50mva TRAFO#1 BAY#106
50mva TRAFO#1 BAY#106
: D-2-01-03-01-04
I. GENERAL DETAILS
DETAILS
Test
Testing Kit Details
Results
Sl.
Name Of Test (Ok/No
No. Date Of Last
Make Kit S.NO t Ok)
Calibration
Page 1 of 19
DOC NO.: D-2-01-03-01-04
Sl. REMARKS /
INSPECTION ACTIONS DATE TIME
No READING
3 Check Main Tank has been provided with double earthing YES
Check neutral is grounded through separate connections.
4 Ensure metallic requirements as per specification (e.g. Cu) YES
in earthing strips used
Check that Marshalling Box, T/C Driving Gear, Diverter,
5 YES
Radiator Bank Pump & Fan Motor etc. has been earthed
All nuts and bolts are tightened correctly as per specified
6 YES
torque (as per manufacturers recommendation)
7 Check tightness of Terminal Connectors YES
Page 2 of 19
DOC NO.: D-2-01-03-01-04
15 Check oil drain valves are properly closed and locked YES
Page 3 of 19
DOC NO.: D-2-01-03-01-04
Location Value
With Grid (Earth Pit -1) 0.72 Ω
Without Grid (Earth Pit -1) (Neutral Earth ) 3.43 Ω
With Grid (Earth Pit -2) 0.77 Ω
Without Grid (Earth Pit -2) (Neutral Earth) 2.00Ω
Page 4 of 19
DOC NO.: D-2-01-03-01-04
Note:
i. (1)= (2) + (3), Approx.
Page 5 of 19
DOC NO.: D-2-01-03-01-04
ii. When outer phase is excited, voltage induced in the center phase shall be 50 to 90% of the applied voltage.
However, when the center phase is excited then the voltage induced in the outer phases shall be 30 to 70%
of the applied voltage.
Voltage
Tap Current Measured
Applied Remarks
Position (mAmps)
(Volts)
R-Y 418 R - PH 2.4
LOWEST Y-B 414 Y - PH 1.3
B-R 415 B - PH 2.6
R-Y 426 R - PH 2.7
NORMAL
Y-B 426 Y - PH 1.5
B-R 427 B - PH 2.9
R-Y 425 R - PH 3.4
HIGHEST Y-B 428 Y - PH 1.9
B-R 426 B - PH 3.5
a) HV TO LV
HV LV
1U 1V 1W 1U 1V 1W 2U 2V 2W 2U 2V 2W
Page 6 of 19
DOC NO.: D-2-01-03-01-04
a) Insulation Resistance Measurement of Cable and others (Using 500 Volt Megger)
Status
Sl. No. Description Remarks, If Any
Yes No
1 Control wiring YES
2 a) Motor YES
b) Control YES
Page 7 of 19
DOC NO.: D-2-01-03-01-04
Turn Ratio : HV / LV
Note:
1. The variation of result should be within ± 0.5 % from specified values (i.e. factory test result)
2. Measurement to be done by Automatic Turns ratio meter
BUSHING DETAILS
a) HV side
VOLTAGE CAPACITANCE (MEASURED VALUE) REMARKS
Page 8 of 19
DOC NO.: D-2-01-03-01-04
CAPACITANCE(nF) % OF TAN δ
WINDING
VOLTAGE TEST MODE REMARK
COMBINATION FACTOR FACTOR
SITE SITE
Y Y
5 KV 6874(nF) 3883 0.366 0.387
HV-E GSTg
10 KV 6874(nF) 3883 0.432 0.380
5 KV 13.10(pF 11530 0.338 0.383
)
LV-E GSTg
10 KV 13.10(pF 11530 0.344 0.378
)
5 KV 8463(nF) 5240 0.305 0.260
HV-LV UST
10 KV 8463(nF) 5239 0.387 0.255
Note:
i. C2 values shall be only for record purpose.
