Professional Documents
Culture Documents
Tracer® Adaptiview™ Display Upgrade For Series R™ Chillers: Programming Guide
Tracer® Adaptiview™ Display Upgrade For Series R™ Chillers: Programming Guide
Tracer® Adaptiview™ Display Upgrade For Series R™ Chillers: Programming Guide
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment.
WARNING
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury.
All field wiring MUST be performed by qualified personnel. Improperly installed and
grounded field wiring poses FIRE and ELECTROCUTION hazards. To avoid these hazards,
you MUST follow requirements for field wiring installation and grounding as described in
NEC and your local/state/national electrical codes.
WARNING
Personal Protective Equipment (PPE) Required!
Failure to wear proper PPE for the job being undertaken could result in death or serious
injury.
Technicians, in order to protect themselves from potential electrical, mechanical, and
chemical hazards, MUST follow precautions in this manual and on the tags, stickers, and
labels, as well as the instructions below:
• Before installing/servicing this unit, technicians M UST put on all PPE required for
the work being undertaken (Examples; cut resistant gloves/sleeves, butyl gloves,
safety glasses, hard hat/bump cap, fall protection, electrical PPE and arc flash
clothing). ALWAYS refer to appropriate Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
• When working with or around hazardous chemicals, ALWAYS refer to the
appropriate SDS and OSHA/GHS (Global Harmonized System of Classification and
Labelling of Chemicals) guidelines for information on allowable personal exposure
levels, proper respiratory protection and handling instructions.
• If there is a risk of energized electrical contact, arc, or flash, technicians MUST put
on all PPE in accordance with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to servicing the unit. NEVER PERFORM
ANY SWITCHING, DISCONNECTING, OR VOLTAGE TESTING WITHOUT PROPER
ELECTRICAL PPE AND ARC FLASH CLOTHING. ENSURE ELECTRICAL METERS AND
EQUIPMENT ARE PROPERLY RATED FOR INTENDED VOLTAGE.
WARNING
Follow EHS Policies!
Failure to follow instructions below could result in death or serious injury.
• All Trane personnel must follow the company’s Environmental, Health and Safety
(EHS) policies when performing work such as hot work, electrical, fall protection,
lockout/tagout, refrigerant handling, etc. Where local regulations are more
stringent than these policies, those regulations supersede these policies.
• Non-Trane personnel should always follow local regulations.
Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission. Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change.
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
(New)
BAS-SVP031B-EN 3
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Table of Contents
Preparing for Chiller Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Startup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Tracer TU Service Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Obtaining the Product Installation File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Additional Equipment You Will Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Major Programming Tasks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
4 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Table of Contents
BAS-SVP031B-EN 5
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Table of Contents
6 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Preparing for Chiller Configuration
The purpose of this document is to guide an experienced Series R chiller service technician
through Tracer ™ UC800 controller configuration and setpoint selections for an AdaptiView™
Panel Upgrade installation using the Tracer TU service tool.
N o t e : Each of the individual retrofit kits sold has a specific installation manual. This manual is
intended to be used for the programming and startup process. It is not intended to be the
installation manual.
Startup Procedures
The complete RTAC startup procedures are included in the “Startup Checklist,” p. A–1. As you
work through the sequence of steps, references are made to the various configuration tables and
setpoint tables in this guide.
Additional Resources
Tracer TU Service Tool Documents
Refer to the following documents for additional information about using the Tracer TU Service
Tool:
• Tracer TU Service Tool Getting Started Guide (TTU-SVN01x-EN),
The Getting Started Guide is included with the Tracer TU software. It introduces the Tracer TU
utilities, lists hardware and software requirements, and explains installation and connection
procedures.
• Tracer TU Help for Chillers
This Help file is included with the Tracer TU Service Tool application. It provides conceptual
information, procedures, and screen descriptions. You can access the Online Help from the
application Help menu or directly from the application screens.
Series R Chiller Documents
Refer to the Series R library documents intended for your chiller model for a description of Tracer
AdaptiView installation tasks. Use the chiller installation operation, and maintenance manuals to
assure proper installation and for reference purposes. Use the forms in the back of the manual to
assure readiness for startup. Also, use the startup log sheet. (Be sure you have the appropriate
log sheets.)
BAS-SVP031B-EN 7
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Preparing for Chiller Configuration
• Tracer AdaptiView™ Rotary Chiller Control Upgrade Installation Instructions for RTAC
ChillersRCDA-SVN002x
Describes the procedures required to successfully install Tracer AdaptiView™ controls on
RTAC chillers with a CH530-based control system.
8 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Model Number Descriptions
For service purposes, AdaptiView Panel Upgrade Kits are assigned a multiple character
alphanumeric model number that precisely identifies each unit. An explanation of the
identification code that appears on the unit nameplate is shown below. Use of the service model
number will enable the owner/operator, installing contractors and service technicians to define
the operation, components and options for any specific unit. Refer to the control panel model
number printed on the nameplate when ordering replacement parts or requesting service.
BAS-SVP031B-EN 9
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Starting Tracer TU and Connecting to the UC800
Before connecting your laptop to the Tracer® AdaptiView™ controller, be sure to have your
laptop fully booted up. After you have connected your laptop to the Tracer® AdaptiView™
control using the chiller panel USB port or the UC800 USB port, you can start Tracer® TU and
establish the software connection to the UC800.
Type A/B cable UC800
Notes:
• Observe existing USB standards for cable length. (For more information go to relevant
Web sites resulting from search terms, such as "USB standard cable length”.)
• If you encounter an error condition or message when connecting to the UC800, refer
to “Appendix A. Tracer TU Installation and Connection Error Conditions,” p. B–1.
Upon successfully connecting to the UC800, the Unit Summary screen appears generated for the
particular chiller model you are servicing.
10 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Starting Tracer TU and Connecting to the UC800
The Unit Summary screen provides a common presentation format for all chiller models. (Refer
to “The Status Utility - Unit Summary Tab Screen,” p. 33.
Data logging starts automatically at this time without any intervention on your part.
N o t e : When session logging starts, Tracer® TU creates a log file to store the operating data.
Occasionally, you may need to perform file maintenance tasks on your laptop hard drive to
eliminate old files. A message appears when your hard drive approaches its storage
capacity.
You can now navigate to the Chiller Settings screens as described in the subsection that follows.
BAS-SVP031B-EN 11
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Navigating to the Chiller Settings Screens
To navigate to the Chiller Settings screens in the Equipment Utility, perform the following steps:
1. Click the E q u i p m e n t U t i l i t y tab (wrench icon), which is located on the right side of the
Tracer® TU window.
Initially, you will see the Setpoints screen shown in the following figure. (The Setpoints
screen is the first of four Chiller Settings screens, which also include the Field Startup,
Configuration, and LLID Binding screens.)
The selections you make on the Configuration tab screen cause setpoints to appear or not
appear on other Tracer® TU screens according to how you specify items as installed or not
installed. Therefore, be sure the required items are properly configured.
12 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Use the Configuration tab screen on the Equipment Utility tab to verify the unit type, chiller
options, starter settings, and Nameplate settings.
Figure 3. RTAC version of the Configuration Tab screen
The reference section that follows (“Configuration Tab Screen Setpoint Reference Tables”) lists
and describes the setpoints for each of the expanding boxes on the Configuration tab screen.
After verifying or modifying settings on the Configuration tab screen, you can specify settings on
additional Equipment Utility tab screens including Setpoints and Field Startup. You can also
verify settings on the Unit Status screen in the Status Utility.
BAS-SVP031B-EN 13
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Minimum
Tracer TU and Visibility
Configuration Default Maximum (When Description/
screen item Possible Values Units Value Range Displayed) Comments
Minimum
Tracer TU and Visibility
Configuration Default Maximum (When Description/
screen item Possible Values Units Value Range Displayed) Comments
14 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
The following table lists and describes the options for each setting.
Table 3. Equipment Utility – Configuration Table Screen: UC800 Box
Visibility
Possible Values Minimum
Default (When
Configuration Parameter (FCODE/ and Description/Comments
Value Dis-
UCODE) Maximum
played)
BAS-SVP031B-EN 15
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Visibility
Possible Values Minimum
Default (When
Configuration Parameter (FCODE/ and Description/Comments
Value Dis-
UCODE) Maximum
played)
16 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Visibility
Configuration Default
Possible Values (when Description/Comments
Parameter Value
displayed)
BAS-SVP031B-EN 17
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Visibility
Configuration Default
Possible Values (when Description/Comments
Parameter Value
displayed)
5. BAS Interface
• Not Installed
• Tracer LCI-C (LonTalk
Comm5) Not Installed Always visible
• BACnet
• Modbus
6. Ice Building
• Not Installed
Not Installed Always visible
• Installed
7. Programmable Status
• Not Installed
Relays (STAT) Not Installed Always visible
• Installed
9. Refrigerant Service
• Without Suction Service
Valves
Valves — Pueblo Only
• With Suction Service Valves —
Pueblo Only
• With Suction Service Valves —
Pueblo Only Without
Suction
• Suction Valve — Charmes Always visible
Service Valves
Only – Pueblo Only
• With Gauges — Charmes Only
• With Suction Valve and
Gauges — Charmes Only
• No Suction Service Valve —
Charmes Only
18 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Visibility
Configuration Default
Possible Values (when Description/Comments
Parameter Value
displayed)
Non-Latching
Alarm
Alarm
Alarm Circuit 1
Alarm Circuit 2
Circuit 1 Running
Circuit 2 Running
Chiller Running
Maximum
Capacity
Non-Latching
Alarm
Alarm
Alarm Circuit 1
Alarm Circuit 2
Circuit 1 Running
Circuit 2 Running
Chiller Running
Maximum
Capacity
BAS-SVP031B-EN 19
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Table 5. Equipment Utility – Configuration Tab Screen: Options Setup Box (continued)
Non-Latching
Alarm
Alarm
Alarm Circuit 1
Alarm Circuit 2
Circuit 1 Running
Circuit 2 Running
Chiller Running
Maximum
Capacity
Non-Latching
Alarm
Alarm
Alarm Circuit 1
Alarm Circuit 2
Circuit 1 Running
Circuit 2 Running
Chiller Running
Maximum
Capacity
X13650796
(External
Electronics for
Analog Level
Sensor)
X13790508
(90mm Top Mount
Sensor)
20 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Table 5. Equipment Utility – Configuration Tab Screen: Options Setup Box (continued)
X13650796
(External
Electronics for
Analog Level
Sensor)
X13790508
(90mm Top Mount
Sensor)
Voltage Speed
Signal 0-10VDC
(Trane TR1 2800
Series)
Voltage Speed
Signal 0-10VDC
(Trane TR1 2800
Series)
BAS-SVP031B-EN 21
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Table 5. Equipment Utility – Configuration Tab Screen: Options Setup Box (continued)
6. STARTER Box
Verify the following starter configuration variables in the Starter expanding box.
Table 6. Equipment Utility – Configuration Tab Screen: Starter
Solid State
Starters
Wye-Delta Closed
Transition Starters
Solid State
Starters
Wye-Delta Closed
Transition Starters
22 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
Solid State
Starters
Wye-Delta Closed
Transition Starters
Solid State
Starters
Wye-Delta Closed
Transition Starters
BAS-SVP031B-EN 23
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
100,
150,
200,
275,
400,
500,
700,
1000
100,
150,
200,
275,
400,
500,
700,
1000
7. COMPRESSOR 1A Box
The settings shown in the following table appear on the Compressor 1A expanding box on the
Configuration tab screen.
24 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
BAS-SVP031B-EN 25
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
8. COMPRESSOR 2A Box
The settings shown in the following table appear on the Compressor 2A expanding box on the
Configuration tab screen.
Table 8. Equipment Utility – Configuration Tab Screen: Compressor 2A Box
1. Product Model Number The specific model number of the unit (40 characters maximum)
2. Product Serial Number The individual product serial number (40 characters maximum)
3. Product Sales Order The sales order number under which the chiller was sold to the customer. (40
characters maximum)
26 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The Equipment Utility Configuration Tab Screen
BAS-SVP031B-EN 27
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
The LLID Binding Tab Screen
When all the configuration inputs are complete, click the S a v e button at the bottom of the
screen. After a few moments, the LLID Binding screen appears.
Figure 5. Equipment Utility—LLID Binding tab screen
Note that the LLIDs appearing on this list are dependent on selections made previously on the
Configuration screen. Initially, the LLIDs will show up as red squares indicating they are
unbound. Binding is a process by which a particular LLID is assigned to monitor or control a
particular function or component. All LLIDs required for a configuration must be bound (green
circle) to complete this section.
Binding Devices
Use the following procedure to bind the configured LLIDs.
1. Select the LLID to be bound and click on the B i n d button in the task bar.
For example when binding the Motor Start Command LLID, a dialog box appears stating
“Activate LLID using Magnet and click OK.”
2. Locate the targeted LLID in the control panel, unit or starter and place the Trane provided
magnetic screwdriver (South pole magnet) near the LED under the SW1 arrow.
The green LED turns on at the device.
3. Click Y e s in the dialog box.
If the binding is successful, the red square changes to a green circle next to that LLID on the
binding view menu.
If the wrong type of LLID was selected during this binding process an error message appears.
Check the LLID Type column entry to be sure it corresponds to the physical LLID you selected
with your magnet.
