RT Series: User Manual
RT Series: User Manual
UPS has high voltage inside, do not repair it by yourself. If any questions,
please contact local service center or dealer.
CAUTION
2. Product Overview
2.1 Specifications
Input
Rated input voltage
208Vac / 220Vac / 230Vac / 240Vac
Rated input frequency
50Hz / 60Hz (auto-sense)
Input voltage range
110 ~ 176Vac (power derating linearly between 50% and 100% load);
176 ~ 280Vac (no derating); 280 ~ 300Vac (power derating 50%)
Input frequency range
40 ~ 70Hz
PFC
≥ 0.99
THDI
≤ 6%
Bypass voltage range
-25% ~ +15% (settable)
Output
Voltage accuracy ± 1%
Output PF 0.9
DC voltage
24V 36V 36V 48V 72V 72V 72V 96V 96V
Charger output 27.1 40.7 40.7 54.2 81.3 81.3 81.3 108.4 108.4
voltage ±0.4 ±0.6 ±0.6 ±0.8 ±1.2 ±1.2 ±1.2 ±1.6 ±1.6
Communication port Standard: RS232; Options: USB, SNMP card, dry contacts
Display LCD
Environmental
Operating altitude ≤ 1000m, above 1000m, derate 1% for each rising 100m
Others
Dimensions (mm) 440*44 440*44 440*44 440*63 440*63 440*44 440*63 440*44 440*4
W ×D×H 0*88 0*88 0*88 0*88 0*88 0*8 0*88 0*88 40*88
Weight (kg) 12.26 13.78 7.58 22.73 25.86 9.66 29.26 9.45 10.04
* Derate capacity to 70% in CUCF mode and to 90% when the output voltage is adjusted to 208Vac.
①
10 ⑧ ④ USB port
EPO (Emergency
a. 1KVAS-RT(24V), 1KVAS-RT(36V) and 1KVAH-RT rear panel.
⑤ Power Off) port
② ⑧ ③ ⑨ ④⑤ ⑥ RS232 port
⑦ Intelligent slot
Surge protection
⑧ for network/fax/
modem
⑨ Output sockets
① ①
10 ⑥ ⑦ ①
10 Battery connector
② ⑧ ⑨ ③ ⑦ ④
Note:
The figure is for reference only.
Due to the technology upgrading
and development, the real unit
might be different from the figure.
① ①
10 ⑤ ⑥
c. 2KVAH-RT, 3KVAH-RT and 3KVAS-RT(96V) rear panel.
Note:
Keep the packaging box and packaging materials for future transport use.
The equipment is heavy. Always handle it with care.
• One end of battery cable is for UPS terminals while the other end with triple cables is for battery terminals.
Correct installation procedure is highly vital or else probable electric shock will arise. Users are strictly
required to follow the below procedure.
• Connect batteries correctly and make sure the total battery voltage is available for UPS.
• Correctly connect the long battery cable to battery terminals first, red wire is to positive plate while black
is to negative. If users connect the UPS first, electric shock or other danger may not be avoided.
• Before connecting loads, users should supply mains power and energize the UPS.
• Connect long battery cable to UPS terminals with correct poles link (red is for ‘+’, black is for ‘-‘), UPS will
start charging automatically.
• Connect the battery pack to the battery connector.
RS232 Port:
Pins 1 2 3 4 5 6 7 8 9
Indication empty send receive empty ground empty empty empty empty
Note:
RS232 interface is set as below: Txd 1
6
Rxd 2
7
• Bit rate: 1200bps 3
8
• Byte: 8bit 4
9
• Completion code: 1bit GND 5
USB Port:
2 1
Pins 1 2 3 4
Indication +5V date+ date- GND 3 4
UPS Fail
1
Dry Contacts Card (optional) 6
Bypass
Summary Alarm
2
Battery Low
Insert the dry contacts card into the intelligent 7
GND 3
slot. It’s another type function of intelligent 8
UPS On
Position Definition
PIN1 ON: UPS is malfunctioning
PIN2 ON: Alarm (system failure)
PIN3 Ground
PIN4 Remote shutdown
PIN5 Common
PIN6 ON: Bypass mode
PIN7 ON: Battery low
ON: Inverter mode
PIN8
OFF: Bypass mode
PIN9 ON: No AC power in
VAC
E
LIN
Hz
OUTPUT
25% 50% 75% 100%
Button Function
“ON” key
Press the two keys for more than half a second to turn on the UPS.
“OFF” key
Press the two keys for more than half a second to turn off the UPS.
Press the two keys for more than 1 second and less than 5 seconds in Line
TEST/MUTE key mode or ECO mode or CUCF mode: UPS runs the self-test function.
INQUIRING key Press for more than 2 seconds: Circularly and orderly display the items
every 2 seconds, when press the key for some time again, it will turn to
output status.
