General 5
CBX series, up to 12 kV
29
fixed version
CVX series, up to 12 kV
36
fixed/withdrawable version
Order forms 48
1
Customer requirements
High Safety
Ease of installation
Robustness
2
Our solutions
Our proven range of vacuum contactors offers the best solution to suit MV feeders for
industrial projects. They have a fast switching rate and a long mechanical life.
The design and contact materials fulfil the general requirements for contactor applications
of motor starters, transformers or capacitor bank feeders (incl. back-to-back installations) in
various industrial sectors.
High safety
> Highly visible mechanical indicators
> No hazardous tripping
> Comprehensive interlocks
> Strict application of quality standards
> Compliance with the highest standards
> Certification by independent organizations
Ease of installation
> Usage for all application in medium voltage
> Compact dimensions
> Easy to integrate into any panel
> Easy to operate, well suited for retrofit
> Environmentally friendly with no gas or oil interrupting medium
Robustness
> Extremely resistant to harsh environments
> Solid construction
> High mechanical stability against vibrations, altitude and temperature
> Limited Maintenance
Our components add value
to your installations
4
Fixed and withdrawable
vacuum contactors up to 12 kV
General
Presentation 6
Applications 6
Product range 9
5
Fixed and withdrawable
vacuum contactors up to 12 kV
General
Presentation
B BSC_0049.eps
Bearing
of this ongoing effort to be the pacesetter in the field.
Flexible bellows
It features:
Ceramic envelope bbUp to 12 kV, AC3/AC4 duty for motors, transformers, resistors
Bellows shield
Spatter shield and general switching
Contacts (open) bbLow chopping current up to 0.5 A
Contacts (closed)
bbHigh interrupting current up to 6 kA
Fixing contact Fixing end plate
bbUp to 12 kV, AC3/AC4 duty for capacitor switching
bbLow shopping current up to 2.3 A
bbHigh interrupting current up to 4.5 kA
PM100225.eps
Applications
Vacuum contactors are mainly used in MV switchboards for high
requirement applications such as motor starting applications, and
applications in the Industrial, Mine & Metal or Oil & Gas sectors.
Industries, Mine & Metal or Oil & Gas. They can be used in more
specific activities such as public lighting or power factor correction.
6
Fixed and withdrawable
vacuum contactors up to 12 kV
General
Protected environment
Schneider Electric is committed to a long-term environmental
approach. All necessary measures have been taken in connection
with our services, suppliers and subcontractors to ensure that the
materials used in the composition of the equipment do not contain
any substances prohibited by regulations and directives.
In order to help you protect the environment and relieve you of any
concerns in terms of stocking or dismantling, Schneider Electric
Services offers to take back your equipment at the end of its life.
Certification
The certificate of conformity provides guarantees that the vacuum
contactor:
bbhas been subject to type tests according to EN 45001
standard procedures in accredited laboratories by independent
organizations
bbis in conformity with recognized international standards
Our range of vacuum contactors is currently being certified by
external EN 45011 accredited organizations, members of the STL
(Short circuit Testing Liaison):
