Professional Documents
Culture Documents
Presentation On: General Classes of Power Quality Problems
Presentation On: General Classes of Power Quality Problems
on
General Classes of Power Quality Problems
Presented by:
Umamani Subudhi
1 Introduction
2 Waveform Distortion
3 Voltage Fluctuation
5 IEEE Standards
7 conclusion
2 / 20
Introduction
Waveform Distortion
3 / 20
Waveform Distortion
Waveform Distortion
Waveform distortion is defined as a steady-state deviation from an ideal
sine wave of power frequency. There are five primary types of waveform
distortion:
DC offset:
The presence of a dc voltage or current in an ac power system is
termed dc offset. Effects: (a) It may saturate the transformer core
causing additional heating and loss of transformer life. (b) Direct
current may also cause the electrolytic erosion of grounding electrodes
and other connectors.
Harmonics
Harmonics are sinusoidal voltages or currents having frequencies that
are integer multiples of the supply frequency (fundamental frequency).
Sources: Non-linear loads
Total Harmonic Distortion is used to measure the effective value of
harmonic distortion. The following figureillustrates the waveform and
harmonic spectrum for a typical adjustablespeed- drive (ASD) input
current. 4 / 20
Waveform Distortion
Waveform Distortion
Interharmonics
Voltages or currents having frequency components that are not
integer multiples of the frequency at which the supply system is
designed to operate (e.g., 50 or 60 Hz) are called interharmonics.
Sources: Static frequency converter, cycloconverters, induction
furnaces, and arcing devices.Power line carrier signals can also be
considered as interharmonics.
Notching
Notching is a periodic voltage disturbance caused by the normal
operation of power electronic devices when current is commutated
from one phase to another.
5 / 20
Waveform Distortion
Waveform Distortion
The following figure shows an example of voltage notching from a
three-phase converter that produces continuous dc current. The
notches occur when the current commutates from one phase to
another. During this period, there is a momentary short circuit
between two phases, pulling the voltage as close to zero as permitted
by system impedances.
Waveform Distortion
Noise
Noise is the unwanted electrical signals with broadband spectral
content lower than 200 kHz superimposed upon the power system
voltage or current in phase conductors, or found on neutral
conductors or signal lines.
Sources: Power electronic devices, control circuits, arcing equipment,
loads with solid-state rectifiers, and switching power supplies.
The problem can be mitigated by using filters, isolation transformers,
and line conditioners.
7 / 20
Voltage Fluctuation
Voltage Fluctuation:
Voltage Fluctuation:
Voltage fluctuations can be described as repetitive or random
variations of the voltage envelope due to sudden changes in the real
and reactive power drawn by a load. The characteristics of voltage
fluctuations depend on the load type and size and the power system
capacity.
Figure 1 illustrates an example of a fluctuating voltage waveform.
The voltage waveform exhibits variations in magnitude due to the
fluctuating nature or intermittent operation of connected loads.
The frequency of the voltage envelope is often referred to as the
flicker frequency. Thus there are two important parameters to voltage
fluctuations, the frequency of fluctuation and the magnitude of
fluctuation. Both of these components are significant in the adverse
effects of voltage fluctuations.
8 / 20
Voltage Fluctuation
Voltage Fluctuation:
Voltage Fluctuation:
10 / 20
Power Frequency Variations
11 / 20
Power Frequency Variations
12 / 20
IEEE Standards
IEEE Standards:
IEEE power quality standards: Institute Of Electrical and Electronics
Engineer.
IEEE power quality standards: International Electro Technical
Commission.
IEEE power quality standards: Semiconductor Equipment and
Material International.
IEEE power quality standards: The International Union for Electricity
Applications IEEE Std 519-1992: IEEE Recommended practices and
requirements for Harmonic control in Electric power systems.
IEEE Std 1159-1995: IEEE Recommended practices for monitoring
electrical power
IEEE std 141-1993, IEEE Recommended practice for electric power
distribution for industrial plants.
IEEE std 1159-1995, IEEE recommended practice for Monitoring
electrical power quality.
13 / 20
IEEE Standards
IEC Standards:
Definitions and methodology 61000-1-X
Environment 61000-2-X
Limits 61000-3-X
Tests and measurements 61000-4-X
Installation and mitigation 61000-5-X
Generic immunity and emissions 61000-6-X
14 / 20
CBEMA and ITI Curves
15 / 20
CBEMA and ITI Curves
16 / 20
CBEMA and ITI Curves
17 / 20
CBEMA and ITI Curves
Fig 1.5 A portion of the CBEMA curve commonly used as a design target for equipment
And a format for reporting power quality variation data.
18 / 20
CBEMA and ITI Curves
19 / 20
conclusion
Other PQ disturbances
PQ standards
Standard curves for PQ
20 / 20