ATLANTA ELECTRICALS PVT. LTD.

TRANSFORMER TEST REPORT Page : 3 OF 5


Customer : ABP Induction System Pvt. Ltd W.O.No. : AET 929 Sr.No. : 929/4570

3 (I) VECTOR GROUP TEST (Dy11) : (At Tap No.:3)

Measurement * 1U - 2U Shorted.
1U1V = 433 1V3V = 422 1U2N = 20
1V1W = 436 1V3W = 421 1V2N = 409
1W1U = 430 1W3W = 423 1U1V = 429
1W3V = 432

Sr. No. Varification Condition Measured Value


1. 1W3W < 1W3V 423 < 432
2. 1V3V = 1V3W 422= 421
3. 1U2N + 1V2N = 1U1V 20 + 409 = 429 Hence Vector Group Is Dy11.

3 (II) VECTOR GROUP TEST (Dd0) : (At Tap No.: 3)


* 1U - 3U Shorted.
Measurement
1U1V = 430 1V2V = 420 1W2V = 424
1V1W = 434 1V2W = 424 1U2V = 8
1W1U = 428 1W2W = 421 1U2W = 8

Sr. No. Varification Condition Measured Value


1. 1V2V = 1W2W 420 = 421
2. 1V2W = 1W2V 424 = 424
3. 1U2V + 1V2V = 1U1V 8 + 420 = 428
4. 1U2W + 1W2W = 1U1W 8 + 421 = 429
Hence Vector Group Is Dd0.
4. WINDING RESISTANCE TEST : (Avg. Temp : 21.20 Deg. C)

H.V. Winding Resistance (Ohm) (Normal Tap No. : 3)


Tap No. 1U - 1V 1V - 1W 1W - 1U Average

3 2.3610 2.3600 2.3600 2.3603

Average Resistance :- 2.3603 x 1.5 = 3.54045 Ohm / Ph.

LV Winding (m. Ohm) (delta) LV Winding (m. Ohm) (Star)


2U - 2V 1.6733 3U - 3V 1.7265
2V - 2W 1.6729 3V - 3W 1.7260
2W - 2U 1.6724 3W - 3U 1.7252
Average 1.6729 Average 1.7259

Average Resistance :- 1.6729 x 1.5 = 2.50935 m. Ohm / Ph. Average Resistance :- 1.7259 x 0.5 = 0.86295 m. Ohm / Ph.

5. INSULATION RESISTANCE MEASUREMENT : ( Avg. Temp : 21.20Deg. C )


( @ 5Kv ) ( @ 2.5Kv ) Instrument :- Insu. Tester
H.V to L.Vd1 :- 32.70 G Ohm L.Vd1 to E :- 13.80 G Ohm
H.V to L.Vs2:- 31.20 G Ohm L.Vs2 to E :- 18.90 G Ohm
H.V to E :- 31.50 G Ohm L.Vd1 L.Vs2:- 11.60 G Ohm
6. SEPARATE SOURCE VOLTAGE WITHSTAND TEST : (At Tap No. : 3)
Instrument :- HV AC Transformer With
Following Voltages Applied At 50 Hz For 60 Sec. Digital KV Meter.
Make :- ATLANTA / KRUTAM
Voltage applied between short - circuited H.V. terminal. Sr. No. :- AET - 21 Cal Due On :- 23/10/10
(All L.V. + N terminals & tank earthed.) : 70.0 kV & Withstood OK. From :

Voltage applied between short - circuited L.V. + N terminals.


(All H.V. terminals & tank earthed.) : 3.0 kV & Withstood OK.

Tested By : Witnessed By :

Chirag Makavana, Mr. Kinjal Patel,


Engr., (Testing), Engineer - Design & Quality,
AEPL, V.U. Nagar. ABP I. S. P. L.