Cho long 155MW Wind Power Project
EARTHING SYSTEM AND GROUND VERIFICATION STUDY
Index No.: CLW‐EPC‐CAL‐0514‐WFM‐IFR‐02_Earth_Ground_Verif
REV.C
May 2021
Qualitycon control sheet
Document EARTHING SYSTEM AND GROUND VERIFICATION STUDY
Project Vietnam Cho long 155MW Wind Power Project
Code CLW‐EPC‐CAL‐0514‐WFM‐IFR‐02_Earth_Ground_Verif
Authors Signed:
Date
Verified Signed:
Date
Recipient
Notes
Contents
1. Introduction ................................................................................................................................. 1
1.1 Requirements .................................................................................................................. 1
1.2 International standards ................................................................................................. 1
1.3 Relevant documents ....................................................................................................... 1
2. Calculation ................................................................................................................................... 2
2.1 Resistivity of TWG farms ................................................................................................. 2
2.2 Calculation of the size for down lead conductor and grounding conductor ................ 3
2.3 Calculation of grounding resistance of the farm grounding grid .................................. 4
3. Conclusion ................................................................................................................................... 8
1. Introduction
1.1 Requirements
The calculation report is computation on grounding system underground of
Vietnam Cho long 155MW Wind Power Project. The purpose of the calculation is to
prove the validity of the designed grounding system.
1.2 International standards
The design for the grounding system of wind turbines farm execute international
standards. The calculation is based on following standards:
-IEEE Standard 80: Guide for Safety in AC Substation Grounding
-IEEE Standard 665: Guide for Generating Station Grounding
1.3 Relevant documents
The wind turbines of this project is purchased from Xinjiang Goldwind Science
& Technology Co., Ltd. The designed grounding system implement the demand of
equipment manufacturer. The relevant documents are referenced as follows:
- GW-08JT.0004, Guide for lightning protection and grounding system
- 70.02.01194, Guide for 130m (6-section) anchor bolt foundation
- Geophysical survey document, Report on resistivity test of soil and rock
1
2. Calculation
2.1 Resistivity of TWG farms
According to the report on resistivity test of soil and rock in cho long
geophysical survey document, the resistivity of 35 TWG farms are summarized in the
following table.
Resistivity from surface to bellow
Average
Wind turbine (Ωm)
(Ωm)
Depth 1 Depth 2
WTG01 522 107 314.5
WTG02 45.8 37.2 41.5
WTG03 73.8 25.9 49.85
WTG04 18.4 21.8 20.1
WTG05 728 1207 967.5
WTG06 29 766 397.5
WTG07 222 21 121.5
WTG08 672 71.1 371.55
WTG09 114 17.8 65.9
WTG10 16.8 43.9 30.35
WTG11 130 53.1 91.55
WTG12 959 220 589.5
WTG13 36.8 26.6 31.7
WTG14 713 179 446
WTG15 49.1 25.1 37.1
WTG16 37.2 63.4 50.3
WTG17 302 65.6 183.8
WTG18 37.2 26.6 31.9
WTG19 60.3 30.7 45.5
WTG20 270 64.9 167.45
WTG21 163 36.4 99.7
WTG22 1217 1829 1523
WTG23 143 23.2 83.1
WTG24 164 35 99.5
WTG25 2016 246 1131
WTG26 2383 378 1380.5
WTG27 638 196 417
WTG28 4375 822 2598.5
WTG29 1437 833 1135
WTG30 411 228 319.5
WTG31 431 94.5 262.75
WTG32 54.9 78.4 66.65
2
2.2 Calculation of the size for down lead conductor and grounding conductor
Maximum single-phase short circuit fault current: 25kA (As there is no
impedance of system now, the most serious condition is to be considered).
2 t f
T
D f 1 a (1 e Ta
)
tf
Ta is the dc offset time constant
Ta X /(R)
X / R 14
2f 314
Ta 0.0449
tf 1
2
0.0449
Df 1 (1 e 0.0449 ) 1.022
1
3
1 1 1
R g (1 )
LT 20A 1 h 20 / A
- the soil resistivity.
4
WTG01 6.629838
WTG02 0.874843
WTG03 1.050866
WTG04 0.423719
WTG05 20.39545
WTG06 8.379524
WTG07 2.561289
WTG08 7.832484
WTG09 1.389209
WTG10 0.639795
WTG11 1.929926
WTG12 12.42699
WTG13 0.668254
WTG14 9.401932
WTG15 0.782089
WTG16 1.060352
WTG17 3.874608
WTG18 0.67247
WTG19 0.959166
WTG20 3.529941
WTG21 2.101732
WTG22 32.1057
WTG23 1.751795
WTG24 2.097516
WTG25 23.84212
WTG26 29.10172
WTG27 8.790595
WTG28 54.77785
WTG29 23.92644
WTG30 6.73524
WTG31 5.538918
WTG32 1.40502
WTG33 17.80254
WTG34 21.71298
WTG35 1.058244
Depending IEEE80 14.1, the usually acceptable is from 1Ω~5Ω. However,
according to the requirements of Vietnam, the grounding resistance should be less
than 4Ω. There are 16 grounding grids of wind turbine that not satisfy this
requirement, they are WTG01, WTG05, WTG06, WTG08, WTG12, WTG14, WTG22,
WTG25, WTG26, WTG27, WTG28, WTG29, WTG30, WTG31, WTG33, WTG34.
5
6
WTG18 0.04067
WTG19 0.058009
WTG20 0.213485
WTG21 0.127109
WTG22 1.941701
WTG23 0.105946
WTG24 0.126854
WTG25 1.441933
WTG26 1.760025
WTG27 0.531641
WTG28 3.312875
WTG29 1.447032
WTG30 0.407336
WTG31 0.334985
WTG32 0.084973
WTG33 1.076668
WTG34 1.313166
WTG35 0.064001
From the result calculated above, all the grounding resistance are reduced under
4Ω.
7
3. Conclusion
The hot-dip galvanized flat steel 80×6 can be accepted as the grid horizontal
grounding conductor, all the grounding resistance of WTG are reduced under 4Ω. The
farm main grounding grid can meet design requirement.