4. Repeat the same procedure for all red square LLIDs in the list.
28 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Additional Chiller Settings Screens
You can now verify or make changes to setpoints on the other Equipment Utility tab (Chiller
Settings) screens: Setpoints and Field Startup. See the following subsections:
• Equipment Utility - Setpoints Tab Screen
• Equipment Utility - Field Startup Tab Screen
BAS-SVP031B-EN 29
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Additional Chiller Settings Screens
Table 10. Equipment Utility - Setpoints Tab Screen: Chiller Setpoints Box (continued)
30 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Additional Chiller Settings Screens
1. AFD Running RLA Setpoint 12.0 Percent Existence is dependent on AFD starter type installed.
(0.0 to 120.0)
BAS-SVP031B-EN 31
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Additional Chiller Settings Screens
Table 14. Equipment Utility — Field Startup Tab Screen: Level 4 Gains and Start Sequence (continued)
15. Low Discharge Superheat Limit 0.5 unitless Existence is dependent on AFD starter type installed.
Kp (0 to 100)
16. Low Discharge Superheat Limit Ti 60 seconds Existence is dependent on AFD starter type installed.
(1 to 600)
17. Low Discharge Superheat Cutout 10 °F Existence is dependent on AFD starter type installed.
(0 to 50)
32 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
The Status Utility tab screens provide different sets of information that allow you to monitor
chiller performance.
The data presented on the Unit Summary tab screen is divided into separate categories delimited
by expanding boxes, including Evaporator, Condenser, Setpoints, Motor, and so on.
The gray alert boxes in the screen header (top right) draw your attention to the following
information:
• The current top level operating mode and submode
• The presence of any active alarms
• Any currently active manual overrides
N o t e : You can click these boxes to see the Alarms screen or the Modes boxes on the Unit
Status screen.
BAS-SVP031B-EN 33
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
34 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
BAS-SVP031B-EN 35
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
1. Chiller Mode at Time of Last Diagnostic 5. Chiller Sub Mode 4 at Time of Last Diag
2. Chiller Sub Mode 1 at Time of Last Diag 6. Chiller Sub Mode 5 at Time of Last Diag
3. Chiller Sub Mode 2 at Time of Last Diag 7. Chiller Sub Mode 6 at Time of Last Diag
Table 24. Status Utility - Unit Status Tab Screen: Diagnostic Modes Ckt1 Expanding Box
1. Top Level Mode at Last Diagnostic Ckt1 5. Submode 4 at Last Diagnostic Ckt1
36 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
Table 25. Status Utility - Unit Status Tab Screen: Diagnostic Modes Ckt2 Expanding Box
1. Top Level Mode at Last Diagnostic Ckt2 5. Submode 4 at Last Diagnostic Ckt2
9. CHILLER Box
The following table lists settings that may be included in the Chiller expanding box of the Unit
Status screen.
Table 26. Status Utility - Unit Status Tab Screen: Chiller Expanding Box
2. Active Chilled Water Setpoint Source 16. Evaporator Water Pump Command
3. Active Current Limit Setpoint 17. Evaporator Water Pump Off Delay
4. Active Current Limit Setpoint Source 18. External Chilled Water Setpoint
6. BAS Chilled Water Setpoint 20. Front Panel Chilled Water Setpoint
7. BAS Current Limit Setpoint 21. Front Panel Current Limit Setpoint
8. Chilled Water Softload Target 22. Front Panel Ice Termination Setpoint
10. Cooling Low Ambient Lockout 24. Ice Building Current Limit Setpoint
11. Cooling Low Ambient Lockout Temperature 25. Low Evaporator Water Temp Cutout
2. Evaporator Refrigerant Liquid Level Ckt1 9. Front Panel Circuit Lockout Ckt1
4. Evaporator Saturated Rfgt Temp Ckt1 11. Oil Return Solenoid Valve Cprsr1A
5. External Circuit Lockout Status Ckt1 12. Oil Return Solenoid Valve Cprsr1B
BAS-SVP031B-EN 37
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
2. Evaporator Refrigerant Liquid Level Ckt2 9. Front Panel Circuit Lockout Ckt2
4. Evaporator Saturated Rfgt Temp Ckt2 11. Oil Return Solenoid Valve Cprsr2A
5. External Circuit Lockout Status Ckt2 12. Oil Return Solenoid Valve Cprsr2B
3. Condenser Fan Board 1 Relay 1 Ckt1 8. Condenser Saturated Rfgt Temp Ckt1
5. Condenser Fan Board 1 Relay 3 Ckt1 10. Differential Refrigerant Pressure Ckt1
3. Condenser Fan Board 1 Relay 1 Ckt2 8. Condenser Saturated Rfgt Temp Ckt2
5. Condenser Fan Board 1 Relay 3 Ckt2 10. Differential Refrigerant Pressure Ckt2
38 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
BAS-SVP031B-EN 39
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
40 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
BAS-SVP031B-EN 41
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
Alarm Reset
You can also reset active alarms on this screen. Clicking the Reset button transfers active alarms
to history and allows the chiller to resume operation.
NOTICE
Avoid Potential Chiller Damage!
Failure to properly resolve the source of an alarm before restarting the chiller could
cause recurring alarms or result in chiller damage.
If an active alarm causes the chiller to stop operating, do not reset the alarm or attempt to
restart the chiller before diagnosing and fixing the source of the problem. Restarting an
alarm may restart the chiller.
42 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
BAS-SVP031B-EN 43
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
44 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Status Utility Tab Screens
BAS-SVP031B-EN 45
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Chiller Reports
Tracer TU includes an enhanced Chiller Service Report along with some new reports. Additional
output formats and capabilities have also been added to the Reports menu.
Available Reports
You can generate the following types of reports from the Tracer TU Reports menu. These reports
can be archived or printed. You can also convert these reports to PDF format for e-mailing to
customers. Finally, these reports can be archived on ComfortSite.
• Chiller Service Report
The Chiller Service report is a complete report of the chiller status, configuration, service tool
configuration, PC environment, connected devices, and alarm history. Tracer TU generates a
printable chiller status report that serves as a maintenance record. You can:
– Enter details about the work performed on a specific date and any work that should be
performed in the future.
– Enter other job site notes and additional observations and data.
– Generate a backup of the configuration that you can e-mail or archive to ComfortSite
along with the report.
– Save the report in PDF format for e-mailing.
• Difference (Comparison) Report
This report is an option within the Chiller Service Report. It produces a "before and after"
comparison between a previous Chiller Service Report (generated to troubleshoot the unit
before you begin servicing it) and the report you are generating after completing the service.
You can also compare a current report to one produced at an earlier service inspection.
N o t e : Currently, if you are generating a Differences Report that involves a report generated
by a version of Tracer TU earlier than 8.2, any data that is not common to both of the
chillers is omitted from the report.
• Design Data Report
Chiller design data serves as the reference point or baseline to which you compare live chiller
performance data. Design data for a specified chiller serial number is retrieved from
ComfortSite and saved to your hard drive using the Design Data dialog box. Design Data
Report components include the chiller name, model number, serial number and a grid with
three columns (description, value, unit) for each line of design data.
N o t e : If the chiller serial number is for equipment shipped before 4/1/2000, it must be
manually looked up by the Global Aftermarket Team (GAM). A request will be made on
your behalf through Tracer TU and the information will be sent to you by e-mail.
• Historical Chiller Service Report
You can produce a Chiller Service Report for any point in time as it exists in the Tracer TU
Data Log files. The Historical Chiller Service Report provides a specific date and time stamp
snapshot view of previous chiller conditions, which can serve as a basis for comparison,
troubleshooting, and diagnosis. The report output is presented in the same format as the
normal Chiller Service Report.
• Running Chiller Report
Use the Running Chiller Report to confirm stable chiller operation at startup. Tracer TU takes
three samples at a specified collection interval (the default is every 15 minutes). The report
includes many of the same categories as the Chiller Service Report and can be saved as a PDF
file.
• ASHRAE Chiller Report
Tracer TU generates a printable ASHRAE Chiller Report that lists a number of setpoints. This
report is similar to the Chiller Service Report. You can enter job site information and notes,
and then save the report. Finally, you can save the report in PDF format for the customer.
46 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Chiller Reports
Report Format
Tracer TU formats reports as shown in the following figure.
BAS-SVP031B-EN 47
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Chiller Reports
Reporting Options
In addition to the report options, the Reports menu includes the following functional options.
• E - m a i l F i l e s — Presents the E-Mail Files dialog box on which you can select and send
multiple reports, data logs, images, Report Setup files, and backup files to e-mail to a
recipient and/or for uploading to ComfortSite.
N o t e : You must send or save each individual e-mail message one at a time. Tracer TU is not
operational until you either send or save the current e-mail message.
• V i e w R e p o r t s —Presents an Open File dialog box on which you can select archived data for
viewing.
• C o n v e r t R e p o r t s t o P D F — Opens the Convert Reports to PDF dialog box on which you can
select archived reports and convert them to PDF format.
• R e p o r t S e t u p — Opens the Report Setup dialog box on which you can enter text used in the
report headers of all reports referring to the same chiller serial number. Use the Report Setup
dialog box to automate the entry of technician and chiller unit data (cover sheet or header)
that appears at the top of chiller reports. You enter the Chiller Information data only once for
each chiller serial number. The data related to a specific serial number is stored on your
computer, and it can also be archived on ComfortSite for future use. Once entered, all
subsequent reports for a particular serial number are populated with the appropriate cover
sheet data automatically. In addition, Report Setup data is preserved on your hard drive
separately from the Tracer TU application, so it survives upgrades and reinstallations.
48 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Appendix A. Startup Checklist
Complete the following startup steps. As you work your way through the procedure, references
are made to the configuration and setpoint reference tables in the programming portion of this
guide.
Table 41. Startup Checklist
1. Obtain the Tracer TU software. See “Obtaining the Product Installation File,” p. 7.
2. Unplug the IPC bus from the power supply LLID. Unplug the AdaptiView™ display power connection from the power supply
LLID. This will isolate the power supply LLIDs.
3. Remove temporary oil heater wiring and restore Oil heater should be powered for a minimum of 8 hours prior to start up.
oil heater wiring.
4. “Power Up” the control panel using auxiliary The Starter disconnect is locked open. Perform the following substeps:
power.
1. Inspect all low voltage binary inputs to verify that no 115 Vac leads
are connected to any low voltage binary input LLIDs.
Important: If 115Vac is connected to a low voltage binary input,
such as external auto/stop, major damage to other
connected LLIDs on the bus can occur.
2. Remove fuse from control power transformer (2F4 or equivalent load
side CPT fuse).
3. Connect auxiliary 115Vac power cord to starter panel.
4. Connect cord to 115Vac source. Control panel is now energized.
5. Ensure green LED on power supply LLID is on.
6. Configure the UC800 using the Configuration Specify configuration variable values corresponding to items installed.
screen on the Equipment Utility tab. See “Configuration Tab Screen Setpoint Reference Tables,” p. 38 for
details on configuration items. Record the programmed values.
For cases where the firmware needs to be installed, or new firmware
needs to be installed see “Installing Firmware on a Blank UC800,” p. D–1
or “Changing Firmware on the UC800,” p. D–1 for the correct firmware
installation procedure.
7. Configure the Starter using the “Starter” Configure Starter items to correspond to items installed. See . Make sure
expanding box on the Configuration screen. the CT Meter Scale parameter is properly set. See “CT Meter Scale
Table,” p. E–1 to determine the correct CT meter scale.
8. Bind the LLIDs using the Binding screen. See “The LLID Binding Tab Screen,” p. 28 for an explanation of the
correct binding procedure.
9. Set the setpoint values using the Setpoints and See “Equipment Utility – Setpoints Tab Screen,” p. 29 and “Equipment
Field Startup tabs on the Equipment Utility tab. Utility - Field Startup Tab Screen,” p. 30 for details on setpoint items. Low
Refrigerant Temperature Cutout should be adjusted to 28. Record the
entered values.
BAS-SVP031B-EN A–1
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Startup Checklist
12. Dry run the starter. The following notes assume direct starter control. This can be found in
the Tracer TU ‘Properties portion of the LLID Binding Screen.
1. Make sure starter disconnect is locked open.
2. Use the manual override view to initiate starter test mode.
3. Observe correct operation of the following items (if applicable for
starter type present):
• Shorting relay
• Start relay
• Transition relay
• Start and run relays (on together)
• Run relay
• Disable starter test mode
17. Observe startup. Confirm that unit starts and loads as expected. Watch motor currents to
help troubleshoot if problems exist.
Note: If contactor integrity test was enabled in starter configuration,
contactors may be heard prior to actual start sequence in starter
cabinet.
18. Check current and voltage readings. Verify that the current reading on the AdaptiView™ display matches
expected values. If it does not, the CT meter scale may need to be
adjusted. See “CT Meter Scale Table,” p. E–1 to determine the correct CT
meter scale.
A–2 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Startup Checklist
20. Log startup. If active diagnostics are encountered, see “Alarms Tab Screen,” p. 42.
BAS-SVP031B-EN A–3
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Appendix B. Appendix A. Tracer TU Installation and
Connection Error Conditions
During installation or initial connection to a controller, you may encounter an error message or
error condition. The messages with corrective actions are listed in the following table.
Table 42. Tracer TU installation and connection error conditions
Error Message/Condition Corrective Action
Tracer TU does not respond, or the screen is blank. The phrase “Connected Local USB” should appear in the lower left hand corner
of the Tracer TU screen. If it does not, the connection has been lost. Restart
Tracer TU by clicking the Connection icon (lightning bolt) in the upper left of the
application window.
