How To Use The KV-FL Setup Tool

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

6

HOW TO USE THE KV-FL


SETUP TOOL
Using the KV-FL Setup Tool provided with KV STUDIO, you can set up
common memory area of KV-FL20V simply by inputting required items as per
the screen instructions.
This chapter describes how to use the KV-FL Setup Tool.

6-1 KV-FL Setup Tool Overview••••••••••••••••••••••••••••••• 6-2


6-2 How to Use the KV-FL Setup Tool ••••••••••••••••••••••• 6-8
6-3 Functions of the KV-FL Setup Tool ••••••••••••••••••• 6-15

- KV-FL20V User's Manual - 6-1


6-1 KV-FL Setup Tool Overview
KV-FL Setup Tool is a software included with KV STUDIO, used to set up common memory area of
KV-FL20V, KV-5000 (FL-net mode) and KV-FL20. This section describes the KV-FL Setup Tool in
general.

Functions of KV-FL Setting Tools

Using KV-FL Setup Tool, you can easily assign the common memory area of KV-FL20V unit (the
memory area for the data FL-net cyclic transmission function).

For data link in KV-FL20 (KV-5000/3000/1000/700) (other than third-party FL-net equipment), FL-net

6 common area can be assigned by inputting leading relay No., leading DM No., and common data size
following the wizard.
If third-party FL-net equipment is used, you can also input the offset and size of FL-net common area
HOW TO USE THE KV-FL SETUP TOOL

by following the wizard to complete the settings easily.

The settings by KV-FL setup tool can also be transferred into the Unit Editor. The settings can also be
printed.

Procedure to Use the KV-FL Setup Tool

The following describes the procedure to set up KV-FL20V common area using KV-FL Setup Tool.

1 Start KV STUDIO Unit Editor, and configure KV-FL20V.

When using KV-5000 's FL-net mode, please select "FL-net" in "Communication mode".

6-2 - KV-FL20V User's Manual -


6-1 KV-FL Setup Tool Overview

2 Click to start the KV-FL Setup Tool.

6
3

HOW TO USE THE KV-FL SETUP TOOL


Please enter leading relay No. and leading DM No. of
KV-FL20V, device type and No. for storing memory
cyclic data and size of the common storage area
according to KV-FL Setup wizard.

4 After inputting all the equipmnet


connected to FL-net, common area will
be displayed.

5 Select "Transfer to Unit Editor".

- KV-FL20V User's Manual - 6-3


6-1 KV-FL Setup Tool Overview

6 Select the data to be transferred, and click "OK".

Setup is completed after transfer is finished.

6
HOW TO USE THE KV-FL SETUP TOOL

Setup of
common area is
finished.

Refresh setup
is finished

6-4 - KV-FL20V User's Manual -


6-1 KV-FL Setup Tool Overview

Screen Name and Function of the KV-FL20 Setup Tool

Display communication area


Display write/read area of the equipment connected to FL-net.

Display communication area


bar graph *1
Display the shared state of bit
device, word device of data
link established by FL-net and
the system area in bar graph
6
fomat *2.

HOW TO USE THE KV-FL SETUP TOOL


*1 Not displayed when connected manually.
*2 System area (occupied area) refers to the area requied by unit operation outside the common
storage area.

- KV-FL20V User's Manual - 6-5


6-1 KV-FL Setup Tool Overview

Possible Data Link setup by KV-FL Setup Tool

The following describes the data links that can be set up by the KV-FL Setup Tool.

■ KV-FL 1:1 connection


Through this connection form, you can connect two KV-5000/3000/1000/700 via KV-FL20V or KV-
5000's built-in Ethernet port (communication mode set to "FL-net") and establish data link (sharing).

Communication mode is set to


6 "FL-net"
HOW TO USE THE KV-FL SETUP TOOL

STP/UTP crossover cable

■ KV-FL 1:N connection


Through this connection form, you can manage slave data through the master. Taking one KV-5000/
3000/1000/700 as the master, while the other one 5000/3000/1000/700 as the slave. Up to 16 slaves
can be set up, including the reserved slaves.

