OMICRON PTL Siemens 7UT8x V7.

80 Transformer PTT User Manual

OMICRON PTL

Siemens 7UT8x V7.80 Transformer PTT

User Manual

V1.000

© OMICRON electronics GmbH 1/7


OMICRON PTL Siemens 7UT8x V7.80 Transformer PTT User Manual

Content
1. General ...................................................................................................................................................3
1.1 Supported Relays .................................................................................................................................3
2. Software and Hardware Requirements ...............................................................................................3
3. Hardware ................................................................................................................................................4
4. Functional Range...................................................................................................................................6
5. XRIO Converter ......................................................................................................................................7
5.1 Additional Information ...........................................................................................................................7
5.1.1 Relay Information ...........................................................................................................................7
5.1.2 Transformer Information .................................................................................................................7
6. Specific Protection Tests ......................................................................................................................7
6.1 Differential Protection – Harmonic Restraint Test ................................................................................7

© OMICRON electronics GmbH 2/7


OMICRON PTL Siemens 7UT8x V7.80 Transformer PTT User Manual

1. General
This user manual describes details of testing 7UT8x relays with the OMICRON Protection Test Template
(PTT). General information on the usage of OMICRON Protection Testing Library items can be found in
the OMICRON PTL user manual.

The template has been tested with the following relay:


Manufacturer: SIEMENS
Model: 7UT87
Firmware Version: 7.80

1.1 Supported Relays


The following relays can be tested with the Protection Test Template:
• 7UT82
• 7UT85
• 7UT86
• 7UT87 (only two- or three-winding transformer applications supported)

2. Software and Hardware Requirements


To use this template, you must have a valid test license for the OMICRON Test Universe 3.20 software or
higher versions and the following test modules:
• Control Center
• Diff Configuration
• Diff Trip Time Characteristic
• Diff Operating Characteristic
• Diff Harmonic Restraint
• Overcurrent
• Pulse Ramping
• Ramping
• State Sequencer

A CMC test set with six current outputs is required. A CMA 156 current amplifier may be additionally
required for testing with higher currents e.g. relays with 5A current measuring inputs.

© OMICRON electronics GmbH 3/7


OMICRON PTL Siemens 7UT8x V7.80 Transformer PTT User Manual

3. Hardware
There are multiple possibilities of wiring a 7UT8x relay to a CMC test set. The advised connections for
testing side 1 and 2 are shown in Figure 1 and for side 1 and 3 in Figure 2. These connections are the
default settings in the Hardware Configuration of the PTT.

IC Side 1
IA Side 1
IB Side 1

N Side 1

*CB aux. Side 3 (52b)


Trip Side 2
Trip Side 1
*Trip Side 3

CB aux. Side 1 (52b)


CB aux. Side 2 (52b)
Pickup
IA Side 2

IC Side 2
IB Side 2

N Side 2

*: This signal can be ignored for two-winding


transformer applications

Figure 1: Connection diagram for testing side 1 and 2


IA Side 1

IC Side 1
IB Side 1

N Side 1

Trip Side 3
Trip Side 2
Trip Side 1

CB aux. Side 1 (52b)


CB aux. Side 2 (52b)
Pickup

CB aux. Side 3 (52b)


IC Side 3
IA Side 3
IB Side 3

N Side 3

Figure 2: Connection diagram for testing side 1 and 3

© OMICRON electronics GmbH 4/7


OMICRON PTL Siemens 7UT8x V7.80 Transformer PTT User Manual

Hardware Configuration for Overcurrent Protection, Ground (IN-separate)


For testing a ground-fault overcurrent protection with a residual current measured by a separate current
transformer (IN-separate), please change the connections according to the advised connections in Figure
3 for ground-fault overcurrent protection side 1, Figure 4 for ground-fault overcurrent protection side 2 and
Figure 5 for ground-fault overcurrent protection side 3.