Found New Hardware popup message (Windows 7) If the popup message does not appear, run the Tracer TU installation file:
Tracer TU Setup_x.x.xxx.exe.
B–1 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Appendix C. Upgrading UC800 Firmware
If a new level of UC800 firmware is issued, you can upgrade the firmware by completing the
following steps:
1. Connect your laptop to the USB port on the UC800 or on the Control Panel.
2. Start Tracer TU.
3. Select U t i l i t i e s > E q u i p m e n t > C o n f i g u r a t i o n to display the Configuration screen.
4. Click the U p g r a d e C o n t r o l l e r button at the bottom left of the window.
The Application Software Download dialog box appears.
5. Select the version number from the Version drop-down list box.
6. Click U p g r a d e D e v i c e .
A message box appears asking you to confirm your decision to upgrade the UC800.
7. Click O K .
BAS-SVP031B-EN C–1
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Appendix D. Installing Firmware on the UC800
This appendix explains the procedures to follow in each of two cases:
• Firmware installation on a blank UC800
• Firmware installation on a UC800 that currently has a different version of the firmware
installed.
Service Pin
D–1 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Installing Firmware on the UC800
4. Press the Connect button on the Startup Task Panel dialog box.
A message dialog box appears asking if you want to change the application.
5. Click O K to display the Download Software dialog box.
6. Click C l e a n D e v i c e to remove the old buld on the UC800.
The dialog box displays the message, “No application found.”
7. Select the chiller model from the Product Name drop-down list and the version number from
the Version drop-down list.
8. Click U p g r a d e D e v i c e .
A confirmation dialog box appears.
9. Click O K .
The upgrade routine starts to download firmware to the UC800. A message indicates that the
upgrade has successfully completed.
Because no configuration is present on the UC800, Tracer TU automatically displays the
Configuration screen, so you can prepare and save a configuration to the controller.
BAS-SVP031B-EN D–2
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Appendix E. CT Meter Scale Table
The CT Meter Scale is an especially critical factor and must be determined correctly. Use the
following table to determine CT Meter scale for your application. Using the part number on the
CT, which provides the CT ratio, the RLA of the motor, and the number of turns through the CT,
you can read the resulting CT meter scale from this table.
Table 43. CT Meter Scale
Actual Motor CT CT Ratio (A: CT Rating Inside Outside Primary CT Meter
RLA (A) Extension A) (A) Diameter B Diameter B Turns Scale
X13580253 (inches) (inches)
or
X13580269
E–1 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Appendix F. RTAC Diagnostics
This document lists all the diagnostics by major category (for example, Starter, UC800). For each
diagnostic, it lists the hex code (if applicable), diagnostic name, target severity, target
persistence, active (inactive) modes, criteria and reset level. The table column information can be
described as follows:
• H e x C o d e —A two or three digit hexadecimal code used to uniquely identify each diagnostic
• A f f e c t e d T a r g e t —Defines the “target” or what is affected by the diagnostic. Usually either
the entire chiller, or a particular component is affected by the diagnostic (the same one as the
source), but in special cases functions are modified or disabled by the diagnostic. N o n e
implies that there is no direct affect to the chiller, sub components or functional operation.
• T a r g e t S e v e r i t y —Defines the severity of the above effected target. I m m e d i a t e means
immediate shutdown of the affected portion, N o r m a l means normal or friendly shutdown of
the affected portion and S p e c i a l M o d e means a special mode of operation (limp along) is
invoked, but without shutdown, and I n f o means an Informational Note or Warning is
generated.
• P e r s i s t e n c e —Defines whether or not the diagnostic and its effects are to be manually reset
( L a t c h i n g ) , or can be either manually or automatically reset ( N o n l a t c h i n g ) .
• A c t i v e M o d e s [ I n a c t i v e M o d e s ] —States the modes or periods of operation that the
diagnostic is active in and, as necessary, those modes or periods that it is specifically not
active in as an exception to the active modes. The inactive modes are enclosed in brackets, [ ].
Note that the modes used in this column are internal and not generally enunciated to any of
the formal mode displays.
• C r i t e r i a —Quantitatively defines the criteria used in generating the diagnostic and, if
Nonlatching, the criteria for auto reset.
• R e s e t L e v e l —Defines the lowest level of manual diagnostic reset command which can clear
the diagnostic. The manual diagnostic reset levels in order of priority are: L o c a l and R e m o t e .
A diagnostic that has a reset level of Local can only be reset by a local diagnostic reset
command, but not by the lower priority remote Reset command, whereas a diagnostic listed
as Remote reset can be reset by either reset command.
BAS-SVP031B-EN F–1
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
AFD Diagnostics
Table 44. AFD Diagnostics
Diagnostic Name and Affects Severity Persistence Active Criteria Reset Level
Source Target Modes
[Inac-
tive
Modes]
AFD Fault – 1A Cprsr Immediate NonLatch All AFD Fault. Numerous drive faults Local
can cause this general fault
AFD Fault – 1B Cprsr Immediate NonLatch All AFD Fault. Numerous drive faults Local
can cause this general fault
AFD Fault – 2A Cprsr Immediate NonLatch All AFD Fault. Numerous drive faults Local
can cause this general fault
AFD Fault – 2B Cprsr Immediate NonLatch All AFD Fault. Numerous drive faults Local
can cause this general fault
AFD Motor Current Circuit Immediate Latch All Compressor current exceeded Local
Overload – 1A overload time vs. trip
characteristic. Must trip = 132%
RLA, Must hold=125%
AFD Motor Current Circuit Immediate Latch All Compressor current exceeded Local
Overload – 1B overload time vs. trip
characteristic. Must trip = 132%
RLA, Must hold=125%
AFD Motor Current Circuit Immediate Latch All Compressor current exceeded Local
Overload – 2A overload time vs. trip
characteristic. Must trip = 132%
RLA, Must hold=125%
AFD Motor Current Circuit Immediate Latch All Compressor current exceeded Local
Overload – 2B overload time vs. trip
characteristic. Must trip = 132%
RLA, Must hold=125%
AFD Interrupt Failure – 1A Chiller Immediate Latch AFD Respective AFD is reporting that Local
Shutdown Intended it is still running the compressor
and Special to be OFF when the MP has commanded the
Action drive/compressor to be Off.
Detection time shall be 10
seconds minimum and 15
seconds maximum. On detection
and until the controller is
manually reset: this diagnostic
shall be active and the alarm
relay shall be energized, the Evap
Pump Output will be energized,
the effected compressor will be
continually commanded off, and
be unloaded, while a normal stop
shall be commanded to all other
compressors. For as long as
compressor operation continues,
the MP shall continue oil return
and fan control on the circuit
affected.
AFD Interrupt Failure – 1B Chiller Immediate Latch AFD See Criteria for ‘AFD Interrupt
Shutdown Intended Failure – 1A’ above.
and Special to be OFF
Action
F–2 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
Diagnostic Name and Affects Severity Persistence Active Criteria Reset Level
Source Target Modes
[Inac-
tive
Modes]
AFD Interrupt Failure – 2A Chiller Immediate Latch AFD See Criteria for ‘AFD Interrupt
Shutdown Intended Failure – 1A’ above.
and Special to be OFF
Action
AFD Interrupt Failure – 2B Chiller Immediate Latch AFD See Criteria for ‘AFD Interrupt
Shutdown Intended Failure – 1A’ above.
and Special to be OFF
Action
Starter Diagnostics
The diagnostics listed in the following table are called out by the Starter module and
communicated to the Main Processor.
Table 45. Starter Diagnostics
180 Starter Did Cprsr Immediate Latch On the first The Starter Module did not Local
Not Transition check after receive a transition complete
- 1A transition. signal in the designated time
from its command to transition.
The must hold time from the
Starter Module transition
command is 1 second. The Must
trip time from the transition
command is 6 seconds. Actual
design is 2.5 seconds. This
diagnostic is active only for Y-
Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters.
181 Starter Did Cprsr Immediate Latch On the first The Starter Module did not Local
Not Transition check after receive a transition complete
- 1B transition. signal in the designated time
from its command to transition.
The must hold time from the
Starter Module transition
command is 1 second. The Must
trip time from the transition
command is 6 seconds. Actual
design is 2.5 seconds. This
diagnostic is active only for Y-
Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters.
BAS-SVP031B-EN F–3
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
182 Starter Did Cprsr Immediate Latch On the first The Starter Module did not Local
Not Transition check after receive a transition complete
- 2A transition. signal in the designated time
from its command to transition.
The must hold time from the
Starter Module transition
command is 1 second. The Must
trip time from the transition
command is 6 seconds. Actual
design is 2.5 seconds. This
diagnostic is active only for Y-
Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters.
183 Starter Did Cprsr Immediate Latch On the first The Starter Module did not Local
Not Transition check after receive a transition complete
- 2B transition. signal in the designated time
from its command to transition.
The must hold time from the
Starter Module transition
command is 1 second. The Must
trip time from the transition
command is 6 seconds. Actual
design is 2.5 seconds. This
diagnostic is active only for Y-
Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters.
184 Phase Cprsr Immediate Latch Compressor A phase reversal was detected Local
Reversal - 1A energized to on the incoming current. On a
transition compressor startup the phase
command [All reversal logic must detect and
Other Times] trip in a maximum of 0.3 second
from compressor start.
185 Phase Cprsr Immediate Latch Compressor A phase reversal was detected Local
Reversal - 1B energized to on the incoming current. On a
transition compressor startup the phase
command [All reversal logic must detect and
Other Times] trip in a maximum of 0.3 second
from compressor start.
186 Phase Cprsr Immediate Latch Compressor A phase reversal was detected Local
Reversal - 2A energized to on the incoming current. On a
transition compressor startup the phase
command [All reversal logic must detect and
Other Times] trip in a maximum of 0.3 second
from compressor start.
187 Phase Cprsr Immediate Latch Compressor A phase reversal was detected Local
Reversal - 2B energized to on the incoming current. On a
transition compressor startup the phase
command [All reversal logic must detect and
Other Times] trip in a maximum of 0.3 second
from compressor start.
F–4 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
19C Phase Loss - Cprsr Immediate Latch Start Sequence a) No current was sensed on Local
1A and Run modes one or two of the current
transformer inputs while
running or starting (See
Nonlatching Power Loss
Diagnostic for all three phases
lost while running). Must hold =
20% RLA. Must trip = 5% RLA.
Time to trip shall be longer than
guaranteed reset on Starter
Module at a minimum, 3
seconds maximum. Actual
design trippoint is 10%. The
actual design trip time is 2.64
seconds. b) If Phase reversal
protection is enabled and
current is not sensed on one or
more current xformer inputs.
Logic will detect and trip in a
maximum of 0.3 second from
compressor start.
19D Phase Loss - Cprsr Immediate Latch Start Sequence a) No current was sensed on Local
1B and Run modes one or two of the current
transformer inputs while
running or starting (See
Nonlatching Power Loss
Diagnostic for all three phases
lost while running). Must hold =
20% RLA. Must trip = 5% RLA.
Time to trip shall be longer than
guaranteed reset on Starter
Module at a minimum, 3
seconds maximum. Actual
design trippoint is 10%. The
actual design trip time is 2.64
seconds. b) If Phase reversal
protection is enabled and
current is not sensed on one or
more current xformer inputs.
Logic will detect and trip in a
maximum of 0.3 second from
compressor start
19E Phase Loss - Cprsr Immediate Latch Start Sequence a) No current was sensed on
2A and Run modes one or two of the current
transformer inputs while
running or starting (See
Nonlatching Power Loss
Diagnostic for all three phases
lost while running). Must hold =
20% RLA. Must trip = 5% RLA.
Time to trip shall be longer than
guaranteed reset on Starter
Module at a minimum, 3
seconds maximum. Actual
design trippoint is 10%. The
actual design trip time is 2.64
seconds. b) If Phase reversal
protection is enabled and
current is not sensed on one or
more current xformer inputs.
Logic will detect and trip in a
maximum of 0.3 second from
compressor start
BAS-SVP031B-EN F–5
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
19F Phase Loss - Cprsr Immediate Latch Start Sequence a) No current was sensed on
2B and Run modes one or two of the current
transformer inputs while
running or starting (See
Nonlatching Power Loss
Diagnostic for all three phases
lost while running). Must hold =
20% RLA. Must trip = 5% RLA.
Time to trip shall be longer than
guaranteed reset on Starter
Module at a minimum, 3
seconds maximum. Actual
design trippoint is 10%. The
actual design trip time is 2.64
seconds. b) If Phase reversal
protection is enabled and
current is not sensed on one or
more current xformer inputs.
Logic will detect and trip in a
maximum of 0.3 second from
compressor start
1A0 Power Loss - Cprsr Immediate NonLatch All compressor The compressor had previously
1A running modes established currents while
[all compressor running and then all three
starting and phases of current were lost.
non-running Design: Less than 10% RLA, trip
modes] in 2.64 seconds. This diagnostic
will preclude the Phase Loss
Diagnostic and the Transition
Complete Input Opened
Diagnostic from being called
out. To prevent this diagnostic
from occurring with the
intended disconnect of main
power, the minimum time to trip
must be greater than the
guaranteed reset time of the
Starter module. Note: This
diagnostic prevents nuisance
latching diagnostics due to a
momentary power loss – It does
not protect motor/compressor
from uncontrolled power
reapplication. See Momentary
Power Loss Diagnostic for this
protection. This diagnostic is
not active during the start mode
before the transition complete
input is proven. Thus a random
power loss during a start would
result in either a “Starter Fault
Type 3” or a “Starter Did Not
Transition” latching diagnostic.