bbEN 45001: general requirements for the competence of testing
and calibration laboratories
bbEN 45011: general requirements for bodies of operating product
certification systems
7
Vacuum contactor
range
8
Fixed and withdrawable
vacuum contactors up to 12 kV
Vacuum contactor range
CLX series
> CLX: For motor starters up to 7.2 kV, offering front access to
terminals with its slim line
CBX series
> CBX/CBX-C/CBXS-C: A cubic arrangement for up to 7.2 kV &
12 kV applications
bbThree-phase or single-phase
bbInductive load or capacitive load category
bbMechanical interlock between two contactors for motor reverse
commands
CVX series
> CVX-C-F: A fixed type of CBX for capacitive switching
applications equipped with fuse holders (DIN or BS standard) up
to 12 kV
9
Fixed and withdrawable
vacuum contactors up to 12 kV
Vacuum contactor range
PM103792.eps
PM103789.eps
PM103784.eps
PM103787.eps
Functions
Protection and control of network
Rated voltage
3.6 kV 7.2 kV 7.2 kV 12 kV 7.2 kV 12 kV
Number of poles
3P 3P 1Р - ЗР 3P 3P
Mechanical switching cyc/es (ON/OFF)
250,000 (mechaпical latch) 250,000 (mechaпical latch) 250,000 (mechaпical latch) 250,000 (mechaпical latch) 250,000 (mechaпical latch)
апd 1,000,000 (magпetically апd 1,000,000 (magпetically апd 1,000,000 (magпetically апd 1,000,000 (magпetically апd 1,000,000 (magпetically
held) held) held) held) held)
Mechanism
Magnetic Magnetic Magnetic Magnetic Magnetic
or mechanical latch or mechanical latch or mechanical latch or mechanical latch or mechanical latch
IEC staпdards IEC staпdards IEC, GB (Chinese) standards IEC, GB staпdards IEC, GB staпdards
Benefits
Special withdrawable version Froпt access to terminals Special version available for ● High short circuit breaking ● High short circuit breaking
for capacitor banks capacitor bаnks capacity in combinatioп capacity in combinatioп
with fuses with fuses
● LV supply thaпks to optional
оn board VТ
10
Fixed and withdrawable
vacuum contactors up to 12 kV
Vacuum contactor range
11
12
Fixed and withdrawable
vacuum contactors up to 12 kV
Vacuum contactor range
Order forms
CPX/CPX-C, up to 3.6 kV fixed version 48
CLX, up to 7.2 kV fixed version 49
CBX/CBX-C/CBXS-C, up to 12kV fixed version 50
CVX series, up to 12 kV fixed version /withdrawable version 51
13
Vacuum contactor range CPX/CPX-C series, up to 3.6 kV
fixed version
Front view
PM100226.eps
Pivot point
Main terminals (top)
Auxiliary block
Vacuum switch
Main moulding
Rear view
PM100227.eps
Opening spring
Applications
CPX/CPX-C vacuum contactors are three phase switching devices, and
each phase has a separate vacuum switch which switches at the first
available current zero point.
bbCPX: Up to 3.6 kV, for motor starting/reversing applications
bbCPX-C: Up to 3.6 kV, for capacitor bank switching applications
14
Vacuum contactor range CPX/CPX-C series, up to 3.6 kV
fixed version
Main characteristics
CPX CPX-C
Electrical characteristics according to IEC 60470
Phase to phase distance mm 63.5 63.5
Rated voltage Ur kV 50/60 Hz 3.6 3.6
Insulation power frequency withstand Ud kV 50/60 Hz 1 min 10 10
level
lightning impulse withstand Up kV peak 40 40
Rated operational current Ith A 400 315
Rated thermal current Ie A 400 400
Rated short-circuit breaking current Isc kA 6 4.5
Rated short-time withstand current Ik/tk kA/1 s 6 5
Rated peak withstand current Ip kA 15 12.5
15