ii. For bushing acceptable Limit for Tan δ1 should be comparable (+/- 0.001) with factory
value subjected to max of 0.005 & Tan δ2:-0.01
iii. For winding acceptable Limit for Tan δ1 should be comparable (+/- 0.001) with factory
value subjected to max of 0.005 & Tan δ2:-0.01
iv. Acceptable Limit for Capacitance -5% to + 10%
Page 9 of 19
DOC NO.: D-2-01-03-01-04
Resistance(Ω) Resistance At 36 °C In Ω
Between Windings % Deviation
Site Value@ -23-ºC Factory Site
2U– 2V 0.0369 0.04224 0.038759302 -8.24029
2V – 2W 0.0368 0.04238 0.038654264 -8.79126
2W – 2U 0.0370 0.04232 0.038864341 -8.16555
NOTE:
Page 10 of 19
DOC NO.: D-2-01-03-01-04
Page 11 of 19
DOC NO.: D-2-01-03-01-04
STATUS
SL.NO DESCRIPTION
OK NOT OK
1 Rotation direction of Pumps NA
2 Rotation direction of Fans 0k
c) Protection Check
CLAS PROTECTION /
CORE RATIO BURDEN KVP
S METERING
Phase CT 300/1A PS - 800V PROTECTION
Neutral CT 300/1A PS 800V PROTECTION
WTI CT 257/1.5A 3 10VA WTI
LV SIDE
CLAS PROTECTION /
CORE RATIO BURDEN KVP
S METERING
Phase CT 1000/1A PS - 1000V PROTECTION
Neutral CT 1000/1A PS - 1000V PROTECTION
WTI CT 875/1.5A 3 10VA LV WTI
Measurement HV LV
Unit
Between R–Ø Y-Ø B-Ø R-Ø Y-Ø B-Ø
Earth – Phase CT GΩ >1 >1 >1 >1 >1 >1
Page 12 of 19
DOC NO.: D-2-01-03-01-04
ii.
LV side
BETWEEN R-Ø Y–Ø B–Ø
CORE UNIT
TERMINAL FACTORY SITE FACTORY SITE FACTORY SITE
Phase CT 1S1 – 1S2 Ω - 1.2 - 1.2 - 1.3
Core-II(WTI) 3S1-3S2 Ω - - - - - 0.6
iii.
Neutral Side
BETWEEN HV LV
CORE UNIT
TERMINAL FACTORY SITE FACTORY SITE
Core I 1S1 – 1S2 Ω - 1.4 - 1.2
Page 13 of 19
DOC NO.: D-2-01-03-01-04
i. LV side R – Phase
Page 14 of 19
DOC NO.: D-2-01-03-01-04
i. HV Side R – Phase
Voltage Core – I
Unit
To Be Applied Actual Value 1S1-1S2
0.25 x KVp 200 mA 22.2
0.50 x KVp 400 mA 33.3
0.75 x KVp 600 mA 46.4
1.00 x KVp 800 mA 65.2
1.10 x KVp 880 mA 81.0
Voltage Core – I
Unit
To Be Applied Actual Value 1S1-1S2
0.25 x KVp 200 mA 25.2
0.50 x KVp 400 mA 38.2
0.75 x KVp 600 mA 53.2
1.00 x KVp 800 mA 86.2
1.10 x KVp 880 mA 99.0
Page 15 of 19
DOC NO.: D-2-01-03-01-04
i. HV Side Neautral
Voltage Core – I
Unit
To Be Applied Actual Value 1S1-1S2
0.25 x KVp 200 mA 23.7
0.50 x KVp 400 mA 36.8
0.75 x KVp 600 mA 52.0
1.00 x KVp 800 mA 77.3
1.10 x KVp 880 mA 98.6
Page 16 of 19
DOC NO.: D-2-01-03-01-04
Note
a) CT should not saturate at 110% of Knee Point Voltage (KVp)
b) If Knee Point Voltage is not mentioned then Knee Point Current may be taken into
consideration.
settings √
NOTE : Prove the tripping of associated breakers by actual operation of the various
devices and relays as per the schemes.
Page 17 of 19
DOC NO.: D-2-01-03-01-04
b) All electrical test results compared with factory test results & found to
Yes No
be in order
√
f) Thermo vision scanning done at least after 24 hours of loading & repeated after
one week.
Yes No Remarks
Page 18 of 19
DOC NO.: D-2-01-03-01-04
Note: If any abnormal increase in fault gasses observed after 24 Hrs. of charging, immediate
oil sampling to be sent to Lab for confirmation and matter shall be referred to OEM
Page 19 of 19