P o w e r -
I n t e r r u p t i o n r a t e > mi4 .average d u r i t i o i l b a r e g i v e n Sy>tpm R _ r J i a b i l i t i ( . .
a -.
lc.u. l.a .
t ~. o n s . The ElIT Pres>T--
i n T a b l e s I1 t h r o u g h V f o r i n t e r r u p t i o n < v h p r r s r r v i c r Camhridgr, ?lais., 1973.

213
APPENDIX D RELIABILITY OF ELECTRIC UTILITY SUPPLIES TO INDUSTRIAL PLANTS

m m
r.
"- m
N *1 r.
rl

m .m
r m 0
rl
rl
ul
m
ri

m
5 m m
I
rl N

rl .r ul N a
m r.
0 m rl m
m
N
ul a m m X I
rl
m 4 4 rl

m r. m .r
L n
m d a
m
m 0
0 d r.
.rrl u3
U
00 -3 0 4 4 0
N 4 d

m r. m N m m
m
ul m m N m
4" I 0
m
I N
m m N r. 0 -3

4 ul -3
rl
m 0
m
r. N
0
ul m
m
rl

m 0 .r N m 4
c? u3 0
N m ul ul ul ul
4

rnh
U U

.r rD m a
W 0
U
ul
N ul rl -3 Trn
I *
.r N
4
rl
.r
d
rl
u x
.rl
N
rl c w
3 0

I
:
10
> m
% m a
3
m
V I U
W r Wn
5
> > n o . m
V
m > ?L: o O
>
m
m
rl
r ld
u U rl
4 x
m rl Y rl
;' rl
ru m

214

.
75-CH0947-1-1A, IEEE-I & CPS CONFERENCE RECORD MAY 1975

N m m
N r. m
.Y d d U
m ri d

m m
i Y.
m
m 0
N
m
-3
ri m 0
N
d d r? ri

r. 0 0
.r 0 i

.Y Y. \=
c .r i
4

m .Y 3
.N m 3
m ri
i
r.
m
u3 u3
CJ m
0
s. - 1 m

m .Y r. co m 3
.Y
3 Io
0 u3
0
co ri
0 0 0

0 0 r- N
h
b l 0
U
\D m
0 m
m m
.Y m
N
3

N r, m .Y 3 0.
3 ri

N m m m m m
m r? ul -I
h

3 In 3 d
m 0 L 1
rpI
ul 9 m
d m m m hl .r
m .r m U m U
d rl

> >
x
m
In Y
M
L n

>
m
Y
" 1
2' >
Y
>
x
;'>x
L- m
rpI rl
lrl > m
In
3
V I x
In r. Y
d > I; m
d A
Appendix E
Report of Switchgear Bus Reliability
Survey of Industrial Plants
and Commercial Buildings

3Y
Power Systems Reliability Subcommittee
Power Systems Support Committee
Industrial Power Systems Department
IEEE Industry Applications Society

P. 0. O’Donnell, Coordinating Author P. E. Gannon, Chairman


J. W. Aquilino D. W. McWilliams
C. E. Becker R. N. Parisian
W. H. Dickinson A. D. Patton
B. Douglas C. Singh
I. Harley W. L. Stebbins
C. R. Heising H. T. Wayne
D. Kilpatrick S. J. Wells

Industrial and Commercial Power Systems Technical Conference


Institute of Electrical and Electronic Engineers, Inc
Cincinnati, Ohio
June 58-1978

Published by
IEEE Transactions on Industry Applications
Mar/Apr 1979 pp 141-147

216
Report of Switchgear Bus Reliability Survey of Industrial
Plants and Commercial Buildings
Power Systems Reliability Subcommittee
Power Systems S u p p o r t Committee
Industrial Power Systems Department

PAT O’DONNELL, MEMBER, lEEE


COORDINATING AUTHOR^

Abstruct-The Power Systems Reliability Subcommittee of the categorize information into major areas of application. An area
IEEE Industry Applications Society has been conducting surveys of primary concern is maintenance because of its obvious rela-
of the reliability of electrical equipment in industrial plants and com-
tion t o failure rate. However, this is the most difficult datum to
mercial buildings. Switchgear bus was included in a previous survey
published in 1973 and 1974 [ I ] and generated some controversy con- obtain in complete and uniform format for meaningful results.
cerning bare and insulated bus. For this reason, and also for an ongoing Responses in this survey did not permit these results to appear,
effect to continually update the 1973 and 1974 survey [ I ] , switchgear partly due to the respondents’ failure to submit information
bus reliability has been investigated in a new survey in 1977, and the and partly due to the survey format.
results are presented. Reference is made to a paper (21 given at the Failed unit data were requested in the form shown in the
1977 Industrial and Commercial Power Systems Technical Conference
on reasons for conducting the new survey. second portion of the questionnaire. The major categories are
causes of failure, types of failure, duration of failure, and
failed components. This form is less extensive, but more
INTRODUCTION
specifically oriented for switchgear bus than in 1973 and 1974

