Professional Documents
Culture Documents
Boiler Sizing: Boiler Output (KW) Heat Loss (KW) + Boiler Power For HW Cylinder (KW)
Boiler Sizing: Boiler Output (KW) Heat Loss (KW) + Boiler Power For HW Cylinder (KW)
The boiler output is based on the total heat losses for the building plus hot water
boiler power.
Other additional items that can be considered are; heater battery outputs and
other equipment that require heat.
For details of Boiler Power for Hot Water cylinder see Hot and Cold water section
– Hot water generation & storage page 2.
Boiler Output (kW) = Heat Loss (kW) + Boiler Power for HW cylinder
(kW)
Boiler Margin.
Total Boiler Output (kW) = Heat Loss (kW) + Boiler Power for HW cylinder
(kW) + 20% margin.
Note:
In most cases a margin has already been added to the heat loss to size heat emitters.
It should be remembered that if this margin is 10% and a further 20% margin is added for
boiler sizing then the net resultant margin is 32%.
In continuously operated heating systems such as hospitals, a smaller margin is
acceptable since the system is not heated from cold each morning.
In the past if two boilers were to be installed, each one was sized at 2/3 rds of the
total capacity.
This overall margin of 33% is on the high side so a lower margin is more
acceptable.
A multiple boiler installation is a more efficient method of providing heating since
the more boilers that are installed the more they will operate at full load when
switched on.
Recommendations
CIBSE guide F (2002) section 10.1.2.2 and BSRIA Guidance Note 12/97 Oversized
Heating Plant gives details of plant sizing.
As a guide to boiler capacity (heating load) the following yard sticks can be used;
90 W/m2 for offices and industrial buildings, 110 W/m2 for retail, health care and
education establishments.
Also for Hot Water calorifier sizing the following yard sticks can be used; 4
l/person for offices, retail, education and restaurant establishments, 23 l/person
for hotels, 33 l/person for health care.
CIBSE guide B1 (2002) section 4.7 gives details of Plant Size Ratio (PSR).
This is defined as; PSR = installed heat emission / design heat loss
A building with low thermal inertia heats up more quickly than one with high
thermal inertia and therefore a lower plant size ratio may be used.
The optimum plant size ratio is a compromise between the following factors;
1. occupancy pattern.
2. pre-heat time.
3. thermal response of the building.
4. greater capital cost and maintenance cost.
5. stability of controls..
6. seasonal efficiency.