F–6 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
1A1 Power Loss - Cprsr Immediate NonLatch All compressor The compressor had previously
1B running modes established currents while
[all compressor running and then all three
starting and phases of current were lost.
non-running Design: Less than 10% RLA, trip
modes] in 2.64 seconds. This diagnostic
will preclude the Phase Loss
Diagnostic and the Transition
Complete Input Opened
Diagnostic from being called
out. To prevent this diagnostic
from occurring with the
intended disconnect of main
power, the minimum time to trip
must be greater than the
guaranteed reset time of the
Starter module.
1A2 Power Loss - Cprsr Immediate NonLatch All compressor The compressor had previously
2A running modes established currents while
[all compressor running and then all three
starting and phases of current were lost.
non-running Design: Less than 10% RLA, trip
modes] in 2.64 seconds. This diagnostic
will preclude the Phase Loss
Diagnostic and the Transition
Complete Input Opened
Diagnostic from being called
out. To prevent this diagnostic
from occurring with the
intended disconnect of main
power, the minimum time to trip
must be greater than the
guaranteed reset time of the
Starter module.
1A3 Power Loss - Cprsr Immediate NonLatch All compressor The compressor had previously
2B running modes established currents while
[all compressor running and then all three
starting and phases of current were lost.
non-running Design: Less than 10% RLA, trip
modes] in 2.64 seconds. This diagnostic
will preclude the Phase Loss
Diagnostic and the Transition
Complete Input Opened
Diagnostic from being called
out. To prevent this diagnostic
from occurring with the
intended disconnect of main
power, the minimum time to trip
must be greater than the
guaranteed reset time of the
Starter module.
1B2 Severe Circuit Immediate Latch All Running A 30% Current Imbalance has
Current Modes been detected on one phase
Imbalance - relative to the average of all 3
1A phases for 90 continuous
seconds.
1B3 Severe Circuit Immediate Latch All Running A 30% Current Imbalance has
Current Modes been detected on one phase
Imbalance - relative to the average of all 3
1B phases for 90 continuous
seconds.
BAS-SVP031B-EN F–7
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
1B4 Severe Circuit Immediate Latch All Running A 30% Current Imbalance has
Current Modes been detected on one phase
Imbalance - relative to the average of all 3
2A phases for 90 continuous
seconds
1B5 Severe Circuit Immediate Latch All Running A 30% Current Imbalance has
Current Modes been detected on one phase
Imbalance - relative to the average of all 3
2B phases for 90 continuous
seconds.
1E9 Starter Fault Cprsr Immediate Latch Starting - Y This is a specific starter test
Type I – 1A Delta Starters where 1M(1K1) is closed first
Only and a check is made to ensure
that there are no currents
detected by the CT's. If currents
are detected when only 1M is
closed first at start, then one of
the other contactors is shorted.
1EA Starter Fault Cprsr Immediate Latch Starting - Y This is a specific starter test
Type I – 1B Delta Starters where 1M(1K1) is closed first
Only and a check is made to ensure
that there are no currents
detected by the CT's. If currents
are detected when only 1M is
closed first at start, then one of
the other contactors is shorted.
1EB Starter Fault Cprsr Immediate Latch Starting - Y This is a specific starter test
Type I – 2A Delta Starters where 1M(1K1) is closed first
Only and a check is made to ensure
that there are no currents
detected by the CT's. If currents
are detected when only 1M is
closed first at start, then one of
the other contactors is shorted.
1EC Starter Fault Cprsr Immediate Latch Starting - Y This is a specific starter test Local
Type I –2B Delta Starters where 1M(1K1) is closed first
Only and a check is made to ensure
that there are no currents
detected by the CT's. If currents
are detected when only 1M is
closed first at start, then one of
the other contactors is shorted.
1ED Starter Fault Cprsr Immediate Latch Starting All a. This is a specific starter test Local
Type II – 1A types of where the Shorting Contactor
starters (1K3) is individually energized
and a check is made to ensure
that there are no currents
detected by the CT's. If current
is detected when only S is
energized at Start, then 1M is
shorted. b. This test in a. above
applies to all forms of starters
(Note: It is understood that
many starters do not connect to
the Shorting Contactor.).
F–8 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
1EE Starter Fault Cprsr Immediate Latch Starting – All a. This is a specific starter test Local
Type II –1B types of where the Shorting Contactor
starters (1K3) is individually energized
and a check is made to ensure
that there are no currents
detected by the CT's. If current
is detected when only S is
energized at Start, then 1M is
shorted. b. This test in a. above
applies to all forms of starters
(Note: It is understood that
many starters do not connect to
the Shorting Contactor.).
1EF Starter Fault Cprsr Immediate Latch Starting – All a. This is a specific starter test Local
Type II –2A types of where the Shorting Contactor
starters (1K3) is individually energized
and a check is made to ensure
that there are no currents
detected by the CT's. If current
is detected when only S is
energized at Start, then 1M is
shorted. b. This test in a. above
applies to all forms of starters
(Note: It is understood that
many starters do not connect to
the Shorting Contactor.).
1F0 Starter Fault Cprsr Immediate Latch Starting – All a. This is a specific starter test Local
Type II – 2B types of where the Shorting Contactor
starters (1K3) is individually energized
and a check is made to ensure
that there are no currents
detected by the CT's. If current
is detected when only S is
energized at Start, then 1M is
shorted. b. This test in a. above
applies to all forms of starters
(Note: It is understood that
many starters do not connect to
the Shorting Contactor.).
1F1 Starter Fault Cprsr Immediate Latch Starting As part of the normal start Local
Type III – 1A [Adaptive sequence to apply power to the
Frequency compressor, the Shorting
Starter Type] Contactor (1K3) and then the
Main Contactor (1K1) were
energized. 1.6 seconds later
there were no currents detected
by the CT's for the last 1.2
Seconds on all three phases.
The test above applies to all
forms of starters except
Adaptive Frequency Drives.
1F2 Starter Fault Cprsr Immediate Latch Starting As part of the normal start Local
Type III –1B [Adaptive sequence to apply power to the
Frequency compressor, the Shorting
Starter Type] Contactor (1K3) and then the
Main Contactor (1K1) were
energized. 1.6 seconds later
there were no currents detected
by the CT's for the last 1.2
seconds on all three phases.
The test above applies to all
forms of starters except
Adaptive Frequency Drives.
BAS-SVP031B-EN F–9
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
1F3 Starter Fault Cprsr Immediate Latch Starting As part of the normal start Local
Type III –2A [Adaptive sequence to apply power to the
Frequency compressor, the Shorting
Starter Type] Contactor (1K3) and then the
Main Contactor (1K1) were
energized. 1.6 seconds later
there were no currents detected
by the CT's for the last 1.2
seconds on all three phases.
The test above applies to all
forms of starters except
Adaptive Frequency Drives.
1F4 Starter Fault Cprsr Immediate Latch Starting As part of the normal start Local
Type III –2B [Adaptive sequence to apply power to the
Frequency compressor, the Shorting
Starter Type] Contactor (1K3) and then the
Main Contactor (1K1) were
energized. 1.6 seconds later
there were no currents detected
by the CT's for the last 1.2
seconds on all three phases.
The test above applies to all
forms of starters except
Adaptive Frequency Drives.
5AC Transition Cprsr Immediate Latch Pre-Start The Transition Complete input Local
Complete was found to be shorted before
Input Shorted the compressor was started.
–1A This is active for all
electromechanical starters.
5AD Transition Cprsr Immediate Latch Pre-Start The Transition Complete input Local
Complete was found to be shorted before
Input Shorted the compressor was started.
–1B This is active for all
electromechanical starters.
5AE Transition Cprsr Immediate Latch Pre-Start The Transition Complete input Local
Complete was found to be shorted before
Input Shorted the compressor was started.
–2A This is active for all
electromechanical starters.
5AF Transition Cprsr Immediate Latch Pre-Start The Transition Complete input Local
Complete was found to be shorted before
Input Shorted the compressor was started.
–2B This is active for all
electromechanical starters.
5B0 Transition Cprsr Immediate Latch All running The Transition Complete input Local
Complete modes was found to be opened with the
Input Opened compressor motor running after
–1A a successful completion of
transition. This is active only for
Y-Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters. To prevent this
diagnostic from occurring as the
result of a power loss to the
contactors, the minimum time
to trip must be greater than the
trip time for the power loss
diagnostic.
F–10 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5B1 Transition Cprsr Immediate Latch All running The Transition Complete input Local
Complete modes was found to be opened with the
Input Opened compressor motor running after
–1B a successful completion of
transition. This is active only for
Y-Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters. To prevent this
diagnostic from occurring as the
result of a power loss to the
contactors, the minimum time
to trip must be greater than the
trip time for the power loss
diagnostic.
5B2 Transition Cprsr Immediate Latch All running The Transition Complete input Local
Complete modes was found to be opened with the
Input Opened compressor motor running after
–2A a successful completion of
transition. This is active only for
Y-Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters. To prevent this
diagnostic from occurring as the
result of a power loss to the
contactors, the minimum time
to trip must be greater than the
trip time for the power loss
diagnostic.
5B3 Transition Cprsr Immediate Latch All running The Transition Complete input Local
Complete modes was found to be opened with the
Input Opened compressor motor running after
–2B a successful completion of
transition. This is active only for
Y-Delta, Auto-Transformer,
Primary Reactor, and X-Line
Starters. To prevent this
diagnostic from occurring as the
result of a power loss to the
contactors, the minimum time
to trip must be greater than the
trip time for the power loss
diagnostic.
BA Motor Current Circuit Immediate Latch Cprsr Compressor current exceeded Local
Overload - 1A Energized overload time vs. trip
characteristic. For A/C products
Must trip = 140% RLA, Must
hold=125%, nominal trip
132.5% in 30 seconds
BB Motor Current Circuit Immediate Latch Cprsr Compressor current exceeded Local
Overload - 1B Energized overload time vs. trip
characteristic. For A/C products
Must trip = 140% RLA, Must
hold=125%, nominal trip
132.5% in 30 seconds
BC Motor Current Circuit Immediate Latch Cprsr Compressor current exceeded Local
Overload - 2A Energized overload time vs. trip
characteristic. For A/C products
Must trip = 140% RLA, Must
hold=125%, nominal trip
132.5% in 30 seconds
BAS-SVP031B-EN F–11
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
BD Motor Current Circuit Immediate Latch Cprsr Compressor current exceeded Local
Overload - 2B Energized overload time vs. trip
characteristic. For A/C products
Must trip = 140% RLA, Must
hold=125%, nominal trip
132.5% in 30 seconds
F–12 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
D7 Over Voltage Chiller Normal NonLatch Pre-Start and Nom. trip: 60 seconds at Remote
Any Ckt(s) greater than 112.5%, ± 2.5%,
Energzd Auto Reset at 109% or less.
D8 Under Voltage Chiller Normal NonLatch Pre-Start and Nom. trip: 60 seconds at less Remote
Any Ckt(s) than 87.5%, ± 2.8% at 200V ±
Energzd 1.8% at 575V, Auto Reset at
90% or greater.
BAS-SVP031B-EN F–13
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
D9 MP: Reset Has Platform Warning NonLatch All The main processor has successfully Remote
Occurred come out of a reset and built its
application. A reset may have been
due to a power up, installing new
software or configuration. This
diagnostic is immediately and
automatically cleared and thus can
only be seen in the Historic
Diagnostic List
194 Low Evaporator Rfgt Circuit Immedi- Latch All Ckt a. The inferred Saturated Evap Remote
Temperature - Ckt1 ate Running Refrigerant Temperature (calculated
Modes from suction pressure transducer(s))
[reversible dropped below the Low Refrigerant
heat pump Temperature Cutout Setpoint for
in heating 120°F-sec (8°F-sec max rate) while
mode, the circuit was running after the
excluding ignore period had expired. The
defrost] integral is held at zero for the ignore
time (which is a function of outdoor
air temp) following the circuit startup
and the integral will be limited to
never trip in less than 15 seconds, i.
e. the error term shall be clamped to
8°F. The minimum LRTC setpoint is
-5°F (18.7 Psia) the point at which oil
separates from the refrigerant. b.
During the timeout of the trip
integral, the unload solenoid(s) of the
running compressors on the circuit,
shall be energized continuously.
Normal load/unload operation will be
resumed if the trip integral is reset by
return to temps above the cutout
setpoint.
195 Low Evaporator Rfgt Circuit Immedi- Latch All Ckt a. The inferred Saturated Evap Remote
Temperature - Ckt2 ate Running Refrigerant Temperature (calculated
Modes from suction pressure transducer(s))
[reversible dropped below the Low Refrigerant
heat pump Temperature Cutout Setpoint for
in heating 120°F-sec (8°F-sec max rate) while
mode, the circuit was running after the
excluding ignore period had expired. The
defrost] integral is held at zero for the ignore
time (which is a function of outdoor
air temp) following the circuit startup
and the integral will be limited to
never trip in less than 15 seconds, i.
e. the error term shall be clamped to
8°F. The minimum LRTC setpoint is
-5°F (18.7 Psia) the point at which oil
separates from the refrigerant. b.