C URRENT reliability data on failure rate of electrical equip-


ment can provide a valuable tool for the power systems
designer or planner. These data can also be a valuable tool for
survey [ 11 .

SURVEY RESPONSE
the manufacturer of the equipment concerned. Table I summarizes the survey response including number
Many parameters were included in this new survey in an of buses, companies, and plants. In this survey, bus “unit-year’’
effort to uncover the most influencing factors on the reliability is defined as the product of the total number of switchgear
of bare bus and insulated bus and to allow any new obvious connected circuit breakers and connected switches reported in
and significant applications considerations to be identified. a category times the total exposure time. In the previous
The questionnaire submitted was condensed t o a practical and survey, the unit-year did not include the number of connected
useful form to obtain optimum response in as short of time switches; that is, only the connected circuit breakers were
period as possible, counted. Table 11 shows the 1973 and 1974 [ l ] survey and is
Results of the survey are presented in tabular form, and included for comparison of responses. The total number of
discussion is included primarily where adequate response and plants in the new survey response is considerably greater than
population data were obtained. Many questions and uncertain- in the 1973 and 1974 survey, but it is interesting to note that
ties still exist, and the intent of the following presentation is unit-year sample size is slightly less. Also some discrepancy
to report the results of the survey with some discussion, but appears in the total number of failures reported in Table I and
drawing of definite conclusions is left to the reader. those of some subcategories in tables to follow. This is due to
all companies not responding to every category.
SURVEY FOKM
The questionnaire form (Fig. 1) and cover letter used in the
survey are included in the Appendix. Total populations data SURVEY RESULTS
Insulated and Bare Bus
Paper ISPD approved by the Power Systems Protection Committee A major controversy emerged in the results of the 1973 and
of the IEEE Industry Applications Society for presentation at the 1978
Industrial and Commercial Power Systems Technical Conference, 1974 survey [ I ] concerning bare and insulated switchgear bus.
Cincinnati, OH, June 5-9. Manuscript released for publication October Insulated bus, 601-15 000 V , showed a higher failure rate than
25, 1978. bare bus, above 600 V, but data were heavily influenced by
The author is with El Paso Natural Gas Company, El Paso, TX
79978. the chemical industry. The new survey shows the opposite of
1 Other members of the subcommittee are Phillip E. Cannon this, as seen in Table I , with less chemical industry influence.
(Chairman), I. W. Aquilino, Carl E. Becker, W. H. Dickinson, Bruce Bare bus, above 600 V, shows a relatively high failure rate, but
Douglas, Ian Harley, C. R . Heising, Don Kilpatrick, D. W . McWilliams,
R. N . Parisian, A. D. Patton, Dr. Chanan Singh, Wayne L. Stebbins, the sample size is not large, thus making this observation some-
Harold T. Wayne, and Stanley J . Wells. what questionable. With more companies responding in the
APPENDIX E SURVEY OF INDUSTRIAL PLANTS AND COMMERCIAL BUILDINGS

Company Name a n d P l a n t :

I n d u s t r y Type:

Period Reported - From: kbnth Year

To: Month Year

Plant Climte: Temperature R e l a t i v e Humidity

Contamination Level and Type:

Total Population:

F a i l e d U n i t Data:

Fig. 1. Switchgear bus reliability survey for metalclad and metal


enclosed switchgear bus.

218
IEEE-IAS TRANSACTIONS MAR/APR 1979

new survey but with less overall unit-year sample size, the without sufficient supplement from respondents concerning
failure rate for all bus shows to he slightly higher than in the operating procedures, maintenance type, spare parts inventory,
previous survey. But on breaking this down further, bare bus etc., the data relate to a very general or all-inclusive type of
failure rate is higher and insulated bus failure rate is lower in information.
the new survey.
Table I shows the chemical industry data broken out since Grounding Type
it is believed to be a major contributor in the controversy of
the 1973 and 1974 survey [ l ) . In the new survey the chemical Survey results are shown in Tables 111-V. Inadequate response
industry dominated the number of failures in each category, and the general nature of the questionnaire format prohibit
but did not dominate sample sizes. This supports the argument sufficient results for this category. It is believed that grounding
of some that bus utilized in the chemical industry should have type related to failures is important data, but data should be
a relatively high failure rate. especially in the use of hare bus. specific, for example, in types of failures in ungrounded sys-
Table I also shows median outage duration time after a tems and in impedance value of impedance grounded systems.
failure of each category, in hours per failure. It is important to This category may he pursued in greater detail in the next
emphasize that these data are based on many factors, and survey.