In setting mode:
Press or for more than half a second (less than 2 seconds):
Select the setting option.
Button Function
Press and hold and for more than 5 second: Change the direction
to display items.
ROTATE key
VAC
E
LIN
Press and hold The direction has
keys for more been changed in
Hz
OUTPUT
Icon display
INPUT BATTERY OUTPUT LOAD TEMP
100%
100%
INPUT BATTERY OUTPUT LOAD TEMP
25%
25%
VDC
KW Battery capacity
Load capacity
75%
75%
display area
50%
50%
VAC
display area
C%
50%
50%
75%
75%
KVA
Digital display area Hz
25%
25%
100%
100%
KVA
Hz
C%
VAC
VDC
KV
Working mode
display area
fa
ST
ba
by
LI
ba
ec
pa
DB
ul
NE
tt
o
ss
Y
Display Function
Icon Display
Load Icon
The approximate load capacity percentage (0-25%, 26-50%, 51-75% and
76-100%) is indicated by the number of load bar sections illuminated.
When UPS is overloaded, the load icon will flash.
Mute Icon
Indicates the audible alarm is disabled/mute.
Press the mute key in the battery mode, the mute icon flash.
Fan Icon
Indicates fan working status. When the fan normally runs, the icon
displays rotation; if the fan is not connected or faulty, the icon will flash.
Fault Icon
Operation Mode
Working Mode Indicates UPS operation mode in 20 seconds, such as STDBY (standby
Display Area mode), BYPASS (Bypass mode), LINE (AC mode), BAT (Battery mode), BATT
(Battery Self Test mode), ECO (Economic mode), SHUTDN (Shutdown
mode), CUCF (Constant Voltage and Constant Frequency mode).
Operation Description
Icon Display
• When UPS is in LINE Mode, press the self-test/mute key for more than
UPS 1 second. UPS gets to self-test mode and tests its status. It will exit
Self-Test/Mute Test automatically after finishing test.
Operation • When UPS is in BAT Mode, press the self-test/mute key for more than
1 second, the buzzer stops beeping. If you press the self-test/mute
key for one more second, it will restart to beep again.
• Enter Setup interface. Press and hold the function setting key
for more than 2 seconds, then come to Setup interface, press and hold
the inquiring key ( , ) for more than half a second (less than
2 seconds), select the function setting, choose the setup interface,
at the moment, the letters flash.
• Enter the setup interface. Press and hold the function setting key
for more than half a second (less than 2 seconds), then come to the
setup interface, at this time, the letters doesn’t flash any more, the
numerical value flash. Press and hold the inquiring key ( , ) for
UPS Setting
more than half a second (less than 2 seconds), select the numerical
value in accordance with the function.
• Confirm the setup interface. After selecting numerical value, press
and hold the function setting for more than half a second (less
than 2 seconds). Now, the setting function is completed and the
numerical value illuminates without flashing.
• Exit from the setup interface. Press and hold function setting key
for more than half a second (less than 2 seconds), exit from the setup
interface and return to the main interface.
BY
ST
NE
NE
LI
LI
LI
Epcom Power Line
Y
dEF (default): EOD voltage automatically 25%
varies with
DB
DB
DB
25% 50% 75% 100% 25% 50% 75% 100% 50% 75% 100% 25% 50%
ST
ST
ST
loads, including 21.5 hours dicharge protection.
24.0 22 0 90 0
VDC
w
VAC
s 0.0
NE
NE
NE
1 00 10 40
LI
LI
LI
%
KVA
25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
Hz
60 0
ON: converter mode enable
OFF (default): converter mode disable 22 0 V
Y
Y
DB
DB
DB
DB
25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
ST
ST
ST
ST
22 0 90 0 22 0
C
w
VAC
s 0.0
NE
NE
NE
NE
10 40 50 0
LI
LI
LI
LI
% C
KVA
25% 50% 75% 100% 25% 50% 75% 100%
Hz
60 0 22 0
50 (default): presentsV output frequency is 50Hz.
60: presents output frequency is 60Hz.
Y
Y
DB
DB
DB
ST
ST
EP setting ON required.
AUO setting only can be set in Stdby mode or Bypass
mode. You may choose the following two options:
ON: UPS will start up automatically and works in Line
AUO Setting
mode when connect mains.
OFF: UPS won’t start up automatically when connect
mains except EOD, it will work in standby or bypass
mode (Default).