POWER

LINK LINK

1 2
100 100

communication
M M

3 4

5 6
mode is set to
"FL-net"
7 8

NE-V08

PULL

Master Ethernet
switch
(HUB)

Slave station (Max. 16 units)

6-6 - KV-FL20V User's Manual -


6-1 KV-FL Setup Tool Overview

■ Common Data of N KV-FLs


The following graph shows the data link (common) connection of all the KV-5000/3000/1000/700
connected by KV-FL20V. Up to 16 units of KV-5000/3000/1000/700 can be set, including the reserved
slaves.

POWER

LINK LINK

1 2
100 100
M M

3 4
communication
mode is set to
5 6

7 8

NE-V08
"FL-net"
PULL

Ethernet
switch 6
(HUB)

HOW TO USE THE KV-FL SETUP TOOL


■ Manual connection
If third-party FL-net equipment other than KV-FL20V is used, then it can be connected manually. In this
case, the offset and size of FL-net common area should be entered.

- KV-FL20V User's Manual - 6-7


6-2 How to Use the KV-FL Setup Tool
This section describes how to use the KV-FL Setup Tool.

How to Use the KV-FL Setup Tool

1 Start KV STUDIO, and start Unit Editor.


"5-1 How to Set up With Unit Editor", Page 5-2

2 Drag KV- FL20 V to the unit configuration area.


"5-1 How to Set up With Unit Editor", Page 5-2

6 3 Double click the KV- FL20 V to be


configured. The "Unit Setup" tab
HOW TO USE THE KV-FL SETUP TOOL

appears.

4 Click the button.

5 Start the KV-FL setup wizard (KV-FL


Setup Tool).

6-8 - KV-FL20V User’s Manual -


6-2 How to Use the KV-FL Setup Tool

How to Operate the KV-FL Setup Wizard

Select data link mode and click "Next(N)".


"Possible Data Link setup by KV-FL Setup Tool", Page
6-6

HOW TO USE THE KV-FL SETUP TOOL


■ When selecting "KV-FL 1:1 connection", "KV-FL 1:N connection", "Common
Data of N KV-FLs"

1 If you select "KV-FL 1:N Connection" or


"Common Data of N KV-FLs", the number of data
link slaves or the number of common data
equipment should be input.

If you select "KV-FL 1:1 connection", this dialog box


won't appear. Jump to step 4.

2 If you select "KV-FL 1: N connection" or


"Common Data of N KV-FLs", input the number
of slaves that are planned to add in the future.

If you select "KV-FL 1:1 connection", this dialog box


won't appear.

Note
When building the system, if the number of reserved slaves (equipment) is set to "0", the
assignment of relays and data memory of slaves (equipment) may vary when adding slaves
(equipment). Therefore, you should perform unit setup again for the existing KV-FL20V.

- KV-FL20V User’s Manual - 6-9


6-2 How to Use the KV-FL Setup Tool

3 Select slave type (mode), enter every item.

Set up the slaves with corresponding set number of


units.

6 Item Description
Sets the name of equipment.
Slave name However, the set name can only be used in screen display and
HOW TO USE THE KV-FL SETUP TOOL

printing of the KV- FL Setup Tool.