TABLE I
SWITCHGEAR B U S : INDOOR A N D O U T D O O R

NUMBER NLMBER OF NUMBER SAMPLE N M E R OF FAILURE RATE MEDIAJl HWRS


~~

OF PWWTS I N OF SIZE FAILURES EQUIPMENT FAILURE DWNTIME PER


CCMPANIES SAMPLE-SIZE BUSES UNIT-YR REPORTED INDUSTRY SUB-CLASS PER UNIT-YEAR FAILURE

39 56 444 51391 54 ALL ALL .001050 28


INSULATED
28 36 245 24855 28 ALL ABOVE 6POV .001129 28
BARE
25 35 199 26592 26 ALL (ALL VOLTAGES) .000977 28
BARE
17 23 132 22420 18 ALL 0-600V .000802 27
BARE
14 18 67 4172 8 ALL ABOVE 600V ,001917 36
PETROLEUM INSULATED
14 19 92 7425 15 CHEMICAL ABOVE 600V .002020 40
PETROLEUM BARE
11 13 135 7002 18 CHEMICAL (ALL VOLTAGES) .002570 28
PETROLELM BARE
10 11 83 4707 13 CHEMICAL 0-600V ,002761 22
PETROLEUM BARE
7 8 52 2295 5’ CHEMICAL ABOVE 600V 48
* Small sample-size.

TABLE I1
R E S U L T S O F P R E V I O U S S U R V E Y P U B L I S H E D IN 1973 A N D 1974 [ I ]
SWITCHGEAR BUS: INDOOR A N D O U T D O O R

N W E R OF SAMPLE NLMBER OF FAILURE RATE ACTUAL HOURS D O W I ME / FA I LURE


PWWQ SIZE FAILURES EQUIPMENT FAILURES PER INDUSTRY MINIMUM MEDIAN MAXIMUM
SAMPLE-SIZE (UNIT-YEAR) REPORTED INDUSTRY SUB-CLASS UNIT-YEAR AVERAGE PLT. AVG. PLT. AVG. PLT. AVG.
INSULATED
12 11740 20 ALL 601-15OOOV 0.001700 261 5 26.8 1613
BARE
12 32280 11 ALL 0-bOOV. 0.000 340 550 2 24 2520
BARE
5 20560 13 ALL >600V 0.000630 17.3 6.9 13 4 8
PETROLEUM INSULATED
5 4003 15 CHEMICAL 601-15OOOV 0.003750 340 18 26.8 1613
PETROLEUM BARE
3 17270 10 CHEMICAL >600V 0.000580 19.3 6.9 42 48

219
A P P E N D I X E S U R V E Y OF I N D U S T R I A L P L A N T S A N D COMMERCIAL BUILDINGS

TABLE 111
TYPE OF G R O U N D I N G OVERALL, BUS INSULATED AND
BUS B A R E

NOT
UNGROUNDED SOLID-GROUND IMPEDANCE-GROUND REPORTED TOTAL
(Unit-Year)
Samp 1 e- Si zc 20262 9787 17280 4062 51391

# FAILURE 17 12 23 2* 54

FAILURE RATE .000839 .001226 .001331 .001050

* Small sample size.

TABLE IV
BUS INSULATED

NOT
UNGROUNDED SOLID-GRCUND IMPEDANCE-GROUND REPORTED TOTAL
( it - Y ear)
Sample-Size 4626 4274 14270 1685 24855

# FAILURE 7* 4* 16 1* 28

FAILURE RATE .001121 - .001126

* Small sample size.

TABLE V
BUS B A R E

NOT
UNGROUNDED SOLID-GROUND IMPEDANCE-GROUND REPORTED TOTAL

-
( U n i t Year)
Sample- Si ze 15636 5513 3010 2377 26536

# FAILURE 10 8 7* I* 26

FAILURE RATE .000640 ,001451 .000980

* Small sample size.


