Data Sheet For Pressure Gauge and DP Gauge

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Copyright © 2015 DATASHEET KPGA40 Print:06-08-2021 10:48:17

1 Installation area data


2 B51 Installation location Outdoor installation B67 Remote hazardous area class Zone 2, Group IIC
3 B52 Corrosive influence by(1) B68 Remote area min. ign. temp. T3 (> 200 °C)
4 B53 Ambient temp.[min]\[max] 5.6 47 °C B69 Max. allow. sound press. level
5 B54 Ambient work temp.[min]\[max] B20 Remark(1)
6 B55 Max. relative humidity 89 % B21 Remark(2)
7 B57 Altitude above sea level
8 Location data (HP) Location data (LP)
9 B04 PI-Diagram/Sheet no. 854-15-014 B04 PI-Diagram/Sheet no.
10 B80 Reference location 15-EHCHC-20"-01402-DCER61-H235
* B80 Reference location
11 B84 Pipe spec. selected DCER61 B84 Pipe spec. selected
12 B92 Line material A333 GR6/A671 GR.CC60 CL22(H2) B92 Line material
13 B10 Nozzle [no.]/[length] B10 Nozzle [no.]/[length]
14 B61 Nozzle [DN]\[PN] B61 Nozzle [DN]\[PN]
15 B88 Nozzle [lining]\[inside dia] B88 Nozzle [lining]\[inside dia]
16 B70 Design pressure [min]/[max] -1 53.5 bar-g B70 Design pressure [min]/[max] bar-g
17 B72 Design temp. [min]/[max] 105 340 °C B72 Design temp. [min]/[max] °C
18 B35 Steam out \ Full vacuum B35 Steam out \ Full vacuum
19 B98 Remark(1) B98 Remark(1)
20 B99 Remark(2) B99 Remark(2)
21 Process data (HP) Process data (LP)
22 B25 Fluid Hydrocarbon B25 Fluid
23 B39 Special fluid properties(1) B39 Special fluid properties(1)
24 B40 Special fluid properties(2) B40 Special fluid properties(2)
25 B46 Water hazard class (WHC) B46 Water hazard class (WHC)
26 B47 Indicat.of danger (67/548/EEC) B47 Indicat.of danger (67/548/EEC)
27 B50 Pollution restriction B50 Pollution restriction
28 B48 Inline hazardous area B48 Inline hazardous area
29 B26 Phase Liquid B26 Phase
Runcase value min. norm. max. unit Runcase value min. norm. max. unit
30
31 D24 Operating pressure p1 27.3 27.3 bar-g D24 Operating pressure p1 26.6 23 bar-g
32 D30 Operating temperature t1 113 113 °C D30 Operating temperature t1 113 113 °C
33 D59 Remark(1) D59 Remark(1)
34 D60 Remark(2) D60 Remark(2)
35 Component process design Component process design (continued)
36 N01 Manufacturer * T89 Calculated diff.-pressure 4.3 bar
37 N02 Manufacturer model no. * N04 Calibration range [lower]/[upper] 0 5 bar
38 N03 Type of construction DP Gauge N05 Calc zero[elevatn.]/[suppress.]
39 N10 Cleaning requirement N06 Nomin. accuracy grade +/- 2,0 % of full scale
40 N11 SIL Class N07 Overload protection 1.3 of measuring range
41 F01 N12 Remark(1)
42 F02 N13 Remark(2)
43 N08 Compon. conn. HP [style]/[stand.] Threaded ANSI B1.20.1 T75 Compon. conn. LP [style]/[stand.] Threaded ANSI B1.20.1
44 N43 Compon.conn.HP[DN]\[PN] 1/2 Inch NPT (F) T60 Compon.conn.LP[DN]\[PN] 1/2 in NPT (F)
45 N44 Facing compon. conn. HP T62 Facing compon. conn. LP
46 N42 Compon. conn. location HP T90 Compon. conn. location LP
47 N09 Material body/process conn. HP SS316 T77 Material body/process conn. LP SS316
48 N97 Material meas. cell(wetted) HP SS316 N99 Material meas. cell(wetted) LP SS316
49 Mechanical design Additional accessories / Material part no.
50 N14 Enclosure protection class IP 65 N34 Mount. set incl. in delivery Yes 2" Vertical Pipe Mounting
51 N15 Case[type]\[style] Bayonet type Bezel ring N35 Mounting set material/coating SS 304
52 N16 Material case SS 316 N60
53 N17 Case filling No N61
54 N18 Indicator size/diam. 150 mm N62
55 N19 Dial scale type Round, 270 ° N37 Remark(1) Special material testing:H2 service
56 N41 Scale resolution N38 Remark(2) Selected gauge shall withstand design pressure
57 N20 Pointer adjustment Yes, Internal
58 N21 Graduation and color Linear, scale div. black
59 N22 Material [dial]\[window] Aluminium shatter proof glass
60 T68 Repeatability
61 F01 Blow Out Disk Required, Rear Side
62 F02 Movement Material SS 304
63 N25 Remark(1) Dial Clolour : White with black graduations
64 N26 Remark(2) and yellow,green & red band
TAG Identific. 15-PDI -01403 Part no. Instr. Type: Differential Pressure Gauge

UAN / Code C4HU_OPAL /


Instrument Data Sheet Plant C4 Hydrogenation
0 06-08-2021

R Date Client Doc ID:


Doc. ID-Code: 15-PDI -01403-SP CC: UA: Form No: 27 Page S-33 / 33