During the timeout of the trip
integral, the unload solenoid(s) of the
running compressors on the circuit,
shall be energized continuously.
Normal load/unload operation will be
resumed if the trip integral is reset by
return to temps above the cutout
setpoint.
F–14 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
8A Evaporator Water Chiller Immedi- Latching Ckt Large evaporator approach temps, Remote
Flow (High Approach ate Energized low evap sat temps, and presence of
Temperature)– Shutdown [Ckt Not liquid refrigerant, suggest this circuit
Circuit 1 Energized] is running with no or reversed
evaporator water flow.
8A Evaporator Water Chiller Immedi- Latching Ckt Large evaporator approach temps, Remote
Flow (High Approach ate Energized low evap sat temps, and presence of
Temperature)– Shutdown [Ckt Not liquid refrigerant, suggest this circuit
Circuit 2 Energized] is running with no or reversed
evaporator water flow.
8A Evap Water Flow Chiller Immedi- Latching Any Ckt The entering evaporator water temp Remote
(Entering Water ate Energized [ fell below the leaving evaporator
Temp) Shutdown No Ckts water temp by more than 2°F for 180
Energized] °F-sec, minimum trip time 1 minute.
198 Low Oil Flow - Cprsr Cprsr Immedi- Latch Cprsr The intermediate oil pressure Local
1A ate Energized transducer for this compressor was
and Delta P out of the acceptable pressure range
above 35 for 15 seconds, while the Delta
Psid Pressure was greater than 35 Psid.:
Acceptable range is 0.50 > (PC-PI) /
(PC-PE) for the first 2.5 minutes of
operation, and 0.25 > (PC-PI) / (PC-
PE) thereafter,
199 Low Oil Flow - Cprsr Cprsr Immedi- Latch Cprsr The intermediate oil pressure Local
1B ate Energized transducer for this compressor was
and Delta P out of the acceptable pressure range
above 35 for 15 seconds, while the Delta
Psid Pressure was greater than 35 Psid.:
Acceptable range is 0.50 > (PC-PI) /
(PC-PE) for the first 2.5 minutes of
operation, and 0.25 > (PC-PI) / (PC-
PE) thereafter,
19A Low Oil Flow - Cprsr Cprsr Immedi- Latch Cprsr The intermediate oil pressure Local
2A ate Energized transducer for this compressor was
and Delta P out of the acceptable pressure range
above 35 for 15 seconds, while the Delta
Psid Pressure was greater than 35Psid.:
Acceptable range is 0.50 > (PC-PI) /
(PC-PE) for the first 2.5 minutes of
operation, and 0.25 > (PC-PI) / (PC-
PE) thereafter,,.
19B Low Oil Flow - Cprsr Cprsr Immedi- Latch Cprsr The intermediate oil pressure Local
2B ate Energized transducer for this compressor was
and Delta P out of the acceptable pressure range
above 35 for 15 seconds, while the Delta
Psid Pressure was greater than 35 Psid.:
Acceptable range is 0.50 > (PC-PI) /
(PC-PE) for the first 2.5 minutes of
operation, and 0.25 > (PC-PI) / (PC-
PE) thereafter,
1AE Low Differential Rfgt Circuit Immedi- Latch Cprsr The system differential pressure for Remote
Pressure - Ckt1 ate Energized the respective circuit was below 35
Psid for more than 2000 Psid-sec with
either a 1 minute (single cprsr circuit)
or 2.5 minute (manifolded cprsr
circuit) ignore time from the start of
the circuit.
BAS-SVP031B-EN F–15
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
1AF Low Differential Rfgt Circuit Immedi- Latch Cprsr The system differential pressure for Remote
Pressure - Ckt2 ate Energized the respective circuit was below 35
Psid for more than 2000 Psid-sec with
either a 1 minute (single cprsr circuit)
or 2.5 minute (manifolded cprsr
circuit) ignore time from the start of
the circuit.
1C6 High Differential Rfgt Circuit Normal Latch Cprsr The system differential pressure for Remote
Pressure - Ckt1 Energized the respective circuit was above 275
Psid for 2 consecutive samples or
more than 10 seconds.
1C7 High Differential Rfgt Circuit Normal Latch Cprsr The system differential pressure for Remote
Pressure - Ckt2 Energized the respective circuit was above 275
Psid for 2 consecutive samples or
more than 10 seconds
1DD High Oil Temperature Cprsr 1A Immedi- Latch Cprsr The respective oil temperature as Remote
– 1A ate Energized supplied to the compressor,
exceeded 200°F for 2 consecutive
samples or for over 10 seconds.
Note: As part of the Compressor High
Temperature Limit Mode (aka
Minimum Limit), the running
compressor’s female load step will be
forced loaded when its oil
temperature exceeds 190F and
returned to normal control when the
oil temperature falls below 170°F.
1DE High Oil Temperature Cprsr 1B Immedi- Latch Cprsr The respective oil temperature as Remote
–1B ate Energized supplied to the compressor,
exceeded 200°F for 2 consecutive
samples or for over 10 seconds.
Note: As part of the Compressor High
Temperature Limit Mode (aka
Minimum Limit), the running
compressor’s female load step will be
forced loaded when its oil
temperature exceeds 190F and
returned to normal control when the
oil temperature falls below 170°F.
1DF High Oil Temperature Cprsr 2A Immedi- Latch Cprsr The respective oil temperature as Remote
–2A ate Energized supplied to the compressor,
exceeded 200°F for 2 consecutive
samples or for over 10 seconds.
Note: As part of the Compressor High
Temperature Limit Mode (aka
Minimum Limit), the running
compressor’s female load step will be
forced loaded when its oil
temperature exceeds 190F and
returned to normal control when the
oil temperature falls below 170°F.
1E0 High Oil Temperature Cprsr 2B Immedi- Latch Cprsr The respective oil temperature as Remote
– 2B ate Energized supplied to the compressor,
exceeded 200°F for 2 consecutive
samples or for over 10 seconds.
Note: As part of the Compressor High
Temperature Limit Mode (aka
Minimum Limit), the running
compressor’s female load step will be
forced loaded when its oil
temperature exceeds 190F and
returned to normal control when the
oil temperature falls below 170°F.
F–16 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
1E5 Oil Temperature Circuit Normal Latch All Bad Sensor or LLID Remote
Sensor – 1A
1E6 Oil Temperature Circuit Normal Latch All Bad Sensor or LLID Remote
Sensor – 1B
1E7 Oil Temperature Circuit Normal Latch All Bad Sensor or LLID Remote
Sensor – 2A
1E8 Oil Temperature Circuit Normal Latch All Bad Sensor or LLID Remote
Sensor – 2B
27D Evaporator Liquid Circuit Immedi- Latch All Bad Sensor or LLID Remote
Level Sensor – Ckt1 ate
3F9 Evaporator Liquid Circuit Immedi- Latch All Bad Sensor or LLID Remote
Level Sensor – Ckt2 ate
2A1 Condenser Fan VFD All Special Latch Prestart and The MP has received a fault signal Remote
Fault - Ckt1 Dr 1 inverters Mode Running w/ from the respective condenser fan
on this Variable Variable Speed Inverter Drive, and
circuit Spd Fan unsuccessfully attempted (5 times
enabled within 1 minute of each other) to
clear the fault. The 4 th attempt
removes power from the inverter to
create a power up reset. If the fault
does not clear, the MP will revert to
constant speed operation without the
use of the inverter’s fan. The inverter
must be manually bypassed, and fan
outputs rebound, for full fixed speed
fan operation.
5B4 Condenser Fan VFD All Special Latch Prestart and The MP has received a fault signal Remote
Fault - Ckt1 Dr 2 inverters Mode Running w/ from the respective condenser fan
on this Variable Variable Speed Inverter Drive, and
circuit Spd Fan unsuccessfully attempted (5 times
enabled within 1 minute of each other) to
clear the fault. The 4 th attempt
removes power from the inverter to
create a power up reset. If the fault
does not clear, the MP will revert to
constant speed operation without the
use of the inverter’s fan. The inverter
must be manually bypassed, and fan
outputs rebound, for full fixed speed
fan operation.
2A2 Condenser Fan VFD All Special Latch Prestart and The MP has received a fault signal Remote
Fault - Ckt2 Dr 1 inverters Mode Running w/ from the respective condenser fan
on this Variable Variable Speed Inverter Drive, and
circuit Spd Fan unsuccessfully attempted (5 times
enabled within 1 minute of each other) to
clear the fault. The 4 th attempt
removes power from the inverter to
create a power up reset. If the fault
does not clear, the MP will revert to
constant speed operation without the
use of the inverter’s fan. The inverter
must be manually bypassed, and fan
outputs rebound, for full fixed speed
fan operation.
BAS-SVP031B-EN F–17
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5B5 Condenser Fan VFD All Special Latch Prestart and The MP has received a fault signal Remote
Fault - Ckt2 Dr 2 inverters Mode Running w/ from the respective condenser fan
on this Variable Variable Speed Inverter Drive, and
circuit Spd Fan unsuccessfully attempted (5 times
enabled within 1 minute of each other) to
clear the fault. The 4 th attempt
removes power from the inverter to
create a power up reset. If the fault
does not clear, the MP will revert to
constant speed operation without the
use of the inverter’s fan. The inverter
must be manually bypassed, and fan
outputs rebound, for full fixed speed
fan operation.
390 BAS Failed to Chiller Special NonLatch At power-up The BAS was setup as "installed" and Remote
Establish the BAS did not communicate with
Communication the MP within 15 minutes after
power-up. Refer to Section on
Setpoint Arbitration to determine
how setpoints and operating modes
may be effected. Note: The original
requirement for this was 2 minutes,
but was implemented at 15 minutes
for RTAC.
398 BAS Communication Chiller Special NonLatch All The BAS was setup as "installed" at Remote
Lost the MP and the Comm 3 llid lost
communications with the BAS for 15
contiguous minutes after it had been
established. Refer to Section on
Setpoint Arbitration to determine
how setpoints and operating modes
may be effected by the comm loss.
The chiller follows the value of the
Tracer Default Run Command which
can be previously written by Tracer
and stored nonvolatilely by the MP
(either use local or shutdown).
583 Low Evaporator Circuit Warning NonLatch Starter The liquid level sensor is seen to be at Remote
Liquid Level – Ckt1 Contactor or near its low end of range for 80
Energized contiguous minutes while the
[all Stop compressor is running. Design: 20%
modes] or less of bit count corresponding to –
21.2 mm or less liquid level for 80
minutes)
5B6 Low Evaporator Circuit Warning NonLatch Starter The liquid level sensor is seen to be at Remote
Liquid Level – Ckt2 Contactor or near its low end of range for 80
Energized contiguous minutes while the
[all Stop compressor is running. Design: 20%
modes] or less of bit count corresponding to –
21.2 mm or less liquid level for 80
minutes)
584 High Evaporator Circuit Normal Latch Starter The liquid level sensor is seen to be at Remote
Liquid Level – Ckt1 Contactor or near its high end of range for 80
Energized contiguous minutes while the
[all Stop compressor is running. (The
modes] diagnostic timer will hold, but not
clear when the circuit is off). Design:
80% or more of bit count
corresponding to +21.2 mm or more
liquid level for 80 minutes)
F–18 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5B7 High Evaporator Circuit Normal Latch Starter The liquid level sensor is seen to be at . Remote
Liquid Level – Ckt2 Contactor or near its high end of range for 80
Energized contiguous minutes while the
[all Stop compressor is running. (The
modes] diagnostic timer will hold, but not
clear when the circuit is off). Design:
80% or more of bit count
corresponding to +21.2 mm or more
liquid level for 80 minutes)
6B9 Evaporator Rfgt Drain Circuit NA Latch Circuit non- This diagnostic is effective only with Remote
– Circuit 1 running Remote Evap units. The liquid level of
modes the respective evaporator was not
[Drain Valve seen to be below the level of –21.2
commanded mm within 5 minutes of the
closed] commanded opening of its Drain
Valve Solenoid. The diagnostic will
not be active if the drain valve is
commanded closed.
6BA Evaporator Rfgt Drain Circuit NA Latch Circuit non- This diagnostic is effective only with Remote
– Circuit 2 running Remote Evap units. The liquid level of
modes the respective evaporator was not
[Drain Valve seen to be below the level of –21.2
commanded mm within 5 minutes of the
closed] commanded opening of its Drain
Valve Solenoid Valve. The diagnostic
will not be active if the drain valve is
commanded closed.
87 External Chilled Chiller Warning NonLatch All a. Function Not "Enabled": no Remote
Water Setpoint diagnostics. b. "Enabled ": Out-Of-
Range Low or Hi or bad LLID, set
diagnostic, default CWS to next level
of priority (e.g. Front Panel SetPoint).
This Info diagnostic will automatically
reset if the input returns to the
normal range.
89 External Current Chiller Warning NonLatch All a. Not "Enabled": no diagnostics. b. Remote
Limit Setpoint "Enabled ": Out-Of-Range Low or Hi
or bad LLID, set diagnostic, default
CLS to next level of priority (e.g.
Front Panel SetPoint. This Info
diagnostic will automatically reset if
the input returns to the normal
range.
