NOTES:

1. THE POSITION OF ALL DEVICES/EQUIPMENT AS SHOWN IN THE DRAWINGS ARE APPROXIMATE


ONLY. THE EXACT POSITIONS SHALL BE DETERMINED BY QUALIFIED INSTALLER/ENGINEER ON SITE.

S I D E W A L K S I D E W A L K 2. ALL MATERIALS TO BE USED SHALL BE NEW AND OF APPROVED TYPE BOTH LOCATION AND
PURPOSE INTENDED.

3. MOUNTING SHALL BE AS FOLLOWS:


3.1 FIRE ALARM SOUNDER/BEACON
FEMALE TOILET RENTABLE RENTABLE RENTABLE RENTABLE RENTABLE
11 m² 5 m² 4 m² 5 m² 5 m² 5 m² PANTRY
16 m²
HEIGHT : 2.1 m TO 2.4 m AFL
HOLDING AREA PRE-DEPARTURE AREA
LOUNGE
10 m² 3.2 BELL
20 m² 240 m²
HEIGHT: 2 m AFL
TOILET
1 m² FA 3.3 FIRE ALARM MANUAL CALL POINT/PULL STATION
HEIGHT : 1.10 m TO 1.37 m AFL
MANAGER'S
MANAGER'S
3.4 DETECTORS
MALE TOILET OFFICE
HEIGHT : CEILING HEIGHT OR AS REQUIRED SHOULD NOT BE MOUNTED WITHIN 500 mm OBSTRUCTION
FA

10 m²
OFFICE5 m²

FA FA
MALE TOILET
12 m²
IATF OFFICE
17 m²
3.5 FIRE ALARM CONTROL PANEL
RENTABLE HEIGHT : AS REQUIRED

TICKETING BOOTH

F
4. BELL/SOUNDERS IN THE BUILDING SHALL HAVE SIMILAR SOUND.

R
25 m²
FACP

U
THERMAL SCANNING
THERMAL SCANNER DEPARTURE AREA

T
240 m²

RESTAURANT/
8. ALL WORKS SHALL BE DONE UNDER DIRECT SUPERVISION OF A DULY LICENSED PROFESSIONAL ELECTRONICS

PWD
RENTABLE SPACE

3 m²
ARRIVAL AREA 29 m²
240 m² ENGINEER.
ELECTRICAL /
ELECTRONICS
ROOM
GENERAL SPECIFICATIONS:
FA FA 3 m²
1. ALL MATERIALS USED IN THIS PROJECT SHALL BE GOOD STANDARD
QUALITY
S I D E W A L K S I D E W A L K 2. DO NOT COMBINE ELECTRONICS OUTLET TO ELECTRICAL OUTLET
3. ALL INSTALLATION SHALL BE UNDER THE DIRECT SUPERVISION OF A
DULY LICENSE PROFESIONAL ELECTRONICS PLAN SHALL BE SIGNED AND
SEALED BY A PROFESSIONAL ELECTRONICS ENGINEER UNDER R.A. 9292.
T U R F T U R F T U R F
5. ALL ELECTRONICS INSTALLATIONS SHALL BE IN ACCORDANCE WITH THE
LATEST
PROVISIONS OF THE PHILIPPINE ELECTRONICS CODE.
R A M P U P
6. ELECTRONICS CONVENIENCE OUTLET: 0.30M ABOVE FINISH FLOOR LEVEL
UNLESS SPECIFIED FOR OTHER PURPOSES.

SMOKE DETECTOR LAYOUT


LEGENDS

SMOKE DETECTOR LAYOUT


SCALE : 1:100 mts
PHOTOELECTRIC SMOKE DETECTOR

FACP FIRE ALARM CONTROL PANEL

FA
FIRE ALARM MANUAL STATION WITH ALARM BELL

RISER DIAGRAM
PROJECT TITLE: CERTIFIED BY : PRC NO. : PREPARED BY : CHECKED & REVIEWED BY : RECOMMENDING APPROVAL : APPROVED BY : SHEET CONTENTS : SHEET NO. :
VALIDITY :
SMOKE DETECTOR
REPUBLIC OF THE PHILIPPINES
DEPARTMENT OF AGRICULTURE
PHILIPPINE RURAL DEVELOPMENT PROJECT
REPUBLIC OF THE PHILIPPINES
REGION VI-WESTERN VISAYAS
PROVINCE OF ILOILO
REHABILITATION AND EXPANSION
OF PUNTALES FEEDER PORT
P T R NO. :

DATE ISSUED :
LAYOUT

RISER DIAGRAM
ES01
BONIFACIO DRIVE , ILOILO CITY 5000
EVA MAE V. PARRENAS ROMEO ANDIG RAUL N. BANIAS M.D.,MPA ATTY. SUZETTE A. MAMON ARTHUR R. DEFENSOR JR.
PROJECT SP ID NP.:
PRDP-IB-R006-ILO-010-000-000-2019-AF
PROJECT LOCATION: BRGY. NIPA , CONCEPCION , ILOILO
PLACE ISSUED :

T I N:
M U N I C I P A L E N G I N E E R ACTING PROVINCIAL ENGINEER MUNICIPAL MAYOR , MUNICIPALITY OF CONCEPCION PROVINCIAL ADMINISTRATOR P R O V I N C I A L G O V E R N O R 49-59

You might also like