RiZone-ReleaseNotes-v3 11 xEN - V3
RiZone-ReleaseNotes-v3 11 xEN - V3
Version: 3.11.9.0
Operating system: Windows Server 2012R2 Standard
Windows Server 2016 Standard
Windows Server 2019 Standard
Platform: OVF, installer
Date: May 2021
http://www.rittal.com/de_de/rimatrix-downloads/
dotNet Framework
To install RiZone 3.10.x or newer dotNet Version 3.5 and 4.8.x is required.
RAM
We recommend that the RAM for existing RiZone installations is increased to 8 GB.
The RAM must be increased to 8 GB when DRC is used in RiZone.
Database
The database for installations commissioned with a RiZone version prior to 2.5.x
must be adapted by executing an SQL script.
The script and a HowTo file are available at the Rittal Service Team.
Using the SQL Express Database Server, the name field will not evaluated.
RiZone 3.11.x supports Microsoft SQL 2017 and Microsoft SQL 2019.
%appdata%Rittal\RiZone\Data\MetaData\DeviceDrivers
C:\Program Files (x86)\Rittal\RiZone\drv\devices\concrete
C:\Program Files (x86)\Rittal\RiZone\ Core\DeviceDrivers
Supported devices
RiZone supports all components of the CMC-TC product family, including CMC III.
The following are excluded in version 3.8.xxx.1 and following versions:
LCP
Bei dem Einsatz der LCP Produktfamilie wird bei einer Änderung der Einheit der
Durchflussmenge von Liter/Minute auf Gallonen/ Minute das LCP nicht in den
Wartungsmodus gesetzt. Es erfolgt eine falsche Darstellung der Einheit in RiZone.
Bei der Umstellung von l/m auf g/m muss das LCP neu entdeckt werden und im
Projektbaum erneuert werden.
LCP VX
When using "Virtual Devices", care must be taken to ensure that the "Virtual Devices"
are configured in the LCP or CMCIII before they are detected by RiZone. If the
configuration is subsequently changed, a display error occurs in RiZone. If the
"Virtual Device" is configured in the CMC after discovery in RiZone, the "Virtual
Devices" must be rediscovered and replaced in the RiZone project.
Known errors
GUI:
1 The GUI is installed with the “Execute as administrator” function.
Server:
The Server is installed with the “Execute as administrator” function.
Device support:
1 To use the CMC III PU firmware update function, the PU must have firmware
version 3.13.xx or later. A remote update is not possible for older firmware
versions.
2 If two access systems, each with their own PU III, are installed in an enclosure,
the behaviour of the one-time PIN in this constellation must be considered. If the
one-time PIN is set on the higher-level infrastructure component (enclosure), both
access systems can be opened with the one-time PIN. If, for example, the front
enclosure door is opened with the one-time PIN, the rear door can also be
opened subsequently with the same one-time PIN.
For a configuration with only one PU III, the one-time PIN allows only the front or
the rear door to be opened.
3 If a device in the project is replaced with an identical device (Discover > ALT-
drag-and-drop to the old device), it must be guaranteed that the same SNMP
connection settings (e.g. the Read- and Write-Community for v1/2c) are set.
5 RiZone 3.9.xx and newer supports PDU Firmware Version 5.15.xx or newer.
6 When creating a third-party device driver, the created default chart must be saved
via the menu. If you close the window with the "x", the changes are discarded.
Communications modules:
1 In additional to the network ports described in Section 29.3 of the RiZone manual,
as of RiZone version 3.6.xx.5, port 22221 is also used for the communication
between the RiZone GUI and the server.
2 As of version 3.8.xx.1, RiZone can write status information in the event log of the
Windows Server operating system.
Meaning of the possible log entries:
Start (1100)
Connection to core (1101)
Project loaded (1102)
Stop (1110)
Error (1120)
Lost connection to core (1121)
Offline configuring:
1 The offline configuring must be performed from top to bottom in the device tree.
Example: For RiMatrix S, the RiMatrix S node must be moved in before fans in
the location tree.
1 The server key is given triple DES encryption and saved on the server. The key is
encrypted with the processor ID and the processor revision. The key is stored on
the server in the folder:
%ProgramData%\Rittal\RiZone\ServerKey.enc
C:\rizone_install\RittalSSLCfg.exe
RZGuiUser
The encryption of the password of the RZGuiUser is done by the CPU ID. If the CPU
ID or the encryption method changes due to an update of the operating system, the
password must be reset in the Windows user administration and in the RiZone GUI
installer.
Variable ElectricalWorkMonthly
When calculating the variable "ElectricalWorkMonthly", the value before the first
calculation is specified with "-100". The value does not get the status "Quality Bad".
Version 3.8.41.1
One-time PIN and the emergency PIN status information will be displayed only inside
the executed GUI (Multiuser operating)
Version 3.9.2x
Sending traps from a workflow is not possible. The Rizone.Messaging service
crashes.