8E Evaporator Entering Chilled Warning Latch All Bad Sensor or LLID a. Normal Remote
Water Temp Sensor Water operation, no effects on control. b.
Reset Chiller shall remove any Return or
Constant Return Chilled Water Reset,
if it was in effect. Apply slew rates per
Chilled Water Reset spec.
AB Evaporator Leaving Chiller Normal Latch All Bad Sensor or LLID Remote
Water Temp Sensor
5B8 Condenser Rfgt Circuit Immedi- Latch All Bad Sensor or LLID Remote
Pressure Transducer - ate
Ckt1
5B9 Condenser Rfgt Circuit Immedi- Latch All Bad Sensor or LLID Remote
Pressure Transducer - ate
Ckt2
BAS-SVP031B-EN F–19
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5BA Suction Refrigerant Special Immedi- Latch All Bad Sensor or LLID Circuit target if Remote
Pressure Sensor - 1A ate no isolation valves, Compressor
target if isolation valves. Design
Note: In the case of manifolded
compressors w/o isolation valves, the
occurrence of this diagnostic will also
generate a comm loss with the
nonexistent Suction Press Cprsr 1B in
order to accomplish circuit shutdown.
5BB Suction Refrigerant Cprsr 1B Immedi- Latch All Bad Sensor or LLID. Design Note: For Remote
Pressure Sensor - 1B ate circuits with manifolded compressors
w/o isolation valve option, this
diagnostic will occur with the
preceding diagnostic, even though
this transducer is not required or
installed.
5BC Suction Refrigerant Special Immedi- Latch All Bad Sensor or LLID Circuit target if Remote
Pressure Sensor - 2A ate no isolation valves, Compressor
target if isolation valves. Design
Note: In the case of manifolded
compressors w/o isolation valves, the
occurrence of this diagnostic will also
generate a comm loss with the
nonexistent Suction Press Cprsr 2B in
order to accomplish circuit shutdown.
5BD Suction Refrigerant Cprsr 2B Immedi- Latch All Bad Sensor or LLID. Design Note: For Remote
Pressure Sensor - 2B ate circuits with manifolded compressors
w/o isolation valve option, this
diagnostic will occur with the
preceding diagnostic, even though
this transducer is not required or
installed
5BE Intermediate Oil Cprsr 1A Immedi- Latch All Bad Sensor or LLID Remote
Press Xdcr - Cprsr 1A ate
5BF Intermediate Oil Cprsr 1B Immedi- Latch All Bad Sensor or LLID Remote
Press Xdcr - Cprsr 1B ate
5C0 Intermediate Oil Cprsr 2A Immedi- Latch All Bad Sensor or LLID Remote
Press Xdcr - Cprsr 2A ate
5C1 Intermediate Oil Cprsr 2B Immedi- Latch All Bad Sensor or LLID Remote
Press Xdcr - Cprsr 2B ate
1E1 Oil Flow Protection Circuit Immedi- Latch Starter The Intermediate Oil Pressure Local
Fault - 1A ate Contactor Transducer for this cprsr is reading a
Energized pressure either above its respective
[all Stop circuit’s Condenser Pressure by 15
modes] Psia or more, or below its respective
Suction Pressure 10 Psia or more for
30 seconds continuously.
1E2 Oil Flow Protection Circuit Immedi- Latch Starter The Intermediate Oil Pressure Local
Fault - 1B ate Contactor Transducer for this cprsr is reading a
Energized pressure either above its respective
[all Stop circuit’s Condenser Pressure by 15
modes] Psia or more, or below its respective
Suction Pressure 10 Psia or more for
30 seconds continuously.
F–20 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5A0 Oil Flow Protection Circuit Immedi- Latch Starter The Intermediate Oil Pressure Local
Fault - 2A ate Contactor Transducer for this cprsr is reading a
Energized pressure either above its respective
[all Stop circuit’s Condenser Pressure by 15
modes] Psia or more, or below its respective
Suction Pressure 10 Psia or more for
30 seconds continuously.
5A1 Oil Flow Protection Circuit Immedi- Latch Starter The Intermediate Oil Pressure Local
Fault - 2B ate Contactor Transducer for this cprsr is reading a
Energized pressure either above its respective
[all Stop circuit’s Condenser Pressure by 15
modes] Psia or more, or below its respective
Suction Pressure 10 Psia or more for
30 seconds continuously.
B5 Low Suction Rfgt Circuit Immedi- Latch Cprsr a. The Suction Refrigerant Pressure Local
Pressure – Ckt 1 ate Prestart and (or either of the compressor suction
Cprsr pressures) dropped below 10 Psia
Energized just prior to compressor start (after
EXV preposition). b. The pressure fell
below 16 Psia while running after the
ignore time had expired, or fell below
10 Psia (or 5 Psia in sftw prior to
Oct’02) before the ignore time had
expired. The ignore time is function
of outdoor air temperature. Note:
Part b. is identical to Low Evaporator
Refrigerant Temperature diagnostic
except for the trip integral and trip
point settings.
B7 Low Suction Rfgt Circuit Immedi- Latch Cprsr a. The Suction Refrigerant Pressure Local
Pressure – Ckt 2 ate Prestart and (or either of the compressor suction
Cprsr pressures) dropped below 10 Psia
Energized just prior to compressor start (after
EXV preposition). b. The pressure fell
below 16 Psia while running after the
ignore time had expired, or fell below
10 Psia (or 5 Psia in sftw prior to
Oct’02) before the ignore time had
expired. The ignore time is function
of outdoor air temperature. Note:
Part b. is identical to Low Evaporator
Refrigerant Temperature diagnostic
except for the trip integral and trip
point settings.
771 Very Low Evaporator Chiller Immedi- Latch All The evaporator pressure dropped Local
Rfgt Pressure - Ckt1 ate [compres- below 8 psia regardless of whether or
sor or circuit not compressors are running on that
in manual circuit. This diagnostic was created to
lockout] prevent compressor failures due to
crossbinding by forcing an entire
chiller shutdown. If a given
compressor or circuit is locked out,
the suction pressure transducer(s)
associated with it, will be excluded
from causing this diagnostic.
BAS-SVP031B-EN F–21
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
772 Very Low Evaporator Chiller Immedi- Latch All The evaporator pressure dropped Local
Rfgt Pressure - Ckt2 ate [compres- below 8 psia regardless of whether or
sor or circuit not compressors are running on that
in manual circuit. This diagnostic was created to
lockout] prevent compressor failures due to
crossbinding by forcing an entire
chiller shutdown. If a given
compressor or circuit is locked out,
the suction pressure transducer(s)
associated with it, will be excluded
from causing this diagnostic.
8C Pumpdown Circuit Warning NonLatch Pumpdown The pumpdown cycle for this circuit Remote
Terminated - Ckt1 Mode was terminated abnormally due to
excessive time or due to a specific set
of diagnostic criteria – but w/o
associated latching diagnostics
8D Pumpdown Circuit Warning NonLatch Pumpdown The pumpdown cycle for this circuit Remote
Terminated - Ckt2 Mode was terminated abnormally due to
excessive time or due to a specific set
of diagnostic criteria – but w/o
associated latching diagnostics
C5 Low Evaporator Evap Special NonLatch Unit in Stop The leaving Evaporator water temp. Remote
Water Temp (Unit Pump Mode Mode, or in fell below the leaving water temp
Off) Auto Mode cutout setting for 30 degree F
and No Ckt seconds while the Chiller is in the
(s) Energzd Stop mode, or in Auto mode with no
[Any Ckt compressors running. Energize Evap
Energzd] Water pump Relay until diagnostic
auto resets, then return to normal
evap pump control. Automatic reset
occurs when the temp rises 2°F (1.1°
C) above the cutout setting for 30
minutes.
6B3 Low Evaporator Temp Evap Special NonLatch Unit in Stop Any of the evap sat temps fell below Remote
(Unit Off) - Ckt1 Pump Mode Mode, or in the water temp cutout setting while
Auto Mode the respective evap liquid level was
and No Ckt's greater than –21.2mm for 150
Energzd degree F seconds while Chiller is in
[Any Ckt the Stop mode, or in Auto mode with
Energzd] no compressors running. Energize
Evap Water pump Relay until
diagnostic auto resets, then return to
normal evap pump control.
Automatic reset occurs when either
the evap temp rises 2°F (1.1°C)
above the cutout setting or the liquid
level falls below –21.2mm for 30
minutes
6B3 Low Evaporator Temp Evap Special NonLatch Unit in Stop Any of the evap sat temps fell below Remote
(Unit Off) - Ckt2 Pump Mode Mode, or in the water temp cutout setting while
Auto Mode the respective evap liquid level was
and No Ckt's greater than –21.2mm for 150
Energzd degree F seconds while Chiller is in
[Any Ckt the Stop mode, or in Auto mode with
Energzd] no compressors running. Energize
Evap Water pump Relay until
diagnostic auto resets, then return to
normal evap pump control.
Automatic reset occurs when either
the evap temp rises 2°F (1.1°C)
above the cutout setting or the liquid
level falls below –21.2mm for 30
minutes
F–22 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
C6 Low Evap Leaving Chiller Immedi- NonLatch Any Ckt[s] The evaporator water temp. fell Remote
Water Temp: Unit On ate and Energzd [No below the cutout setpoint for 30
Special Ckt(s) degree F Seconds while the
Mode Energzd] compressor was running. Automatic
reset occurs when the temperature
rises 2 °F (1.1°C) above the cutout
setting for 2 minutes. This diagnostic
shall not de-energize the Evaporator
Water Pump Output.
384 Evaporator Water Chiller Normal NonLatch Estab. Evap. Evaporator water flow was not Remote
Flow Overdue Water Flow proven within 20 minutes of the
on going Evaporator water pump relay being
from STOP energized (4 minutes, 15 seconds
to AUTO. when the pump is energized due to
the ‘Low Evaporator Temp (Unit Off)
– Cktx’ diagnostic).
ED Evaporator Water Chiller Immedi- NonLatch [All Stop a. The Evaporator water flow switch Remote
Flow Lost ate modes] input was open for more than 6-10
contiguous seconds. b. This
diagnostic does not de-energize the
evap pump output c. 6-10 seconds of
contiguous flow shall clear this
diagnostic. d. Even though the pump
times out in the STOP modes, this
diagnostic shall not be called out in
the STOP modes.
6B8 High Evaporator Chiller Immedi- NonLatch All The evaporator refrigerant pressure Remote
Refrigerant Pressure ate of either circuit has risen above 190
psig. The evaporator water pump
relay will be de-energized to stop the
pump regardless of why the pump is
running. The diagnostic will auto
reset and the pump will return to
normal control when all of the
evaporator pressures fall below 185
psig. The primary purpose is to stop
the evaporator water pump and its
associated pump heat from causing
refrigerant side pressures, close to
the evaporator relief valve setting,
when the chiller is not running, such
as could occur with Evap Water Flow
Overdue or Evaporator Water Flow
Loss Diagnostics.
BAS-SVP031B-EN F–23
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
6B6 High Evaporator Chiller Warning Latch Only The leaving water temperature Remote
Water Temperature and effective if exceeded the high evap water temp
Special either 1) limit (TV service menu settable –
Action Evap Wtr default 105F) for 15 continuous
Flow seconds. The evaporator water pump
Overdue,2) relay will be de-energized to stop the
Evap Wtr pump but only if it is running due one
Flow Loss, of the diagnostics listed on the left .
or 3)Low The diagnostic will auto reset and the
Evap Rfgt pump will return to normal control
Temp,-Unit when the temperature falls 5°F below
Off, the trip setting. The primary purpose
diagnostic is is to stop the evaporator water pump
active. and its associated pump heat from
causing excessive waterside
temperatures and waterside
pressures when the chiller is not
running but the evap pump is on due
to either Evap Water Flow Overdue,
Evaporator Water Flow Loss , or Low
Evap Temp – Unit Off Diagnostics.
This diagnostic will not auto clear
solely due to the clearing of the
enabling diagnostic.
F5 High Pressure Cutout Circuit Immedi- Latch All A high pressure cutout was detected Local
- 1A ate on Compressor 1A; trip at 315 ± 5
PSIG. Note: Other diagnostics that
may occur as an expected
consequence of the HPC trip will be
suppressed from annunciation. These
include Phase Loss, Power Loss, and
Transition Complete Input Open.
F6 High Pressure Cutout Circuit Immedi- Latch All A high pressure cutout was detected Local
- 1B ate on Compressor 1A; trip at 315 ± 5
PSIG. Note: Other diagnostics that
may occur as an expected
consequence of the HPC trip will be
suppressed from annunciation. These
include Phase Loss, Power Loss, and
Transition Complete Input Open.
BE High Pressure Cutout Circuit Immedi- Latch All A high pressure cutout was detected Local
- 2A ate on Compressor 1A; trip at 315 ± 5
PSIG. Note: Other diagnostics that
may occur as an expected
consequence of the HPC trip will be
suppressed from annunciation. These
include Phase Loss, Power Loss, and
Transition Complete Input Open.
BF High Pressure Cutout Circuit Immedi- Latch All A high pressure cutout was detected Local
- 2B ate on Compressor 1A; trip at 315 ± 5
PSIG. Note: Other diagnostics that
may occur as an expected
consequence of the HPC trip will be
suppressed from annunciation. These
include Phase Loss, Power Loss, and
Transition Complete Input Open.
FD Emergency Stop Chiller Immedi- Latch All a. EMERGENCY STOP input is open. Local
ate An external interlock has tripped.