IA Side 1

IC Side 1
IB Side 1

N Side 1

*CB aux. Side 3 (52b)


Trip Side 2
Trip Side 1
*Trip Side 3

CB aux. Side 1 (52b)


CB aux. Side 2 (52b)
Pickup
IN Side 1
IN_N Side 1

Figure 3: Connection diagram for testing a ground-fault overcurrent protection (IN-separate) side 1
IN Side 2
IN_N Side 2

Trip Side 2
Trip Side 1
*Trip Side 3

*CB aux. Side 3 (52b)


Pickup
CB aux. Side 1 (52b)
CB aux. Side 2 (52b)
IA Side 2

IC Side 2
IB Side 2

N Side 2

Figure 4: Connection diagram for testing a ground-fault overcurrent protection (IN-separate) side 2

© OMICRON electronics GmbH 5/7


OMICRON PTL Siemens 7UT8x V7.80 Transformer PTT User Manual

IN Side 3
IN_N Side 3

Trip Side 2
Trip Side 3
Trip Side 1

Pickup
CB aux. Side 1 (52b)
CB aux. Side 2 (52b)
CB aux. Side 3 (52b)
IA Side 3

IC Side 3
IB Side 3

N Side 3

Figure 5: Connection diagram for testing a ground-fault overcurrent protection (IN-separate) side 3

4. Functional Range
Supported functions:
• Differential Protection for two- or three-winding transformer applications
• Overcurrent Protection, Phases
• Overcurrent Protection, Ground
• Thermal Overload Protection

Not supported parameters or configurations:


• Differential Protection – Inrush Blocking: Blocking with CWA = yes
• Differential Protection: Starting detection = yes.

Not supported functions:


• Restricted Ground-Fault Protection
• Sensitive Ground-Fault Protection
• Distance Protection
• Impedance Protection
• Power-Swing Blocking
• External Trip Initiation 3-Pole
• Directional Overcurrent Protection, Phases
• Directional Overcurrent Protection, Ground
• Negative-Sequence Protection
• Undercurrent Protection
• Overexcitation Protection
• Unbalanced-Load Protection
• Instantaneous High-Current Tripping
• Voltage Protection
• Frequency Protection
• Rate of Frequency Change Protection
• Phase-Sequence Switchover
• Instantaneous Tripping at Switch onto Fault
• Thermal Overload Protection, 1-Phase

© OMICRON electronics GmbH 6/7


OMICRON PTL Siemens 7UT8x V7.80 Transformer PTT User Manual

• Hot-Spot Calculation
• Circuit-Breaker Failure Protection
• Circuit-Breaker Restrike Protection
• Arc Protection
• Inrush-Current Detection
• Power Protection

5. XRIO Converter
The Test Object already contains the Siemens 7UT8x XRIO Converter, which includes setting
parameters of the modelled protection relay. The setting parameters are built as an image of the DIGSI 5
software.

5.1 Additional Information

5.1.1 Relay Information


The Relay Information block contains relay specific parameters. It includes the tolerances which can be
found in the 7UT8x relay manual and are required for testing. Please adjust the type of the relay output
(Standard Relay (Type S), Fast Relay (Type F) or High-Speed Relay with Semiconductor
Acceleration (Type HS)) to get appropriate tolerance times. Typically, the parameters in the specific
blocks don't have to be changed, as the parameters are already set to the values given in the user manual
of the relay.

5.1.2 Transformer Information


The Transformer Information block includes the parameter Number of Sides, which states whether the
protected object is a two- or three-winding transformer. The parameter has to be set before testing.

6. Specific Protection Tests


In this chapter the specific protection tests, which are not covered by the OMICRON PTT User Manual,
are described.

6.1 Differential Protection – Harmonic Restraint Test


The Diff Harmonic Restraint test module is used to check the correct relay behavior of the harmonic
restraint of the differential protection. Three currents are required for this test, which is carried out on
transformer side 1. For the test a search line is placed at Idiff = 1.3 × Iref. Additional search lines can be
added by the user.

© OMICRON electronics GmbH 7/7