Vacuum contactor range CPX/CPX-C series, up to 3.6 kV
fixed version
Description of functions
Basic frame
PM100228.eps
(4)
Power part
PM100229.eps
(9)
For vacuum contactors CPX/CPX-C, 3 pieces of power parts are
assembled whereby each power part consists of:
bb(6) Vacuum switch
bb(7) Main terminals (top)
(7) bb(8) Main terminals (bottom)
(6) bb(9) Phase assembly
For the vacuum switch type,
(8)
bbVS2 is for CPX, inductive load category
bbVS2-C is for CPX-C, capacitive load category
Closing coil
PM100230.eps
16
Vacuum contactor range CPX/CPX-C series, up to 3.6 kV
fixed version
Auxiliary contact
PM100231.eps
bbAC 110-240 V
17
Vacuum contactor range CPX/CPX-C series, up to 3.6 kV
fixed version
Dimensions
230
PM100241.eps
PM100238.eps
207
193
103
13
230
PM100239.eps
PM100238.eps
193
207
230 103
13
18
Vacuum contactor range CPX/CPX-C series, up to 3.6 kV
fixed version
T (2 pts) AS 1 AS 2
+ 20 22 24 42 40 20 22 24 42 40
CC1 1 CC2 1
2 2
- 21 23 25 43 41 21 23 25 43 41
L1 L2 L3
T (4 pts) AS 1 AS 2
1 3 21 23 25 43 41 21 23 45 43 41
CC1 CC2 TC
1 2 1
2 1 2
2 4 20 22 24 42 40 20 22 44 42 40
L1 L2 L3
19
Vacuum contactor range CPX/CPX-C series, up to 3.6 kV
fixed version
T (2 pts)
1
AS 1 AS 2
20 22 24 42 40 20 22 24 42 40
GB
- +
V
CC1 1 CC2 1
2 2
21 23 25 43 41 21 23 25 43 41
L1 L2 L3
T (4 pts) AS 1 AS 2
1 3 21 23 25 43 41 21 23 25 43 41
GB
- + CC1
1
CC2
1 TC
V 1
2 2
2
2 4 20 22 24 42 40 20 22 24 42 40
L1 L2 L3
20
Vacuum contactor range Spare parts
Spare parts *
Auxiliary switch
3.6 kV 400 A Inductive load Magnetical hold 2NO + 1NC
PM100231-red.eps
Coils
3.6 kV 400 A Inductive load DC 24 V
PM100230-red.eps
Mechanical latch
3.6 kV 400 A Inductive load
PM100232-red.eps
Tripping coil
3.6 kV 400 A Inductive load DC 24-30 V
PM100233-red.eps
*: The spare parts could be ordered through the logistics of the manufacturing plant.
21
Vacuum contactor range CLX series, up to 7.2 kV
fixed version
Front view
Main terminals
PM100242.eps
Main terminals
Moulded terminals
bar Isolating rod
Flexible connection
Auxiliary switches
Electronic card
Rear view
4 x M10 fixing holes
PM100243.eps
Pivot point
L shaped armature
Applications
CLX vacuum contactors are three phase switching devices, and each
phase has a separate vacuum switch that switches at the first available
current zero point.
bbCLX: Up to 7.2 kV, for motor starting/reversing applications
22
Vacuum contactor range CLX series, up to 7.2 kV
fixed version
Main characteristics
x CLX
Electrical characteristics according to IEC 60470
Phase to phase distance mm 120
Rated voltage Ur kV 50/60 Hz 7.2
Insulation power frequency withstand Ud kV 50/60 Hz 1 min 20
level
lightning impulse withstand Up kV peak 60
Rated operational current Ith A 400
Rated thermal current Ie A 400
Rated short-circuit breaking current Isc kA 6
Rated short-time withstand current Ik/tk kA/1 s 6
Rated peak withstand current Ip kA 15
23
Vacuum contactor range
CLX series, up to 7.2 kV
fixed version
Description of functions
Basic frame
PM100244.eps
(1)
(4)
(2)
(3)
Power part
(5)
PM103052.eps
For the vacuum contactors CLX, 3 pieces of power parts are assembled,
every power part includes:
bb(5) Main terminals (top)
bb(6) Main terminals (bottom)
bb(7) Vacuum switch
(6)
(7)
For the vacuum switch type,
bbVS3 is for CLX, inductive load category
PM103053.eps
Closing coil
For the vacuum contactors CLX, 2 pieces of closing coils are assembled,