Select the CPU unit and operation mode of KV- FL20V.
Slave type Set KV-5000 's communication mode to "FL-net". To connect via
the built-in Ethernet port, select "KV-5000 (KV-FL20V mode)".
Set the leading No. of the relays used in KV-FL20V (in ch).
R (in ch)
Start No.setting of the The setting range varies according to the CPU units connected.
occupied area Set up DM start No. used in KV-FL20V.
DM
The setting range depends on the CPU unit connected.
Can be set after the "Use auto refresh function" checkbox is
selected. *1
Leading No. of Specifies the device type and leading device No. of CPU unit
area 1 ("ch" unit) for saving data in the common memory area 1 in buffer memory
(in ch).
In area 1, either B (link relay) or R (relay) can be selected.
Auto Refresh
Can be set after the "use auto refresh function" checkbox is
Setting
selected.
Specifies the device type and leading device No. of CPU unit
Area 2 leading
for saving data in the common memory area 2 in buffer
No.
memory.
In area 2, either W( link register) or DM ( Data Memory) can be
selected.
Sets the size of data written into the FL-net common memory
Write size
space 1 by the setting of number of relay channels (words).
Area 1
Setting of the Sets the size of data read from the FL-net common memory
Read size
communicatio space 1 by the setting of number of relay channels (words).
n area Sets the size of data written into the FL-net common memory
Write size
size setting space 2 by the setting of number of the words.
Area 2
Sets the size of data read from the FL-net common memory
Read size
space 2 by the setting of number of the words.
*1 When auto refresh function is not used, you should use UREAD/UWRIT command in Ladder
Program to read/write the expansion buffer memory of KV-FL20V.

6-10 - KV-FL20V User’s Manual -


6-2 How to Use the KV-FL Setup Tool

4 If "KV-FL 1:N connection" or "Common data of N


KV-FLs" is selected, and the numbert of reserved
salves is set to 1 above, and the reserved slaves
should be also set.

If you select "KV-FL 1:1 connection", this dialog box


won't appear.

5 When selecting "KV-FL 1: N connection", set up the 6


master.

HOW TO USE THE KV-FL SETUP TOOL


When setting up the master, the communication area
size will be displayed as the value calculated
automatically via the salve (reserved slave) setting.

After related settings of all equipment connected are


performed, the settings are displayed in a list.

If you select "KV-FL 1:1 connection", this dialog box


won't appear.

Verify the settings, if there is nothing to be changed, click the "Finish" button. If you want to change the
settings, click the "Return (B)" button, and make changes.

- KV-FL20V User’s Manual - 6-11


6-2 How to Use the KV-FL Setup Tool

When all the setting have been done, exit the wizard, the KV-FL Setting Tools list will show (in bar
graph) the relay/DM area occupied by every connected equipment, or the common state of bit device/
word device for establishing the data link.

When the "Use auto refresh


function" check box is selected*,

6 the device No. will be displayed.


HOW TO USE THE KV-FL SETUP TOOL

* If the "Use auto refresh function" checkbox is not checked, then the offset of leading address of buffer
memory of the expansion unit.

■ When selecting "Other than the above connections (manual connection)"

1 Input the total number of data link equipment


connected to FL-net.

6-12 - KV-FL20V User’s Manual -


6-2 How to Use the KV-FL Setup Tool

2 For each equipment connected, set up the leading


address (offset) and size written into the FL-net
common memory area in "word" unit.

6
Item Description

HOW TO USE THE KV-FL SETUP TOOL


Sets the name of equipment. However, the set name can only be used in
Name of the Device Connected
screen display and printing of the KV-FL Setup Tool.
Selects equipment connected to KV-FL20V.
Type of the eguipment
To connect units other than KEYENCE products, select " Equipment other
Connected
than KV-FL".
Leading Sets leading address of common memory when the set equipment writes
(offset) data to common memory area 1 of FL-net.
Sets the data size when writing data into common memory area 1 of the
Area 1
FL-net in "word" unit.
Write Size
If there is no data written into common memory area 1, the setting will be
FL-net "0".
Setup Leading Sets leading address of common storage when the set equipment writes
(offset) data to common storage area 2 of FL-net.
For devices being setup, set up the data size written into the FL-net
Area 2
common memory space 2 in word unit.
Write Size
If there is no data written into common memory space 1, the setting would
be "0".
Sets the leading No. of the relays used in KV-FL20V (in ch).
Start No.setting of R (in ch)
The setting range depends on the CPU units connected.
occupied area
*1
Sets leading No. of DM used in KV-FL20V.
DM
The setting range depends on the CPU units connected.
Can only be set after the "Use auto refresh function" checkbox is selected.
Area 1
Specifies the device type and leading device No. of CPU for saving the
leading No.
data in the common memory area 1 of buffer memory.(in ch)
Auto (in ch)
In area 1, either B (link relay) or R (relay) can be selected.
refresh
Can only be set after the "Use auto refresh function" checkbox is selected.
setting *1
Area 2 Specifies the device type and leading device No. of CPU for saving and
leading No. the data in the common memory area 2 of buffer memory.
In area 2, either W ( link register) or DM ( Data Memory) can be selected.
Setting of The same value as the write size of area 1 of the FL-net setting.
Area 1 Write Size
the Displayed in "ch" and "bit" (number of points) unit.
communic
ation area Area 2 Write Size The same value as the write size of area 2 of the FL-net setting.
*2
size
*1 It can be entered only when the "Type of equipment connected" is set to KEYENCE CPU unit.
*2 Display only . Can't be set.