Time to trip from input opening to
unit stop shall be 0.1 to 1.0 seconds.
F–24 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
A1 Outdoor Air Chiller Normal Latch All Bad Sensor or LLID. Note that if this Remote
Temperature Sensor diagnostic occurs, operational
pumpdown will be performed
regardless of the last valid
temperature
6B0 Starter Panel Cprsr 2A Special NonLatch All Starter Panel High Limit Thermostat Local
Thermostat Cutout - Mode (170°F) trip was detected. Note:
2A Other diagnostics that may occur as
an expected consequence of the
Panel High Temp Limit trip will be
suppressed from annunciation. These
include Phase Loss, Power Loss, and
Transition Complete Input Open for
Cprsr 2A
6B1 Starter Panel Cprsr 1B Special NonLatch All Starter Panel High Limit Thermostat Local
Thermostat Cutout - Mode (170°F) trip was detected. Note:
1B Other diagnostics that may occur as
an expected consequence of the
Panel High Temp Limit trip will be
suppressed from annunciation. These
include Phase Loss, Power Loss, and
Transition Complete Input Open for
Cprsr 1B
6B2 Starter Panel Cprsr 2B Special NonLatch All Starter Panel High Limit Thermostat Local
Thermostat cutout - Mode (170°F) trip was detected. Note:
2B Other diagnostics that may occur as
an expected consequence of the
Panel High Temp Limit trip will be
suppressed from annunciation. These
include Phase Loss, Power Loss, and
Transition Complete Input Open for
Cprsr 2B
5C5 Starter Module Cprsr Warning Latch All Checksum on RAM copy of the Local
Memory Error Type 1 Starter LLID configuration failed.
- 1A Configuration recalled from EEPROM.
5C6 Starter Module Cprsr Warning Latch All Checksum on RAM copy of the Local
Memory Error Type 1 Starter LLID configuration failed.
- 1B Configuration recalled from EEPROM.
5C7 Starter Module Cprsr Warning Latch All Checksum on RAM copy of the Local
Memory Error Type 1 Starter LLID configuration failed.
- 2A Configuration recalled from EEPROM.
5C8 Starter Module Cprsr Warning Latch All Checksum on RAM copy of the Local
Memory Error Type 1 Starter LLID configuration failed.
- 2B Configuration recalled from EEPROM.
5C9 Starter Module Cprsr Immedi- Latch All Checksum on EEPROM copy of the Local
Memory Error Type 2 ate Starter LLID configuration failed.
- 1A Factor default values used.
5CA Starter Module Cprsr Immedi- Latch All Checksum on EEPROM copy of the Local
Memory Error Type 2 ate Starter LLID configuration failed.
- 1B Factor default values used.
5CB Starter Module Cprsr Immedi- Latch All Checksum on EEPROM copy of the Local
Memory Error Type 2 ate Starter LLID configuration failed.
- 2A Factor default values used.
5CC Starter Module Cprsr Immedi- Latch All Checksum on EEPROM copy of the Local
Memory Error Type 2 ate Starter LLID configuration failed.
- 2B Factor default values used.
5FF MP: Invalid N/A N/A Latch All MP has an invalid configuration based Remote
Configuration on the current software installed
BAS-SVP031B-EN F–25
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
69C MP: Non-Volatile Chiller Warning Latch All MP has determined there was an Remote
Memory Reformatted error in a sector of the Non-Volatile
memory and it was reformatted.
Check settings.
2E6 Check Clock Chiller Warning Latch All The real time clock had detected loss Remote
of its oscillator at some time in the
past. This diagnostic can be
effectively cleared only by writing a
new value to the chiller time clock.
6A1 MP: Could not Store Chiller Warning Latch All MP has determined there was an Remote
Starts and Hours error with the previous power down
store. Starts and Hours may have
been lost for the last 24 hours.
6A2 MP: Non-Volatile Chiller Warning Latch All MP has determined there was an Remote
Block Test Error error with a block in the Non-Volatile
memory. Check settings.
6A3 Starter Failed to Arm/ Cprsr Warning Latch All Starter failed to arm or start within Local
Start - 1A the allotted time (15 seconds).
6A4 Starter Failed to Arm/ Cprsr Warning Latch All Starter failed to arm or start within Local
Start - 1B the allotted time (15 seconds).
6A5 Starter Failed to Arm/ Cprsr Warning Latch All Starter failed to arm or start within Local
Start - 2A the allotted time (15 seconds).
6A6 Starter Failed to Arm/ Cprsr Warning Latch All Starter failed to arm or start within Local
Start - 2B the allotted time (15 seconds).
Software Error 1001: All Immedi- Latch – All A high level software watchdog has
Call Trane Service functions ate power detected a condition in which there
down was a continuous 3 minute period of
reset is compressor operation, with neither
reqd chilled water flow nor a” contactor
interrupt failure” diagnostic active.
The occurrence of this software error
message suggests an internal
software state chart misalignment
has occurred. The events that led up
to this failure, if known, should be
recorded and transmitted to Trane
Controls Engineering
F–26 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
Low Discharge Cprsr Normal Latch Any While Running Normally, the Remote
Superheat –1A Running Discharge Superheat was less than
Mode the Low Discharge Superheat
Setpoint for more than 7800 degree F
seconds. At circuit startup, the
Discharge Superheat will be ignored
for 5 minutes.
Low Discharge Cprsr Normal Latch Any While Running Normally, the Remote
Superheat –1B Running Discharge Superheat was less than
Mode the Low Discharge Superheat
Setpoint for more than 7800 degree F
seconds. At circuit startup, the
Discharge Superheat will be ignored
for 5 minutes.
Low Discharge Cprsr Normal Latch Any While Running Normally, the Remote
Superheat –2A Running Discharge Superheat was less than
Mode the Low Discharge Superheat
Setpoint for more than 7800 degree F
seconds. At circuit startup, the
Discharge Superheat will be ignored
for 5 minutes.
Low Discharge Cprsr Normal Latch Any While Running Normally, the Remote
Superheat –2B Running Discharge Superheat was less than
Mode the Low Discharge Superheat
Setpoint for more than 7800 degree F
seconds. At circuit startup, the
Discharge Superheat will be ignored
for 5 minutes.
BAS-SVP031B-EN F–27
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
Communication Diagnostics
Notes:
• The following communication loss diagnostics will not occur unless the related input
or output is required to be present by the particular configuration and installed
options for the chiller.
• Communication diagnostics (with the exception of “Excessive Loss of Comm”) are
named by the Functional Name of the input or output that is no longer being heard
from by the Main Processor. Many LLIDs, such as the Quad Relay LLID, have more
than one functional output associated with them. A comm loss with such a multiple
function board, will generate multiple diagnostics. Refer to the chiller's wiring
diagrams to relate the occurrence of multiple communication diagnostics back to the
physical LLID boards to which they have been assigned (bound).
Table 47. Communication Diagnostics
5C4 Excessive IPC Comm Chiller Immediate Latch All Loss of comm with 75% or more Remote
Loss (Rev 18 and earlier 10%) of the llids
configured for the system has been
detected. This diagnostic will
suppress the callout of all
subsequent comm loss diagnostics.
Check power supply(s) and power
disconnects – troubleshoot LLIDS
buss using the Service Tool
5D1 Comm Loss: Slide Cprsr Normal Latch All Continual loss of communication Remote
Valve Unload - 1A between the MP and the Functional
ID has occurred for a 30 second
period.
5D2 Comm Loss: Slide Cprsr Normal Latch All Continual loss of communication Remote
Valve Load - 1A between the MP and the Functional
ID has occurred for a 30 second
period.
5D3 Comm Loss: Slide Cprsr Normal Latch All Continual loss of communication Remote
Valve Unload - 1B between the MP and the Functional
ID has occurred for a 30 second
period.
5D4 Comm Loss: Slide Cprsr Normal Latch All Continual loss of communication Remote
Valve Load - 1B between the MP and the Functional
ID has occurred for a 30 second
period.
5D5 Comm Loss: Slide Cprsr Normal Latch All Continual loss of communication Remote
Valve Unload - 2A between the MP and the Functional
ID has occurred for a 30 second
period.
5D6 Comm Loss: Slide Cprsr Normal Latch All Continual loss of communication Remote
Valve Load - 2A between the MP and the Functional
ID has occurred for a 30 second
period.
5D7 Comm Loss: Slide Cprsr Normal Latch All Continual loss of communication Remote
Valve Unload - 2B between the MP and the Functional
ID has occurred for a 30 second
period.
5D8 Comm Loss: Slide Cprsr Normal Latch All Continual loss of communication Remote
Valve Load - 2B between the MP and the Functional
ID has occurred for a 30 second
period.
F–28 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5D9 Comm Loss: Step Load Cprsr Normal Latch All Continual loss of communication Remote
- 1A between the MP and the Functional
ID has occurred for a 30 second
period.
5DA Comm Loss: Step Load Cprsr Normal Latch All Continual loss of communication Remote
- 1B between the MP and the Functional
ID has occurred for a 30 second
period.
5DB Comm Loss: Step Load Cprsr Normal Latch All Continual loss of communication Remote
- 2A between the MP and the Functional
ID has occurred for a 30 second
period.
5DC Comm Loss: Step Load Cprsr Normal Latch All Continual loss of communication Remote
- 2B between the MP and the Functional
ID has occurred for a 30 second
period.
5DD Comm Loss: External Chiller Normal Latch All Continual loss of communication Remote
Auto/Stop between the MP and the Functional
ID has occurred for a 30 second
period.
5DE Comm Loss: Chiller Normal Latch All Continual loss of communication Remote
Emergency Stop between the MP and the Functional
ID has occurred for a 30 second
period.
5DF Comm Loss: External Circuit Special Latch All Continual loss of communication Remote
Ckt Lockout - Ckt1 Mode between the MP and the Functional
ID has occurred for a 30 second
period. MP will nonvolatily hold the
lockout state (enabled or disabled)
that was in effect at the time of
comm loss.
5E0 Comm Loss: External Circuit Special Latch All Continual loss of communication Remote
Ckt Lockout - Ckt2 Mode between the MP and the Functional
ID has occurred for a 30 second
period. MP will nonvolatily hold the
lockout state (enabled or disabled)
that was in effect at the time of
comm loss
5E1 Comm Loss: External Ice Making Special Latch All Continual loss of communication Remote
Ice Building Command Mode Mode between the MP and the Functional
ID has occurred for a 30 second
period. Chiller shall revert to normal
(non-ice building) mode regardless
of last state.
5E2 Comm Loss: Outdoor Chiller Normal Latch All Continual loss of communication Remote
Air Temperature between the MP and the Functional
ID has occurred for a 30 second
period. Note that if this diagnostic
occurs, operational pumpdown will
be performed regardless of the last
valid temperature
5E3 Comm Loss: Evap Chiller Normal Latch All Continual loss of communication Remote
Leaving Water Temp between the MP and the Functional
ID has occurred for a 30 second
period.
BAS-SVP031B-EN F–29
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5E4 Comm Loss: Evap Chilled Special Latch All Continual loss of communication Remote
Entering Water Temp Water Mode between the MP and the Functional
Reset ID has occurred for a 30 second
period. Chiller shall remove any
Return or Constant Return Chilled
Water Reset, if it was in effect.
Apply slew rates per Chilled Water
Reset spec.
5E5 Comm Loss: Oil Cprsr Normal Latch All Continual loss of communication Remote
Temperature – 1A’ between the MP and the Functional
ID has occurred for a 30 second
period.
5E6 Comm Loss: Oil Cprsr Normal Latch All Continual loss of communication Remote
Temperature – 1B’ between the MP and the Functional
ID has occurred for a 30 second
period.
Comm Loss: Oil Cprsr Normal Latch All Continual loss of communication Remote
Temperature – 2A’ between the MP and the Functional
ID has occurred for a 30 second
period.
Comm Loss: Oil Cprsr Normal Latch All Continual loss of communication Remote
Temperature – 2B’ between the MP and the Functional
ID has occurred for a 30 second
period.
5E9 Comm Loss: Ext External Special NonLatch All Continual loss of communication Remote
Chilled Water Setpoint Chilled Mode between the MP and the Functional
Waterset- ID has occurred for a 30 second
point period. Chiller shall discontinue use
of the External Chilled Water
Setpoint source and revert to the
next higher priority for setpoint
arbitration
5EA Comm Loss: Ext External Special NonLatch All Continual loss of communication Remote
Current Limit Setpoint Current Mode between the MP and the Functional
Limit ID has occurred for a 30 second
setpoint period. Chiller shall discontinue use
of the External Current limit
setpoint and revert to the next
higher priority for Current Limit
setpoint arbitration
5EB Comm Loss: High Cprsr Immediate Latch All Continual loss of communication Remote
Pressure Cutout Sw - between the MP and the Functional
1A ID has occurred for a 30 second
period.
5EC Comm Loss: High Cprsr Immediate Latch All Continual loss of communication Remote
Pressure Cutout Sw - between the MP and the Functional
1B ID has occurred for a 30 second
period.
5ED Comm Loss: High Cprsr Immediate Latch All Continual loss of communication Remote
Pressure Cutout Sw - between the MP and the Functional
2A ID has occurred for a 30 second
period.
5EE Comm Loss: High Cprsr Immediate Latch All Continual loss of communication Remote
Pressure Cutout Sw - between the MP and the Functional
2B ID has occurred for a 30 second
period.