every piece of closing coil has various options for supply voltage:
bbDC 24-60 V
bbDC 110-250 V/AC 110-240 V
PM103054.eps
Auxiliary contact
For the vacuum contactors CLX, various auxiliary contacts are assembled
and optional:
For electromagnetic hold mechanism:
bb5NO + 5NC, right hand side assembly, without opening delay
bb5NO + 5NC, right hand side assembly, with 100 ms opening delay
24
Vacuum contactor range CLX series, up to 7.2 kV
fixed version
bbDC 24-30 V
bbDC 48-60 V
bbDC 110-250 V/AC 110-240 V
Electronic card
PM103067.eps
For the vacuum contactors CLX, a set of electronic card is equipped, and
has various options for supply voltage:
bbDC 24-60 V
bbDC 110-250 V/AC 110-240 V
Operations counter
PM103057.eps
25
Vacuum contactor range
CLX series, up to 7.2 kV
fixed version
Dimensions
PM103059.eps
142
210
398.5
231.5
155
47
334
411.5
PM103060.eps
142
210
398.5
231.5
155
47
334
411.5
26
Vacuum contactor range CLX series, up to 7.2 kV
fixed version
1
Carte Electronique
CC1
Electronic Card 2
2
CC2 1 1 1 1 1 1 1 1 1 1
- + 1
Alimentation
Vdc ou Vac
Vdc or Vac supply
S11 S21 S12 S22 S13 S23 S14 S24 S15 S25
2 4 2 42 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4
L1 L2 L3
1
Carte Electronique
CC1
Electronic Card 2
1 TC
2
2 CC2 1 1 1 1 1 1 1 1 1 1
- + 1
Alimentation
Vdc ou Vac
Vdc or Vac supply
S11 S21 S12 S22 S13 S23 S14 S24 S15 S25
2 4 2 42 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4
L1 L2 L3
27
Vacuum contactor range Spare parts
Spare parts *
Auxiliary switch
Right hand side switch
PM103054-red.eps
Coils
7.2 kV 400 A Inductive load DC 24-60 V
PM103053-red.eps
110-250 V
AC 110-240 V
Mechanical latch
7.2 kV 400 A Inductive load
PM103055-red.eps
Tripping coil
7.2 kV 400 A Inductive load DC 24-30 V
PM100233-red.eps
48-60 V
110-250 V
AC 110-240 V
Electronic card
7.2 kV 400 A Inductive load DC 24-30 V
PM103067-red.eps
110-250 V
AC 110-240 V
Operations counter
7.2 kV 400 A Inductive load
PM103057-red.eps
*: The spare parts could be ordered through the logistics of the manufacturing plant.
28
Vacuum contactor range CBX/CBX-C/CBXS-C series,
up to 12 kV fixed version
Front view
PM103061.eps
Armature moulding
Operations counter
Closing coil
Electronic card Stop pin
Rear view
PM103062.eps
Phase assembly
Main moulding
Vacuum switches
Main terminals (bottom)
Applications
CBX/CBX-C vacuum contactors are three phase switching devices,
and each phase has a separate vacuum switch that switches at the first
available current zero point.
bbCBX: Up to 7.2 kV, for motor starting/reversing applications
bbCBX-C: Up to 12 kV, for capacitor bank switching applications.
(1) For the application of single phase contactor CBXS-C, please consult us for details.
29
Vacuum contactor range CBX/CBX-C/CBXS-C series,
up to 12 kV fixed version
Main characteristics
30
Vacuum contactor range CBX/CBX-C/CBXS-C series,
up to 12 kV fixed version
Description of functions
PM103077.eps
Basic frame
For vacuum contactors CBX/CBX-C, the basic frame comprises by:
bb(1) Main moulding
bb(2) Armature moulding
bb(3) Two pivot points
(2)
bb(4) A steel mounting plate
bb(5) Stop pin
(1) (4)
(3) (5)
Power part
PM103078.eps
(8)
Closing coil
PM103053.eps
Auxiliary contact
PM103079.eps
31
Vacuum contactor range CBX/CBX-C/CBXS-C series,
up to 12 kV fixed version
Electronic card
PM103067.eps
Operations counter
For vacuum contactors CBX/CBX-C, an operations counter is equipped.
