Siemens 7UT8x V7.80 Transformer PTT User Manual ENU
Siemens 7UT8x V7.80 Transformer PTT User Manual ENU
OMICRON PTL
User Manual
V1.000
Content
1. General ...................................................................................................................................................3
1.1 Supported Relays .................................................................................................................................3
2. Software and Hardware Requirements ...............................................................................................3
3. Hardware ................................................................................................................................................4
4. Functional Range...................................................................................................................................6
5. XRIO Converter ......................................................................................................................................7
5.1 Additional Information ...........................................................................................................................7
5.1.1 Relay Information ...........................................................................................................................7
5.1.2 Transformer Information .................................................................................................................7
6. Specific Protection Tests ......................................................................................................................7
6.1 Differential Protection – Harmonic Restraint Test ................................................................................7
1. General
This user manual describes details of testing 7UT8x relays with the OMICRON Protection Test Template
(PTT). General information on the usage of OMICRON Protection Testing Library items can be found in
the OMICRON PTL user manual.
A CMC test set with six current outputs is required. A CMA 156 current amplifier may be additionally
required for testing with higher currents e.g. relays with 5A current measuring inputs.
3. Hardware
There are multiple possibilities of wiring a 7UT8x relay to a CMC test set. The advised connections for
testing side 1 and 2 are shown in Figure 1 and for side 1 and 3 in Figure 2. These connections are the
default settings in the Hardware Configuration of the PTT.
IC Side 1
IA Side 1
IB Side 1
N Side 1
IC Side 2
IB Side 2
N Side 2
IC Side 1
IB Side 1
N Side 1
Trip Side 3
Trip Side 2
Trip Side 1
N Side 3
IA Side 1
IC Side 1
IB Side 1
N Side 1
Figure 3: Connection diagram for testing a ground-fault overcurrent protection (IN-separate) side 1
IN Side 2
IN_N Side 2
Trip Side 2
Trip Side 1
*Trip Side 3
IC Side 2
IB Side 2
N Side 2
Figure 4: Connection diagram for testing a ground-fault overcurrent protection (IN-separate) side 2
IN Side 3
IN_N Side 3
Trip Side 2
Trip Side 3
Trip Side 1
Pickup
CB aux. Side 1 (52b)
CB aux. Side 2 (52b)
CB aux. Side 3 (52b)
IA Side 3
IC Side 3
IB Side 3
N Side 3
Figure 5: Connection diagram for testing a ground-fault overcurrent protection (IN-separate) side 3
4. Functional Range
Supported functions:
• Differential Protection for two- or three-winding transformer applications
• Overcurrent Protection, Phases
• Overcurrent Protection, Ground
• Thermal Overload Protection
• Hot-Spot Calculation
• Circuit-Breaker Failure Protection
• Circuit-Breaker Restrike Protection
• Arc Protection
• Inrush-Current Detection
• Power Protection
5. XRIO Converter
The Test Object already contains the Siemens 7UT8x XRIO Converter, which includes setting
parameters of the modelled protection relay. The setting parameters are built as an image of the DIGSI 5
software.