F–30 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5EF Comm Loss: Chiller Immediate Latch All Continual loss of communication Remote
Evaporator Water Flow between the MP and the Functional
Switch ID has occurred for a 30 second
period.
5F2 Comm Loss: Circuit Immediate Latch All Continual loss of communication Remote
Condenser Rfgt between the MP and the Functional
Pressure - Ckt1 ID has occurred for a 30 second
period.
5F3 Comm Loss: Circuit Immediate Latch All Continual loss of communication Remote
Condenser Rfgt between the MP and the Functional
Pressure - Ckt2 ID has occurred for a 30 second
period.
5F4 Comm Loss: Cprsr Immediate Latch All Continual loss of communication Remote
Intermediate Oil between the MP and the Functional
Pressure - 1A ID has occurred for a 30 second
period.
5F5 Comm Loss: Cprsr Immediate Latch All Continual loss of communication Remote
Intermediate Oil between the MP and the Functional
Pressure - 1B ID has occurred for a 30 second
period.
5F6 Comm Loss: Cprsr Immediate Latch All Continual loss of communication Remote
Intermediate Oil between the MP and the Functional
Pressure - 2A ID has occurred for a 30 second
period.
5F7 Comm Loss: Cprsr Immediate Latch All Continual loss of communication Remote
Intermediate Oil between the MP and the Functional
Pressure - 2B ID has occurred for a 30 second
period.
5F8 Comm Loss: Chiller Normal Latch All Continual loss of communication Remote
Evaporator Water between the MP and the Functional
Pump Relay ID has occurred for a 30 second
period.
5FA Comm Loss: Ice Ice- Special Latch All Continual loss of communication Remote
Building Status Relay Machine Mode between the MP and the Functional
ID has occurred for a 30 second
period. Chiller shall revert to normal
(non-ice building) mode regardless
of last state.
5FB Comm Loss: Suction Special Immediate Latch All Continual loss of communication
Rfgt Pressure - 1A between the MP and the Functional
ID has occurred for a 30 second
period.Circuit target if no isolation
valves, Compressor target if
isolation valves or simplex. Design
Note: In the case of manifolded
compressors w/o isolation valves,
the occurrence of this diagnostic
will also generate a comm loss with
the nonexistent Suction Press Cprsr
1B in order to accomplish circuit
shutdown.
BAS-SVP031B-EN F–31
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
5FC Comm Loss: Suction Cprsr Immediate Latch All Continual loss of communication
Rfgt Pressure - 1B between the MP and the Functional
ID has occurred for a 30 second
period. Design Note: For circuits
with manifolded compressors w/o
isolation valve option, this
diagnostic will occur with the
preceding diagnostic, even though
this transducer is not required or
installed.
5FD Comm Loss: Suction Special Immediate Latch All Continual loss of communication
Rfgt Pressure - 2A between the MP and the Functional
ID has occurred for a 30 second
period. Circuit target if no isolation
valves, Compressor target if
isolation valves or simplex. Design
Note: In the case of manifolded
compressors w/o isolation valves,
the occurrence of this diagnostic
will also generate a comm loss with
the nonexistent Suction Press Cprsr
2B in order to accomplish circuit
shutdown.
5FE Comm Loss: Suction Cprsr Immediate Latch All Continual loss of communication
Rfgt Pressure - 2B between the MP and the Functional
ID has occurred for a 30 second
period. Design Note: For circuits
with manifolded compressors w/o
isolation valve option, this
diagnostic will occur with the
preceding diagnostic, even though
this transducer is not required or
installed.
680 Comm Loss: Fan Circuit Normal Latch All Continual loss of communication
Control Ckt1, Stage 1 between the MP and the Functional
ID has occurred for a 30 second
period.
681 Comm Loss: Fan Circuit Normal Latch All Continual loss of communication
Control Ckt1, Stage 2 between the MP and the Functional
ID has occurred for a 30 second
period.
682 Comm Loss: Fan Circuit Normal Latch All Continual loss of communication
Control Ckt1, Stage 3 between the MP and the Functional
ID has occurred for a 30 second
period.
683 Comm Loss: Fan Circuit Normal Latch All Continual loss of communication
Control Ckt1, Stage 4 between the MP and the Functional
ID has occurred for a 30 second
period.
684 Comm Loss: Fan Circuit Normal Latch All Continual loss of communication
Control Ckt2, Stage 1 between the MP and the Functional
ID has occurred for a 30 second
period.
685 Comm Loss: Fan Circuit Normal Latch All Continual loss of communication
Control Ckt2, Stage 2 between the MP and the Functional
ID has occurred for a 30 second
period.
686 Comm Loss: Fan Circuit Normal Latch All Continual loss of communication
Control Ckt2, Stage 3 between the MP and the Functional
ID has occurred for a 30 second
period.
F–32 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
687 Comm Loss: Fan Circuit Normal Latch All Continual loss of communication
Control Ckt2, Stage 4 between the MP and the Functional
ID has occurred for a 30 second
period.
688 Comm Loss: Evap Rfgt Circuit Immediate Latch All Continual loss of communication
Liquid Level - Ckt1 between the MP and the Functional
ID has occurred for a 30 second
period.
689 Comm Loss: Evap Rfgt Circuit Immediate Latch All Continual loss of communication
Liquid Level - Ckt2 between the MP and the Functional
ID has occurred for a 30 second
period.
68A Comm Loss: Fan Circuit Warning Latch All Continual loss of communication
Inverter Power- Ckt1 between the MP and the Functional
ID has occurred for a 30 second
period.
68B Comm Loss: Fan Inverter Special Latch All Continual loss of communication
Inverter Speed Cmd - Mode between the MP and the Functional
Ckt1 ID has occurred for a 30 second
period. Operate the remaining fans
as fixed speed fan deck.
68C Comm Loss: Fan Inv Inverter Special Latch All Continual loss of communication
Fault, Ckt1, Dr 1 Mode between the MP and the Functional
ID has occurred for a 30 second
period. Operate the remaining fans
as fixed speed fan deck.
68D Comm Loss: Fan Inv Inverter Special Latch All Continual loss of communication
Fault, Ckt1, Dr 2 Mode between the MP and the Functional
ID has occurred for a 30 second
period. Operate the remaining fans
as fixed speed fan deck.
68E Comm Loss: Oil Return Cprsr Normal Latch All Continual loss of communication Remote
Solenoid Valve - 1A between the MP and the Functional
ID has occurred for a 30 second
period.
68F Comm Loss: Oil Return Cprsr Normal Latch All Continual loss of communication Remote
Solenoid Valve - 2A between the MP and the Functional
ID has occurred for a 30 second
period.
69E Comm Loss: Oil Return Cprsr Normal Latch All Continual loss of communication Remote
Solenoid Valve - 1B between the MP and the Functional
ID has occurred for a 30 second
period.
69F Comm Loss: Oil Return Cprsr Normal Latch All Continual loss of communication Remote
Solenoid Valve - 2B between the MP and the Functional
ID has occurred for a 30 second
period.
690 Comm Loss: Starter 1A Cprsr Immediate Latch All Continual loss of communication Local
between the MP and the Functional
ID has occurred for a 30 second
period.
691 Comm Loss: Starter 1B Cprsr Immediate Latch All Continual loss of communication Local
between the MP and the Functional
ID has occurred for a 30 second
period.
BAS-SVP031B-EN F–33
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
692 Comm Loss: Starter 2A Cprsr Immediate Latch All Continual loss of communication Local
between the MP and the Functional
ID has occurred for a 30 second
period.
693 Comm Loss: Starter 2B Cprsr Immediate Latch All Continual loss of communication Local
between the MP and the Functional
ID has occurred for a 30 second
period.
694 Comm Loss: Electronic Circuit Normal Latch All Continual loss of communication Remote
Expansion Valve 1 between the MP and the Functional
ID has occurred for a 30 second
period.
695 Comm Loss: Electronic Circuit Normal Latch All Continual loss of communication Remote
Expansion Valve 2 between the MP and the Functional
ID has occurred for a 30 second
period.
696 Comm Loss: Oil Cprsr Normal Latch All Continual loss of communication Remote
Temperature – 1B between the MP and the Functional
ID has occurred for a 30 second
period.
697 Comm Loss: Oil Cprsr Normal Latch All Continual loss of communication Remote
Temperature –2B between the MP and the Functional
ID has occurred for a 30 second
period.
698 Comm Loss: Fan Circuit Warning Latch All Continual loss of communication Remote
Inverter Power - Ckt2 between the MP and the Functional
ID has occurred for a 30 second
period.
699 Comm Loss: Fan Inverter Special Latch All Continual loss of communication Remote
Inverter Speed Cmd - Mode between the MP and the Functional
Ckt2 ID has occurred for a 30 second
period. Operate the remaining fans
as fixed speed fan deck.
69A Comm Loss: Fan Inv Inverter Special Latch All Continual loss of communication Remote
Fault, Ckt 2, Dr 1 Mode between the MP and the Functional
ID has occurred for a 30 second
period. Operate the remaining fans
as fixed speed fan deck.
69B Comm Loss: Fan Inv Inverter Special Latch All Continual loss of communication Remote
Fault, Ckt 2, Dr 2 Mode between the MP and the Functional
ID has occurred for a 30 second
period. Operate the remaining fans
as fixed speed fan deck.
5CD Starter 1A Loss of Cprsr Immediate Latch All Starter has had a loss of Local
Comm with MP communication with the MP for a 15
second period.
5CE Starter 1B Loss of Cprsr Immediate Latch All Starter has had a loss of Local
Comm with MP communication with the MP for a 15
second period.
5CF Starter 2A Loss of Cprsr Immediate Latch All Starter has had a loss of Local
Comm with MP communication with the MP for a 15
second period.
5D0 Starter 2B Loss of Cprsr Immediate Latch All Starter has had a loss of Local
Comm with MP communication with the MP for a 15
second period.
F–34 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
69D Comm Loss: Local BAS Chiller Special Latch All Continual loss of communication Remote
Interface Mode between the MP and the Functional
ID has occurred for a 30 second
period.
6A0 Comm Loss: Chiller Warning Latch All Continual loss of communication Remote
Programmable Relay between the MP and the Functional
Board 1 ID has occurred for a 30 second
period.
6AB Starter Panel Cprsr Warning Latch All Continual loss of communication Local
Thermostat Comm between the MP and the Functional
Loss 2A ID has occurred for a 30 second
period.
6AC Starter Panel Cprsr Warning Latch All Continual loss of communication Local
Thermostat Comm between the MP and the Functional
Loss 1B ID has occurred for a 30 second
period.
6AD Starter Panel Cprsr Warning Latch All Continual loss of communication Local
Thermostat Comm between the MP and the Functional
Loss 2B ID has occurred for a 30 second
period.
6BB Comm Loss: Evap Rfgt Circuit Normal Latch All Continual loss of communication Remote
Drain Valve - Ckt1 between the MP and the Functional
ID has occurred for a 30 second
period.
6BC Comm Loss: Evap Rfgt Circuit Normal Latch All Continual loss of communication Remote
Drain Valve - Ckt2 between the MP and the Functional
ID has occurred for a 30 second
period.
Comm Loss: Adaptive Chiller Immediate NonLatching All Continual loss of communication Remote
Frequency Drive 1A between the MP and the Functional
ID has occurred for a 35-40 second
period. Flow calculation shall be
disabled.
Comm Loss: Adaptive Chiller Immediate NonLatching All Continual loss of communication Remote
Frequency Drive 1B between the MP and the Functional
ID has occurred for a 35-40 second
period. Flow calculation shall be
disabled.
Comm Loss: Adaptive Chiller Immediate NonLatching All Continual loss of communication Remote
Frequency Drive 2A between the MP and the Functional
ID has occurred for a 35-40 second
period. Flow calculation shall be
disabled.
Comm Loss: Adaptive Chiller Immediate NonLatching All Continual loss of communication Remote
Frequency Drive 2B between the MP and the Functional
ID has occurred for a 35-40 second
period. Flow calculation shall be
disabled.
Comm Loss: Cprsr Normal Latch All Continual loss of communication Remote
Compressor Discharge between the MP and the Functional
Temp – 1A ID has occurred for a 35-40 second
period. Flow calculation shall be
disabled.
Comm Loss: Cprsr Normal Latch All Continual loss of communication Remote
Compressor Discharge between the MP and the Functional
Temp – 1B ID has occurred for a 35-40 second
period. Flow calculation shall be
disabled.
BAS-SVP031B-EN F–35
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
RTAC Diagnostics
Comm Loss: Cprsr Normal Latch All Continual loss of communication Remote
Compressor Discharge between the MP and the Functional
Temp – 2A ID has occurred for a 35-40 second
period. Flow calculation shall be
disabled.
Comm Loss: Cprsr Normal Latch All Continual loss of communication Remote
Compressor Discharge between the MP and the Functional
Temp – 2B ID has occurred for a 35-40 second
period. Flow calculation shall be
disabled.
F–36 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Notes
BAS-SVP031B-EN 93
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Notes
94 BAS-SVP031B-EN
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Notes
BAS-SVP031B-EN 95
Confidential and proprietary Trane information
Distribute only to authorized agents conducting Trane business
Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient
indoor environments for commercial and residential applications. For more information, please visit
trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without
notice. We are committed to using environmentally conscious print practices.