Inspection and Test Plan For LNG Tank Installation
Inspection and Test Plan For LNG Tank Installation
FOR APPROVAL
B 01 Oct 2021 Issue for Approval Y.J Kim C.H. Lee J.M Baek J.M Oh
A 13 Sep 2021 Issue for Approval Y.J Kim C.H. Lee J.M Baek J.M Oh
Rev. No. Issue Date Revision Text Prepared Checked Reviewed Approved
The contents of this document are the sole property of CONTRACTOR. Any rights not expressly granted
herein are reserved. Reproduction, transfer or distribution of part or all of the contents in any form without the
prior written permission of CONTRACTOR is prohibited.
Title INSPECTION AND TEST PLAN FOR LNG TANK INSTALLTION
Document No. ELT-05-CT-PC-0001
Revision No. B
Page No. 2 of 26
ABBREVIATIONS;
EnaDOM : Company or Owner, Energia Natural Dominicana ENADOM, S.R.L.
Vendor : STE’s collaborator which performs one or more processes (except welding for main components) for STE on the contract basis such
as nondestructive examination, post-weld heat treatment, painting, etc.
H : Hold Point
Hold Point (H) means, a point, designated by prior stated agreement in the Inspection and Test Plan(s), at which the performance of
an activity must be stopped and put on hold until specified actions are completed.
W : Witness Point (W) means, a designated inspection or test operation where, by prior agreement, the supplier / contractor is obligated to
advise the Company or his designee of a specified time in advance of the operation so that it may be witnessed; but the supplier /
contractor may proceed with work past the witness point if the Inspector or Engineer is not present at the appointed time providing
proper notification has been provided. When the inspection activity is performed by the supplier, then there must be documented
objective evidence of the satisfactory completion of the operation which can be verified at a later date by the purchaser.
R : Review Point (R) means, a process where there is review of relevant document instead of inspection / witness.
C of C : Certificate of Compliance
HT : Hydrostatic test
I&T : Inspection and test
ID : Identification
IRC : (or IRN), Inspection release certificate (or notice) issued by the Purchaser
ITP : Inspection and test plan
LT : Air leakage test
MT : Magnetic particle examination
MTR : Material (or mill) test report or material certificate
NDE : Nondestructive examination
PMI : (or PAMI), Positive alloy material identification
PP : Pneumatic pressure test
PQR : Welding procedure qualification record
PS : Purchase specification
PQT : Welding procedure qualification test
PT : Liquid penetrant examination
Repad : Reinforcing pad
RIR : Receiving inspection record
RT : Radiographic examination
Spec. : Specification
SS : Austenitic stainless steel
TCW : Table of certified welders or welding operators
TOM : Tabulation of materials
UT Ultrasonic examination in lieu of RT
VE Visual examination
VB Partial vacuum box test
WPQ Welder or welding operator’s performance qualification
WPQR Welder or welding operator’s performance qualification record
WPS Welding procedure specification
w/ with
Title INSPECTION AND TEST PLAN FOR LNG TANK INSTALLATION
Document No. ELT-05-CT-PC-0001
Revision No. B
Page No. 4 of 26
6.5.9 PT for back gouge surface, if required ELT-05-ET-PC-0004 - PT Report W*/R W/R R W*: Submission of NDE application
6.5.10 PAUT for longitudinal & circum. joints PAUT Procedure - PAUT Report W*/R W/R R W*: Submission of NDE application
6.5.11 PAUT for three-plate junctions PAUT Procedure - PAUT Report W*/R W/R R W*: Submission of NDE application
6.5.12 PT for completed welds ELT-05-ET-PC-0004 - PT Report W*/R W/R R W*: Submission of NDE application
6.5.13 VB on welds ELT-05-ET-PC-0005 Para. 6 5TR-0002-007 W* W R Only above HT level
7.0 PIPING
7.1 Lines Carrying Liquid Located Outside Primary Liquid Containers, if any
7.1.1 Fit-up inspection API 620 6.9 & 6.14 5TR-0002-003 W W -
7.1.2 VE on welds API 620 6.14 & 7.15 5TR-0002-003 W W R
7.3 Piping Does Not Carrying Liquid or Vapor (e.g Instrument conduct, purge lines)
7.3.1 VE on welds API 620 6.14 & 7.15 5TR-0002-003 W W R
A1-5 Others
Note: Air test with solution film shall be in accordance with following requirements.
1) Ordinary unmodified household soap or detergents should not be used as substitutes for
specified Solution Film Testing. No liquid should be used that is detrimental to the
component being tested or other components in a system.
2) Soap solution for Solution Film Test consists of a household dishwashing liquid detergent
or liquid soap mixed with glycerol and water in the following proportions ;
1 part of liquid detergent or soap, 1 part of glycerol, and 4.5 parts of water.
3) To prevent the soap film solution from icing in the applicator container in cold weather when
the temperature is below freezing, alcohol or ethylene glycol (antifreeze) can be added to
the soap film solution described above, in the proportion of 1 part of antifreeze to 10 parts
of the modified soap solution.
Title INSPECTION AND TEST PLAN FOR LNG TANK INSTALLATION
Document No. ELT-05-CT-PC-0001
Revision No. B
Page No. 18 of 26
- Requirement :
- Location of Check Point
The location of each check point is to be allocated at the internal of 9m along the
circumference.
NOTE :
PREPARED BY : DATE :
INSPECTED BY : DATE :
APPROVED BY : DATE :
VERTICALITY CHECK:
Check Points Design Actual Difference
NOTE :
PREPARED BY : DATE :
INSPECTED BY : DATE :
APPROVED BY : DATE :
DISCIPLINE : SUBCON :
LOCATION : ELEVATION :
RESULT
NO DESCRIPTION REMARK
ACCEPT REJECT N/A
Fit-up Requirement
Weld Requirement
PREPARED BY : DATE :
INSPECTED BY : DATE :
APPROVED BY : DATE :
L H
Mark. Size Angle
Design Actual Design Actual
NOTE :
PREPARED BY : DATE :
INSPECTED BY : DATE :
APPROVED BY : DATE :
2. Pumbness Check
Course Check Point
No. 1 2 3 4
ST
1
3RD
5TH
7TH
9TH
NOTE :
PREPARED BY : DATE :
INSPECTED BY : DATE :
APPROVED BY : DATE :
PREPARED BY : DATE :
INSPECTED BY : DATE :
APPROVED BY : DATE :
LOCATION : ELEVATION :
1. PRESSURE
DESIGN TEST TEST HOLDING
PRESSURE PRESSURE TEMP. TIME REMARKS
(psig) (psig) ( ℃ ) (MIN)
REQUIREMENT
ACTUAL RESULT
2. GAUGE
PRESSURE GAUGE 1 2 3 4 REMARKS
CALIBRATION DATE
SKETCH :
PREPARED BY : DATE :
INSPECTED BY : DATE :
APPROVED BY : DATE :
Inspection Notification
Notification
System
No./Date
Inspection
Discipline
Date/Time
Reference
DWG.
Inspection
Items
Detail Description (If Required)
Subcontractor
POSCO E&C Construction POSCO E&C QA/QC
(S-Tank Engineering)
Name
Position
Signature
Date