32
Vacuum contactor range CBX/CBX-C/CBXS-C series,
up to 12 kV fixed version
Dimensions
Weight kg 28 28
193 348
PM103073.eps
153.5
258
65 66
+1
343 -10
193 348
PM103074.eps
153.5
258
65 66
33
Vacuum contactor range CBX/CBX-C/CBXS-C series,
up to 12 kV fixed version
1
Carte Electronique
CC1
Electronic Card 2
2
CC2 1 1 1 1 1 1 1 1 1 1
- + 1
Alimentation
Vdc ou Vac
Vdc or Vac supply
S11 S21 S12 S22 S13 S23 S14 S24 S15 S25
2 4 2 42 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4
L1 L2 L3
1
Carte Electronique
CC1
Electronic Card 2
1 TC
2
2 CC2 1 1 1 1 1 1 1 1 1 1
- + 1
Alimentation
Vdc ou Vac
Vdc or Vac supply
S11 S21 S12 S22 S13 S23 S14 S24 S15 S25
2 4 2 42 4 2 4 2 4 2 4 2 4 2 4 2 4 2 4
L1 L2 L3
34
Vacuum contactor range Spare parts
Spare parts *
Auxiliary switch
Right hand side switch
PM103079-red.eps
Coils
7.2 kV 400 A CBX Inductive load 24-60 Vdc
PM103053-red.eps
110-250 Vdc/110-240Vac
Mechanical latch
7.2 kV 400 A CBX Inductive load
PM103080-red.eps
Tripping coil
7.2 kV 400 A CBX Inductive load DC 24-30 V
PM100233-red.eps
Electronic card
7.2 kV 400 A CBX Inductive load DC 24-30 V
PM103067-red.eps
AC 110-240 V
Operations counter
7.2 kV 400 A CBX Inductive load
PM103057-red.eps
Cover
7.2 kV 400 A CBX Inductive load
PM103087.eps
*: The spare parts could be ordered through the logistics of the manufacturing plant.
35
Vacuum contactor range CVX series, up to 12 kV
fixed version /
withdrawable version
Description of the device
PM103792.eps
Armature moulding
Operations counter
Closing coil
Electronic card Stop pin
Phase assembly
Main moulding
Vacuum switches
Main terminals (bottom)
36
Vacuum contactor range
CVX series, up to 12 kV
fixed version /
withdrawable version
Enclosure for CVX-C-F/CVX-07/CVX-C-07
Mainly contains:
bbLV plugging-in plug
bbIndicators (C/O, fuse fusion, operations counter)
bbHandling bar
bbHandles (not for CVX-C-F)
bbOperation holes for crank (not for CVX-C-F)
PM103081.eps
Hardling bar
(only for handling)
LV plug
Handle
Hardling bar
(only for handling)
LV plug
Handles Handle
C/O indicator
37
Vacuum contactor range CVX series, up to 12 kV
fixed version /
withdrawable version
Fuse holder for CVX series
Mainly contains:
bbFuse holder
bb DIN fuse: 442 mm / 292 mm with extension. Or BS fuse: 454 mm / 410 mm /
305 mm.
bbThe fuses are not standard configuration
Fuse holder
PM103083.eps
442mm fuse
(not defaut configured)
It mainly contains:
bbSpindle
bbSlide
bbWheels
bbLocking shaft
PM103084.eps
Spindle
38
Vacuum contactor range
CVX series, up to 12 kV
fixed version /
withdrawable version
Option: cradle
The cradle is used to enable the rack in and rack out functions of
contactor through rising shuttle mechanism interlocking and earthing
switch mechanism. This allows easy integration of CVX for the panel
builders.