Y
DB
DB
DB
DB
% 100% 25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
ST
ST
ST
ST
LCD Display Description
% 100% 25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
.0 75%
VDC
100%
VAC
100%
90 0
Output:
25%
Display
50% 75%w
the
100%
output voltage and output frequency of the
UPS. As the following graphic shows, the output voltage is 220V,
22 0 VAC
s 0.0
NE
NE
NE
NE
NE
0 10 40 50 0
LI
LI
LI
LI
LI
% C
60 0 22 0
Hz Hz
% 100% 25% 50% 75% 100% 25% 50% 75% 100% V 25% 50% 75% 100% 25% 50% 75% 100%
Y
Y
DB
DB
DB
75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
ST
ST
ST
75% 100% 25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
.0
NE
NE
NE
NE
10 40 50 0
LI
LI
LI
LI
0
75% 100%
Hz
22 0
25% 50% 75% 100%
V a small numerical value of WATT and VA). Hz
25% 50% 75% 100% 25% 50% 75% 100%
Y
Y
DB
DB
ST
0 w
22 0
Temperature: Display the maximum temperature of
VAC
the components in the UPS. As the following graphics
NE
NE
NE
00 40 50 0
LI
LI
LI
75% 100%
ST
22 0 VAC
Input: Display the voltage and frequency of the input. As the
following graphics shows, the input voltage is 220V, input
NE
NE
0 50 0
LI
LI
frequency is 50Hz.
Hz
Y
DB
DB
DB
DB
25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
ST
ST
ST
ST
LCD Display Description
25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
24.0 22 0 90 0
Battery: Display the voltage and capacity of the battery.
VDC
w
As the followingVAC graphics shows, the battery voltage is 24V,
s 0.0
NE
NE
NE
NE
1 00 10
the capacity of battery is 100% (the capacity of battery is
40
LI
LI
LI
LI
% C
KVA
approximately Hzreckoned according to the battery voltage).
25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100% 25% 50% 75% 100%
6. Fault Messages
Table 1: Fault Code Messages
Fault Code Fault Type Bypass Output Note
0, 1, 2, 3, 4 Bus high yes
5, 6, 7, 8, 9, Bus low yes
10, 11, 12, 13, 14 Bus unbalance yes
15, 16, 17, 18, 19 Bus soft start fail yes
20, 21, 22, 23, 24 Inverter soft start fail yes
25, 26, 27, 28, 29 Inverter high yes
30, 31, 32, 33, 34 Inverter low yes
35, 36, 37, 38, 39 Bus discharge fail yes
40, 41, 42, 43, 44 Over heat yes
45, 46, 47, 48, 49 OP(inverter) short yes
50, 51, 52, 53, 54 Overload yes
55, 56, 57, 58, 59 Line NTC break yes
60, 61, 62, 63, 64 Shutdown fault yes
65, 66, 67, 68, 69 AC input fuse open yes unused
70, 71, 72, 73, 74 Communication fault yes unused
75, 76, 77, 78, 79 Communication fault yes
80, 81, 82, 83, 84 Relay fault yes
85, 86, 87, 88, 89 AC input SCR fault yes unused
90, 91, 92, 93, 94 CAN fault yes
RT Series True Online UPS | 19
Table 2: Working Status Messages
Battery Mode
One beep /
Battery voltage - normal Working mode displays bAT
4 sec
2
Bypass Mode
2 beeps /
Warning for mains power overload Working mode displays Line, load icon flash
sec
Protect operation for mains power Working mode displays FAULT and the
5 Long beep
mode overload corresponding codes
2 beeps /
Warning for battery overload Working mode displays bAT, load icon flash
sec
Protect operation for battery mode Working mode displays FAULT
Long beep
overload and the corresponding codes
Working mode displays byPASS, One beep /
6 Warning for bypass mode overload
load icon flash all the time 2 sec
Fan icon flash, working mode displays One beep /
7 Fans fault (fan icon)
depending on current mode 2 sec
Note:
• End user need to provide below information when require to maintain the UPS.
• UPS Model No. & Serial No.
• Date of fault occurrence.
• Fault details (LCD status, noise, AC power situation, load capacity, battery capacity configuration ect.).
Alarm icon
Alarm code
NE
LI
B
C
D
E
F
5
The third 6
digital tube
from right to 7
left
8
Display Bypass
Over Load Fault Mains Lost
Value Abnormal
1
The fourth 2
digital tube
from right to 3
left
4
Example:
• If the alarm code “2000” appears on the LCD screen, it indicates loss of mains power.
t
ul
fa
Fault icon
Fault code
Fault icon display, audible Check whether the input & output
buzzer alarm continually, Power fault power are normal or not, contact the
the fault code is 60-64 supplier if it is abnormal.
Fault icon display, audible Check if the input fuse is burnt. Replace
buzzer alarm continually, Input fuse fault the old fuse and restart the UPS. If the
the fault code is 65-69 problem persists, contact the supplier.
UPS fail to start when The input connection is not Connect the input well, if the battery
operate ‘On’ key ready or UPS internal voltage is too low, disconnect the input
battery disconnect and start the UPS with no-load
Note:
When the output is short-circuited, the action of UPS protection will show up. Before
turning off the UPS, make sure to disconnect the entire loads and cut off the mains
CAUTION power supply, otherwiseit will make the AC inpushort circuit.