220
IEEE-IAS TRANSACTIONS MAR/APR 1979

T A B L E VI
A V E R A G E A G E OF S W I T C H G E A R B U S

ALL INSULATED BARE

AGE 1-10 y r s . 6526 unit-year 1899 unit-year 4627 unit-year

>10 y r s . 44596 unit-year 22887 unit-year 21709 unit-year


-

Age of Bus
Tables VI-VIII illustrate how failures of insulated and bare
bus relate to age in this survey. An interesting observation here
is that newer bus appears to experience a higher failure rate
T A B L E VI1
than older bus. This might be expected if one considers
N U M B E R OF F A I L U R E S V E R S U S A G E
improper installation, new components failure rate, type of
construction of new switchgear. etc. As discussed below under ALL INSULATED BARE
“causes” of failures, the logicality of this observation is not
AGE 1-10 yrs. 15 5’ 10
consistent.
As incoming data were analyzed. it became apparent that >10 y r s . 37 23 14
the period reported (it was assumed that the period reported * Small sample size.
was the period of best kept records) and the age of bus did not
correlate as well as expected in every case, a fallacy in the
questionnaire format perhaps. Note that the older bus sample
size is much larger.
Indoor and Outdoor Bus
The results of this category are summarized in Tables IX-XI T A B L E VI11
below. Table XI shows an overall result of outdoor bus failure F A I L U R E RATE ( F A I L U R E PER U N I T - Y E A R )
rate versus indoor bus failure rate. Outdoor bus shows a higher
failure rate than indoor bus, an observation not too surprising. ALL INSULATED BARE

Failure Duration AGE 1-10 yrs. .002298 * .002161


Failure duration results are reported in Tables XI1 and XI11 >lo yrs. ,000829 .001005 .000645
below and categorized into repair on a round-the-clock emer-
gency basis and repair on a normal working hour basis. This
* Small sample size.
adds more meaning to the data in Table I , but would be more
meaningful if repair methods were known. Urgency of repair
as shown in Table XIV reveals that most repairs were made on
an emergency basis. The data of these tables compare very
favorable with those of the previous survey.
T A B L E IX
Type of Maintenance
SWITCHGEAR BUS INSULATED
Response was disappointingly low in this category and results
are presented in Tables XV and XVI. The tables show results OUTDOOR INDOOR
of maintenance cycles and time since last maintenance in three Sample-Size
Unit-Year 4275 20356
groups: 1) less than 12 months. 2) 12-24 months, and 3) more
than 24 months. This is a very important category regarding FAILURE 7’ 19
reliability, and hopefully the next survey will produce better
results. FAILURE RATE ,000933

Cnuses of Failures * Small sample size.


Primary and contributing causes of failures are summarized
in Tables XVIl and XVIII. As might be expected inadequate
maintenance is a large contributor to failures. This does not
necessarily follow from the observation above on age of bus.
However, defective components are a large primary cause of
failures, which is logical for new installations. Correlation
between the two tables below is clearly evident from the con-
tributing cause of exposure to contaminants and the primary TABLE X
SWITCHGEAR B U S B A R E
cause of inadequate maintenance, Exposure to contaminants.
which includes dust. moisture. and chemicals, also supports OUTDOOR INDOOR
the data showing outside bus with a relatively high failure rate. Sampl e-Size
Inadequate maintenance was reported as the single largest U n i t -Year 2750 22339
primary cause of failures in the 1973 and 1974 survey [ 1 1 . FAILURE 8 11
This prompted the effort to survey type of maintenance in the
new survey. FAILURE RATE ,002909 ,000492
APPENDIX E SURVEY OF INDUSTRIAL PLANTS AND COMMERCIAL BUILDINGS

TABLE XI
SWITCHGEAR BUS (OVERALL)

CXt"lOOR INDOOR
Sample- Size
Unit -Year 7825 42695

FAILURE 15 30

FAILURE RATE .001917 .000703


TABLE XI1
F A I L U R E DURATION:ROUND CLOCK VERSUS NORMAL HOUR
(HOURS DOWNTIME PER FAILURE)
FAILURE
REPAIR BUS INSULATED BUS BARE
URGENCY MEDIAN AVERAGE MEDIAN AVERAGE

ROUND CLOCK 24 h r . 87 h r . 32 h r . 39 h r .

NORMAL HOUR 2 4 0 h r . 430 h r . 24 h r . 154 h r .

