LIGHTING FIXTURE
2 7 x LED DOWNLIGHT 8 WATTS 56 230
12 SPARE
13 SPARE
14 SPARE
TOTAL 15732
DESIGN COMPUTATION
TOTAL AMPACITY
TOTAL LOAD IN VA
Application of DF
PROTECTIVE DEVICES
2.42 1 15 60 15
0.24 1 15 60 15
3.91 1 20 60 15
7.04 1 20 60 15
26.09 1 40 60 15
6.52 1 30 60 15
2.17 1 30 60 15
12 1 30 60 15
8 1 30 60 15
1 30 60 15
1 30 60 15
0 1 20 60 15
0 1 20 60 15
0 1 30 60 15
68.40
15,732.00
12,293.60
Amperes
S 14mm² THHN + 5.5mm² GROUND CONDUCTOR in 50mm dia RMC
100.00 AMPS
100AT/125AF, 2P, 230V MCCB
73,761.60 VA
320.70 AMPS