- KV-FL20V User’s Manual - 6-13


6-2 How to Use the KV-FL Setup Tool

After related settings of all equipment connected have


been down, the settings are displayed in a list.

• If a KEYENCE CPU unit selected as a connected


equipment, then the leading No. will be displayed
according to relay No. and DM No.
• However, if equipment other than KV-FL is selected,
then the leading No. will be displayed in FL-net
address.

6
HOW TO USE THE KV-FL SETUP TOOL

Verify the settings, if there is nothing to be changed, click the "Finish". If you want to change the
settings, click the "Return (B)" button, and make changes.

When all settings have been done, exit the wizard, KV-FL Setup Tool will show (in bar graph) the relay/
DM area occupied by every connected equipment, or the common state of bit device/word device.
No bar chart will be displayed.

3 If a KEYENCE CPU unit is selected as the connected equipment, the size of read area in area 1/2
and the leading address of common memory can be manually set on the communication area of
the KV-FL Setup Tool.

6-14 - KV-FL20V User’s Manual -


6-3 Functions of the KV-FL Setup Tool
This section describes the functions of the KV-FL Setup Tool and how to use them.

New KV-FL Setup File

1 Select "File(F)" "New(N)" from the menu.


Other procedure
• Click button
• Press + key

2 The "KV-FL Setup Wizard" appears.


6
For operating method of the KV-FL Setup Wizard, see

HOW TO USE THE KV-FL SETUP TOOL


"How to Operate the KV-FL Setup Wizard", Page
6-9.

Open Existing KV-FL Setup File

1 Select "File(F)" "Open(O)" from the menu.


Other procedure
• Click button
• Press + key

The "Open file" dialog box pops up.

2 Select the KV-FL setup file to be read.

3 Click the "Open(O)" button.


Read the specified KV-FL setup file.

- KV-FL20V Use’s Manual - 6-15


6-3 Functions of the KV-FL Setup Tool

Overwrite and Save KV-FL Setup File

1 Select "File(F)" "Save(S)" from the menu.


Other procedure
• Click button
• Press + key

Overwrite and save the KV-FL setup file.

6 Name and Save KV-FL Setup File


HOW TO USE THE KV-FL SETUP TOOL

1 Select "File(F)" "Save as(A)" from the menu.

The "Save as" dialog box pops up.

2 Select a locating for saving, and input the file name.

Click "Save(S)" button after inputting the name.


The file will be saved to the location selected.

Open KV-FL Setup File

1 Select "File(F)" "Print(P)" from the menu.


Other procedure
• Click button
• Press + key

The "Print setup" dialog box pops up.


2 Select "Print Chart" if you want to print bar charts.

Click the "OK" button.


The "Print setup" dialog box pops up.

3 If necessary, click "Properties(P)" to set up according


to the printer used.

Click "OK" to print.