TABLE XI11
FAILURE DURATION: ROUND CLOCK VERSUS NORMAL HOUR
(HOURS DOWNTOWN PER FAILURE)
BUS INSULATED BUS BARE
ROUND NORMAL ROUND NORMAL
CLOCK HOUR CLOCK HOUR

25 PERCENTILE 8 hr. 8 hr. 3 hr. 4 hr.

50 PERCENTILE 2 4 h r . 2 4 0 h r . 32 h r . 24 h r .

75 PERCENTILE 4 8 h r . 350 h r . 4 8 h r . 48 hr.

TABLE XIV
FAILURE REPAIR URGENCY

ROUND NOWL SCHEDULE


CLOCK HOUR LATER
BUS INSULATED 64% 28% 8%

BUS BARE 53% 41% 6%

TABLE XV
NUMBER OF SWITCHGEAR BUS-INSULATED FAILURES VERSUS
MAINTENANCE CYCLE

L E S S THAN MORE "AN


12 Mo. 12-24 MO. 24 MO.

Sample-Size
(hit-Year) 3563 8812 7253

I FAILURE 2' 13
_I
6'

FAILURE RATE - .001475


* Small sample size.

222
IEEE-IAS TRANSACTIONS MAR/APR 1979

TABLE XVI TABLE XIX


N U M B E R OF S W I T C H G E A R B U S B A R E F A I L U R E S V E R S U S FAILURE TYPE
MAINTENANCE CYCLE
BUS BUS
L E S S THAN MORE THAN INSULATED BARE
12 MO. 1 2 - 2 4 MO. 24 MO.
57% 33% 1. Short L-G
Sample- Size
(Unit-Year) 980 10,455 6312 40% 60% 2. Short L - L
# FAILURE 2' 12 4'
7% 3. Open
FAILURE RATE - .001147
3% - 4. Other
* Small sample size.
Forlure TIP
T A B L E XVlI The survey results o n types o f failures. shown ~n Table X I Y
SUSPECTED PRIMARY C A U S E O F F A I L U R E show I rurprirmgiy high percentage of fadurer line lo lkne

G E N t R A L DlSCUSSlON
BUS BUS
INSULATED BARE A i this point 11 IS well f o note the contidence ~nterualsof
failure race far bare and insulated bur Table XX shows t h e
26% I'% 1 Defective colnponent i a 90 percent confidence ~nierval T h e rable l l l ~ ~ l r a l ~ ~
l h ~ t lor
the statisiical lirnm uithin which 90 percent o f [he failures
4". 4: 2 . Improper Appllcatlon could he expected to occur
Lack of specific derails limits the integrity of some data.
7'. 9
'
. 3 . Improper H a n d l I n g
and as previously indicated not all categories surveyed were
7: 13% 4. ~ m p r o p e r Installation reported in this paper due primarily lo small rample m e i and
numbers o f fadurer As with most ~ u l v e y raccurale data corn
19% 22: 5.- ~ n a d e q u a t ewintenance bined with large response are difficult to ohtam smce rerponre
definitelv rclafes I O simplicity in quertionnaire format Data o f
. 18% 6 . I m p r o p e r operating Procedure the effect of maintenance on fatlure rate are hi&hly desirable
for obvious rearonr. and effort wiil bo made IO acqutre thlr
11% 4% 7 . ~ u r s l d e~ g e -~ Personnel
y data in the future in a meaningful and usable form

26: - 8 . Outside Agency - Other

~ 13% 9. OYerheatlng

TABLE XVIll
C O N T R I B U T I N G CAUSE TO F A I L U R E

BUS BUS
INSUWTLD BbRL

6 6i - I mcrmoc).clIng
TABLE XX
3% 8% 2 . Mechanical Structure Failure
CONFIDENCE INTERVALS FOR FAILURE R A T E A
6 6% ~ J Necham'al Oalnage From Foreign
Source
~~-
15% 1 Shorting By T o o l s or Merat FAILURE RATE ( A ) INSULATED RARE WJS PARE BUS
Ob,ecrs FAILURE PER W I T - Y R BUS > 6 0 0 V > 600V < 600V
3% ~ 5 . Shorting By Snakcr. B i r d s ,
Rodentr, e i c A L ' .DO0779 .000958 .000521
10% 18 6 . Matfuncrlon of P r o f r c f ~ u eD c v l c e
A .001129 .001917 .000802
4'. 7 ,mproper serr,ng o f PTotective

A U * .001569 ,003488 .001203

% DEVIATION - L 31% 5 0% 35%

% DEVIATION - U 39% 82% 50%

* Upper and lower limits of 90 percent confidence interval for A.