Adaptation for:
bbCVX-07/CVX-C-07 (Width = 400 mm)
bbCVX-C-12 (Width = 650 mm)
PM103085.eps
PM103086.eps
39
Vacuum contactor range CVX series, up to 12 kV
fixed version /
withdrawable version
Main characteristics
CVX-07 CVX-C-07 CVX-C-12 CVX-C-F
Electrical characteristics according to IEC 60470
Phase to phase distance mm 106 106 185 150
Rated voltage Ur kV 50/60 Hz 7.2 7.2 12 12
Insulation level power frequency withstand Ud kV 50/60 Hz 1 min 20/32 (1) 20/32 (1) 28/42 (1) 28
lightning impulse withstand Up kV peak 60 75 75 75
Rated operational current Ith A 400 (2) 400 (2) 315 (3) 315 (3)
Rated thermal current Ie A 400 (2) 400 (2) 400 (3) 400 (3)
Rated short-circuit breaking current Isc kA 6 (4) 6 (4) 4 (4) 4 (4)
Rated short-time withstand current Ik/tk kA/1 s 8 8 5 5
Rated peak withstand current Ip kA 20 20 12.5 12.5
(1) The value in the brackets is specific for the China market
(2) The rated current linked to the capacity of the fuse: 270 A with a maximum fuse size of 400 A
(3) The rated current linked to the capacity of the fuse: 195 A with a maximum fuse size of 250 A
(4) The rated current linked to the capacity of the fuse: 50 kA for the standard DIN fuse
40
Vacuum contactor range
CVX series, up to 12 kV
fixed version /
withdrawable version
Description of functions
PM103077.eps
Basic frame
For vacuum contactors CBX/CBX-C, the basic frame includes:
bb(1) Main moulding
(2) bb(2) Armature moulding
bb(3) Two pivot points
(1) (4) bb(4) A steel mounting plate
bb(5) Stop pin
(3) (5)
PM103078.eps
Power part
For vacuum contactors CBX/CBX-C, 3 pieces of power parts are assembled.
(7) For CBXS-C, 1 piece of power part is assembled.
Every piece of power part includes:
bb(6) Vacuum switch
bb(7) Main terminals (top)
bb(8) Main terminals (bottom)
(8)
Closing coil
PM103053.eps
41
Vacuum contactor range CVX series, up to 12 kV
fixed version /
withdrawable version
Auxiliary contact
PM103079.eps
A corresponding tripping coil with various options for the supply voltage:
bbDC 24-30 V
bbDC 48-60 V
bbDC 110-250 V/AC 110-240 V
PM100233.eps
Electronic card
For vacuum contactors CBX/CBX-C, an electronic card is equipped, and
has various options for the supply voltage:
PM103067.eps
bbDC 24-60 V
bbDC 110-250 V/AC 110-240 V
Operations counter
For vacuum contactors CBX/CBX-C, an operations counter is equipped.
PM103057.eps
42
Vacuum contactor range CVX series, up to 12 kV
fixed version /
withdrawable version
Dimensions
CVX-07/CVX-C-07
Phase to phase distance mm 106
Weight kg 70
731.5 359
PM103063.eps
106 106
330.5 774
178
212.5
14
67
346
CVX-C-12
Phase to phase distance mm 185
Weight kg 75
737 528.3
PM103064.eps
185 185
340 745
180
208
12.5
63.8
497.5
43
Vacuum contactor range
CVX series, up to 12 kV
fixed version /
withdrawable version
Dimensions
CVX-C-F
Phase to phase distance mm 150
Weight kg 60
450 631
PM103065.eps
75.2 150 150
218
566
268
A/2 E
PM103066.eps
C C
340
44
Vacuum contactor range CVX series, up to 12 kV
fixed version /
withdrawable version
Electric circuit diagram
For CVX-07/CVX-C-07/CVX-C-12 DC & AC supply voltage:
PM103070.eps
A5 A3 C3 B3 D13 A9 A11A13 A15 B9 B11 B13 B15 C13 C15 D11 D15 1
S001
alimentation Vdc ou Vac
S002
Carte Electronique
Electronic Card
TC 2 4
2 E2
S21
S12
S22
S13
S23
S14
S24
S15
S25
S11
1 1 1 1 1 1 1 1 1 1
4 2 244 2 2 4 4 2 2 4 4 2 2 4 4 2 2
S003
4
1
2 4
L1 L2 L3 A6 A4 C4 B4 D14 A10 A12 A14 A16 B10 B12 B14 B16 C14 C16 D12 D16