6-16 - KV-FL20V Use’s Manual -


6-3 Functions of the KV-FL Setup Tool

■ Print Example

System Properties FL-net memory map

HOW TO USE THE KV-FL SETUP TOOL


Common memory aear setting Diagram

- KV-FL20V Use’s Manual - 6-17


6-3 Functions of the KV-FL Setup Tool

Display Print Preview

1 Select "File(F)" -> "Print Preview(V)" from the menu.


Other procedure
• Click button

2 Select "Print Chart" if you want to print bar charts. 

6 Click "OK".
The print preview will be displayed.
HOW TO USE THE KV-FL SETUP TOOL

Printer Setup

Set up the size and format of print paper.

1 Select "File(F)" -> "Print Setup(R)" from the menu.

2 If necessary, click "Properties(P)" to set up


according to printer used.

Click "OK" to print.

End KV-FL Setup Tool

1 Select "File(F)" -> "Exit Application(X)" from the menu.

6-18 - KV-FL20V Use’s Manual -


6-3 Functions of the KV-FL Setup Tool

Set up the System Properties

1 Select "Edit(E)" -> "System Properties" from the menu.


Other procedure
• Click button

The "KV-FL System Properties" dialog box appears.

2 Select the item to be set and input contents.

HOW TO USE THE KV-FL SETUP TOOL


After setting up, click "OK".
The settings are as follows.

Item Description
Connection Type Displays the type of connection that has been set.
File name Displays the location (folder) for saving file and file name.
Number of connected device Displays the number of units connected that has been set.
Number of Reserved device Displays the number of reserved units that has been set.
Header Adds title in the KV-FL setup file.
Maker Info Adds the name of creator in the KV-FL setup file.
Memo Adds date of creation, version, and other remarks in the KV-FL setup file.

Set up the Properties of the Connected Deivce

1 Select "Edit(E)" -> " Properties of the Connected Deivce" from


the menu.
Other procedure
• Click button

The "Properties of the connected device" dialog box appears.

2 Select the device to be set up in "Select connected


device", and click the item to be set.

After setting up, click "OK".


The settings are as follows.

- KV-FL20V Use’s Manual - 6-19


6-3 Functions of the KV-FL Setup Tool

Item Description
Select of connected device Select device to be set up from the pull-down list.
If this checkbox is selected, the selected device will be set as
Set the device to be reserved device
reserved.
Name of Connected device Names the device selected.
Type of Connected device Displays the CPU unit of KV-FL20V selected for communication.
In addition, by selecting from the pull-down menu, CPU unit can
be changed. For device other than KV-FL20V or FL-net device
built in KV-5000, this won't be displayed.
Use the auto refresh function of Area 1 When selected, automatic refresh function of Area1 is enabled.

6 Use the auto refresh function of Area 2


Comment
When selected, automatic refresh function of Area 2 is enabled.
Adds comments for the device selected.
HOW TO USE THE KV-FL SETUP TOOL

Add connected device

Connected equpment will be added. However, if "KV-FL 1:1 connection" is selected in the connection
type, then no device can be added. Only KV-FL20V(KV-5000/3000/1000/700)\KV-5000 built-in FL-net
compatible device can be added.

1 Select "Edit(E)"->"Add devices to be


connected device(A)" from the menu.
Other procedure
• Click button
• Press + key

If a reserved equpment is set, then the "Verify" dialog box will appear.
Click No to stop operation.
If you click "Yes", then the "Add Slave" dialog box will appear.

2 Set up the added device

For setting, see "How to Operate the KV-FL Setup


Wizard", Page 6-9.

After setting up, click "OK".

6-20 - KV-FL20V Use’s Manual -


6-3 Functions of the KV-FL Setup Tool

Delete the Connected Device

The selected equpment will be deleted.


However, the device can not be deleted if "KV-FL 1:1 connection" is selected in connection type.

1 Select the device to be deleted from the pull-down


menu.

2 Select "Edit(E)" -> "Delete connected device(D)" from the 6


menu.

HOW TO USE THE KV-FL SETUP TOOL


Other procedure
• Click button
• Press + key

The "Verify" dialoge box appears.


Click "Yes" to delete. Click "No" to stop operation.

Change to Manual Connection

The connection type will be changed to manual connection. If you add third-party FL-net compatible
device other than KV-FL20V, or you add device to "KV-FL setup file". When the connection type is "KV-
FL20 1:1 connection", then change to manual connection.