223
APPENDIX E SURVEY OF INDUSTRIAL PLANTS AND COMMERCIAL BUILDINGS

APPENDIX Our schedule dictates that responses be received no later


than April 1. 1977. Your participation in this project will be
A. D. Patton
greatly appreciated
Texas A & M University
Department of Electrical Engineering Sincerely.
College Station, Texas 77843
A. D. Patton
Dear Sii
Chairman, Reliability Subcommittee
RE: Switchgear Bus Reliability Survey for Metalclad and Metal
Enclosed Switchgear SURVEY QUESTIONNAIRE
The Reliability Subcommittee of the Industrial and Coni-
Primaty Cause of Failure:
mercial Power Systems Committee requests your cooperation
in a survey to determine the reliability of metal-clad and 1) defective component.
metal-enclosed switchgear bus in industrial plants. The survey 2) improper application.
is a follow-up to the general reliability survey of plant equip- 3) improper handling.
ment in 197 1 and is intended to provide more meaningful data 4) improper installation.
on switchgear bus. Attached for your information is a report 5) inadequate maintenance.
by the subcommittee on reasons for the survey. 6) improper operating procedures
The results of the survey will be published in an IEEE paper 7) outside agency- personnel,
and are expected to be of value to system planners and designers 8) outside agency other.
in the reliability evaluation of alternatives. Individual responses 9) overheating.
will be held in confidence and only summaries published.
Contributing Cause to Failure:
SURVEY INSTRUCTIONS I) persistent overloading,
It is hoped that the survey form is reasonably self-explana- 2) transient overvoltage.
tory. Nevertheless. a sample filled-out data sheet is attached 3) overvoltage,
for your guidance, and some brief instructions follow. We wish 4) therniocycling.
to emphasize that all requested data are important. but it is 5) mechanical structural failure,
realized that some of the requested information may be un- 6) mechanical damage from foreign source.
known. In such cases, simply provide the information whlch 1s 7) shorting by tools or metal objects. ’
known and leave the other spaces blank, We also encourage 8) shorting by snakes, birds, rodents, etc..
you to provide explanatory comments on any of your data as 9) malfunction of protective device.
you feel appropriate. If additional data sheets are needed, I O ) improper setting of protective device.
please duplicate the data sheet provided. 1 1 ) above normal ambient temperature,
12) below normal ambient temperatures,
General Dora 13) exposure to chemicals or solvents.
1) It is vitally important that the period reported be given. 14) exposure to moisture.
2) The plant climate and contamination data should be 15) exposure to dust or other contammants.
your general estimates of the requested information. 16) exposure to nonelectrical fire or burning
17) obstruction of ventilation,
Total Population Data 18) normal deterioration from age,
1) Using the total population data block. give requested 19) severe weather conditions,
data for all buses in service during the period reported 20) loss or deficiency of cooling medium,
whether or not failures have been experienced. (Note the 2 I) testing error.
period reported may not exceed the age of a bus. Use Comments:
separate data sheets for newer busses.)
2) It is vitally important that the number of connected cir-
cuit breakers and switches be given for each bus.

Failed Unit Data


1) List each bus failure event separately REFERENCES
2) Identify the bus in each failure event by specifying the
[ 1 1 IEt 1. Committee Report, “Report on reliability surve) of indus-
bus number as assigned in the total population data trial plant,” fh2.E Trnris Ind. A p p l . Mar iApr., JulyiAug.. and
block. Sept./Oct., 1974. (Part 1 -Reliability of electrical equipment; Part
3-Causes and types of failures of electrical equipment. the
3) Specify failure cause and contributing cause, where methods of repair, and the urgency of repair;Part 5-Plant cliniatr.
known, using the code numbers on the attached sheet. atmosphere and operating schedule, the average age of electrical
4) Specify months since bus was last maintained. equipment, percent production lost. and the method of restoring
electrical service after a failure; Part 6-Maintenance quality o f
5 ) Check off urgency of restoration effort. electrical equipment.)
6) Specify time in hours from onset of failure until bus was 121 l E t E Committee Report, “Reasons Tor conducting a new relia-
restored to service. bil~tysurvey on switchgear bus-insulated and switchgear bus-bare,”
Industrial and Commercial Power System Tech Conf., May 1977,
7) Describe component which first failed, including com- Conf. Rec.. p 91-95.
ponent material

224

You might also like