When selecting a cable, the performance of the cable under fault conditions is an important
consideration. It is important that calculations be carried out to ensure that any cable is able to
withstand the effects of any potential fault or short circuit. This note looks at how to do this.
The primary concern with cables under a fault condition is the heat generated, and any potential
negative effect this may have on the cable insulation.
Calculation of fault rating is based on the principle that the protective device will isolate the fault
in a time limit such that the permitted temperature rise within the cable will not be exceeded.
Contents [hide]
The normally used equation is the so-called adiabatic equation. For a given fault of I, which
lasts for time t, the minimum required cable cross sectional area is given by:
√
=
A - the nominal cross section area, mm2
Alternatively, given the cable cross section and fault current, the maximum time allowable for
the protective device can be found from: t=
The factor k is dependent on the cable insulation, allowable temperature rise under fault
conditions, conductor resistivity and heat capacity. Typical values of k are:
Value of k
Temperature Conductor Material
Initial °C]Final [°C] Copper Aluminium Steel
Thermoplastic 70°C (PVC) 70 160/140 115/103 76/78 42/37
*where two values; lower value applied to conductor CSA > 300 mm2
* these values are suitable for durations up to 5 seconds, source: BS 7671, IEC 60364-5-54
Tip: for a better understanding of cable insulation and how it is categorized, refer to our Cable
Insulation Properties note.
Example : Consider a maximum fault current of 13.6 kA and the protective device trips in 2.6
s. The minimum safe cable cross sectional area of a copper thermosetting 90°C cable (k=143) is:
.
S= = 154mm2
Any selected cable larger than this will withstand the fault.
From physics, the heat Q, required to rise a material ΔT is given by: Q=cmΔT
Q - heat added, J
ΔT - temperature rise, K
⍴
m=ρcAl and R=
⍴r
t = c⍴ A
A
and rearranging for A gives:
S= by letting k= ⍴
Note: ΔT is the maximum allowable temperature rise for the cable:
ΔT=θf−θi
Units: are expressed in g (grams) and mm2, as opposed to kg and m. This is widely adopted by
cable specifiers. The equations can easily be redone in kg and m if required.
Obtaining Values of k
A more common approach for is to use the tabulated values for k, for example, from BS 7671[1].
Qc( + ) +
k= In( )
20 +
Qc - volumetric heat capacity of conductor at 20°C, J.K-1.mm-3
Substituting the above values and rearranging the IEC equation slightly, gives:
k = 226 In(1 + ) -copper conductors
.
k = 148 In(1 + ) -aluminum conduct
k = 78 In(1 + )-steel
Non-adiabatic effects
As mentioned, the adiabatic equation assumes no heat is dissipated from the cable during a fault.
While putting the calculation on the safe side, in some situations, particularly for longer fault
duration there is the potential to be able to get away with a smaller cross section. In these
instances, it is possible to do a more accurate calculation.
Considering non-adiabatic effects is more complex. Unless there is some driver, using the
adiabatic equations is just easier. Software is available to consider non adiabatic effects,
however, there is a cost, time and complexity associated with this.
The IEC also publish a standard which deals with non-adiabatic equations:
I=εIAD
The bulk of the IEC 60949 standard is concerned with the calculation of ε.
electro-mechanical stress and fault levels large enough to cause cable failure
performance of joint and terminations under fault conditions
While in most cases the none heating effects are not serious, there may be situations where these
could pose a risk to the cable or equipment/personnel in the vicinity.