ATTENUATION DESIGN
In accordance with CIRIA publication C753 - The SUDS Manual
Tedds calculation version 1.0.04
Table equations
Peak flow; Qpost_imp = cr Imax Aimp
Runoff volume; Vpost_imp = Qpost_imp D / cr
Post development runoff; Qpost = Qpost_imp + Qpost_open
Permitted discharge; Oexist = Q D
Post development runoff volume; Ipost = Qpost_open D + Vpost_imp
Storage volume required; Spost = Ipost - Oexist
Duration 100 year Rainfall Peak Runoff Post Permit Post Storage
(min) rainfall intensity flow volume dev. dischrge dev. vol. reqd
(mm) (mm/hr) (m3/s) (m3) runoff (m3) runoff (m3)
(m3/s) vol (m3)
5 11.1 133.1 0.11 25.3 0.11 1.03 25.87 24.84
10 15.8 94.6 0.08 35.9 0.08 2.05 37.10 35.05
15 19.3 77.3 0.06 44.1 0.07 3.08 45.83 42.75
30 24.5 49.0 0.04 55.8 0.04 6.15 59.35 53.20
60 29.9 29.9 0.02 68.2 0.03 12.31 75.25 62.95
120 35.1 17.5 0.01 80.0 0.02 24.61 94.05 69.44
240 40.1 10.0 0.01 91.5 0.01 49.23 119.58 70.35
360 43.6 7.3 0.01 99.3 0.01 73.84 141.41 67.56
600 47.9 4.8 0.00 109.3 0.01 123.07 179.46 56.39
1440 56.6 2.4 0.00 129.1 0.00 295.37 297.47 2.11
Interception storage
Interception rainfall depth; dint = 5 mm
Volume of interception storage required; Vint_req = 0.8 Aimp dint = 9.12 m3