Note
• If you have been changed to manual connection, then you can't return to the original
connection types of "KV-FL 1:1 connection","KV-FL 1:N connection" or "Common data of
N KV-FLs".
• No bar chart will be displayed for manual connection.

1 Select "Edit(E)" -> "Switch to Manual Connection(M)" from the menu.


Other procedure
• Click button
• Press + key

The "Verfiy" dialoge box appears.


If you change to manual connection, click "Yes".
If you want to stop operation without changing to
manual connection, click "No".

- KV-FL20V Use’s Manual - 6-21


6-3 Functions of the KV-FL Setup Tool

Display/Hide Setup ToolBar and Status Bar

Select "View(V)"->"Toolbar(T)" or "Status bar(S)" from the menu, to display/hide of toolbar/status bar.
When selected: displayed.
When unselected: hidden.

Toolbar

6
HOW TO USE THE KV-FL SETUP TOOL

Status bar

Each time selected, display/hide will be toggled.

Option Setup

1 Select "View(V)"->"Options(O)" from the menu.


Other procedure
• Click button

2 Click the checkbox of each item and set it to "Enabled" or


"Disabled".
After setting up, click "OK".
The settings are as follows.

Item Description
If selected, the assignment status of the high speed area (high speed write area
and high speed read area, DM). When KV-FL20V is selected, and can be
Display high speed area
changed.
* If KV-FL20V mode is used, it won't be displayed even if selected.
Display FL-net area If selected, the assignment status of FL-net common memory area will be displayed.
If selected, the common status of bit device and word device for extablishing FL-
Display chart net data link will be displayed by a bar chart.
* In case of manual connection, it won't be displayed even if checked.

6-22 - KV-FL20V Use’s Manual -


6-3 Functions of the KV-FL Setup Tool

Transfer to Unit Editor

To transfer the settings of relay No., DM No. and FL-net common memory area to the unit settings of
KV-FL20V or KV-5000 (FL-net mode).

Note
Please perform the following operation before transferring.
1. Start KV STUDIO.
2. Open KV STUDIO project including KV-5000 or KV-FL20V as the transferred object.
3. No transferring can be done if the above steps are not executed.

1 Select "Transfer(T)"->"Transfer to Unit Editor(T)" from the menu.


6

HOW TO USE THE KV-FL SETUP TOOL


Other procedure
• Click button
• Press + key

The "Transfer to Unit Editor" dialoge box appears.

2 Select source device to transfer from the pull-down list.

Click "OK".
The data will be transferred to the KV-FL20V unit
settings of an opened Unit Editor.

(1)The KV STUDIO Unit Editor is not started.


(2) If the CPU unit type of the opened Unit
Editor is different from that of the connected
device of the transfer source (CPU unit), the
dialog box at the right will appear.

First, start the Unit Editor consistent with the


connected device of transfer source, then start
to transfer.
If no KV-FL20V or KV-5000 (FL-net mode) is
configured in an opened Unit Editor, the dialog
box at the right will appear.
Use the Unit Editor to configure KV-FL20V or KV-5000
(FL-net mode) first, then start to transfer.
If no KV-FL20V or KV-5000 (FL-net mode) is configured in
an opened Unit Editor, the dialog box at the right will
appear.
Please select KV-FL20V or KV-5000 (FL-net mode) as an
transfer object, then click "OK".

- KV-FL20V Use’s Manual - 6-23


6-3 Functions of the KV-FL Setup Tool

Display Help

1 Select "Help(H)"->"KV-FL20 Setup Tool Help(T)" from the menu.


Other procedure
• Click button
• Press key

Display Version Info


6
1 Select "Help(H)"->"Version Info for KV-FL Setup Tool(A)" from the menu.
HOW TO USE THE KV-FL SETUP TOOL

The "Version Info KV-FL Setup Tool " dialog box appears.

6-24 - KV-FL20V Use’s Manual -