A B C D E F G H I J
Components:
A: Fuse contactor
B: Closing
C: (Options) tripping coil (for the mechanical latch mechanism)
D: (Options) Blocking magnet (handle)
E: (Options) Control power transformer (only for CVX-07/CVX-C-07)
F: Fuse blowing
G: Auxiliary contact: 5NO + 5NCa
H: Mandatory electrical interlock
I: Plug-in socket
J: Earthing
X0 1 7 3 5 11 21 13 23 15 25 17 27 19 29
S001
S002
1 1
Carte 1 2 4 4 2
Electronique TC
alimentation
Vdc ou Vac 2
Electronic
Card
S11
S21
S12
S22
S13
S23
S14
S24
S15
S25
Vdc or Vac
supply 1 1 1 1 1 1 1 1 1 1
4 2 2 4 4 2 2 4 4 2 2 4 4 2 2 4 4 2 2 4
L1 L2 L3 2 8 4 6 12 22 14 24 15 26 18 28 20 30
A B C D E
Explanations:
A: Fuse contactor
B: Closing
C: (optional) Tripping coil (for the mechanical latch mechanism)
D: Fuse blowing
E: Auxiliary contact: 5NO + 5NCa
45
Vacuum contactor range CVX series, up to 12 kV
fixed version /
withdrawable version
Fuse selection
The table in below contains a summary of the requirements of the
different types of fuse according to the type of load:
Selection rules IA < IN transf. < IB Fixed by IP and tD IN bank x 1.7 < IN fuse
IN motor x 1.2 Insc fixed by î. t
I fusing 10 s Low for close-up protection High Low for close-up protection
I3 No specification
UN 0 to 36 kV 0 to 12 kV 0 to 36 kV
a b c
46
Vacuum contactor range Spare parts
Spare parts *
Auxiliary switch
12 kV 315 A Capacitive load 5NO + 5NC Right hand side switch
PM103079-red.eps
Coils
12 kV 315 A Capacitive load 24-60 Vdc
PM103053-red.eps
110-250 Vdc/110-240Vac
Mechanical latch
12 kV 315 A Capacitive load
PM103080-red.eps
Tripping coil
12 kV 315 A Capacitive load DC 24-30 V
PM100233-red.eps
48-60 V
110-250 V
AC 110-240 V
Electronic card
12 kV 315 A Capacitive load DC 24-30 V
PM103067-red.eps
110-250 V
AC 110-240 V
Operations counter
12 kV 315 A Capacitive load
PM103057-red.eps
*: The spare parts could be ordered through the logistics of the manufacturing plant.
47
CPX/CPX-C,
up to 3.6 kV fixed version
Frequency 50 Hz 60 Hz
Auxiliary contact
For electromagnetic hold mechanism 2NO + 1NC, left side
4NO + 4NC, left & right side 4NO + 4NC, L side & R facing
For mechanical latch mechanism 2NO + 3NC, left side
5NO + 5NC, left & right side 5NO + 5NC, L side & R facing
Gauge YES NO
Remark: Only one of the boxes (ticked or filled by the needed value) has to be
considered between each horizontal line.
48
Order forms
CLX,
up to 7.2 kV fixed version
Quantity
Frequency 50 Hz 60 Hz
Gauge YES NO
Remark: Only one of the boxes (ticked or filled by the needed value) has to be
considered between each horizontal line.
49
Order forms
CBX/CBX-C/CBXS-C,
up to 12 kV fixed version
Frequency 50 Hz 60 Hz
Gauge YES NO
Remark: Only one of the boxes (ticked or filled by the needed value) has to be
considered between each horizontal line.
50
Order forms CVX series,
up to 12 kV fixed version /
withdrawable version
Fixed vacuum contactor, CVX series
PM103792.eps
Quantity
Frequency 50 Hz 60 Hz
Gauge YES NO
Remark: Only one of the boxes (ticked or filled by the needed value) has to be
considered between each horizontal line.
51
Notes
52
ART.XXXXXX ©2014 - Schneider Electric - All rights reserved
RCS Nanterre 954 503 439 Publication: Schneider Electric Industries SAS his document has been
T
Capital social 896 313 776 € Photos: Schneider Electric printed on ecological paper.
www.schneider-electric.com Publishing: Altavia St Etienne
NRJED313585EN 09-2014